Upload
philip-beere
View
5
Download
0
Embed Size (px)
Citation preview
Energy Code Workshop – Level 201Commercial Provisions of the 2009 IECC
Instructor – Anthony C. Floyd, AIA, ICC Certified Professional, LEED AP
Workshop Outline• Scope and Application• Mandatory and Prescriptive Path
Provisions• Performance Path• ASHRAE 90.1 Compliance Option• Existing Buildings and Renovations• Case Study and Exercise• 2012 IECC, IgCC, ASHRAE 189.1 and
other codes/standards on the horizon
International Energy Conservation Code
ASHRAE Standard 90.1
International GreenConstruction Code
Building Energy Codes
Structure of IECC
Chapter 1 AdministrativeChapter 2 DefinitionsChapter 3 Climate ZonesChapter 4 Residential Energy EfficiencyChapter 5 Commercial Energy EfficiencyChapter 6 Referenced Standards
• Scope and Application– Section 501 - General
• Mandatory and Prescriptive Path Provisions– Section 502 - Building Envelope– Section 503 - Mechanical Systems– Section 504 - Service Water Heating– Section 505 - Electrical Power and Lighting
• Performance Path– Section 506 - Building Performance Path
IECC Chapter 5
Baseline: IECC and ASHRAE 90.1
Both IECC and ASHRAE 90.1 apply, ASHRAE 90.1 likely used
Both IECC and ASHRAE 90.1 apply, either used to comply
IECC applies
General Requirements Climate Zones
Figure 301.1
General Requirements Arizona Climate Zones
Commercial Compliance Process
Section 501.2 Application requires 90.1 to be used in its entirety (Envelope, Lighting, Mechanical) if used as an alternate compliance path
Must the Project Comply with the
IECC?
Comply with the Envelope
Requirements
Comply with the Mechanical/SWH
Requirements
Comply with the Lighting
Requirements
Section 502 90.1 Section 5 Sections 503 and 504 90.1 Section 6 Section 505 90.1 Section 9
Document Compliance with
the IECC
Plan Review
Inspection
• Scope and Application– Section 501 - General
• Mandatory & Prescriptive Path Provisions– Section 502 - Building Envelope– Section 503 - Mechanical Systems– Section 504 - Service Water Heating– Section 505 - Electrical Power and Lighting
• Performance Path– Section 506 - Building Performance Path
IECC Chapter 5
Commercial Compliance Options
What are my Options for Complying with the IECC?Chapter 5 of the IECC General Prescriptive Approach
Use for ≤ 40% of gross wall area in vertical fenestration
Use for ≤ 3% of gross roof area in skylights
ORSection 506 Total Building Performance Approach
502 & 506
• Roof/Ceiling Assemblies• Wall Assemblies• Below Grade Walls• Floor Assemblies over unconditioned
space• Slab Edge• Vertical Fenestration and Skylights
Building Thermal Envelope
Tables separated by occupancy type Group R occupancies use “Group R” high rise column Non-Group R occupancies use “All other” column
Tables 502.1. & 502.1.2(1)
Building Thermal Envelope
Window and door assemblies Curtain wall, storefront glazing & commercial entrance doors Sealing of the building envelope Outdoor air intakes and exhaust openings Loading dock weather-seals Vestibules Recessed lighting
502.4
Building Thermal Envelope
Mandatory: Air Leakage
All penetrations, openings, joints and seams in the building envelope must be sealed. Materials that can be used include:
Caulking Gasketing Tapes Moisture vapor-permeable wrapping material
Sealing materials spanning joints between dissimilar materials must allow for expansion and contraction
Photo courtesy of Ken Baker, K energy
502.4.3
Building Thermal Envelope
Mandatory: Air Leakage
Buildings ≥ 3 stories in height above grade
Class 1 motorized leakage-rated damper– Maximum leakage rate ≤
4cfm /ft2 @ 1.0 inch w.g.Buildings < 3 stories in height
Gravity (non-motorized) allowed
502.4.5
Building Thermal EnvelopeMandatory: Outdoor Air Intakes & Exhaust
Openings
Equip cargo doors and loading dock doors with weatherseals
Goal is to restrict infiltration
502.4.6
Building Thermal EnvelopeMandatory: Weatherseals
All recessed luminaires installed in the building envelope Type IC rated and sealed
with gasket or caulk between housing and interior wall or ceiling covering
Type IC rated and labeled in accordance with ASTM E 283 to allow ≤ 2.0 cfm of air movement from conditioned space to ceiling cavity
502.4.8
Building Thermal EnvelopeMandatory: Recessed Lighting
Table 502.1.2
Building Thermal EnvelopePrescriptive
Building Thermal EnvelopePrescriptive: Opaque Elements and Assemblies
502.1.2 (U-Factor); 502.2.2(1) and (2) (R-Value)
Roof R-values and U-factor requirements are based on assembly type / insulation placement Insulation entirely above
deckMetal buildingsAttic and other
502.1.2 (U-Factor); 502.2.2(1) and (2) (R-Value)
Building Thermal EnvelopePrescriptive: Roof R-Value and U-Factor
Climate Zone 1 2 3
4Except Marine
5And
Marine 46 7 8
Insulation entirely above deck
R-15ci
R-20ci
R-20ci
R-20ci
R-20ci
R-20ci
R-20ci
R-20ci
R-20ci
R-20ci
R-20ci
R-20ci
R-25ci
R-25ci
R-25ci
R-25ci
Metal buildings (with R-5 thermal blocks)
R-19 R-19R-
13+R-13
R-13+R-13
R-13+R-13
R-19R-
13+R-13
R-19R-
13+R-13
R-19R-
13+R-19
R-19R-
13+R-19
R-19+R-19
R-11+R-19
R-19+R-10
Attic and other R-30 R-38 R-38 R-38 R-38 R-38 R-38 R-38 R-38 R-38 R-38 R-38 R-38 R-38 R-49 R-49
ROOFS
Table 502.2(1)
Building Thermal EnvelopeR-Value: Roof Insulation
Dropped CeilingDropped Ceiling
Insulation placed on Suspended Ceiling with Removable Ceiling Tiles
Will not count for code compliance
Will not comply with Section 502.4.3 – “Sealing of the building envelope”
502.2.1
Building Thermal EnvelopeR-Value: Roof Insulation
Climate Zone 1 2 3 4
Except Marine5
And Marine 4 6 7 8
Mass NR R-5.7ci
R-5.7ci
R-7.6ci
R-7.6ci
R-9.5ci
R-9.5ci
R-11.4ci
R-20ci
R-13.3ci
R-13.3ci
R-15.2ci
R-15.2ci
R-15.2ci
R-25ci
R-25ci
Metal building R-
16 R-16 R-16 R-16 R-19 R-19 R-19 R-19R-
13+5.6ci
R-13+5.6ci
R-13+5.6ci
R-13+5.6CI
R-19+5.6CI
R-19+5.6CI
R-19+5.6CI
R-19+5.6CI
Metal Framed R-
13 R-13R-
13+7.5ci
R-13+7.5ci
R-13+3.8ci
R-13+7.5ci
R-13+7.5ci
R-13+7.5ci
R-13+7.5ci
R-13+7.5ci
R-13+7.5ci
R-13+7.;5ci
R-13+7.5cfi
R-13+15.6ci
R-13+7.5ci
R-13+18.8
ci
Wood Framed & Other
R-13 R-13 R-13 R-13 R-13 R-13 R-13 R-13=
3.8ciR-
13+3.8ci
R-13+3.8ci
