19
POWER QUALITY THAILAND LTD SINCE 1986

Power Quality training tool and PQ meter test tool

Embed Size (px)

Citation preview

Page 1: Power Quality training tool and PQ meter test tool

POWER QUALITY THAILAND LTD

SINCE 1986

Page 2: Power Quality training tool and PQ meter test tool

INTRODUCING THE PQSIM 200D POWER QUALITY TRAINING TOOL AND PQ METER EVALUATION TOOL

A Power Quality Thailand LTD /Power Quality Inc Product

Page 3: Power Quality training tool and PQ meter test tool

THE PQSIM 200 D

• A 3 channel Power Quality signal generator dedicated to task of generating the unique signals, waveforms and RMS values needed to test, demonstrate and evaluate a Power Quality meter.

• It generates on command the power quality parameter variations. (events)• The power quality event designs are based on 25+ years of actual power quality

events recorded at 100s of sites worldwide• It continuously generates voltage and current signal outputs for 230v 50Hz or 120

60 HZ or 230 V 60HZ• The continuous waveform contains distortion typical of an inverter output.

Page 4: Power Quality training tool and PQ meter test tool

POWER QUALITY TRAINING TOOL • The task of training new users of Power Quality meters has always

been challenging.• Power Quality generally consists of 10 basic electrical properties or

characteristics.• Power Quality meters can record hundreds of parameters simultaneously.• The sudden disturbance of one of these parameters is captured, recorded

and time stamped. The sensitivity settings for capturing those parameters is the challenge.

• Defining the allowable variance in a parameter disturbance (setting the threshold limits) requires knowledge of the International standards and understanding of the exceptions to normal setting for specific situations.

Page 5: Power Quality training tool and PQ meter test tool

POWER QUALITY PARAMETERS AT THE PUSH OF A BUTTON

• RMS voltage variations by magnitude and duration• Voltage sags (user selects magnitude and duration)• Voltage notching• Voltage swells (user selects duration)

• Voltage transients Phase to neutral• Unipolar• Bipolar• Decaying ringwave

• Voltage transients Neutral to Ground

Page 6: Power Quality training tool and PQ meter test tool

As generated by PQSIM 200 and recorded on a Dranetz PX-5 6

A SINGLE CYCLE WAVEFORM DISTORTION EVENT IEC DEFINES AS A DECAYING RING WAVE

Event #28 at 07/13/2015 18:19:52.058AV Mild Cap Switch Neg 1/2 Cyc

Phase 205.3 DegA B C D A-B B-C C-A

Vrms 118.6 0.08989 0.08056 0.4805 118.6 0.1364 118.5VPeak 182.7 0.2072 0.2060 0.8300 Irms 1.392 0.000328 0.000409 0.002612 IPeak 2.153 0.000838 0.001117 0.009783

Capacitor switching event

18:19:52.0507/13/2015

Monday

18:19:52.10 18:19:52.15 18:19:52.20

-150

-50

50

150

Vol

ts

A V D V

0

25

50

75

100

125

Vol

ts

A Vrms (val) D Vrms (val)

As recorded in 1995 (RPM PQ meter)

Page 7: Power Quality training tool and PQ meter test tool

BIPOLAR TRANSIENT RING Event 6 Bipolar transient Phase to neutral

224 Vpeak

10:31:37.56007/15/2015Wednesday

10:31:37.565 10:31:37.570 10:31:37.575 10:31:37.580

-150

-100

-50

0

50

100

150

200

Volts

A V A Vrms (val) A VPeak (val)

A V Val 233.9V07/15/2015 10:31:17.4381

A V Val 224.4V07/15/2015 10:31:37.5680

Event 6 Bipolar transient Phase to neutral 224 Vpeak

10:31:37.407/15/2015Wednesday

10:31:37.5 10:31:37.6 10:31:37.7

-150

-100

-50

0

50

100

150

200

Volts

A V A Vrms (val) A VPeak (val)

A V Val 233.9V07/15/2015 10:31:17.43

A V Val 224.4V07/15/2015 10:31:37.56

Page 8: Power Quality training tool and PQ meter test tool

VOLTAGE SAG 2 CYCLES

Event #12 at 07/13/2015 12:54:51.994AVrms Instantaneous Sag

CATEGORY: Short Duration Instantaneous SagThreshold crossed 118.0 VMagnitude 89.3 VMaxRMS 123.6 VDuration 0.0584 Sec.

Event # 1 Details/Waveforms

12:54:51.907/13/2015

Monday

12:54:52.0 12:54:52.1 12:54:52.2

-200-150-100

-500

50100150

Vol

ts

A V D V

0

25

50

75

100

125

Vol

ts

A Vrms (val) D Vrms (val)

A Vrms Val 89.30V07/13/2015 12:54:52.01

Page 9: Power Quality training tool and PQ meter test tool

VOLTAGE SAG RMS AND WAVEFORM

Event #12 at 07/13/2015 12:54:51.994AVrms Instantaneous Sag

Event 1 Voltage sag to 90v

12:54:52.007/13/2015

Monday

12:54:52.2 12:54:52.4 12:54:52.6 12:54:52.8

90

95

100

105

110

115

120

125

Vol

ts

A Vrms (max/min/val)

-0.5

0.0

0.5

1.0

1.5

2.0

Vol

ts

D Vrms (max/min/val)

A Vrms Min 89.30V07/13/2015 12:54:53.00

A Vrms Val 89.30V07/13/2015 12:54:52.01

D Vrms Val 0.368V07/13/2015 12:54:52.01

Event #12 at 07/13/2015 12:54:51.994AVrms Instantaneous Sag

CATEGORY: Short Duration Instantaneous SagThreshold crossed 118.0 VMagnitude 89.3 VMaxRMS 123.6 VDuration 0.0584 Sec.

