34
By: By: By: By: Er Er Er Er. . . . Rahul Rahul Rahul Rahul Sharma Sharma Sharma Sharma EE DEPARMENT SEMINAR April 23, 2012

Generator Protection By - Er Rahul Sharma

Embed Size (px)

DESCRIPTION

Generator Protection Switchgear and protection Power System - II

Citation preview

Page 1: Generator Protection By - Er Rahul Sharma

By: By: By: By: ErErErEr. . . . RahulRahulRahulRahul SharmaSharmaSharmaSharma

EE DEPARMENT SEMINAR April 23, 2012

Page 2: Generator Protection By - Er Rahul Sharma

Introduction:� In a generating station the generator and transformer

are the most expensive equipments and hence it is desirable to employ a protective system to isolate the faulty equipment as quickly as possible to keep the healthy section in normal operation and to ensure healthy section in normal operation and to ensure uninterruptable power supply.

� The basic electrical quantities those are likely to change during abnormal fault conditions are current, voltage, phase angle and frequency . Protective relays utilizes one or more of these quantities to detect abnormal conditions in a power system.

Page 3: Generator Protection By - Er Rahul Sharma

Generator protection:�Stator protection

�Differential

�Restricted earth fault�Restricted earth fault

�Negative sequence current

�Loss of load

Page 4: Generator Protection By - Er Rahul Sharma

Cont..�Rotor earth fault

�Over speed

�Over voltage�Over voltage

�Loss of field

�Back –up over current

Page 5: Generator Protection By - Er Rahul Sharma

Differential protection:� CTs are provided at each end of the generator winding

which is to be protected.(as shown in fig.)

� When there is no fault the differential current (I1-I2) through the relay is zero. So the relay will not operate.through the relay is zero. So the relay will not operate.

� When the fault occurs the balance is disturbed and differential current (I1-I2) flows through the operating coil of the relay causing relay operation and the trip circuit of the circuit breaker is closed.

Page 6: Generator Protection By - Er Rahul Sharma

Differential protection of generator:

Page 7: Generator Protection By - Er Rahul Sharma

Differential protection using balancing resistor:

Page 8: Generator Protection By - Er Rahul Sharma

Biased differential protection

Page 9: Generator Protection By - Er Rahul Sharma

Modified differential protection:� Generally protection is made for 80 to 85% of the

winding.

� If any fault occurs near the neutral point then the fault current is very small and relay does not operate.current is very small and relay does not operate.

� Modified differential protection scheme is used to over come this.

� Two phase elements (PC and PA) and balancing resistor(BR) is connected in star and the earth relay(ER) is connected between the star point and neutral pilot wire.

Page 10: Generator Protection By - Er Rahul Sharma

Modified differential protection

Page 11: Generator Protection By - Er Rahul Sharma

Restricted or balanced earth fault

protection:� In case of small size generators star point is not

available because it is made inside the generator and grounded through some low resistance then percentage differential relay for ground fault is percentage differential relay for ground fault is provided and is known as restricted earth fault protection.

� This scheme can be used only for ground faults but not for phase faults.

Page 12: Generator Protection By - Er Rahul Sharma

Restricted or Balanced earth fault protection

Page 13: Generator Protection By - Er Rahul Sharma

Stator protection:Stator faults include the following-

i. Phase-to-earth faults

ii. Phase-to-phase faults

iii. Inter-turn faultsiii. Inter-turn faults

From these phase faults and inter turn faults are less

common ,these usually develop into an earth faults.

This causes-

• Arcing to core

• Damage of conductor and insulation

Page 14: Generator Protection By - Er Rahul Sharma

Stator inter-turn fault protection:� Inter-turn fault on the same phase of the stator

winding cannot be detected by transverse differential protection as it does not disturb the balance between the currents in neutral and high voltage CTs.the currents in neutral and high voltage CTs.

� For protection against inter-turn faults the following protection schemes are used.

(1)Cross differential protection.

(2)Residual voltage protection.

Page 15: Generator Protection By - Er Rahul Sharma

Cross differential protection:� Used in case of hydro-

electric generator having double winding armature.

� As shown in figure relay � As shown in figure relay

Rc provides protection against phase to ground and phase to phase fault.

� The relay R1 provides protection against inter-turn faults.

Page 16: Generator Protection By - Er Rahul Sharma

Residual voltage protection:� These method is used in

case of alternators those don’t have parallel stator windings.

� During normal operation

VRES=VRN+VBN+VYN=0.

In case of fault VRES is not

zero and this residual

voltage operates the relay.

Page 17: Generator Protection By - Er Rahul Sharma

Rotor faults:� Faults in the rotor circuit may be either earth faults or

between the turns of the field winding .