R-13+7.5ci
R-13+7.5ci
R-13+7.5ci
R-13+7.5ci
R-13+15.6
ci
R-13+15.6
ci
WALLS, ABOVE GRADE
Table 502.2(1)
Building Thermal EnvelopeR-Value: Wall Insulation
Walls weighing at least 35 lbs/ft2 of wall surface area
OR
25 lbs/ft2 of wall surface area if material weight is ≤ 120 lb/ft3
502.2.3, Table 502.2(1)
Building Thermal EnvelopeMass Walls
Climate Zones 1 (Group R) and 2 (all other) – Can use integral insulation instead of R-5.7 ci
Concrete block walls must comply with ASTM C 90, and
Ungrouted or partially grouted @ 32 inch. o.c. or less vertically or 48 inch. o.c. or less horizontally, and
Ungrouted cells must be filled with insulation material ≤ of 0.44 Btu-in./h-ft2 F
Climate Zone 1 “all other” No insulation required for mass walls
Table 502.2(1)
Building Thermal EnvelopeMass Walls: Concrete Masonry Units
Climate Zone
R-Value
1-2 R-163-4 except
MarineR-19
Marine 4-6 R-13+R-5.6ci7-8 R-19+R-5.6ci
Table 502.2(2)
Building Thermal EnvelopeMetal Building Walls
Cavity insulation or cavity plus continuous (ci)
Continuous insulation not broken up by framing members e.g. rigid board insulation
Table 502.2(1)
Building Thermal EnvelopeWood, Metal, Frame and Other Walls
Joist/Framing (Steel/Wood)
Insulation installed between framing
Mass Floors Materials weighing (of
floor surface area)35 lbs/ft2, or
25 lbs/ft2 if material weight is ≤ 12 lbs/ft3
Insulation installed continuously
Steel Floor Joist Systems (footnoted to Table 502.2(1))
R-38 in Climate Zones 6-8
502.2.5
Building Thermal EnvelopeFloors over Unconditioned Space
Climate Zone 1 2 3
4Except Marine
5And Marine
46 7 8
Mass NR
NR
R-6.3ci
R-8.3ci
R-6.3ci
R-8.3ci
R-10ci
R-10.4ci
R-10ci
R-12.5ci
R-12.5ci
R-14.6ci
R-15ci
R-16.7ci
R-15ci
R-16.7ci
Joist/FramingSteel/(Wood)
NR
NR R-19 R-30 R-19 R-30 R-30 R-30 R-30 R-30 R-30 R-30 R-30 R-30 R-30 R-30
Table 502.2(1), 502.2.5
FLOORS
Building Thermal EnvelopeFloors over Unconditioned Space
Climate Zone 1 2 3
4Except Marine
5And Marine 4 6 7 8
Unheated Slabs NR NR NR NR NR NR NR
R-10 for24 in. below
NRR-10 for 24 in. below
R-10 for 24 in. below
R-15 for 24 in. below
R-15 for 24. in. below
R-15 for24 in. below
R-15 for24 in. below
R-20 for 24 in. below
HeatedSlabs
R-7.5 for12 in. below
R-7.5 for12 in. below
R-7.5 for12 in. below
R-7.5 for12 in. below
R-10 for24 in below
R-10 for24 in. below
R-15 for24 in. below
R-15 for24 in. below
R-15 for24 in. below
R-15 for24 in. below
R-15 for24 in. below
R-20 for 48 in. below
R-20 for 24 in. below
R-20 for48 in. below
R-20 for48 in. below
R-20 for48 in. below
SLAB-ON GRADE FLOORS
Table 502.2(1), 502.2.6
Building Thermal EnvelopeSlab-on-Grade
Unheated slab – insulation required:
“All Other” in Climate Zones 6-8
“Group R” in Climate Zones 4-8
Heated slabs – insulation required in all Climate Zones
502.2.6
Building Thermal EnvelopeSlab-on-Grade
Climate
Zone1 2 3
4Except Marine
5And
Marine 46 7 8
Swinging
U-0.70
U-0.70
U-0.70
U-0.70
U-0.70
U-0.70
U-0.70
U-0.70
U-0.70
U-0.70
U-0.70
U-0.50
U-0.50
U-0.50
U-0.50
U-0.50
Roll-Up OrSliding
U-1.45
U-1.45
U-1.45
U-1.45
U-1.45
U-1.45
U-0.50
U-0.50
U-0.50
U-0.50
U-0.50
U-0.50
U-0.50
U-0.50
U-0.50
U-0.50
Table 502.2(1), 502.2.7
OPAQUE DOORS
Building Thermal EnvelopeOpaque Doors
Table 502.3, 502.3
Building Thermal EnvelopePrescriptive: Fenestration
Percentage of Vertical Fenestration Area to Gross Wall Area Allowed up to 40%
maximum of above grade wall
502.3.1 – Prescriptive (Max Area)
Building Thermal EnvelopePrescriptive: Maximum Vertical Fenestration
Based on above-grade wall area (gross) Includes walls between conditioned space and
unconditioned space or the great outdoors• Includes walls that are > 15% above grade
Total fenestration area (includes frame and glazing) Does not include opaque door area
502.3.1
Building Thermal EnvelopeVertical Fenestration
Two Options for Meeting the SHGC Requirements Fenestration product rated and labeled to NFRC 200, or Select default from Table 303.1.3(3)
Table 303.1.3(3)
Building Thermal EnvelopeFenestration SHGC Requirements
The Effect of Overhangs on Fenestration SHGC Overhangs allow a higher SHGC
product to be installed Projection factor must be
calculated
502.3.2
Building Thermal EnvelopeFenestration SHGC Requirements
Class Exercise
• Scope and Application– Section 501 - General
• Mandatory & Prescriptive Path Provisions– Section 502 - Building Envelope– Section 503 - Mechanical Systems– Section 504 - Service Water Heating– Section 505 - Electrical Power and Lighting
• Performance Path– Section 506 - Building Performance Path
IECC Chapter 5
503.2 - Mandatory Provisions
503.3 - Simple HVAC Systems and Equipment (503.3)
Section 503
Mechanical Systems
503.4 - Complex HVAC Systems and Equipment
- OR -
Provisions Applicable to ALL Mechanical Systems Duct and Plenum
Insulation and Sealing Piping Insulation HVAC System
Completion Air System Design and
Control Motor Nameplate
Horsepower Heating Outside a
Building
HVAC Load Calculations Equipment and System
Sizing HVAC Equipment
Performance Requirements HVAC System Controls Ventilation Energy Recovery
Ventilation Systems
503.2
Mechanical: Mandatory Provisions
Heating and cooling load sizing calculations required ASHRAE/ACCA Standard 183 Other approved computation procedures –
defined in Chapter 3• Exterior design conditions
– Specified by ASHRAE• Interior design conditions
– Specified by Section 302 of the IECC• ≤ 72oF for heating load• ≥ 75oF for cooling load
503.2.1 Mandatory
Mechanical: MandatoryHVAC Load Calculations
Output capacity SHALL NOT exceed sizing Select the system which serves the greater load,
heating or cooling– Exceptions
• Standby Equipment with Required Controls• Multiple Units with Combined Capacities Exceeding
Loads– Sequencing Controls Required
503.2.2 Mandatory
Mechanical: MandatoryHVAC Load Calculations
• Applies to all equipment used in heating and cooling of buildings
– Where components from different manufacturers are used calculations & supporting data demonstrating combined efficiency meets requirements
• Must comply with all listed efficienciesException: Water-cooled centrifugal water-
chilling packages
