Asset: P.S. 124 - BROOKLYN, 515 4TH AVENUE, New York, 11215
Inspection Id Inspection Type Time In Last Edited
SA : K124 Architectural - Senior 2020-07-13 11:03 AM 2020-07-13 3:48 PM
AA : K124 Architectural - Associate 2020-07-13 11:41 AM 2020-07-13 2:47 PM
Asset Data
Question Answer
Was the building fully accessible for inspection No
Inspection Access Comment Grounding System (No Key)
Principal(s) Information
Principal Name Maria Interlandi
Organization P.S. 124 - Brooklyn
Did you meet with this Principal? Yes
Did this Principal provide feedback? Yes
Summary of Principal's Feedback The Principal's comments are as follows: 1. Water penetration fromroof in Room 304A2. Water penetration from roof at Exit Stairs 6E (C/D).3. Water penetration from Foundation Walls at Exit Stair 7F (A/B)Basement Staff Toilet Room, Multipurpose Room, Cafeteria.4. Climate control system is not functioning properly.5. Window balances throughout the building are defective.
Custodian Scott Rittenhouse
Fireman Desmond Hylegar (Handyman)
Building Square Footage 33,000
Comments on the Area None
Comments on the Stories (Floors) plus Basements 3+B
Comments on the Number of Classrooms 20
Comments on the Year Built 1900
Student Population 276
Staff Population 60
Weather Fair
Facade Photo
Corner of 4th Avenue and 13th Street -South View
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 1 of 50
Main Entrance Photo
Facade A - 4th Avenue
Roof Photo
Roof 1 - South View
Have any Systems/Major Building Components been upgraded? Yes
Systems: Flood Elimination Program including All RoofReplacement , Parapets Repairs and Facade C ExteriorWalls Repairs and Repointing. Bulkhead Repairs. NewRoof Guardrails. Boiler Room Foundation WallWaterproofing. New Canopy at Facade B. (Original FoyerRemoved). Partial Exterior Doors Replacement. SidewalkElevator Removed and opening closed.
Year: 2019
Systems: Partial Exterior Doors replacement; Ash Hoist Vault DoorsReplacement
Year: 2016
Systems: Basement Boys and Girls Toilet Rooms upgraded;Bulkhead Plaster Repairs; Exterior Stair Railings Repairs
Year: 2014
Systems: 1st Floor Boys and Girls Toilet Rooms upgraded
Year: 2013
Systems: Exterior Stairs and Partial Concrete PavementReplacement
Year: 2010
Systems: Roof 1 - Perimeter Roofing and Flashing Replacement;Parapets and Coping Replacement
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 2 of 50
Year: 2008
Systems: Window and Window Guards replacement; Twoclassrooms converted to a Library and a Music Room
Year: 1999
Have there been any New Building Additions? No
Tandem Schools? No
Leased Space? No
Priority Condition
PriorityCondition ExistLast Year?
PriorityCategory
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No ProtrudingElements
DamagedRailing is apotential safetyhazard.
INTERIOR |STAIRS/RAMPS: INTERIOR |Railings
StairAB/Bulkhead
ScottRittenhouse
Custodian
Yes Tripping Hazard Damaged draincover is apotentialtripping hazard.
