Upload
scott-conwell-faia
View
4.460
Download
3
Embed Size (px)
DESCRIPTION
This is a companion program to Moisture Control for Masonry, and therefore will not address the important topic of moisture. This program analyzes a masonry wall from the vantage point of quality control in both design and construction. It covers ASTM standards, brick and block selection, mortar types, and a detailed discussion of movement control for masonry. The program also looks at acceptable tolerances in materials and workmanship.
Citation preview
QUALITY CONTROL FOR MASONRY
presented by International Masonry Institute
Craftworker certification training
Sustainable Masonry Certification Program
Contractor College
Pre-job and apprentice training
International Union of Bricklayers and Allied Craftworkers
International Masonry Institute
LIFELONG LEARNING
Journeyman upgrade training
Safety, scaffold, OSHA training
Supervisor certification
PROFESSIONAL EDUCATION
MASONRY DETAILING SERIES
www.masonrydetails.org
ILLINOIS STRUCTURAL MASONRY COALTION
HYBRID MASONRY & STEEL
Garden Hills Elementary School, Champaign, IL BLDD Architects
BAC CONTRACTORS
IMI-TRAINED CRAFTWORKERS
International Union of Bricklayers and Allied Craftworkers
International Masonry Institute
Course Evaluations In order to maintain high-quality learning experiences, please
access the evaluation for this course by logging into CES Discovery and clicking on the Course Evaluation link on the
left side of the page.
MASONRY CODES & STANDARDS
PROPERTIES BRICK
Color
Shape
Size
Bonding pattern
Orientation
Texture of unit
Texture of wall
Accent units
DESIGN FLEXIBILITY
BRICK PROPERTIES
DESIGN FLEXIBILITY
BRICK PROPERTIES
DESIGN FLEXIBILITY
BRICK PROPERTIES
DESIGN FLEXIBILITY
BRICK PROPERTIES
ASTM C 216 TABLE 1 – PHYSICAL REQUIREMENTS
BRICK PROPERTIES
ASTM C 216 TABLE 3 – DIMENSIONAL TOLERANCES
BRICK PROPERTIES
ASTM C 216 TABLE 3 – DIMENSIONAL TOLERANCES
BRICK PROPERTIES
TYPE FBA
BRICK PROPERTIES
Type FBA brick has no requirement for dimensional stability
ASTM C 216 TABLE 3 – DIMENSIONAL TOLERANCES
BRICK PROPERTIES
MAX. PERMISSIBLE DISTORTION PER ASTM TABLE
ASTM C 216 TABLE 4 – DISTORTION TOLERANCES
BRICK PROPERTIES
ASTM C 216 TABLE 2 – ALLOWABLE CHIPPAGE
BRICK PROPERTIES
Not a requirement
in ASTM or MSJC
5-25 g/min/30 in 2 Recommendation:
Consider high IRA
brick for cold weather
construction
Consider low IRA
brick for hot weather
construction
INITIAL RATE OF ABSORPTION (IRA)
BRICK PROPERTIES
MOISTURE RESISTANCE
Brick & mortar leak
Wall system must address moisture penetration
MOISTURE RESISTANCE
MOISTURE RESISTANCE
CAVITY WALL [DRAINAGE WALL]
Air space Flashing Weep holes
REQUIRED by Code
OPTIONAL
Air Barrier *
*depending on project location
Mortar Dropping Collection Device (MDCD)
MOISTURE RESISTANCE
© 2009 INTERNATIONAL MASONRY INSTITUTE
2” recommended
AIR SPACE
1” min. for veneers, per code
4½” max. btwn.
brick & backup
MOISTURE RESISTANCE
© 2009 INTERNATIONAL MASONRY INSTITUTE AIR SPACE
2” recommended
4½” max. between
brick and backup
1” min. for veneers per ACI 530 Code
MOISTURE RESISTANCE
© 2009 INTERNATIONAL MASONRY INSTITUTE AIR SPACE
MOISTURE RESISTANCE
No mortar bridging across the cavity!
AIR SPACE
2” 2”
MOISTURE RESISTANCE
CLEAN CAVITIES
MOISTURE RESISTANCE
Bevel the bed joints
MORTAR
© 2009 INTERNATIONAL MASONRY INSTITUTE
ELEVATIONS DIAGRAM 01.410.0311 REV. 08/10/09
MORTAR JOINT MATERIAL TAKEOFF
UTILITY BRICK, RUNNING BOND MODULAR BRICK, RUNNING BOND
4 @ 12” x 3/8” = 18.000 SQ. IN. BED JOINTS
HEAD JOINTS 8 @ 2.3125” x 3/8” = 6.938 SQ. IN.
2 @ 1.3125” x 3/8” = 0.984 SQ. IN.
25.922 SQ. IN. MORTAR
3 @ 12” x 3/8” = 13.500 SQ. IN.
3 @ 3.625” x 3/8” = 4.078 SQ. IN.
