Chilled Water Piping Systems (VPF Focus)

Roy hubbard

Embed Size (px)

Citation preview

Page 1: Roy hubbard

Chilled Water Piping Systems (VPF Focus)

Page 2: Roy hubbard

Agenda – Chilled Water Distribution Systems

Chilled Water Distribution Systems

Primary (Constant) / Secondary (Variable – 2W Valves)

Low Delta T

Primary Only (Variable Flow - 2W Valves)

VPF Design/Control Considerations

Page 3: Roy hubbard

Primary (Constant Flow) / Secondary (Variable Flow)

Page 4: Roy hubbard

Primary/Secondary System

Primary Pumps

Secondary Pumps

Common Pipe

Typical load with two way valve

Page 5: Roy hubbard

Primary (Constant Flow) / Secondary (Variable Flow)

2 Way Valves

Higher Capital Cost Installed (vs Constant Flow 3W Valve system)

Lower CHW Pumping Energy (vs Constant Flow 3W Valve system)

Well Understood & Easy to Control

Page 6: Roy hubbard

Primary/Secondary System at Design

56.0 °F

56.0 °F

56.0 °F

44.0 °F

44.0 °F

44.0 °F

Primary Pumps

1000 GPM Each

3000 GPM @ 56.0 °F

Secondary Pumps

3000 GPM @ 44.0 °F

Typical Coil

No flow

44.0 °F

56.0 °F

500 ton chillers1000 GPM Each56.0-44.0°F

Page 7: Roy hubbard

Primary/Secondary System at Part Load

53.0 °F

53.0 °F

53.0 °F

44.0 °F

44.0 °F

44.0 °F

Primary Pumps

1000 GPM Each

3000 GPM @ 53.0 °F

Secondary Pumps

2250 GPM @ 44.0 °F

Typical Coil

44.0 °F

56.0 °F

750 GPM @ 44.0 °F

2250 GPM @ 56.0 °F

75% System Load

Page 8: Roy hubbard

Primary/Secondary System

53.0 °F

53.0 °F

44.0 °F

44.0 °F

Primary Pumps

1000 GPM Each

2000 GPM @ 53.0 °F

Secondary Pumps

1500 GPM @ 44.0 °F

Typical Coil

44.0 °F

56.0 °F

500 GPM @ 44.0 °F

1500 GPM @ 56.0 °F

OFF 50% System Load

Page 9: Roy hubbard

Low Delta T Syndrome

Page 10: Roy hubbard

10

Dirty Coils

Major Causes of Low Delta T

Page 11: Roy hubbard

Chilled Water Coil

Page 12: Roy hubbard

12

Dirty Coils

Controls Calibration

Leaky 2 Way Valves

3 Way Valves at end of Index circuit

Major Causes of Low Delta T

Page 13: Roy hubbard

Primary/Secondary System

Primary Pumps

Secondary Pumps

Common Pipe

Page 14: Roy hubbard

Primary/Secondary System

Primary Pumps

Secondary Pumps

Common Pipe

Page 15: Roy hubbard

15

Dirty Coils

Controls Calibration

Leaky 2 Way Valves

3 Way Valves at end of Index circuit

Coils piped up backwards

Major Causes of Low Delta T

Page 16: Roy hubbard

Chilled Water Coil

Page 17: Roy hubbard

17

P Load = Flow X Delta T S Load = Flow X Delta T

Primary (Constant) / Secondary (Variable)

Secondary Pumps

Primary Pumps

Typical load with 2 way valve

Decoupler/Bypass

Page 18: Roy hubbard

18

100% Load = 100% Sec Flow

Primary (Constant) / Secondary (Variable)Ideal Operation

Secondary Pumps

Primary PumpsDecoupler/Bypass

100% Flow = 3000 gpm

100% Flow = 3000 gpm

0 gpm

12

Page 19: Roy hubbard

Secondary Pumps

Primary PumpsDecoupler/Bypass

67% Flow = 2000 gpm

67% Flow = 2000 gpm

0 gpm

19

67% Load = 67% Sec Flow

Primary (Constant) / Secondary (Variable)Ideal Operation

12

Page 20: Roy hubbard

20

Primary / Secondary Rule of Flow

Primary flow must always be equal to or greater than Secondary flow.

