Power Xpert 9395P 750-900 kVA UPS Dimensional Drawings
Notes:1. The system must be installed in a temperature and humidity controlled indoor area free of conductivecontaminants.2. Continuous ambient temperature range: 0-40°C (32-104F) for 750 kVA/750 kW and 900 kVA/825 kW ;Maximum relative humidity: 95% non-condensing.3. Continuous ambient temperature range:0-35°C (32-95F) for 900 kVA/kW; Maximum relative humidity: 95%non-condensing.4. Minimum overhead clearance for ventilation above the UPS cabinet is 457mm (18in.).5. Minimum 915mm (36in.) clearance in front of the UPS cabinet is required for cooling air intake and servicingspace.6. Top and bottom cable entries through removable access plates are standard for all configurations. Access platesshall be custom-modified to suit conduit sizes.7. When using copper bus bars, add 100Kg to the total weight.8. For system installation an additional 130 mm in width is required.
67
1878
UPMUPMISBMFI-UPM
3054
TOP VIEW
BOTTOM VIEWCUSTOMER LANDING PANEL
LEFT VIEW
3800
SIGNAL CABLE OPENINGS(2 PCS)
CUSTOMER LANDING PANEL83062
580
101
520700691899326 326
871
4037537540
©
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 A2
A
B
C
D
E
F
G
H
A
B
C
D
E
F
G
H82
1:16
A2
RELEASED
003
AUTOCAD DRAWING
06.09.2019
27.04.2015
N. Hyppänen
ATIF RASHEED
P-110000421
Power Xpert 9395P-600(900) kVA UPS Dimensional Drawings
Notes:1. The system must be installed in a temperature and humidity controlled indoor area free of conductivecontaminants.2. Continuous ambient temperature range: 0-40°C (32-104F); Maximum relative humidity: 95% non-condensing.3. Minimum overhead clearance for ventilation above the UPS cabinet is 457mm (18in.).4. Minimum 915mm (36in.) clearance in front of the UPS cabinet is required for cooling air intake and servicingspace.5. Top and bottom cable entries through removable access plates are standard for all configurations. Access platesshall be custom-modified to suit conduit sizes.6. When using copper bus bars, add 100Kg to the total weight.7. For system installation an additional 130 mm in width is required.
67
317
0
497
677
857
1037
1217
1397
1577
1098
977
857
627
39722
50
530
3850
315
245
175
105
627
557
697
767
837
A
B
L2(E7)
L3(E8)
L1(E6)
⏚(PE)
N(E12)L3(E3)
L2(E2)
L1(E1)
E4
E5
L2(E10)
L3(E11)
L1(E9)
L2(E2)
L3(E8)
L1(E6)
L3(E3)
L1(E1)
L2(E7)
⏚(PE)
N(E12)
L2(E10)
L3(E11)
L1(E9)
COPPER BUSBARS
SEPARATE BATTERYBUSBARS DC + (E4)
SEPARATEBATTERYBUSBARSDC - (E5)
DC+ (E4,(UPM4)
E5 (dc-,UPM4)
SEE DETAIL D
AC INPUTTO UPSBYPASS
AC OUTPUT TOCRITICAL LOAD
AC INPUTTO UPSRECTIFIER
DC INPUTFROM THEBATTERY
COMMON DC-(E5)
COMMON DC+(E4)
C
DETAIL A
02580135
164
0255075
100∅14
DETAIL B
0275072
100
0 25 80 135
180
∅14
0
0
25
80
135160
25 80 135
320
DETAIL C
∅14
COMMON DC+(E4)
COMMON DC -(E5)
DETAIL DCOMMON BATTERY CONFIGURATION BUSBARS
©
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 A2
A
B
C
D
E
F
G
H
A
B
C
D
E
F
G
H83
1:10
A2
RELEASED
003
AUTOCAD DRAWING
06.09.2019
27.04.2015
N. Hyppänen
ATIF RASHEED
P-110000421
Power Xpert 9395P 750-900 kVA UPS With Copper Bus Bars
Note:1. The Copper Bus Bars are Tin coated and are suitable for both Al and CU Connections.