17.578 SQ. IN. MORTAR
18.00% MORTAR 12.21% MORTAR
ONE SQUARE FOOT ONE SQUARE FOOT
18% 12%
COLORED MORTAR
MORTAR
ASTM C 270
Mortar Options:
- Portland Cement and Lime
- Masonry Cement
- Mortar Cement
Mortar Types: M, S, N,
and O
Mortar Quality Control
ASTM C 270 MASONRY MORTARS
MORTAR
M S N O K r w o a
ASTM C 270 MASONRY MORTARS
MORTAR
ASTM C 270 TABLE 1 – PROPORTION SPECIFICATION
MORTAR
M S N O K 1:1:6
general ratio
cement : lime : sand
1:½:4½
1:2:9 1:3:12 1:¼:3¾
Refer to ASTM C 270 for acceptable ranges
PROPORTION RULES-OF-THUMB
MORTAR
MIXING BY HAND
MORTAR
ASTM C 270 TABLE 2 – PROPERTY SPECIFICATION
MORTAR
JOINT PROFILES
MORTAR
concave
vee
raked
weeping
beaded
flush
grapevine
weathered
struck
WEATHER-RESISTANT MORTAR JOINTS
MORTAR
concave
vee
BOND SEPARATION
MORTAR
TEMPERING
MORTAR
TOOLING THE JOINTS
MORTAR
TOOTHING NOT RECOMMENDED
MORTAR
JOINT PREPARATION FOR REPOINTING
MORTAR
REPOINTING
MORTAR
REPOINTING DETAIL DETAIL 16.101 REV. 05/08/09
© 2009 INTERNATIONAL MASONRY INSTITUTE
N.T.S.
DETAILING MASONRY
SERIES www.imiweb.org 800-IMI-0988
International Masonry Institute
DETERIORATED MORTAR
1. JOINT GROUND TO INCORRECT PROFILE
2. JOINT GROUND TO INCORRECT PROFILE
3. JOINT RAKED TO SOUND MORTAR (d/3 MAX.) AND GROUND TO 90º PROFILE
4.
1/4” LIFT, FIRST PASS 5. 1/4” LIFTS, SUB- SEQUENT PASSES
6. FINAL PASS INCORRECTLY SMEARED ABOUT BRICK EDGES RESULTS IN EXAG- GERATED JOINT WIDTH
7.
FINAL PASS TOOLED TO CONCAVE OR VEE PROFILE TO MATCH EXISTING
8.
1/4” 1/4”
d/3
MAX
d
MOVEMENT CONTROL
Temperature changes
Moisture changes
Elastic deflection
Plastic deformation
Soil movements
Crystallization
MOVEMENT CONTROL
BUILDING MOVEMENTS
Brick expands
Concrete block shrinks
MOVEMENT CONTROL
BUILDING MOVEMENTS
Control Joint
NOT Control Joint nor CJ
NOT Expansion Joint
Expansion Joint
or Masonry Exp. Joint
MOVEMENT CONTROL
BUILDING MOVEMENTS
BRIC
K
BLO
CK
shrinkage architectural precast
expansion
expansion
shrinkage
shrinkage
shrinkage
expansion
brick (clay)
calcium silicate
cast stone
concrete masonry unit
EIFS
expansion terra cotta
stone
expansion tile (ceramic)
? brick (fly ash)
MOVEMENT CONTROL
MOVEMENT CONTROL
DRAWING REQUIREMENTS
3.3 F.7 Movement Joints
“Indicate type and location of
movement joints on the project
drawings.”
1.2 Contract documents
1.2.2 “Show all code-required items
on the project drawings including…
(h) provision for dimensional changes
resulting from elastic deformation,
creep, shrinkage, temperature, and
moisture.”
© 2011 INTERNATIONAL MASONRY INSTITUTE
MOVEMENT JOINT DETAIL 01.030.1301 REV. 02/02/11
HORIZONTAL JOINT REINFORCEMENT, DISCONTINUOUS AT MOVEMENT JOINT
EXPANSION JOINT (EJ): SEALANT, BACKER ROD, & COMPRESSIBLE FILLER OF PRE- MOLDED FOAM OR NEOPRENE PAD
CONTROL JOINT (CJ): PREFORMED SHEAR KEY, SEALANT, & BACKER ROD
MOVEMENT JOINT: CONTROL JOINT AND/ OR EXPANSION JOINT
CONTROL JOINT (CJ): PREFORMED SHEAR KEY, SEALANT, & BACKER ROD
OPTION 1:
EJ & CJ ALIGNED
OPTION 2:
EJ & CJ OFFSET
PILASTERS
INTERSECTING
WALLS
CORNERS
CHANGE IN
THICKNESS
CHANGE
IN HEIGHT
OPENINGS
STRAIGHT
RUNS
MOVEMENT CONTROL
MOVEMENT JOINT LOCATIONS
MOVEMENT CONTROL
EXPANSION JOINT AT INSIDE CORNER
OPENINGS < 6’, CJ
REQUIRED @ ONE SIDE
OPENINGS > 6’, CJ
REQUIRED @ BOTH
SIDES
MJ @ PILASTERS
& INSIDE CORNERS
MOVEMENT CONTROL
MOVEMENT JOINT LOCATIONS
MOVEMENT CONTROL
EXPANSION JOINT AT OPENING
© 2009 INTERNATIONAL MASONRY INSTITUTE
EXPANSION JOINT DETAIL 01.030.1321.PH REV. 08/09/09
AT WINDOW
© 2009 INTERNATIONAL MASONRY INSTITUTE
EXPANSION JOINT DETAIL 01.030.1321 REV. 08/09/09
AT WINDOW
FLASHING MEMBRANE OR PLASTIC BEARING PAD BENEATH BEARING AREA OF ANGLE TO CREATE SLIP PLANE
BACKER ROD OR COMPRESSIBLE MATERIAL AT END OF LINTEL TO AVOID RESTRAINT OF MOVEMENT, AND AT FRONT EDGE OF LINTEL TO PROVIDE BACKER FOR SEALANT