503.2.3 Mandatory Minimum Efficiency Requirements
Mechanical: MandatoryHVAC Performance
Table 503.2.3(2)
Mechanical: MandatoryHVAC Performance
Table 503.2.3(2)
Mechanical: MandatoryHVAC Performance
• Control required for each zone
503.2.4 Mandatory
• Thermostats must have at least a 5°F dead band
Exception:• Thermostats requiring
manual change over between heating and cooling
Mechanical: MandatorySystem Controls
Automatic time clock or programmable systemExceptions
• Zones operated continually• Zones with full HVAC load demand <6,800 Btu/h and has
a readily accessible shut off switch
Thermostatic setback capabilitiesCapability to maintain zone temps down to 55ºF
or up to 85ºF
Automatic setback and shutdown
503.2.4.3 Mandatory
Mechanical: MandatoryOff-Hour Controls
Motorized dampers that will automatically shut when the system or spaces are not in use.
Exceptions• Gravity dampers permitted in buildings < 3 stories• Gravity dampers permitted for buildings of any height
located in Climate Zones 1-3• Gravity dampers permitted for outside air intake or
exhaust airflows of 300 cfm (0.14m3/s) or less.
503.2.4.4 Mandatory
Mechanical: MandatoryShut-Off Dampers
DCV must be provided for each zone with spaces > 500 ft² and the average occupant load > 40 people/1000 ft² of floor area where the HVAC system has:
An air-side economizer, Automatic modulating control of the outdoor air damper,
or A design outdoor airflow > 3,000 cfmDemand control ventilation (DCV): a ventilation system
capability that provides for the automatic reduction of outdoor air intake below design rates when the actual occupancy of spaces served by the system is less than design occupancy.
503.2.5.1 Mandatory
Mechanical: MandatoryDemand Control Ventilation
Exceptions: Systems with energy recovery per 503.2.6 Multiple zone systems without direct digital
control of single zones communicating with central control panel
Systems with design outdoor airflow < 1,200 cfm Spaces where supply airflow rate minus any
makeup or outgoing transfer air requirement < 1,200 cfm
503.2.5.1 Mandatory
Mechanical: MandatoryDemand Control Ventilation
Applies to individual fan systems with Design supply air capacity ≥ 5,000 cfm Minimum outside air supply of ≥ 70% of design supply
air quantityExhaust air recovery efficiency must be ≥ 50%
503.2.6 Mandatory
Mechanical: MandatoryEnergy Recovery Ventilation
Exceptions: Where energy recovery ventilation systems prohibited by the
IMC Lab fume hood system with at least one of the following:
– VAV hood exhaust and room supply systems capable of reducing exhaust and makeup air volume to ≤ 50% of design values
– Direct makeup (auxiliary) air supply equal to at least 75% of exhaust rate, heated no warmer than 2ºF below room setpoint, cooled to no cooler than 3ºF above room setpoint, no humidification added, and no simultaneous heating and cooling use for dehumidification control
Systems serving uncooled spaces and heated to < 60ºF Where > 60% of outdoor heating energy is from site-recovered
or site solar energy Heating systems in climates < 3,600 HDD Cooling systems in climates with a 1% cooling design wet-bulb
temperature < 64ºF Systems requiring dehumidification that employ series-style
energy recovery coils wrapped around the cooling coil
503.2.6 Mandatory
Mechanical: MandatoryEnergy Recovery Ventilation
Insulation required for supply and return ducts and plenums
Located in unconditioned space – minimum R5
Located outside the building - minimum R8
Exceptions When located within
equipment When design temperature
difference between interior and exterior of the duct or plenum doesn’t exceed 15ºF
503.2.7 Mandatory
Mechanical: MandatoryDuct and Plenum Insulation and Sealing
Ducts designed to operate at static pressures ≤ 2 in. wg
Securely fastened and sealedExceptions
• When located within equipment• Design temperature difference between interior and
exterior of duct or plenum <15°F
503.2.7.1 & 503.2.7.2 Mandatory
Mechanical: MandatoryDuct Construction: Low and Medium Pressure
Ducts
Ducts designed to operate at static pressures > 3 in. wg to be leak tested in accordance with SMACNA HVAC Air Duct Leakage Test Manual
Air leakage rate ≤ 6.0CL = F x P0.65
• Where– F = leakage rate per 100 sf of duct surface area– P = test condition static pressure
Must test ≥ 25% of the duct area and meet the requirements
503.2.7.1.3 Mandatory
Mechanical: MandatoryDuct Construction: High Pressure Duct
Systems
FLUID
NOMINAL PIPE DIAMETER
≤ 1.5” ≥ 1.5”
Steam 1 ½ 3
Hot water 1 ½ 2
Chilled water, brine or refrigerant
1 ½ 1 ½
All piping serving heating or cooling system must be insulated in accordance with Table 503.2.8
Minimum Pipe Insulation(thickness in inches)
503.2.8 Mandatory, Table 503.2.8
Mechanical: MandatoryPiping Insulation
Exceptions: Piping internal to HVAC equipment (including
fan coil units) factory installed and tested Piping for fluid in temperature range
– 55 < temp < 105°F Piping for fluid not heated or cooled by
electricity or fossil fuels Runout piping ≤ 4’ in length and 1” in diameter
between the control valve and HVAC coil
503.2.8 Mandatory
Mechanical: MandatoryPiping Insulation
Air System BalancingHydronic System BalancingManuals
– Equipment Capacity and Required Maintenance
– Equipment O & M Manuals – HVAC System Control Maintenance and
Calibration Information– Written Narrative of Each System Operation
503.2.9 Mandatory
Mechanical: MandatoryHVAC System Completion
Maximum fan power requirements Applies to HVAC systems with total fan system power > 5 hp Each HVAC system at design conditions can not exceed allowable fan system motor
nameplate hp (Option 1) or fan system bhp (Options 2) in Table 503.2.10.1(1)
TABLE 503.2.10.1.1(1) FAN POWER LIMITATION
bhp = brake horsepower
503.2.10 Mandatory, Table 503.2.10.1(1)
Mechanical: MandatoryAir System Design and Control
• Fan System BHP – The sum of the fan brake horsepower of all fans that are required to operate a fan system design conditions to supply air from the heating or cooling source to the conditioned space and return it to the source or exhaust it to the outdoors.