317
0
497
677
857
1037
1217
1397
1577
1098
977
857
627
397
2250
5300 315
245
175
105
627
557
697
767
837
A
B
L2(E7)
L3(E8)
L1(E6)
⏚(PE)
N(E12)L3(E3)
L2(E2)
L1(E1)
SEPARATE BATTERYBUSBARS DC + (E4)
SEPARATEBATTERYBUSBARSDC - (E5)
L2(E10)
L3(E11)
L1(E9)
L2(E2)
L3(E8)
L1(E6)
L3(E3)
L1(E1)
L2(E7)
COMMON DC-(E5)
COMMON DC+(E4)
AC INPUTTO UPSBYPASS
AC OUTPUT TOCRITICAL LOAD
AC INPUTTO UPSRECTIFIER
DC INPUTFROM THEBATTERY
DC+ (E4,(UPM4)
E5 (dc-,UPM4)
ISBM CABINET FRONT VIEW ISBM CABINET LEFT VIEW
SEE DETAIL D
ALUMINIUM BUSBARS
⏚(PE)
N(E12)
C
DETAIL A
02580135
164
025
80
135160
∅14
DETAIL B
0 25 80 135
0275072100
∅14
0
0
25
80
135160
25 80 135
DETAIL C
320
∅14
COMMON DC+(E4)
COMMON DC -(E5)
DETAIL DCOMMON BATTERY CONFIGURATION BUSBARS
©
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 A2
A
B
C
D
E
F
G
H
A
B
C
D
E
F
G
H84
1:10
A2
RELEASED
003
AUTOCAD DRAWING
06.09.2019
27.04.2015
N. Hyppänen
ATIF RASHEED
P-110000421
Power Xpert 9395P 750-900 kVA UPS With Aluminium Bus Bars
Note:1. The Aluminum Bus Bars are Tin coated and are suitable for both Al and CU Connections.
BYPASS INPUT
UPS OUTPUT
BATTERYCONNECTIONS
AC INPUT
L1(E6)L2(E7)L3(E8)
GROUND
N(E12)L1(E9)L2(E10)L3(E11)
+(E4)-(E5)
L1(E1)L2(E2)L3(E3)
BEHIND COVERS TB11 REMOTE EPO NC2 REMOTE EPO NO RTN3 REMOTE EPO NO4 REMOTE EPO NO RTN5 BATT AUX6 BATT AUX RTN7 BATT SHUNT +8 BATT SHUNT -9 K3 NC AUX10 K3 NC AUXTB21 PULL CHAIN2 PULL CHAIN RTN3 ALRM RELAY NC4 ALRM RELAY RTN5 ALRM RELAY NO6 ALRM RELAY RTNTB31 BLDG ALARM 12 BLDG ALARM 1 RTN3 BLDG ALARM 24 BLDG ALARM 2 RTN5 BLDG ALARM 36 BLDG ALARM 3 RTN7 BLDG ALARM 48 BLDG ALARM 4 RTN9 BLDG ALARM 510 BLDG ALARM 5 RTNTB61 BYP L12 BYP L23 BYP L34 BYP N5 OUT L16 OUT L27 OUT L38 SYNC L19 SYNC L210 SYNC L3
ɸɸɸ
ɸɸɸɸɸɸ
TB1
X-SLOT 1X-SLOT 2
X-SLOT 3X-SLOT 4
TB2
TB3
TB6
©
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 A2
A
B
C
D
E
F
G
H
A
B
C
D
E
F
G
H85
1:20
A2
RELEASED
003
AUTOCAD DRAWING
06.09.2019
27.04.2015
N. Hyppänen
ATIF RASHEED
P-110000421
9395P 750-900 kVA UPS Customer Connections Isometric
-
UPM 1
L1L2L3NPE
CB13P(OPT)
K2
K3
K1
9395P UPS
ACOutput
56
78
9395P UPS
EPO NC
ALTE
RNAT
ESY
NC B
A3
MAI
NTEN
ANCE
BYPA
SS B
A1
ALM
ALM
RTN
CAN