Event # 1 Details/Waveforms

12:54:51.907/13/2015

Monday

12:54:52.0 12:54:52.1 12:54:52.2

-200-150-100

-500

50100150

Vol

ts

A V D V

0

25

50

75

100

125

Vol

ts

A Vrms (val) D Vrms (val)

A Vrms Val 89.30V07/13/2015 12:54:52.01

Page 10: Power Quality training tool and PQ meter test tool

VOLTAGE SWELL NEUTRAL TO GROUND

Event #136 at 07/13/2015 12:55:13.335DVrms Instantaneous Swell

Event 3 Swell neutral to ground

12:55:13.007/13/2015

Monday

12:55:13.4 12:55:13.8

95

100

105

110

115

120

Vol

ts

A Vrms (max/min/val)

0.0

2.5

5.0

7.5

10.0

12.5

15.0

Vol

ts

D Vrms (max/min/val)

A Vrms Min 89.30V07/13/2015 12:54:53.00

A Vrms Val 89.30V07/13/2015 12:54:52.01

D Vrms Val 0.368V07/13/2015 12:54:52.01

D Vrms Val 15.212V07/13/2015 12:55:13.35

Event # 3 Details/Waveforms

Event #136 at 07/13/2015 12:55:13.335DVrms Instantaneous Swell

CATEGORY: Short Duration Instantaneous SwellThreshold crossed 3.0 VMagnitude 15.22 VMinRMS 9.644 VDuration 0.04173 Sec.

12:55:13.307/13/2015

Monday

12:55:13.4 12:55:13.5 12:55:13.6

-150

-50

50

150

Vol

ts

A V D V

0

25

50

75

100

125

Vol

ts

A Vrms (val) D Vrms (val)

A Vrms Val 89.30V07/13/2015 12:54:52.01

Page 11: Power Quality training tool and PQ meter test tool

AUTO SEQUENCE GENERATES A SAMPLE OF ALL EVENT TYPES

1 full auto sequence with events marked

10:30:3007/15/2015Wednesday

10:31:00 10:31:30 10:32:00 10:32:30

95

100

105

110

115

120

125

130V

olts

A Vrms (avg/val)

0.0

2.5

5.0

7.5

10.0

12.5

15.0

Vol

ts

D Vrms (val)

Event #1 V sag

Event # 3 Neut to ground surge

Ph to neutral sag

event # 4 unipolar transient

event #6 Bipolar transientevent # 8

odd Harmonics event # 7 PF cap ring wave

Event # 5 Unipolar Trans Neutral to Ground

Approx time of Missing event

Phase to neutral swellSmall Voltage Notch

Page 12: Power Quality training tool and PQ meter test tool

PHASE TO NEUTRAL SAGEvent 1 PH to Neutral Sag preceeded by a swell

Event #1 at 07/13/2015 18:18:49.100Pre-trigger

18:18:49.1007/13/2015

Monday

18:18:49.15 18:18:49.20 18:18:49.25 18:18:49.29

90

100

110

120

130

Vol

ts

A Vrms

0.0

2.5

5.0

7.5

10.0

12.5

15.0

Vol

ts

D Vrms

A Vrms Val 130.19V07/13/2015 18:18:49.141

Event #1 at 07/13/2015 18:18:49.100Pre-trigger

event #1 waveforms

18:18:49.1007/13/2015

Monday

18:18:49.15 18:18:49.20 18:18:49.25 18:18:49.29

-200-150-100

-500

50100150

Vol

ts

A V D V

0

25

50

75

100

125

Vol

ts

A Vrms (val) D Vrms (val)

Page 13: Power Quality training tool and PQ meter test tool

UNIPOLAR TRANSIENTEvent 4 transient Phase to neutral 233.9vpt

10:31:17.4307/15/2015Wednesday

10:31:17.44 10:31:17.45 10:31:17.46 10:31:17.47 10:31:17.48

-150

-100

-50

0

50

100

150

200

Volts

A V D V A Vrms (val) D Vrms (val)

D V Val 0.0V07/15/2015 10:31:06.922

A V Val 233.9V07/15/2015 10:31:17.438

Page 14: Power Quality training tool and PQ meter test tool

TRANSIENT NEUTRAL TO GROUNDEvent 5 Bipolar transient neutral to Ground

2.24 vrms 15.48 Vpeak

10:31:28.407/15/2015Wednesday

10:31:28.5 10:31:28.6 10:31:28.7

0

5

10

15

20

25

Vol

ts

D V D Vrms (val) D VPeak (val)

D V Val 0.0V07/15/2015 10:31:06.92

D Vrms Val 2.286V07/15/2015 10:31:28.51

D VPeak Val 15.487V07/15/2015 10:31:28.51

Page 15: Power Quality training tool and PQ meter test tool

VOLTAGE TRANSIENT “NOTCH”

Page 16: Power Quality training tool and PQ meter test tool

WWW.powerqualityinc.com 16Nov 2002

Actual notch at the transformer.

Page 17: Power Quality training tool and PQ meter test tool

ODD HARMONIC INCREASE

Page 18: Power Quality training tool and PQ meter test tool

PQSIM POWER QUALITY PARAMETER GENERATOR OPTIONS• Current cable adapter

• Output 0 to 1.5vac to a BNC connector. Cable converts BNC to connector used by the PQ Meter

• 4 channel voltage set.• Neutral and phase

• 4 channel current adapter