MASONRY EXPANSION JOINT ALIGNED W/ WINDOW JAMB; COMPRESSIBLE FILLER, BACKER ROD & SEALANT
FLASHING END DAM RETURNED INTO HEAD JOINT
WINDOW SYSTEM
STRUCT. STEEL LINTEL
FLASHING SYSTEM W/ DRIP EDGE
MOVEMENT CONTROL
OFFSET EXPANSION JOINT
ALIGN MJ W/ JAMB
OPENINGS < 6’, CJ
REQUIRED @ ONE SIDE
OPENINGS > 6’, CJ
REQUIRED @ BOTH
SIDES
MJ @ PILASTERS
& INSIDE CORNERS
OR HEADER
MOVEMENT CONTROL
MOVEMENT JOINT LOCATIONS
SHORTER WALLS MAY
REQUIRE CJ SPACING
1½ x WALL HEIGHT
ALIGN MJ W/ JAMB
OPENINGS < 6’, CJ
REQUIRED @ ONE SIDE
OPENINGS > 6’, CJ
REQUIRED @ BOTH
SIDES
MJ @ PILASTERS
& INSIDE CORNERS
MOVEMENT JOINT LOCATIONS
OR HEADER
MOVEMENT
JOINT FLUSH
WITH OPENING
MOVEMENT
JOINTS AT END
OF LINTEL
MOVEMENT
JOINT BETWEEN
OPENINGS
MOVEMENT CONTROL
MOVEMENT JOINT LOCATIONS
© 2009 INTERNATIONAL MASONRY INSTITUTE
ELEVATIONS DIAGRAM 01.410.1311 REV. 08/10/09
WHEN WINDOWS ARE SPACED FAR APART, LOCATE VERTICAL EXPANSION JOINTS BETWEEN WINDOWS
MOVEMENT JOINT LAYOUT
WHEN WINDOWS ARE SPACED CLOSE TOGETHER, LOCATE VERTICAL EXPANSION JOINTS AT WINDOW JAMBS
MOVEMENT CONTROL
SEALANT COLOR
MOVEMENT CONTROL
SEALANT COLOR
C
MOVEMENT JOINTS AT CORNER
C
A < 10’ … CLOSER TO CORNER IS BETTER
A + B may equal C
A
B
C
C = REGULAR MJ INTERVAL
MOVEMENT CONTROL
MOVEMENT CONTROL
NO EXPANSION JOINT AT CORNER
CONTROL JOINT DETAIL 03.802A REV. 07/07/08
© 2008 INTERNATIONAL MASONRY INSTITUTE
SIN
GLE
WYTH
E B
LOC
K
DETAILING MASONRY
SERIES www.imiweb.org 800-IMI-0988
International Masonry Institute
GROUT & REINFORCING WHERE REQUIRED
SASH BLOCK
PREFORMED SHEAR KEY
CAULK & BACKER ROD
TERMINATE HORIZONTAL JOINT REINFORCEMENT AT CONTROL JOINT
CONTROL JOINT DETAIL 03.802B REV. 07/07/08
© 2008 INTERNATIONAL MASONRY INSTITUTE
SIN
GLE
WYTH
E B
LOC
K
DETAILING MASONRY
SERIES www.imiweb.org 800-IMI-0988
International Masonry Institute
BUILDING PAPER
GROUT FILL
CAULK & BACKER ROD
TERMINATE HORIZONTAL JOINT REINFORCEMENT AT CONTROL JOINT
FIRE RATED CONTROL JOINT DETAIL 03.802C REV. 07/07/08
© 2008 INTERNATIONAL MASONRY INSTITUTE
SIN
GLE
WYTH
E B
LOC
K
DETAILING MASONRY
SERIES www.imiweb.org 800-IMI-0988
International Masonry Institute
GROUT & REINFORCING WHERE REQUIRED
CAULK & BACKER ROD
TERMINATE HORIZONTAL JOINT REINFORCEMENT AT CONTROL JOINT
CERAMIC FIBER BLANKET WHERE REQUIRED FOR FIRE RATING
MOVEMENT CONTROL
CONTROL JOINTS AT OPENINGS
MOVEMENT CONTROL
CONTROL JOINTS
MOVEMENT CONTROL
SHRINKAGE CRACKING
MOVEMENT CONTROL
BOND SEPARATION
MOVEMENT CONTROL
EXPANSION JOINTS
ISOLATION JOINT DETAIL 03.811 REV. 06/18/08
© 2008 INTERNATIONAL MASONRY INSTITUTE
SIN
GLE
WYTH
E B
LOC
K
DETAILING MASONRY
SERIES www.imiweb.org 800-IMI-0988
International Masonry Institute
GROUT-FILLED CELLS
GROUT-FILLED CELLS
ANCHOR TRANSFERS TRANSVERSE LOADS AND ALLOWS INDEPENDENT MOVEMENT OF INTERSECTING WALLS
SEALANT AND BACKER ROD
COMPRESSIBLE FILLER
ISOLATION JOINT DETAIL 01.811 REV. 06/18/08
© 2008 INTERNATIONAL MASONRY INSTITUTE
MO
VEM
EN
T JO
INTS
DETAILING MASONRY
SERIES www.imiweb.org 800-IMI-0988
International Masonry Institute
EXISTING WALL
ANCHOR TRANSFERS TRANSVERSE LOADS AND ALLOWS INDEPENDENT MOVEMENT OF INTERSECTING WALLS
SEALANT, BACKER ROD, AND COMPRESSIBLE FILLER
CONNECTION OF NEW TO EXISTING WALLS
NEW WALL
STANDARD SPECIFICATION FOR GROUT FOR MASONRY
ASTM C476-10
SCOPE ASTM C476-10
SCOPE ASTM C476-10
Conventional Grout
SCOPE ASTM C476-10
SCG
MATERIALS ASTM C476-10
3. Materials
3.1.1 Cementitious Materials
3.1.1.1 Portland Cement
3.1.1.2 Blended Cements
3.1.1.3 Quicklime
3.1.1.4 Hydrated Lime
3.1.1.5 Coal Fly Ash or Raw Calcined
Natural Pozzolan
3.1.1.6 Granulated Blast Furnace Slag
3.1.2 Air Entraining Admixtures
3.1.3 Aggregates
3.1.4 Water
3.1.5 Admixtures
3.1.5.1 Admixtures for SCG
3.1.6 Pumping Aids
3.1.7 Antifreeze Compounds
3.1.8 Storage of Materials
MATERIALS
Clean & potable
iwr, accelerators, etc.