Page 21: Roy hubbard

Secondary Pumps

Primary PumpsDecoupler/Bypass

100% Flow = 3000 gpm

80% Flow = 2400 gpm (400 gpm over-pumped)

600 gpm

21

67% Load = 80% Sec Flow

Primary (Constant) / Secondary (Variable)Low Delta T Operation

10

Page 22: Roy hubbard

Higher Secondary Pump Energy

Higher CHW Plant Chiller/Auxiliary Energy

Major Effects of Low Delta T

Page 23: Roy hubbard

23

Solution to (or reduce effects of) Low Delta T

Address the causes

Clean Coils

Calibrate controls occasionally

Select proper 2W valves (dynamic/close-off ratings) and maintain them

no 3W valves in design

find and correct piping installation errors

Over pump chillers at ratio of Design Delta T / Actual Delta T

Increase Delta T across chillers with CHW Re-set (down).

Use Variable Speed Chillers & sequence to operate from 30 to 70% Load

Use VPF Systems (mitigates energy waste in plant)

Header pumps & operate more pumps than chillers

If dedicated pumping, over-size (design at 80% speed).

Page 24: Roy hubbard

Primary/Secondary System

Primary Pumps

Secondary Pumps

Common Pipe

P

Page 25: Roy hubbard

Primary Only (Variable Flow)

Page 26: Roy hubbard

Primary/Secondary System

Variable Primary System

Secondary Pumps

Primary Pumps

Primary Pumps

Flow Meter

BypassValve

Automatic Isolation Valve

Typical load with 2 way valve

Typical load with 2 way valve

Page 27: Roy hubbard

Primary Only (Variable Flow)

2 Way Valves

Lower Capital Cost Installed (vs Primary/Secondary)

No secondary pumps/piping/valves/electrical to buy and install

No large Common pipe, but smaller Bypass pipe/valve/flow meter/controls

Lower CHW Pumping Energy

Smaller Footprint (vs Primary/Secondary)

Relatively New & More Complex Controls

Reduces Negative Impacts from Low Delta T

Chillers are not staged on by flow requirements

Chillers can load up and are staged on load

Page 28: Roy hubbard

Primary Only (Variable Flow)

Disadvantages

Higher (potentially) PSID rated 2-Way valves in system

Requires more robust (complex and calibrated) control system

Requires coordinated control of chillers, isolation valves, and pumps in sequencing

Longer (potentially) Commissioning time

Requires greater operator sophistication

Page 29: Roy hubbard

Variable-Primary-Flow System

Primary Pumps

Flow Meter

Typical load with two way valve

Automatic Isolation Valve

Bypass

Page 30: Roy hubbard

Variable Primary System at Design

56.0 °F

56.0 °F

56.0 °F

44.0 °F

44.0 °F

44.0 °F

Primary Pumps

1000 GPM Each

3000 GPM @ 56.0 °F

3000 GPM @ 44.0 °F

Automatic Isolation Valve

Bypass Closed

500 ton chillers1000 GPM Each56.0-44.0°F

Typical load with two way valve

Page 31: Roy hubbard

Variable Primary System – Part Load

56.0 °F

56.0 °F

56.0 °F

44.0 °F

44.0 °F

44.0 °F

Primary Pumps

750 GPM Each

2250 GPM @ 56.0 °F

2250 GPM @ 44.0 °F

Automatic Isolation Valve

Bypass Closed

Typical load with two way valve

75% System Load

Page 32: Roy hubbard

Variable Primary System – Part Load

56.0 °F

56.0 °F

44.0 °F

44.0 °F

Primary Pumps

750 GPM Each

1500 GPM @ 56.0 °F

1500 GPM @ 44.0 °F

Automatic Isolation Valve

Bypass Closed

Typical load with two way valve

50% System LoadChiller off

Pump off

Page 33: Roy hubbard

Variable Primary System – Part Load

52.0 °F

52.0 °F

44.0 °F

44.0 °F

Primary Pumps

750 GPM Each

2250 GPM @ 52.0 °F

2250 GPM @ 44.0 °F

Automatic Isolation Valve

Bypass Closed

Typical load with two way valve

50% System LoadLow Δ T

Chiller off

Pump on

Page 34: Roy hubbard

Variable Primary System – Min Flow (400 gpm each)