L
CAN
HSH
IELD
CAN
LCA
N H
SHIE
LD
12
43
910
EPO NO RTN
EPO N0
EPO NO RTN
BATT AUX NO
BATT SHUNT +
BATT SHUNT -
BATT AUX NO RTN
K3(INV) NC AUXOn Bypass/Offline
TB1
5 6 7 81 2 43 9 10TB3
56
78
12
43
910
PULL
CHA
IN
PULL
CHA
IN R
TNAL
ARM
REL
AY N
C
ALAR
M R
ELAY
RTN
ALAR
M R
ELAY
NO
ALAR
M R
ELAY
RTN
BYP L1BYP L2BYP L3
BYP N
OUT L1
OUT L2
OUT L3
SYNC L1
SYNC L2
SYNC L3
TB6ɸɸɸ
ɸɸ
ɸɸ
ɸ
ɸ
BCB
5 61 2 43TB2
+
BLDG
ALA
RM R
TN
BLDG
ALA
RM 2
BLDG
ALA
RM R
TN
BLDG
ALA
RM 4
BLDG
ALA
RM R
TN
BLDG
ALA
RM 5
OPTIONAL FORPARALLEL UPS
OPTIONAL FORPARALLEL UPS
MOB
RIB BIB
UPM 2
UPM 3
K5
©
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 A2
A
B
C
D
E
F
G
H
A
B
C
D
E
F
G
H86
N/A
A2
RELEASED
003
AUTOCAD DRAWING
06.09.2019
27.04.2015
N. Hyppänen
ATIF RASHEED
P-110000421
Power Xpert 9395P 750-900 kVA UPS Electrical Wiring
L1L2L3NPE
9395P UPS
ALM
ALM
RTN
CAN
LCA
N H
SHIE
LD
9395P UPS
CAN
LCA
N H
SHIE
LD
ALM
ALM
RTN
CAN
LCA
N H
SHIE
LD
CAN
LCA
N H
SHIE
LD
TO MOB 1NC AUX
ALM
ALM
RTN
CAN
LCA
N H
SHIE
LD
CAN
LCA
N H
SHIE
LD
TO MOB 2NC AUX
TO MOB NNC AUX
TO MOB 1NO AUX TO MOB 2NO AUX
TO MOB NNO AUX
a,b
b,c
UPS 1
UPS 1
UPS 2
UPS N
56
78
EPO NC
ALTE
RNAT
ESY
NC B
A3
MAI
NTEN
ANCE
BYPA
SS B
A1
24
39
10
EPO NO RTNEPO N0
EPO NO RTN
BATT AUX NO
BATT SHUNT +
BATT SHUNT -
BATT AUX NO RTN
K3(INV) NC AUXOn Bypass/Offline
TB1
5 6 7 81 2 43 9 10TB3
56
78
12
43
910
PULL
CHA
INPU
LL C
HAIN
RTN
ALAR
M R
ELAY
NC
ALAR
M R
ELAY
RTN
ALAR
M R
ELAY
NO
ALAR
M R
ELAY
RTN
BYP L1BYP L2BYP L3
BYP N
OUT L1
OUT L2OUT L3
SYNC L1
SYNC L2
SYNC L3
TB6ɸɸɸ
ɸɸɸɸ
ɸɸ
5 61 2 43TB2
56
78
EPO NC
ALTE
RNAT
ESY
NC B
A3
MAI
NTEN
ANCE
BYPA
SS B
A1
24
39
10
EPO NO RTNEPO N0
EPO NO RTN
BATT AUX NO
BATT SHUNT +
BATT SHUNT -
BATT AUX NO RTN
K3(INV) NC AUXOn Bypass/Offline
TB1
5 6 7 81 2 43 9 10
BLDG
ALA
RM R
TN
BLDG
ALA
RM 2
TB3
56
78
12
43
910
PULL
CHA
INPU
LL C
HAIN
RTN
ALAR
M R
ELAY
NC
ALAR
M R
ELAY
RTN
ALAR
M R
ELAY
NO
ALAR
M R
ELAY
RTN
BYP L1BYP L2BYP L3
BYP N
OUT L1
OUT L2OUT L3
SYNC L1
SYNC L2
SYNC L3
TB6ɸɸɸ
ɸɸɸɸ
ɸɸ
5 61 2 43TB2
56
78
9395P UPS
EPO NC
ALTE
RNAT
ESY
NC B
A3
MAI
NTEN
ANCE
BYPA
SS B
A1
12
43
910
EPO NO RTNEPO N0
EPO NO RTN
BATT AUX NO
BATT SHUNT +
BATT SHUNT -
BATT AUX NO RTN