Not permitted
Protect from moisture
ASTM C476-10
water-reducers, viscocity modifiers
GROUT TYPE & PROPORTIONS ASTM C476-10
GROUT TYPE & PROPORTIONS
4. Grout Type and Proportions
4.1 Type
4.1.1 Fine grout
4.1.2 Coarse grout
4.2 Proportions of Ingredients
4.2.1 Conventional Grout
4.2.1.1 Table 1
4.2.1.2 Specified Compressive Strength
4.2.2 Self-consolidating Grout
4.2.2.1 Specified Compressive Strength
2,000 psi at 28 days
Per astm c1019
Fine aggregate
Coarse and Fine aggregates
24-30 in. slump flow;
2,000 psi at 28 days
Per astm c1019
Vsi < 1
ASTM C476-10
MSJC 2008 Specification for Masonry Structures
“Grout compressive strength equals or exceeds f’m but not less than 2000 psi.” (Article 1.4 B.2.a.3)b) and 1.4 B.2.b.3)b))
“Grout compressive strength equals or exceeds f’aac but compressive strength is not less than 2000 psi.” (Article 1.4 B.c.3)b))
“unless otherwise required, provide grout that conforms to the requirements of ASTM C 476, or ” (Article 2.2 A.1)
“…attains the specified compressive strength or 2000 psi, whichever is greater, at 28 days when tested…” (for self-consolidating grout) (Article 2.2 A).2)
ASTM C 476-10 Standard Specification for Grout for Masonry
“…and shall have a minimum compressive strength of 2000 psi at 28
days.” (Section 4.2.1.1 (Conventional grout))
…”The grout shall have a minimum compressive strength of 2000 psi at
28 days.” (Section 4.2.2.1 (Self-consolidating grout))
GROUT TYPE & PROPORTIONS ASTM C476-10
MEASUREMENT & PRODUCTION ASTM C476-10
MEASUREMENT & PRODUCTION
5. Measurement and Production
5.1 Measurement of Materials
5.2 Production Methods
5.2.1 Grout Mat’ls Mixed w/ Water @ Job Site
5.2.1.1 Conventional Grout
5.2.1.2 SCG
5.2.2 Ready-Mixed Grout
Transported to Job Site
5.2.2.1 Conventional Grout
5.2.2.2 SCG
mech. Mixer, 5 minutes min.;
continuous mixer per mixer manuf’r recommendations
Volume to batch weight conversions
ASTM C476-10
adjust slump as necessary
by remixing for at least 1 min.
add water per scg Manuf'r recommendations
STANDARD TEST METHOD FOR SAMPLING AND TESTING GROUT
ASTM C1019-09
SCOPE; SIGNIFICANCE & USE ASTM C1019-09 1. Scope
1.1 This test method covers
procedures for both field and
laboratory sampling and
compression testing of grout used
in masonry construction.
3. Significance & Use
3.1 Grout used in masonry is a fluid
mixture of cementitious materials
and aggregate with a high water
content for ease of placement.
3.1.1 During construction,
grout is placed within or
between absorptive masonry
units. Excess water must be
removed from the grout
specimens in order to provide
compressive strength test
results more nearly indicative of
the grout strength in the wall.
TEST SPECIMENS ASTM C1019-09 PROCEDURES
5. Test Specimens
5.1 Each grout specimen shall
have a square cross section,
3 in. or larger on the sides and
twice as high as its width.
5.2 Test at least three specimens
at each age specified.
Note 4: frequency of sampling and
age of test is to be determined by
the specifier, and is usually found
in the construction documents; for
example, one set of specimens may
be specified for every 5,000 s.f. of
wall.
EXAMPLE: IF SPECIMENS ARE TO BE
TESTED AT 7, 14, AND 28 DAYS, THEN
MAKE 9 SPECIMENS.