50.0 °F

44.0 °F

Primary Pumps

400 GPM (one operating)

400 GPM @ 50.0 °F

200 GPM @ 44.0 °F

Automatic Isolation Valve

Bypass Open

Typical load with two way valve

System flow below chiller minimum flow

Chiller off

Chiller off

Closed

Closed

200 GPM @ 44.0

200 GPM @ 56.0 °FFlowmeter

Pumps off

Page 35: Roy hubbard

Chiller Design Considerations

Flow rate changes – Staging on additional chillers

Page 36: Roy hubbard

Variable Primary System (1 chiller running)

56.0 °F

44.0 °F

Primary Pumps

333 GPM Each

1000 GPM @ 56.0 °F

1000 GPM @ 44.0 °F

Automatic Isolation Valve

Bypass Closed

Typical load with two way valve1000 GPM

Page 37: Roy hubbard

Variable Primary System (Staging on second chiller)

57.0 °F

45.0 °F

Primary Pumps

333 GPM Each

1100 GPM @ 57.0 °F

1100 GPM @ 45.0 °F

Automatic Isolation Valve

Bypass Closed

Typical load with two way valve1100 GPM

Need to add chiller

Page 38: Roy hubbard

Variable Primary System (Open isolation valve)

57.0 °F

45.0 °F

Primary Pumps

333 GPM Each

1100 GPM @ 57.0 °F

1100 GPM @ 45.0 °F

Automatic Isolation Valve

Bypass Closed

Typical load with two way valve550 GPM

550 GPM

Load = F X DT DT = 12 = 57- 45 24

Load = 1/2F X 2DT DT = 24 24 LCHWT = 35!

Page 39: Roy hubbard

Variable Primary System (Open isolation valve)

57.0 °F

45.0 °F

Primary Pumps

333 GPM Each

1100 GPM @ 57.0 °F

1100 GPM @ 45.0 °F

Automatic Isolation Valve

Bypass Closed

Typical load with two way valve550 GPM

550 GPM

LCHWT approaches 35

LWT Cutout at 4 deg below44 set-point or 40

Off goes chiller 1

Page 40: Roy hubbard

Variable Primary System (Open isolation valve slowly)

57.0 °F

45.0 °F

Primary Pumps

333 GPM Each

1100 GPM @ 57.0 °F

1100 GPM @ 45.0 °F

Automatic Isolation Valve

Bypass Closed

Typical load with two way valve1100 GPM

Open over 1.5 to 2 min

Page 41: Roy hubbard

42

VPF Systems Design/Control Considerations Summary

Chillers

Equal Sized Chillers preferred, but not required

Maintain Min flow rates with Bypass control (1.5 fps)

Maintain Max flow rates (11.0 to 12.0 fps)

Isolation Valves (Modulating or Stroke-able to 1.5 to 2 min)

Don’t vary flow too quickly through chillers (VSD Ramp function – typical setting of 10%/min)

Chiller Type

System Water Volume

Chiller Load

Active Loads

Sequence

If Constant Speed – run chiller to max load (Supply Temp rise). Do not run more chillers than needed (water-cooled)

If Variable Speed – run chillers between 30% and 70% load (depending on ECWT). Run more chillers than load requires.