Mechanical: MandatoryAir System Design and Control
BHP option includes adjustment “adders” certain devices
Table 503.2.10.1(2)
DEVICE ADJUSTMENT Credits
Fully ducted return and/or exhaust air systems 0.5 in w.c.
Return and/or exhaust air flow control devices 0.5 in w.c Exhaust filters, scrubbers, or other exhaust treatment.
The pressure drop of device calculated at fan system design condition.
Particulate Filtration Credit: MERV 9 thru 12 0.5 in w.c.
Particulate Filtration Credit: MERV 13 thru 15 0.9 in w.c. Particulate Filtration Credit: MERV 16 and greater and electronically enhanced filters
Pressure drop calculated at 2x clean filter pressure drop at fan system design condition.
Carbon and Other gas-phase air cleaners
Clean filter pressure drop at fan system design condition.
Heat Recovery Device Pressure drop of device at fan system design condition.
Evaporative Humidifier/Cooler in series with another cooling coil
Pressure drop of device at fan system design conditions
Sound Attenuation Section 0.15 in w.c. Deductions
Fume hood exhaust exception -1.0 in w.c.
Allowable Fan Motor Horsepower
Commercial Building Mechanical Systems: Allowable Fan Motor Horsepower503.2.10 Mandatory
Mechanical: MandatoryAir System Design and Control
ExceptionsHospital and laboratory systems using
flow control devices on exhaust and/or return for health and safety or environmental control permitted to use variable fan power limitation
Individual exhaust fans ≤ 1 hpFans exhausting air from fume hoods
503.2.10.1 Mandatory
Mechanical: MandatoryAllowable Fan Motor Horsepower
Selected fan motor to be no larger than first available motor size greater than bhp
Fan bhp on design documents
Exceptions Fans < 6 bhp, where first available motor larger than
bhp has nameplate rating within 50% of bhp, next larger nameplate motor size may be selected
Fans ≥ 6 bhp, where first available motor larger than bhp has nameplate rating within 30% of bhp, next larger nameplate motor size may be selected
bhp = brake horsepower503.2.10.2 Mandatory
Mechanical: MandatoryMotor Nameplate Horsepower
Have to be radiant systems
Controlled by an occupancy sensing device or timer switch
System is automatically de-energized when no occupants are present.
503.2.11 Mandatory
Mechanical: MandatoryHeating Outside a Building
• 503.2.11 – Systems installed outside buildings shall be radiant systems, with occupancy systems or timers.
Mechanical: MandatoryHeating Outside a Building
Simple systems Unitary or
packaged HVAC equipment
Serves one zone and controlled by a single thermostat
Buildings served by unitary or packaged
HVAC each serving 1 zone controlled by 1
thermostat. Two-pipe heating systems serving
multiple zones are included if no cooling
system is installed [Tables 503.2.3(1)
through 503.2.3(5)]
Section 503.3 Simple
Systems
503.3, Tables 503.2.3(1) through 502.2.3(5)
Mechanical: PrescriptiveSimple or Complex Systems
Simple Systems
Mechanical: PrescriptiveSimple Systems
Unitary or packaged, single zone controlled by a single thermostat in the zone served.
Simple Systems Unitary packaged heating and cooling
systems Split system heating and cooling systems Packaged terminal A/C and HPs Fuel-fired furnace Electrical resistance heating Two-pipe heating systems w/o cooling
503.3
Mechanical: PrescriptiveSimple HVAC Systems & Equipment
Must include economizers dependent on climate zone Capable of providing 100-percent outdoor air even if
additional mechanical cooling is required (integrated economizer)
Must provide a means to relieve excess outdoor air
503.3
Mechanical: PrescriptiveSimple HVAC Systems & Equipment
CLIMATE ZONES ECONOMIZER REQUIREMENT
1A, 1B, 2A, 7, 8 No requirement
2B, 3A, 3B, 3C, 4A, 4B, 4C, 5A, 5B, 5C, 6A, 6B
Economizers on cooling systems ≥ 54,000 Btu/ha
a The total capacity of all systems without economizers shall not exceed 480,000 Btu/h per building, or 20 percent of its air economizer capacity, whichever is greater
Table 503.3.1(1)
503.3.1, Table 503.3.1(1)
Mechanical: PrescriptiveSimple Economizers
CLIMATE ZONES COOLING EQUIPMENT PERFORMANCE IMPROVEMENT (EER OR IPLV)
2B 10% Efficiency Improvement
3B 15% Efficiency Improvement
4B 20% Efficiency Improvement
Trade-off high cooling efficiency for economizerTable 503.3.1(2)
Two Exceptions
503.3.1, Table 503.3.1(2)
Mechanical: PrescriptiveSimple Economizers
Complex Systems
Mechanical: PrescriptiveComplex Systems
This section applies to all HVAC equipment and systems not included in Section 503.3
Complex Systems Packaged VAV reheat Built-up VAV reheat Built-up single-fan, dual-duct VAV Built-up or packaged dual-fan, dual-duct VAV Four-pipe fan coil system with central plant Water Source heat pump with central plant Any other multiple-zone system Hydronic space heating and cooling system
503.4 Prescriptive
Mechanical: PrescriptiveComplex Systems
System ≥ 300,000 Btu/h must includeTemperature reset or variable flow
• Automatic resets for supply water temperature by at least 25% of design supply-to-return temperature differences or
• Reduce system pump flow by 50% of design flow using
– Multiple Staged Pumps– Adjustable Speed Drives– Control Valves that modulate as a function of load
503.4.3.4
Commercial Building Mechanical Systems: Hydronic Water Loop Heat Pump Systems
Mechanical: PrescriptiveHydronic Systems Controls
• Individual dual duct or mixing reheating and cooling systems with a single fan and with total capacities > 90,000 Btu/h (7.5 tons) should not have economizers
503.4.5.3
Mechanical: PrescriptiveSingle Fan Dual Duct & Mixing VAV Systems,
Economizers
Class Exercise
• Scope and Application– Section 501 - General
• Mandatory & Prescriptive Path Provisions– Section 502 - Building Envelope– Section 503 - Mechanical Systems– Section 504 - Service Water Heating– Section 505 - Electrical Power and Lighting
• Performance Path– Section 506 - Building Performance Path
IECC Chapter 5
Table 504.2 Minimum Performance of Water-Heating Equipment
Water Heater Types Covered• Electric Storage• Gas and Oil Storage• Instantaneous Water Heaters – Gas
and Oil• Hot water boilers – gas and oil• Pool heaters• Unfired storage tanks
Temperature Controls (504.3)Heat Traps (504.4)
504 Mandatory, Table 504.2