GROUT SPECIMEN MOLDS ASTM C1019-09
SCOPE ASTM C1019-09 6. Grout Specimen Molds
6.1 Molds from Masonry Units
6.1.1 Select a level location where the molds
remain undisturbed for up to 48 hours.
6.1.2 The construction of the mold shall simulate
the in-situ construction. If the grout is
placed between two different types of
masonry units, both types shall be used
to construct the mold.
6.1.3 Form a space with a square cross-section,
3 in. or larger on each side and twice as high
as its width, by stacking masonry units of
the same type and moisture condition as
those being used in the construction. The
surface of the unit in contact with the grout
specimen shall not have been previously
used to mold specimens. Place non-
absorbent block, cut to proper size and of
the proper thickness or quantity, at the bottom
of the space to achieve the necessary height
of specimen.
5% tolerance on dims.
SAMPLING GROUT ASTM C1019-09
SAMPLING GROUT ASTM C1019-09
7. Sampling Grout
7.1 Size of Sample
7.2 Procedure
7.2.1 Field Sampling
7.2.2 Laboratory Sampling
7.3 Place the grout sample in a non-
absorptive container, cover the top to
protect sample from the sun, wind,
and any other sources of rapid
evaporation /contamination. Remix
to ensure uniformity prior to filling
molds.
sample used for slump & comp. strength 1/2 ft3 min.
2 or more portions mid-discharge, spaced < 15 min. apart
entire mixed batch of grout is sample
field technician aci or ncma certified, or equal
TEMPERATURE & SLUMP TEST ASTM C1019-09
8. Temperature and Slump Test
8.1 Measure and record the
temperature of the grout sample in
accordance w/ ASTM C1064
8.2 Begin filling the slump cone within 5
min. of obtaining the final portion of
the sample.
8.3 For conventional grout, measure
and record the slump in accordance
w/ ASTM C143
8.4 For SCG, measure and record the
slump flow and VSI in accordance w/
ASTM C1611
Filling Slump Cone
Hold cone firmly
in position so grout
does not escape while filling the cone.
Slump cones are for testing grout
consistency prior to grouting.
SLUMP TEST, CONVENTIONAL GROUT
1/3
Fill the bottom 1/3
and rod 25 times
with the puddle rod.
Straight in and
Straight out… do not
stir.
Filling Slump Cone
SLUMP TEST, CONVENTIONAL GROUT
2/3
Fill the middle 1/3
and rod 25 times.
Penetrate bottom 1/3 only slightly.
Filling Slump Cone
SLUMP TEST, CONVENTIONAL GROUT
3/3
Fill the top 1/3
and rod 25 times.
Penetrate middle
1/3 only slightly.
Filling Slump Cone
SLUMP TEST, CONVENTIONAL GROUT
Grout should slump
8 to 11 inches.
Lift the cone slowly
and straight up. Do not twist or turn.
Remove Slump Cone
SLUMP TEST, CONVENTIONAL GROUT
Conventional Grout
ASTM C 143
8 - 11” slump
SCG
ASTM C1611
24” to 30” slump flow
VSI < 1
SLUMP vs. SLUMP FLOW
COMPRESSIVE TEST SPECIMEN ASTM C1019-09
9. Compressive Test Specimen
9.1 Begin filling molds within 15 min. of
obtaining final portion of sample.
9.2 - 9.5 describe procedures for
conventional grout; see next slide.
For SCG, fill mold w/ grout in one
layer and do not rod.
9.6 Protect specimens from freezing
and variations in temp. Record max.
& min. temps prior to time
specimens are placed in final curing
environment.
Note 9: if storage temps are < 60ºF
or > 80ºF, resulting compressive
strengths will likely be affected.
13. Remove molds 24-48 hours after making specimen
9. Within 30 minutes, remove cloth
2. Line face of units
3. Fill bottom layer w/ grout 4. Rod 15 times w/ tamping rod 1. Masonry pinwheel
6. Rod 15 times w/ tamping rod 7. Strike off top surface 8. Cover w/ absorbent cloth 5. Fill top layer w/ grout
11. Strike off top surface 12. Cover w/ absorbent cloth; do not disturb specimen until molds are removed
COMPRESSIVE TEST SPECIMEN, CONVENTIONAL GROUT ASTM C1019-09
initial water loss 10. Fill depression caused by
COMPRESSIVE TEST SPECIMEN ASTM C1019-09
9. Compressive Test Specimen
9.1 Begin filling molds within 15 min. of
obtaining final portion of sample.
9.2 - 9.5 describe procedures for
conventional grout; see next slide.
For SCG, fill mold w/ grout in one
layer and do not rod.
9.6 Protect specimens from freezing
and variations in temp. Record max.
& min. temps prior to time
specimens are placed in final curing
environment.
2. Line face of units
1. Masonry pinwheel
4. Strike off top surface 5. Cover w/ absorbent cloth
3. Fill to top w/ SCG
7. Fill depression caused by 8. Strike off top surface 9. Cover w/ absorbent cloth;
6. Within 30 minutes, remove cloth
initial water loss do not disturb specimen until molds are removed
COMPRESSIVE TEST SPECIMEN, SCG ASTM C1019-09
10. Remove molds 24-48 hours after making specimen
ALTERNATIVE METHODS ASTM C1019-09
6. Grout Specimen Molds
6.2 Alternative Methods - … used
only with approval of the
specifier.