Add Chiller - CHW Supply Temp or Load (Adjusted* Flow X Delta T) or amps (if CSD)

Subtract Chiller - Load (Adjusted* Flow X Delta T) or Amps (if CSD)

Page 42: Roy hubbard

43

VPF Systems Design/Control Considerations Summary

Pumps

Variable Speed Driven

Headered arrangement preferred

Sequence

with chillers (run more pumps than chillers for over-pumping capability)

on flow (add pump when existing inadequate, subtract when can)

optimized algorithm (total kW of more pumps, lower than less pumps)

Stay within pump/motor limits (25% to 100% speed)

Subtract a Pump at 25 to 30% speed

Add a pump back when speed of operating pumps high enough

Speed controlled by pressure sensors at end of index circuit

Page 43: Roy hubbard

44

VPF Systems Design/Control Considerations Summary

Bypass Valve

Maintain a minimum chilled water flow rate through the chillers

Differential pressure measurement across each chiller evaporator

Flow meter preferred

Modulates open to maintain the minimum flow through operating chiller(s).

Bypass valve is normally open, but closed unless Min flow breeched

Pipe and valve sized for Min flow of operating chillers

High Rangeability (100:1 preferred)

PSID Ratings for Static, Dynamic, And Close Off = Shut Off Head of Pumps

Linear Proportion (Flow to Valve Position) Characteristic preferred

Fast Acting Actuator

Locate in Plant around chillers/pumps (preferrred)

Energy

Avoid Network traffic

Page 44: Roy hubbard

45

VPF Systems Design/Control Considerations Summary

Load Valves

High Rangeability (200:1 preferred)

PSID Ratings for Static, Dynamic, And Close Off = Shut Off Head of Pumps

Equal Percentage (Flow to Load) Characteristic

Slow Acting Actuator

Staging Loads

Sequence AHUs On/Off in 10 to 15 min intervals

Page 45: Roy hubbard

46

Summary on VPF Design

Chillers Size equally with same WPDs (best) Respect Min/Max Flows through chillers Set Pump VSD Ramp function to about 10%/min (600 sec 0 to Max Speed) Use Modulating or Strokeable Valves (preferred) on chiller evaps, headered pumping Use 2 Position Valves (1 min stroke) on chiller evaps, dedicated pumpingPumps VSD Controllers Headered Pumping Arrangement (preferred) Dedicated Pumping OK (over-size pumps)2 Way Valves Select for Static, Dynamic, Close-off ratings (PSID) equal to pump SOH (plus fill pressure) Range-ability 100 to 200:1 If Bypass – fast acting, linear proportion If Coils – slow acting, equal percentage, “On-Off” stagger air units (10-15 min intervals)Controls Set-point far out in index circuit (lower the value, the better the pump energy) Set Ramp function in VSD Controller (10%/min average) Run 1 more pump than chillers (when headered) Chillers On by common Supply Temp, Load, Amps, Adj Flow (Adj for Low Delta T) Chillers Off by Amps, Load, Adj Flow (Adj for Low Delta T) Over-pump Chillers to combat Low Delta T and get Max Cap out of chillers Bypass controlled by Min flow (preferred) or Min WPD of largest chiller (locate in plant for best energy, but can go anywhere in system)

Page 46: Roy hubbard

Chilled Water Piping Systems (VPF Focus)

Questions?

Page 47: Roy hubbard

Su

pply

Terminal

Balanceand

Service Valve

2-WayControlValve

Re

turnService Valve

Air

2 Way Valve/Coil Detail

Page 48: Roy hubbard

Electric Energy Cost Equations

ChillerEnergy Cost

Lbs Refrig/hr X Head

33,015 X Comp EffX Hours X Cost/Unit Energy=

PumpEnergy Cost

GPM X Head

3960 X Pump EffX Hours X Cost/Unit Energy=

FanEnergy Cost

CFM X TSP

6356 X Fan EffX Hours X Cost/Unit Energy=

0.7459

Mot Eff

0.7459

Mot Eff

0.7459

Mot Eff

X

X

X

Energy Cost Mass Flow/t X Lift

33,015 X EfficiencyX Hours X Cost/Unit Energy=

0.7459

Mot EffX