Service Water HeatingMandatory: Performance Efficiency
Non-circulating system insulation requirements First eight feet of outlet piping on systems with no
integral heat traps 1/2 inch of insulation required
Circulating systems 1 inch of insulation
504.5
Service Water HeatingMandatory: Pipe Insulation
Ability to turn off circulating hot water pumps and heat trace tape when the system is not in operation
Automatically or manually
504.6
Service Water HeatingMandatory: System Controls
Pool heaters (504.7.1) Readily accessible on-off switch Natural gas or LPG fired pool heaters will not have
continuously burning pilot lights
Time switches (504.7.2) Automatic controls required to operate pool heaters and
pumps on a preset schedule Exceptions
• Where public health standards require 24 hour operation• Where pumps are required to operate solar and waste heat
recovery pool heating systems
504.7
Service Water HeatingMandatory: Pool Requirements
Heated pools required to have a pool cover Pool cover must be vapor retardant
Pools heated to over 90oF Minimum R-12 insulation
Exception Pools deriving > 60% energy for heating from site-
recovered energy or solar source504.7.3
Service Water HeatingMandatory: Pool Covers
Class Exercise
• Scope and Application– Section 501 - General
• Mandatory & Prescriptive Path Provisions– Section 502 - Building Envelope– Section 503 - Mechanical Systems– Section 504 - Service Water Heating– Section 505 - Electrical Power and Lighting
• Performance Path– Section 506 - Building Performance Path
IECC Chapter 5
• Newly Installed Lighting Systems in a New Building, Addition, or Tenant Improvements and Build-outs
• Existing Lighting Systems that are altered• Change in Occupancy that Increases Energy• Change in Occupancy that requires less LPD as shown in Table
505.3.2Exceptions:
• Historic buildings– State or National listing– Eligible to be listed
• Alterations where less than 50% of the luminaires in a space are replaced and installed interior power lighting is not increased
• Lighting within dwelling units– Where ≥ 50% of permanently installed fixtures include high-
efficacy lamps
101
Lighting SystemsScope
• Interior Lighting requirements Required Controls Wattage/Efficiency Limits
• Interior Lighting Power Allowances
• Exterior Lighting Controls Required Controls Lamp Efficiency
• Exterior Lighting Power Allowances
• Electric Metering505 Mandatory
Lighting SystemsScope
Independent Lighting Control required for each space surrounded by floor-to-ceiling partitions
Must be located in the space served, - OR -
Switched from a remote location• Must have indicator that identifies
the lights served and their status (off or on)
Exemptions• Security or emergency areas that
must be continuously lighted• Lighting in stairways or corridors
that are elements of the means of egress
505.2
Lighting SystemsMandatory: Interior Lighting Controls
Light Reduction Controls must allow the occupant to reduce connected lighting
By at least 50% In a reasonably uniform
illumination pattern
505.2.2.1
Lighting SystemsMandatory: Interior Light Reduction
Controlling all lamps or luminaires Dual switching of alternate rows of luminaires, alternate luminaires
or lamps Switching middle lamp luminaires independently from the outer
lamps Each luminaire or each lamp
SS
Dimmer SwitchD
Alternating Luminaires
Dimming
SS
Alternating Lamps
505.2.2.1
Lighting SystemsMandatory: Interior Light Reduction Control
Options
Light Reduction Control Not required for the following:
Areas with only one luminaire
Areas controlled by occupancy sensor
Corridors, storerooms, restrooms or public lobbies
Sleeping unitsSpaces with <0.6 w/ft2
505.2.2.1
Lighting SystemsMandatory: Interior Light Reduction Exemptions
Automatic lighting shutoff control device required in all buildings larger than 5,000 ft2
Building Defined: “Any structure used or intended for supporting or sheltering any use or
occupancy”Building area surrounded by exterior walls and fire walls
Exempted spacesSleeping unitsLighting for patient careWhen an automatic shutoff would endanger occupant safety or security
505.2.2.2
Lighting SystemsMandatory: Interior Automatic Lighting Shutoff
1. Control lights on a scheduled basis (automatic time switch)• Time-of-day controller• Controls ≤ 25,000 ft2 and
not more than one floor, or
2. Occupant sensor• Turn lights off within 30
minutes of occupant leaving the space
3. Signal from another control or alarm that indicates the area is unoccupied
Office
Occupancy Sensor
ConferenceRoom
Restrooms
Lobby
Connect to Lighting in Lobby
Open Bay Office
Connect to Lighting in Open Bay Office
Automatic Lighting Control
110’
50’
Automatic Lighting Shutoff Compliance Options
Courtesy Britt-Makela Group
505.2.2.2
Lighting SystemsMandatory: Automatic Shutoff Options
Readily accessible Within view of the lights or area controlled Manually operated ≤ 2 hour override
– The override allows lighting to remain on no more than 2 hours when override is initiated
Controls an area ≤ 5,000 ft2
Exemptions– Can be over 2 hour override in malls and arcades, auditoriums,
single-tenant retail space, industrial facilities and arenas when using captive key override
– Override in malls and arcades, auditoriums, single-tenant retail space, industrial facilities and arenas can cover up to 20,000 ft2
505.2.2.2.1
Lighting SystemsMandatory: Automatic Shutoff Occupant
Override
Feature that turns off all loads for 24 hours then resumes the normally scheduled operationExceptions
Retail stores and associated mallsRestaurantsGrocery storesPlaces of religious worshipTheaters
505.2.2.2.2
Lighting SystemsMandatory: Automatic Shutoff Holiday
Scheduling
• Daylight Zones Must have individual control of the lights independent of
general area lighting• Contiguous daylight zones adjacent to vertical fenestration
Can be controlled by a single controlling device if the zone doesn’t include areas facing more than two adjacent orientations (i.e., north, east, south, west)
• Daylight zones under skylights > 15 ft from the perimeter Must be controlled separately from daylight zones adjacent to
vertical fenestrationException: Daylight spaces 1) enclosed by walls or ceiling height