Note 7: fill compartments in
slotted corrugated cardboard
boxes specifically manufactured
to provide grout specimens.
Understand Grout Pours and Lifts
Often confused or used interchangeably. MSJC Definitions:
Grout Pour – The total height of masonry to be grouted prior to erection of additional masonry. A grout pour consists of one or more grout lifts.
Grout lift – An increment of grout height within a total grout pour. A grout pour consists of one or more grout lifts.
Maximum pour height – function of grout type (fine or coarse), minimum grout space dimensions, use of cleanouts, conventional grout or SCG. Maximum pour heights are established by MSJC Table 7.
Maximum lift height – default is 5’, may increase to 12’-8” under some circumstances. SCG may be increased to pour height under some circumstances.
1999 MSJC – 5’ lift height limitation.
2002 MSJC – demonstration panel option permitting any construction procedures that produce proper installation.
2005 MSJC – lift height increased to 12’-8” subject to conditions.
2008 MSJC – Self-consolidating grout provisions
Tip 10 – Understand Grout Pours and Lifts
Grout lift height –
A.) Where the following conditions are met, place grout in lifts not exceeding 12.67 ft
1.The masonry has cured for at least 4 hours.
2. The grout slump is maintained between 10 and 11 in.
3. No intermediate reinforced bond beams are placed between the top and the bottom of the pour height.
B.) As above but intermediate bond beam, then lift height can extend to the bottom of the bond beam but not to exceed 12.67’.
C.) Otherwise, place grout in lifts not exceeding 5 ft.
D.) Demonstration panel option may result in increases.
E.) SCG may, under some circumstances be permitted to have the grout lift equal the pour height.
Understand Grout Pours and Lifts
LOW LIFT GROUTING
LOW LIFT GROUTING
LOW LIFT GROUTING
LOW LIFT GROUTING
LOW LIFT GROUTING
LOW LIFT GROUTING
LOW LIFT GROUTING
LOW LIFT GROUTING
LOW LIFT GROUTING
LOW LIFT GROUTING
LOW LIFT GROUTING
LOW LIFT GROUTING
LOW LIFT GROUTING
LOW LIFT GROUTING
LOW LIFT GROUTING
LOW LIFT GROUTING
LOW LIFT GROUTING
HIGH LIFT GROUTING
HIGH LIFT GROUTING
HIGH LIFT GROUTING
HIGH LIFT GROUTING
HIGH LIFT GROUTING
HIGH LIFT GROUTING
HIGH LIFT GROUTING
HIGH LIFT GROUTING
HIGH LIFT GROUTING - SCG
LOW LIFT GROUTING PROCEDURES DETAIL 02.410.0131 REV. 06/30/10
VERTICAL REINFORCEMENT FOR CLOSED-END CONCRETE MASONRY UNITS CAN BE SET AFTER WALL HAS BEEN LAID.
REBAR POSITIONER, WALL TIE, OR OTHER DEVICE TO POSTION VERTICAL REINFORCEMENT
HORIZONTAL REINFORCEMENT PLACED IN BOND BEAMS AS WALL IS LAID UP
METAL LATH, MESH, OR WIRE SCREEN PLACED IN MORTAR JOINTS UNDER KNOCK-OUT BOND BEAM COURSES TO PREVENT FILLING OF UNGROUTED CELLS
OPTION 2: STANDARD CMU W/ CROSS WEBS KNOCKED OUT AT BOND BEAM COURSE
OPTION 1: U-BLOCK UNITS W/ SOLID BOTTOM AT BOND BEAM COURSE
GROUT IN BOND BEAMS & REINFORCED VERTICAL CELLS PLACED IN TOP OF WALL AFTER WALL HAS BEEN LAID UP
STOP GROUT 1” FROM TOP OF POUR TO CREATE SHEAR KEY
CELLS CONTAINING REINFORCEMENT ARE FILLED SOLIDLY W/ GROUT; VERTICAL CELLS SHOULD PROVIDE A CONTINUOUS CAVITY FREE OF MORTAR DROPPINGS
NOTE: GROUT PLACED IN POURS & LIFTS NOT TO EXCEED 5 FT. CONSOLIDATE LIFTS OVER 12” USING MECH. VIBRATION. LIFTS LESS THAN 12” MAY BE PUDDLED.
HIGH LIFT GROUTING PROCEDURES DIAGRAM 02.410.0131 REV. 07/06/10
VERTICAL REINFORCEMENT FOR CLOSED-END CONCRETE MASONRY UNITS CAN BE SET AFTER WALL HAS BEEN LAID.
