Upload
chad-kurdi-pe
View
79
Download
2
Embed Size (px)
Citation preview
1
Overcurrent Protection:
Fuses & Circuit Breakers
ELECTRICAL SAFETY
Safe Design & Const.Safe Design & Const.Safe Design & Const.Safe Design & Const.
2Safe Work PracticeSafe Maintenance
Safe Equipment
OVERCURRENT PROTECTION
� NEC240 states the requirements for OCPD
� NEC® 240.1 (FPN): use if the current reaches a
value that will cause excessive temperature in
conductors or conductor insulation
OVERCURRENT PROTECTION
� UL and NEMA establish standards for ratings,
types, classifications, and testing procedures
for fuses and circuit breakers
DISCONNECT SWITCHES
� Fused switches are available in ratings of 30-6000A in both 250 and 600 volts
� Used with copper conductors unless marked to indicate suitability for use with aluminum
� Rating, unless otherwise marked, is based on (NEC110.14):
� 140°F (60°C)------ wire (14 -1 AWG)
� 167°F (75°C)------wires 1/0 AWG & larger
� May be equipped with ground-fault sensing and labels that indicate their intended use
DISCONNECT SWITCHES
� Occupants must have access to OCPD for their
circuits, NEC240.24(B)
� OCPD must be readily accessible NEC
240.24(A)
2
FUSES AND CIRCUIT BREAKERS
� Voltage rating: Equal to or greater than the
voltage of the circuit in which they are to be
used
� Continuous current rating: Amperes that the
device can continuously carry
FUSES AND CIRCUIT BREAKERS
� Protection of conductors
�OCPD is rated at 800 A or less: next higher
standard
�OCPD is rated above 800-ampere: must be equal
to or greater than the rating of the fuse or circuit
breaker
FUSES AND CIRCUIT BREAKERS (CONT'D.)
� Interrupting rating: Highest current where a
device is intended to interrupt under standard
test conditions
� Short-circuit current rating: Ability to
withstand fault current equal to or less than
the short-circuit rating for the length of time it
takes the overcurrent device to react
� Speed of response: Time required for a fuse
to open varies inversely with current that
flows through fuse
TYPES OF FUSES
� Dual-element, time-delay fuse
� Provides a time delay in low-overload range to
eliminate unnecessary opening of the circuit
because of harmless overloads
� Using fuses for motor overload protection
� Sizing dual-element fuses slightly larger than the
overload relay provides backup protection
TYPES OF FUSES
� Applying fuses and breakers on motor circuits
�High starting currents of motors can cause
nuisance opening of fuses and nuisance tripping of
circuit breakers
�Check time-current curves of fuses and breakers to
make sure that they will handle the momentary
motor starting inrush currents without nuisance
opening or tripping
TYPES OF FUSES
� Using fuses for motor branch-circuit, short-circuit, and ground-fault protection
�NEC® Table 430.52: maximum size permitted for dual-element fuses is based on a maximum of 175 percent of full-load current of the motor
� Dual-element, time-delay, current-limiting fuses
�Can handle currents five times their ampere rating for at least 10 seconds
3
TYPES OF FUSES
� Fast-acting, current-limiting fuses (nontime-
delay)
� Extremely fast response in both low-overload and
short-circuit ranges
�Has the lowest energy let-through values
� Provides better protection to mains, feeders and
subfeeders, circuit breakers, bus duct,
switchboards, and other circuit components
TYPES OF FUSES
� Types of cartridge fuses
� According to the Code, all cartridge fuses must be
marked to show:
�Ampere rating
�Voltage rating
� Interrupting rating when greater than 10,000 amperes
�Current-limiting type, if applicable
�Trade name or name of manufacturer
CABLE LIMITERS
�Used with parallel cables for service entrances
and feeders
� Isolate a faulted cable
� Selected on the basis of conductor size
� Available for cable-to-cable or cable-to-bus
installation
Three-phase, 3-wire delta system with
grounded “B” phase
CIRCUIT BREAKERS
� NEC® Article 100 definition
�Device designed to open and close a circuit by
nonautomatic means and to open the circuit
automatically on a predetermined overcurrent
� Types of circuit breakers:
�Molded-case circuit breakers
� Power circuit breakers
� Insulated-case circuit breakers
CIRCUIT BREAKERS
� Common misapplication
�Common violation of NEC® 110.9 and 110.10:
� Installation of a main circuit breaker that has a high
interrupting rating while making the assumption that
branch-circuit breakers are protected adequately
against short circuit
� Standard molded case circuit breakers with high
interrupting ratings cannot protect standard end-
use equipment having lower interrupting rating
4
SERIES-RATED APPLICATIONS
� Series-rated systems
� Less costly than fully-rated systems
� Available fault current does not exceed
interrupting rating of the line-side overcurrent
device but does exceed interrupting rating of the
load-side overcurrent device
SERIES-RATED APPLICATIONS
SERIES-RATED APPLICATIONS
�Where high available fault currents indicate
the need for high interrupting breakers or
fuses, fully rated system is generally used
� Another less costly way to safely match main
circuit breaker or main fuses ahead of
branch-circuit breakers is to use listed series-
rated equipment
SERIES-RATED SYSTEMS WHERE ELECTRIC
MOTORS ARE CONNECTED
� NEC® 240.86(C) sets forth two requirements
�Do not connect electric motors between load side
of higher rated overcurrent device and line side of
lower rated overcurrent device
� Sum of connected motor full-load currents shall
not exceed one percent of the interrupting rating
of lower rated circuit breaker
MOTOR CIRCUITS
� NEC® Table 430.52
� Shows that maximum setting of a conventional
inverse-time circuit breaker must not exceed 250
percent of full-load current of the motor
� For instantaneous-trip circuit breaker, maximum
setting is 800 percent of motors’ full-load current
�Design B motors, the maximum setting is 1100
percent
MOTOR CIRCUITS (CONT'D.)
� If an “engineering evaluation” can demonstrate
the need to exceed percentages shown in NEC®
Table 430.52, then:
�800 percent setting may be increased to a
maximum of 1300 percent
�1100 percent setting may be increased to a
maximum of 1700 percent
5
HEATING, AIR-CONDITIONING, AND
REFRIGERATION OVERCURRENT PROTECTION
� Nameplate on HVAC equipment might
indicate “maximum size fuse,” “maximum
size fuse or circuit breaker,” or “maximum
size fuse or HACR circuit breaker”
SHORT-CIRCUIT CALCULATIONS
3-Phase Fault
Current
Calculation
SHORT-CIRCUIT CALCULATIONS SHORT-CIRCUIT CALCULATIONS
29
Electrical system for a Commercial Building
6
SHORT-CIRCUIT CURRENT
� Arcing fault multipliers (approximate)
Hazard Risk
Category 0
Hazard Risk
Category 1
Hazard Risk
Category 2
Hazard Risk
Category 3
Hazard Risk
Category 4
PPE:
32
Hazard Risk
Category 0
Hazard Risk
Category 1
Hazard Risk
Category 2
Hazard Risk
Category 3
Hazard Risk
Category 4
COORDINATION OF OCPD
� Selective coordination: localization of
overcurrent condition to restrict outages to
the circuit or equipment affected,
accomplished by choice of overcurrent
protective devices and their ratings or
settings
Nonselective system verification
Selective system verification
Nonselective system verification
CURRENT-LIMITING FUSES