� Field circuits are normally operated un-earthed. So a single earth fault will not affect its operation.single earth fault will not affect its operation.

� But when a second fault arises then field winding is short circuited and produce unsymmetrical field system which leads to unbalanced forces on rotor and results in excess pressure and bearing and shaft distortion.

Page 18: Generator Protection By - Er Rahul Sharma

Rotor earth fault protection:� The rotor earth fault protection is done by “dc

injection method or ac injection method”.

� The dc or ac voltage is impressed between the field circuit and ground through a sensitive overvoltage circuit and ground through a sensitive overvoltage relay and current limiting resistor or capacitor(in case of ac).

� But dc source is generally used as over-current relay in case of dc is more sensitive than ac.

� A single earth fault in rotor circuit will complete the path and the fault is sensed by the relay.

Page 19: Generator Protection By - Er Rahul Sharma

Rotor earth fault protection

Page 20: Generator Protection By - Er Rahul Sharma

Rotor temperature alarm� It is provided in large

generators.

� It indicates the level of temperature but not the temperature but not the actual hot spot temperature.

� The relay measures the temperature by measuring the resistance .(as shown in fig)

Page 21: Generator Protection By - Er Rahul Sharma

Loss of excitation protection:When the excitation of generator is lost it operate as a

Induction generator. It derives excitation from the

system and supply power at leading power factor.

Which may cause-Which may cause-

� A fall in voltage & so loss of synchronism & system instability.

� Over heating of rotor due to induction current on it.

A protection having MHO characteristic

is used to detect loss of field.

Page 22: Generator Protection By - Er Rahul Sharma

Over voltage protection:� Overvoltage protection is required in case of hydro-

electric or gas turbine generators but not in case of turbo generators.

Over voltage may be caused due to-� Transient over voltage in the transmission line due to � Transient over voltage in the transmission line due to

lightening.� Defective operation of the voltage regulator.� Sudden loss of load due to line tripping.The protection is provided with an over voltage relay.It is usually of induction pattern with an IDMTCharacteristic

Page 23: Generator Protection By - Er Rahul Sharma

Overload protection:� Overloading of the machine causes overheating in the

stator winding.

� This can be prevented by using over-current relay with time delay adjustment.time delay adjustment.

� But overheating not only depends on over-current but also the failure of the cooling system in the generator.

� So temperature detector coils such as thermistors or thermocouples are used at various points in stator winding for indication of the temperature.

Page 24: Generator Protection By - Er Rahul Sharma

Reverse power protection:� When prime-mover fails machine starts motoring and

draws electrical power from the system and this is known as inverted operation .

� The generator can be protected from inverted � The generator can be protected from inverted operation by using single-element directional power relay(reverse power relay) which senses the direction of power flow.

Page 25: Generator Protection By - Er Rahul Sharma

Negative phase sequence

protection:� Unbalance may cause due to single phase fault or

unbalanced loading and it gives rise to negative sequence current .

� This current in rotor causes rotor overheating and � This current in rotor causes rotor overheating and damage to the rotor.

� This can be protected by negative sequence current filter with over current relay.

Page 26: Generator Protection By - Er Rahul Sharma

Negative phase sequence protection:

Page 27: Generator Protection By - Er Rahul Sharma

Automatic field suppression and

use of neutral circuit breaker:� In case of a fault in the generator and though the

circuit breaker is tripped ,the fault continues to fed as long as excitation will exist because emf is induced in the generator itself.the generator itself.

� Hence all protection system not only trip the generator circuit breaker but also trip the “automatic field discharge switch “.

Page 28: Generator Protection By - Er Rahul Sharma

Automatic field suppression and use of neutral circuit breaker

Page 29: Generator Protection By - Er Rahul Sharma

External fault back up protection:

�Over-current and earth-fault protection is provided for back-up protection of large sized generators protected by differential sized generators protected by differential protection.

� Induction type IDMT relay is used for this purpose.

Page 30: Generator Protection By - Er Rahul Sharma

External fault back-up protection

Page 31: Generator Protection By - Er Rahul Sharma

Conclusion:� Protective relays are used to detect electrical faults and

to alarm, disconnects or shutdown the faulted apparatus to provide personnel safety and equipment protection.protection.

� A protective relay does not prevent the appearance of faults rather takes action only after a fault has occurred in the system.

Page 32: Generator Protection By - Er Rahul Sharma

References:� Electrical power system

by C.L.Wadhwa

� Electrical power

by J.B.Guptaby J.B.Gupta

� www.wikipedia.com

Page 33: Generator Protection By - Er Rahul Sharma

Thank

youyou

Page 34: Generator Protection By - Er Rahul Sharma

Any Queries

??????