  • PCD7.D763 displays a black screen or is frozen, it has lost the calibration!

    Solution The boot and the firmware need to be updated! If it isn't possible to force the display in transfer mode (download mode) it is necessary first to

    recalibrate the screen following the description. See FAQ 100868 (see link below)! All displays produced since 16/07/2010 have the new boot! Procedure

    to update boot and firmware If you use PCD8.D81W software version 5.22 skip to point 4 directly or point 5 if the display has already a new boot:

    Download the files attached to this FAQ and unzip the archives.Copy the bootloader files "BT525MTF.FIL" into the following folder: "C:Program

    FilesSAIAPCD8.D81W_51x\boot\" Copy the firmware files "VT525W.BIN" into the following folder: "C:Program FilesSAIAPCD8.D81W_51x\firmware\" The

    boot has to be sent via the bootloader download utility. In PCD8.D81W (programming tool; select the menu TOOLS / BOOT UPDATE-AUTOMATIC), enter

    the password 371013 and follow the instructions. Open the project, compile it again and download it to the panel and active the download option "Update

    operating unit firmware". Remark: during the download the Boot version is desplayed: version 3.9! When the download has finished, after a powerup of

    the panel, please verify that the new firmware version is - 1.13 for PCD7.D763 Remark Please note that the PCD8.D81W version 5.22 CONTAINS this new

    boot and FW version! It can be downloaded with this link: sbc-support.ch/download/pcd8_d81w_v5_22.zip It is mendatory to use this new FW only on

    panel having this new boot!

    faq http://www.sbc-support.com/en/faq/pcd7d763_displays_a_black_scre...

    1 sur 1 14/06/2014 16:51