partitions and 2) containing two or fewer light fixtures • not required to have a separate switch for general area lighting
Note: required controls may be manual or automatic
505.2.2.3
Lighting SystemsMandatory: Daylight Zone Control
the width of the window plus 2 feet on each side, or
the window width plus distance to opaque partitions, or
the window width plus one-half the distance to adjacent skylight or vertical fenestration, whichever is least.505.2.2.3
Lighting SystemsDaylight Zone Definition
The daylight zone depth is assumed to be 15 feet into the space or to the nearest ceiling height opaque partition, whichever is lessThe daylight zone width is assumed to be:
The area under skylights whose horizontal dimension, in each direction, is equal to the skylight dimension plus the smaller of: The floor-to-ceiling height, or The distance to a ceiling height opaque partition, or One-half the distance to adjacent skylights or vertical fenestration
(whichever is least)
505.2.2.3
Lighting SystemsDaylight Zone Under Skylights
Standard Room Suite
$$
$$
$$
$$
$$$$
$$
$$$$
$$
Applies to hotels, motels, boarding houses or similar Master switch required at each room or main room
entry Must control all permanently wired luminaires or
switched receptaclesExceptions: bathrooms
505.2.3
Lighting SystemsMandatory: Sleeping Unit Controls
For dusk-to-dawn lighting: astronomical time switch or photosensor For all other: astronomical time switch OR
photosensor + time switch All time switches must have at least 10 hour battery
backup
505.2.4
Lighting SystemsMandatory: Exterior Lighting Controls
Tandem Wiring for all Odd Numbered Lamp Configurations Exceptions
Where electronic high frequency ballasts are used
Luminaires on emergency circuits
Luminaires with no available pair in the same area
505.3 Mandatory
Lighting SystemsMandatory: Tandem Wiring
Exit Signs Internally illuminated exit signs shall not
exceed 5 watts per side
505.4
Lighting SystemsMandatory: Exit Signs
Sum the wattage of all proposed connected lighting power
This must include all lighting that is part of the design for the space including:
Overhead lighting Task lighting Decorative lighting
505.5.1
Lighting SystemsPrescriptive: Interior Lighting Power
Connected Interior Lighting Power must not exceed Interior Lighting Power Allowance
1. Calculate Interior Lighting Power Allowance• Building Area type allowance• Additional allowances
2. Calculate proposed connected lighting power• Wattage calculation “rules”• Exempted lighting
3. Compare values: proposed wattage must be less than or equal to allowed wattage
505.5
Lighting SystemsPrescriptive: Interior Lighting Power
Connected power for following not included in calculations: Professional sports arena playing field Sleeping unit lighting Emergency lighting automatically off during normal building
operation Lighting in spaces specifically designed for use by occupants
with special lighting needs including visual impairment and other medical and age related issues
Lighting in interior spaces specifically designated as a registered interior historic landmark
Casino gaming areas Lighting equipment used for the following exempt if in
addition to general lighting and controlled by an independent control device
• Task lighting for medical and dental procedures• Display lighting for exhibits in galleries, museums and
monuments
505.5.1
Lighting SystemsExemptions to Interior Lighting Power
Theatrical, stage, film, and video production Used for photographic processes Integral to equipment or instrumentation installed by
manufacturer Plant growth or maintenance Advertising or directional signage Food warming and food prep equipment (in restaurant
bldgs & areas) Lighting equipment that is for sale Lighting demonstration equipment in lighting education
facilities Approved because of safety or emergency
considerations, exclusive of exit lights Integral to both open and glass-enclosed refrigerator and
freezer cases In retail display windows when the display is enclosed by
ceiling-height partitions Furniture-mounted supplemental task lighting controlled
by automatic shutoff505.5.1
Lighting SystemsExemptions to Interior Lighting Power
Building Area TypeNote: Alternate standard
ASHRAE/IESNA 90.1-2007 provides whole building and space-by-space options
Table 505.5.2
505.5.2
Lighting SystemsInterior Lighting Power Allowances
First, choose an appropriate “Building Area Type” from the allowance table (505.5.2)
“Building Area” includes all spaces that are associated with that business or function type.
For example a space with:• Corridors,• Restrooms,• A lobby, and• Office space
…would be considered an Office Building Area Type
Then...multiply the lighting power density (W/ft2) by the total building square footage to get allowed watts for compliance
505.5.2
Lighting SystemsInterior Lighting Power Allowance Calculation
Office: 200,000 ft2
1.0 W/ft2 = 200,000 W
Table 505.5.2
Table 505.5.2
Example: OfficeA 200,000 ft2 office building that contains corridor, restrooms, break rooms and a lobby is given 1.0 W/ft2 for the entire building
Lighting SystemsInterior Lighting Power Allowance Calculation
(Retail Area 1 x 0.6 W/ft2) + (Retail Area 2 x 0.6 W/ft2) + (Retail Area 3 x 1.4 W/ft2) + (Retail Area 4 x 2.5 W/ft2),
Where: Retail Area 1 = the floor area for all
products not listed in Retail Area 2, 3 or 4. Retail Area 2 = the floor area used for the
sale of vehicles, sporting goods and small electronics.
Retail Area 3 = the floor area used for the sale of furniture, clothing, cosmetics and artwork.
Retail Area 4 = the floor area used for the sale of jewelry, crystal, and china.
Table 505.5.2 - Footnotes
Lighting SystemsRetail Lighting Power Allowance
Additional Interior Lighting Power Allowance = 1000 watts +
Exception: Other merchandise categories may be included in Retail Areas 2 through 4 above, provided that justification documenting the need for additional lighting power based on visual inspection, contrast, or other critical display is approved by the authority having jurisdiction. Photo courtesy of Ken Baker, K energy
Table 505.5.2 - Footnotes
Lighting SystemsRetail Lighting Power Allowance
How is an allowance determined if the building has more than one Building Area Type?