K3(INV) NC AUXOn Bypass/Offline
TB1
5 6 7 81 2 43 9 10TB3
56
78
12
43
910
PULL
CHA
INPU
LL C
HAIN
RTN
ALAR
M R
ELAY
NC
ALAR
M R
ELAY
RTN
ALAR
M R
ELAY
NO
ALAR
M R
ELAY
RTN
BYP L1BYP L2BYP L3
BYP N
OUT L1
OUT L2OUT L3
SYNC L1
SYNC L2
SYNC L3
TB6ɸɸɸ
ɸɸɸɸ
ɸɸ
5 61 2 43TB2
TO BCB 1 TO BCB 2 TO BCB N
BLDG
ALA
RM R
TN
BLDG
ALA
RM 4
BLDG
ALA
RM R
TN
BLDG
ALA
RM 5
BLDG
ALA
RM R
TN
BLDG
ALA
RM 2
BLDG
ALA
RM R
TN
BLDG
ALA
RM 4
BLDG
ALA
RM R
TN
BLDG
ALA
RM 5
BLDG
ALA
RM R
TN
BLDG
ALA
RM 2
BLDG
ALA
RM R
TN
BLDG
ALA
RM 4
BLDG
ALA
RM R
TN
BLDG
ALA
RM 5
1 1
OPTIONAL OPTIONAL OPTIONAL
ST ST ST
POWER WIRING
SIGNAL WIRING
-
UPM 1
CB13P(OPT)
K2
K3
K1
9395P UPS
ACOutput
BCB 1
+
MOB 1
RIB BIB UPS 2
-
UPM 1
CB13P(OPT)
K2
K3
K1
9395P UPS
ACOutput
BCB 2
+
MOB 2
RIB BIB UPS N
-
UPM 1
CB13P(OPT)
K2
K3
K1
9395P UPS
ACOutput
BCB N
+
MOB N
RIB BIB
a
c
MBS
L N230v
UPM 2
UPM 2 UPM 2
UPM 3 UPM 3 UPM 3
MIS
MBS
K5 K5 K5
LOADS
©
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 A2
A
B
C
D
E
F
G
H
A
B
C
D
E
F
G
H87
N/A
A2
RELEASED
003
AUTOCAD DRAWING
06.09.2019
27.04.2015
N. Hyppänen
ATIF RASHEED
P-110000421
Power Xpert 9395P 750-900 kVA UPS Wiring Parallel Units
MBS STATUS (Provided by others, Installed by others)
MOB STATUS (Provided by others, Installed by others)
PCAN (DUAL AS OPTION)
Provided by Eaton, Installed by Eaton
PULL CHAIN (REDUNDANT ON BYP STATUS)
Provided by Eaton, Installed by Eaton
ON BYPASS STATUS (NO INVERTORS ONLINE)
Provided by others, Installed by others
1.5 - 2.5mm² , 600v0.75 - 2.5mm² twisted pair (if possible, else shielded)No earth needed
0.75 - 2.5mm² twisted pair (if possible, else shielded) No earth needed
Mechanical bypass interlocking sequence
1. Place UPS system to bypass. On bypass status (K3) will energize Key A solenoid to release it
2. Removing key A will switch on "force bypass" to the UPS system
3. Place key A to MBS breaker and close breaker. Key B will be released.
4. Aux contact of MBS will keep "force bypass" on UPS system
5. Place key B to MIS breaker and open MIS to isolate UPS system from load. Key C will be released
6. Place key C to it's dedicated keyhole to release "force bypass" command to allow UPS system testing