REBAR POSITIONER, WALL TIE, OR OTHER DEVICE TO POSTION VERTICAL REINFORCEMENT
HORIZONTAL REINFORCEMENT PLACED IN BOND BEAMS AS WALL IS LAID UP
METAL LATH, MESH, OR WIRE SCREEN PLACED IN MORTAR JOINTS UNDER KNOCK-OUT BOND BEAM COURSES TO PREVENT FILLING OF UNGROUTED CELLS
OPTION 2: STANDARD CMU W/ CROSS WEBS KNOCKED OUT AT BOND BEAM COURSE
OPTION 1: U-BLOCK UNITS W/ SOLID BOTTOM AT BOND BEAM COURSE
GROUT IN BOND BEAMS & REINFORCED VERTICAL CELLS PLACED IN TOP OF WALL AFTER WALL HAS BEEN LAID UP
STOP GROUT 1” FROM TOP OF POUR TO CREATE SHEAR KEY
CELLS CONTAINING REINFORCEMENT ARE FILLED SOLIDLY W/ GROUT; VERTICAL CELLS SHOULD PROVIDE A CONTINUOUS CAVITY FREE OF MORTAR DROPPINGS
NOTE: GROUT LIFTS NOT TO EXCEED 5 FT. SEE STRUCTURAL DWGS FOR MAX. HEIGHT OF POUR. MECH. CONSOLIDATE & RECONSOLIDATE GROUT
CLEANOUT OPENINGS @ BASE OF VERTICALLY REINF. CELLS, 32” O.C. MAX. SPACING FOR SOLID GROUTED WALLS. REMOVE MORTAR DROPPINGS THROUGH CLEANOUTS AND VERIFY PLACEMENT & LOCATION OF VERTICAL REINF.; FORM OVER OPEN’GS BEFORE PLACING GROUT
HEAD DETAIL DETAIL 01.301 REV. 09/04/07
© 2007 INTERNATIONAL MASONRY INSTITUTE
BRIC
K &
BLO
CK C
AV
ITY W
ALL
DETAILING MASONRY
SERIES www.imiweb.org 800-IMI-0988
International Masonry Institute
STEEL LINTEL & BOND BEAM
INTERIOR VIEW
EXTERIOR VIEW
DETAIL FEATURES
• LOOSE LINTEL AT BRICK • BOND BEAM AT BLOCK • LIGHT GAUGE SUPPORT ACROSS CAVITY
SPANNING OPENINGS
Poly-wrapped steel angles used for temporary support
CAST-IN-PLACE MASONRY LINTEL
SPANNING OPENINGS
Precast masonry lintel fabricated on the ground
PRECAST LINTELS
SPANNING OPENINGS
Lintel is hoisted by lift
PRECAST LINTELS
SPANNING OPENINGS
Precast lintel set into place
PRECAST LINTELS
SPANNING OPENINGS
10-foot span
PRECAST LINTELS
BRACE CLEANOUT AND PLACE GROUT
CUT PORTION OF FACE SHELL TO CREATE CLEANOUT
REINSERT FACE SHELL AND MORTAR IN PLACE
PLACE REINFORCING AND INSPECT WALL FOR OBSTRUCTIONS
REMOVE BRACING
BLOCK CLEANOUT DIAGRAM 02.410.0111 REV. 06/12/09
CUT FACE SHELL FOR CLEANOUT
WOOD BRACING
GROUT & REINFORCEMENT
BLOCK CLEANOUT DIAGRAM 02.410.0112 REV. 06/12/09
REINSERT FACE SHELL PIECE TO RESIST GROUT PRESSURE
CUT WEDGE-SHAPED PORTION OF FACE SHELL TO CREATE CLEANOUT
CLEANOUT
MORTAR FACE SHELL EDGES IF NECESSARY
BLOCK CLEANOUT DIAGRAM 02.410.013 REV. 06/12/09
1. CUT OUT PORTION OF FACE SHELL
2. PLACE ACRYLIC GROUT STOP INTEGRALLY BRACED AGAINST INSIDE OF FACE SHELL
3. HAND-TIGHTEN BRACE
5. REMOVE ACRYLIC AND BREAK OFF PLASTIC BRACE
4. PLACE REBAR & GROUT
BLOCK CLEANOUT DIAGRAM 02.410.0114 REV. 06/12/09
Give the Contractor Some Latitude
Give the contractor some latitude in the….
Selection of Fine or Coarse Grout Technical considerations
Grout space dimensions
Pour height limitations
Compressive strength independent of type
Constructability considerations Ease of use/Personal preference
Cost implications – material, placement
Issues related to pour height (next slide)
Fine Grout might be better suited here
Coarse or Fine Grout here
VERTICAL REINFORCEMENT AS REQ’D
GROUT AS REQ’D
HORIZONTAL JOINT REINFORCEMENT
CMU SHOWN IN LONGITUDINAL SECTION
DOWELS MAY BE BENT UP TO 1” LATERALLY PER 6” VERTICALLY
FOUNDATION
FOUNDATION DOWEL ALIGNMENT DETAIL 02.010.0301 REV. 02/22/09
1/2” MAX.
MORTAR FIN
MORTAR PROTRUSION TOLERANCE DIAGRAM 02.410.0121 REV. 02/22/09
1/2” MIN. FOR COURSE GROUT 1/4” MIN. FOR FINE GROUT
MINIMUM DISTANCE FROM ANY PROTRUSION:
REINFORCEMENT PLACEMENT TOLERANCE DIAGRAM 02.410.0123 REV. 02/22/09
SPACING OF VERTICAL REINFORCEMENT
±1/2” IF d ≤ 8”
d
±1” IF 8”< d ≤ 24” ±1¼” IF d > 24”
±2”
REINFORCEMENT PLACEMENT TOLERANCE DIAGRAM 02.410.0122 REV. 02/24/09
5/8” MIN.
1/2” MIN. 2db MIN.