Example – A building contains the following area types• Museum: 40,000 ft2
• Retail 5,000 ft2
• Cafeteria: 10,000 ft2
Use the more specific building area type where more than one area type exists in the buildingSum the individual (lighting power density x area square footage) values for Total Power Allowance
505.5.2
Lighting SystemsLighting Power Allowance for Multiple
Occupancy
Cafeteria:10,000 ft2
at 1.4 W/ft2 = 14,000 W Museum: 40,000 ft2
at 1.1 W/ft2 = 44,000 W
Retail: 5,000 ft2
at 1.5 W/ft2 = 7,500 W
Total watts allowed = 65,500 W
Table 505.5.2
505.5.2
Lighting SystemsLighting Power Allowance for Multiple
Occupancy
Lighting wattage must be calculated in accordance with Section 505.6
Screw lamp holders: maximum labeled wattage of the luminaire Low voltage lighting: transformer wattage Line voltage track:
1. specified wattage with minimum of 30 W/linear ft OR2. wattage limit of system’s circuit breaker OR3. wattage limit of other permanent current limiting devices
Other: manufacturer’s rated wattage of lamp and associated ballast
505.6 Mandatory
Lighting SystemsMandatory: Exterior Lighting Requirements
Building grounds lighting luminaires over 100 watts must have source efficacy of at least 60 lumens per watt
Exceptions Controlled by motion sensor Any of the exterior lighting power allowance exceptions As approved for a historical, safety, signage, or emergency consideration
Light SourceTypical System Efficacy Range in
LPW(varies depending on wattage and
lamp type)Incandescent 10-18Halogen incandescent 15-20Compact fluorescent (CFL)
35-60
Linear fluorescent 50-100Metal halide 50-90
505.6.1
Lighting SystemsMandatory: Building Grounds Lighting
Connected Exterior Lighting Power must not exceed Exterior Lighting Power Allowance
1. Calculate exterior lighting power allowance • Lighting power densities by exterior function and by
applicable lighting zone2. Calculate proposed connected lighting power
• Wattage calculation “rules”• Exempted lighting
3. Compare values: proposed wattage must be less than or equal to allowed wattage
505.6.2
Lighting SystemsMandatory: Exterior Lighting Power Limits
The following lighting does not need to be included in the proposed lighting calculation:• Specialized signal, directional, and marker lighting associated with transportation• Advertising signage or directional signage• Lighting integral to equipment or instrumentation and installed by its
manufacturer• Lighting for theatrical purposes, including performance, stage, film production,
and video production• Lighting for athletic playing areas• Temporary lighting• Lighting for industrial production, material handling, transportation sites, and
associated storage areas• Theme elements in theme/amusement parks• Lighting used to highlight features of public monuments and registered historic
landmark structures or buildings
505.6.2)
Lighting SystemsExemption from Exterior Lighting Calculation
What areas are covered under exterior lighting allowances?
Tradable surfacesCommon exterior lighted needs that can be traded for other needs.
• For example, wattage allowed for parking lot lighting can be “traded” and used for canopy lighting.
Nontradable surfacesLess common exterior lighted needs that cannot be traded for other needs.
• These applications have more specific security or task illuminance needs.
Table 505.6.2(2)
Lighting SystemsExterior Lighting Power Limits
Uncovered parking lots and areas Walkways (under and over 10 feet
wide) Stairways Pedestrian tunnels Main building entrances and exits Other doors Entry canopies Free-standing and attached sales
canopies Open sales areas Street frontage sales areas
Table 505.6.2(2)
Lighting SystemsExterior Lighting Tradable Surfaces
Building facades Automated teller machines and night depositories Entrances and gatehouse inspection stations at guarded facilities Loading areas for law enforcement, fire, ambulance and other emergency
vehicles Drive-up windows/doors Parking near 24-hour retail entrances
Table 505.6.2(2)
Lighting SystemsExterior Lighting Non-Tradable Surfaces
Lighting Zone
Description
1 Developed areas of national parks, state parks, forest land, and rural areas
2 Areas predominantly consisting of residential zoning, neighborhood business districts, light industrial with limited nighttime use and residential mixed use areas
3 All other areas4 High-activity commercial districts in
major metropolitan areas as designated by the local land use planning authority
Table 505.6.2(1)
Lighting SystemsExterior Lighting Zones
Zone 1 Zone 2 Zone 3 Zone 4 Tradable
SurfacesBuilding Entrances and Exits
Main entries
20 W/linear foot of door width
20 W/linear foot of door
width
30 W/linear foot of door width
30 W/linear foot of door
width
Other doors 20 W/linear
foot of door width
20 W/linear foot of door width
20 W/linear foot of door width
20 W/linear foot of door width
Entry Canopies 0.25 W/ft2 0.25 W/ft2 0.4 W/ft2 0.4 W/ft2
Sales Canopies Free-standing
and attached
0.6 W/ft2 0.6 W/ft2 0.8 W/ft2 1.0 W/ft2
Outdoor Sales Open areas
(including vehicle
sales lots) 0.25 W/ft2 0.25 W/ft2 0.5 W/ft2 0.7 W/ft2
Street frontage for
vehicle sales lots in
addition to “open
area” allowance
No allowance 10 W/linear foot
10 W/linear foot
30 W/linear foot
Table 505.6.2(2)
Lighting SystemsExterior Lighting Power Allowances
Example
Bank
ATM
Walkway5 ft wide
Canopy
Parking Lot
Parking: 10,000 ft2
Canopy: 100 ft2Walkway: 300 ft
ATM –One location
How many tradable watts are allowed for this project? How many nontradablewatts?
Bank
ATM
Walkway5 ft wide
Canopy
Parking Lot
Bank
ATM
Walkway5 ft wide
Canopy
Parking Lot
Parking: 10,000 ft2Canopy: 100
ATM –One location
How many tradable watts are allowed for this project? How many nontradablewatts?
Lighting SystemsExterior Lighting Power Allowances
Separate metering required for each dwelling unit
505.7 Mandatory
Lighting SystemsMandatory: Electrical Energy Consumption
Class Exercise
• Scope and Application– Section 501 - General
• Mandatory and Prescriptive Path Provisions– Section 502 - Building Envelope– Section 503 - Mechanical Systems– Section 504 - Service Water Heating– Section 505 - Electrical Power and Lighting
• Performance Path– Section 506 - Building Performance Path
IECC Chapter 5
• Energy loads that must be included in the Energy Simulation Analysis– Heating, cooling systems and fans systems– Service water heating– Lighting power– Receptacle and process loads
• Mandatory requirements– Mandatory provisions of building envelope,
mechanical, service water heating and lighting
Total Building PerformanceScope
Need to model a standard reference design to the mandatory and prescriptive requirements.
Convert annual energy consumption to annual energy cost.
Need to model your proposed design.Convert annual energy consumption to annual energy cost.
Compliance is based on annual energy cost for proposed design < annual cost for standard reference design.
For both cases unite energy cost has to be the same.For both cases, simulation rules may apply.
506.3
Total Building PerformancePerformance-Based Compliance
506.3
Compliance based on total building performance requires that a proposed building (proposed design) be shown to have an annual energy cost that is less than or equal to the annual energy cost of the standard reference design.
Energy prices shall be taken from a source approved by the code official, such as the Department of Energy, Energy Information Administration's State Energy Price and Expenditure Report.
Total Building PerformancePerformance-Based Compliance
http://www1.eere.energy.gov/buildings/commercial_initiative/modeling_software.html
Calculation Software Tools – Sec. 506.6
ASHRAE 90.1Compliance Option
IECC Code ComplianceExercise
Building Location: Phoenix, AZEnergy Code: 2009 IECCOccupancy: Retail (Gr0up M) Construction:• Single-story, pitched wood roof
with flat ceiling, wood-frame walls (16” o.c.), concrete slab-on-grade without basement. Openings on all four walls.
Energy Code Compliance Exercise
3’ x 7’ door
Energy Code Compliance Exercise
Determine energy code compliance using the following paths:
1)Prescriptive requirements2)COMcheck energy compliance software –
www.energycodes.gov
You must select:3)Insulation values for walls) and ceiling4)U-factor and SHGC for fenestration5)Service water heating6)Mechanical systems7)Interior lighting
COMcheck™ DOE’s commercial compliance software
(Windows or Mac version)
Desktop Software Tools Web-Based Tools
www.energycodes.gov
• For commercial buildings- can show compliance through the prescriptive approach, trade-off approach or the performance approach.
• COMcheck utilizes only the trade-off approach.
COMcheck™
DOE’s commercial compliance software
Case StudyCommercial Renovation
The office space goes beyond code compliance to result in 42.3% energy savings of the proposed building over the baseline building (ASHRAE 90.1 2004).
Commercial Case StudyMajor Renovation – Downtown Scottsdale
Existing Building:Office with 2nd story apartment1614 sq. ft. conditioned space1110 sq. ft. roof deckRenovated Building:Two story design office and studio2330 sq. ft. conditioned space340 sq. ft. roof deck
FLOOR LAYOUT
The building was built in 1981 and is two stories with office on the first floor and residence on the second.
Commercial Case StudyMajor Renovation – Downtown Scottsdale
As a major renovation, the project complies to the scope and requirements of additions and alterations to existing buildings.
Main points of Focus :1. Building Envelope :
Ceiling and Skylights
2. Internal Loads3. High efficiency
HVAC Systems
• Simulation Software Used: eQuest (DOE2.2)
• Code Compliance to: ASHRAE 90.1 2004
Commercial Case StudyMajor Renovation – Downtown Scottsdale
ENERGY MODELING
BUILDING ENVELOPE
• Ceiling insulation has been added to improve the efficiency of the building envelope
• New insulated walls at east and west exposures with exterior radiant finishes
• New high performance windows on east and west exposures with exterior movable louvers
Before Retrofit
After Retrofit
Description IECC Project
Ceiling R Value 20ci 34.29ciWall R Value R-13 R-19Window U Factor 0.75 0.29Window SHGC 0.33 0.39
Commercial Case StudyMajor Renovation – Downtown Scottsdale
Old Systems :• 3 Ton Heat Pump units. SEER 10.New Systems:• Two 5 Ton high efficiency Trane SEER 16
heat pump two stage units with R410A refrigerant.
• No Economizers.Ventilation per IMC:• HP-1 is designed to provide 100 CFM of
OSA• HP-2 is designed to be provide with 200
CFM. • Demand controlled ventilation is exempt
due to an occupant load of less than 40.Description IECC Project
Cooling System Efficiency SEER13 SEER16MECHANICAL SYSTEMS: BEYOND CODE
Commercial Case StudyMajor Renovation – Downtown Scottsdale
MECHANICAL
LIGHTING
LIGHTING EFFICIENCY• 15% energy savings over baseline
building in lighting end use
Occupancy Sensors:• A 10% lighting power credit applied to
all lighting connected to occupancy sensors.
• Project has installed occupancy sensors for 75% of the connected lighting load
LIGHTING SYSTEM: BEYOND CODE
Commercial Case StudyMajor Renovation – Downtown Scottsdale
SOLAR PHOTOVOLTAIC SYSTEM• Twelve Kyocera photovoltaic modules
rated at 2.47 DC• Offsets approximately 23% of the annual
energy use • The actual offset per year in costs is about
$610
Commercial Case StudyMajor Renovation – Downtown Scottsdale
RENEWABLE ENERGY
ANNUAL ENERGY CONSUMPTION
Energy Analysis Summary
Commercial Case StudyMajor Renovation – Downtown Scottsdale
What’s on the horizon? 2012 IECC
International Green Construction Code (IgCC)
ASHRAE 189.1
Released in 2011
New compliance option to choose between high performance lighting, high performance HVAC equipment, or onsite renewable power generation
More efficient air leakage requirements by requiring continuous air barriers for the building envelope
Commissioning requirement for HVAC systems
2012 IECCCommercial Changes
Most significant increase in history of energy efficiency codes
Released in 2011
Increased efficiency of the opaque thermal envelope provisions
Increased fenestration efficiency Mandated automatic daylighting
controls for buildings with a window-to-wall ratio over 30%
A requirement for skylights and daylighting controls for spaces over 10,000 ft2 in certain building types
Recognizes the the energy code as a design document
2012 IECCCommercial Changes (cont.)
Released March 2012
Site Development and Land Use
Materials Resources Energy Efficiency Water Efficiency Indoor Environmental
Quality Commissioning, Operation
and Maintenance
International Green Construction Code (IgCC)
• Commercial and multi-family projects• Overlay code designed to integrate
with established building codes• Written in mandatory language as a
model code for local adoption• Not a substitute for good design• Work within regulatory framework
International Green Construction Code (IgCC)
LEED andOther Green Rating Programs
Signature Buildings
International Green Construction CodeStandard Buildings
Closing gap betweenminimum code requirements
and criteria for LEED certification
Gap between IgCC and LEED
Ceiling
Floor
Energy Efficiency and Atmospheric Quality
Zero Energy Performance Index (zEPI) of 51
Scottsdale’s current energy code requires a baseline energy performance equivalent to a zEPI of 62
2000 2012 2015 2018 2021 2024 2027 20300
20406080
100120
zEPI Score
zEPI Score
Energy Efficiency and Atmospheric Quality
Energy Metering and Monitoring capability to measure energy use and on-site
production data acquisition and management system capable
of storing not less than 36 months of data Renewable Energy Systems renewable energy must
provide at least 2% of total calculated annual energy use
ASHRAE 189.1PStandard for Green Commercial
Buildings
Site SustainabilityWater Use EfficiencyEnergy EfficiencyIndoor Environmental
QualityMaterials and ResourcesConstruction and
Operation
SS
WE
EE
IEQ
MR
CO
2011 Edition
Energy Efficiency Highlights
• More energy efficient than ASHRAE 90.1- 2010
• Renewable energy Provisions
• Energy measurement for verification
• Electric peak load reduction
Resources
Adopt, Implement, EnforceResources
Resources
• http://www.iccsafe.org• http://www.energycodes.gov• http://bcap-energy.org• http://www.naseo.org• http://www.eere.energy.gov• https://energycode.pnl.gov/REScheckWeb/• https://energycode.pnl.gov/COMcheckWeb/• http://resourcecenter.pnl.gov/cocoon/
morf/ResourceCenter