EXTERIOR FACE OF WALL INTERIOR
FACE OF WALL E
XT
ER
IOR
F
AC
E
INT
ER
IOR
F
AC
E
HORIZONTAL JOINT REINFORCEMENT W/ DIAMETER db
2db MIN.
HORIZONTAL JOINT REINFORCEMENT TOLERANCE DIAGRAM 02.410.0124 REV. 02/22/09
WORKMANSHIP
FULL HEAD JOINTS
MOISTURE RESISTANCE
protect materials
protect work
PROTECTION OF WORK
QUALITY CONTROL
SAMPLE PANELS
QUALITY CONTROL
COLOR BLENDING
QUALITY CONTROL
COMMUNICATION
QUALITY CONTROL
COMMUNICATION
QUALITY CONTROL
CONSTRUCTION TOLERANCES
ALLOWABLE MORTAR JOINT VARIATION
CONSTRUCTION TOLERANCES
MORTAR JOINT TOLERANCES DIAGRAM 01.410.0301 REV. 08/06/09
3/8”
3/8”
1/4”
1/2”
1/8” 3/4”
ALLOWABLE JOINT TOLERANCE
BED JOINT ±1/8” HEAD JOINT -1/4”, +3/8” COLLAR JOINT -1/4”, +3/8”
AREA OF DETAIL
ELEVATION
SOURCE: BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES (ACI 530-05/ASCE 5-05/TMS 402-05) REPORTED BY THE MASONRY STANDARDS JOINT COMMITTEE (MSJC)
ALLOWABLE CONSTRUCTION TOLERANCES DETAIL 14.105 REV. 07/09/08
© 2008 INTERNATIONAL MASONRY INSTITUTE
WO
RKM
AN
SH
IP T
OLE
RA
NC
ES
DETAILING MASONRY
SERIES www.imiweb.org 800-IMI-0988
International Masonry Institute STEEL (AISC)
CONCRETE (ACI)
BRICK (MSJC)
1” 1” 2¼” 1/2” 1/2”
1¼”
80’-0”
20’-0”
ALLOWABLE CONSTRUCTION TOLERANCES DETAIL 14.105 REV. 07/09/08
© 2008 INTERNATIONAL MASONRY INSTITUTE
WO
RKM
AN
SH
IP T
OLE
RA
NC
ES
DETAILING MASONRY
SERIES www.imiweb.org 800-IMI-0988
International Masonry Institute STEEL (AISC)
CONCRETE (ACI)
BRICK (MSJC)
1” 1” 2¼” 1/2” 1/2”
1¼”
80’-0”
20’-0”
ALLOWABLE CONSTRUCTION TOLERANCES DETAIL 14.105 REV. 07/09/08
© 2008 INTERNATIONAL MASONRY INSTITUTE
WO
RKM
AN
SH
IP T
OLE
RA
NC
ES
DETAILING MASONRY
SERIES www.imiweb.org 800-IMI-0988
International Masonry Institute STEEL (AISC)
CONCRETE (ACI)
BRICK (MSJC)
1” 1” 2¼” 1/2” 1/2”
1¼”
80’-0”
20’-0”
d
L < 10’-0” d < 1/4“
WHEN
L < 20’-0” d < 3/8“
WHEN
L > 20’-0” d < 1/2“
WHEN
C I L
d
L
LENGTH OF WALL
ALLOWABLE VARIATION FROM PLAN AT ANY POINT
L =
d =
ALLOWABLE VARIATIONS FOR OUT-OF-LINE
CONSTRUCTION TOLERANCES
ALLOWABLE VARIATIONS FOR OUT-OF-PLUMB
D
WALL HEIGHT
ALLOWABLE VARIATION FROM PLUMB AT ANY POINT
L C I D
H =
D =
H < 10’-0” D < 1/4“
WHEN
H < 20’-0” D < 3/8“
WHEN
H > 20’-0” D < 1/2“
WHEN
H
CONSTRUCTION TOLERANCES
C I L
1/4
”
1/2
”
≤10’-0”
1/4
”
1/2
”
≥20’-0”
ALLOWABLE VARIATIONS FOR OUT-OF-LEVEL
CONSTRUCTION TOLERANCES
THEREFORE WHEN WE BUILD, LET US THINK THAT WE BUILD FOR EVER.
LET IT NOT BE FOR PRESENT DELIGHT, NOR FOR PRESENT USE ALONE;
AND LET US THINK AS WE LAY STONE UPON STONE,
THAT A TIME IS TO COME
WHEN THOSE STONES WILL BE HELD SACRED BECAUSE OUR HANDS HAVE TOUCHED THEM,
“SEE! THIS OUR FATHERS DID FOR US.”
AND THAT MEN WILL SAY AS THEY LOOK UPON THE LABOUR AND WROUGHT SUBSTANCE OF THEM,
John Ruskin, 1849 The Seven Lamps of Architecture
LET IT BE SUCH WORK AS
OUR DESCENDANTS WILL THANK US FOR.
[my descendant]
Structural
Durable / Low Maintenance
Economical
Beauty
BENEFITS OF BUILDING WITH MASONRY
Versatility of Design
Ease of Construction
Fire & Impact Resistant
Contextual / Relatable
Sustainable
Energy Efficient
High Performance
Acoustic
Qualified Local Labor
BAC CONTRACTORS
IMI-TRAINED CRAFTWORKERS
International Union of Bricklayers and Allied Craftworkers
International Masonry Institute