INTERIOR |MULTI-PURPOSEROOM | FloorFinish
Near DrinkingFountain
ScottRittenhouse
Custodian
Structural Engineer Required
StructuralCondition Type
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Accessibility
Accessibility Status Question Response
Is the primary or secondary entrance on an accessible route? No
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
Exterior Entrances & Exits Yes
Exterior H/C Lifts No No
Exterior Ramps and Railings No Yes
Interior Routes
Corridor and Lobby H/C Lifts No Yes
Interior Corridor Doors and Hardware Yes Yes
Interior Corridors and Lobbies No Change in Elevation
Interior Elevators No
Interior Lobby Doors and Hardware Yes
Interior Ramps No
Rooms & Spaces
Art Rooms Room 208 Yes No Not on Accessible Route
Auditorium No
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 3 of 50
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
Rooms & Spaces
Cafeteria Basement Yes No Not on Accessible Route Yes No
Classrooms Basement Yes No Not on Accessible Route
Computer Rooms No
Gymnasium No
Library Room 305 Yes No Not on Accessible Route
Main Office Room 106 Yes No Not on Accessible Route
Multi-purpose Room Basement Yes No Not on Accessible Route Yes No
Nurse's Room Room 104A Yes No Not on Accessible Route
Pool No
Science Lab No
Toilet Rooms (Boys) None on Accessible Route Yes No Not on Accessible Route
Toilet Rooms (Girls) None on Accessible Route Yes No Not on Accessible Route
Toilet Rooms (Staff) None on Accessible Route Yes No Not on Accessible Route
Building Template
Inspection
Question Response
Architectural
EXTERIOR Inspected
AREAWAY Inspected
InspectedInstance on AW1 - AW6
Instance Condition 4 - Between Fair and Poor
Instance Quantity 6
Instance Quantity Uom EACH
Deficiency AREAWAY GRATINGS: MAJOR RUSTING AND / OR BROKENSUPPORTS
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 4 of 50
Question Response
EXTERIOR
AREAWAY
Roof Plan reference
Deficiency Quantity 180
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
AW2
Violations No violations recorded.
Deficiency AREAWAY WALLS: CRACKS AND SPALLING
Roof Plan reference
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 5 of 50
Question Response
EXTERIOR
AREAWAY
Deficiency Photo1
AW5
Violations No violations recorded.
AWNINGS AND CANOPIES Inspected
Condition 3 - Fair
Deficiency METAL: WATER PENETRATION
Roof Plan reference
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Facade B
Violations No violations recorded.
CHIMNEY Inspected
Material Type(s) Masonry
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
COPING Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
CORNICE Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 6 of 50
Question Response
EXTERIOR
CORNICE
Condition 2 - Between Good and Fair
Deficiency STONE: MINOR CRACKS, SPALLING
Roof Plan reference
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade B
Violations No violations recorded.
DOORS Inspected
DOORS AND FRAMES Inspected
Condition 5 - Poor
Deficiency METAL CLAD: DETERIORATED DOOR - MAJORDETERIORATION
Roof Plan reference
Deficiency Quantity 2
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 7 of 50
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Deficiency Photo1
Facade D
Violations No violations recorded.
Deficiency METAL: DETERIORATED DOOR AND FRAME - MINORDETERIORATION
Roof Plan reference
Deficiency Quantity 3
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TRANSOM/SIDE LIGHT Inspected
Condition 5 - Poor
Deficiency WOOD: EXCESSIVELY WEATHERED
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 8 of 50
Question Response
EXTERIOR
DOORS
TRANSOM/SIDE LIGHT
Roof Plan reference
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
EXTERIOR WALLS Inspected
Material Type(s) Masonry, Concrete
Replacement Quantity 18,000
Replacement Uom S.F.
InspectedInstance on All Facades
Instance Condition 4 - Between Fair and Poor
Instance Quantity 18,000
Instance Quantity Uom S.F.
Deficiency STONE: CRACKS AT BUILDING CORNERS
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 9 of 50
Question Response
EXTERIOR
EXTERIOR WALLS
Elevation
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade D
Violations No violations recorded.
Deficiency BRICK: WATER INFILTRATION IN NON-INSTRUCTIONALSPACE
Roof Plan reference
Elevation
Deficiency Quantity 50
Quantity Uom S.F.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 10 of 50
Question Response
EXTERIOR
EXTERIOR WALLS
Potential Action REPAIR
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A - MDF Room 302A
Violations No violations recorded.
Deficiency BRICK: OPEN JOINTS
Roof Plan reference
Elevation
Deficiency Quantity 1,800
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 11 of 50
Question Response
EXTERIOR
EXTERIOR WALLS
Facade A
Violations No violations recorded.
Deficiency BRICK: DETERIORATED MASONRY SILLS
Roof Plan reference
Elevation
Deficiency Quantity 80
Quantity Uom L.F.
Potential Action REMOVE AND REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
Deficiency BRICK: MINOR CRACKS AND SPALLING
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 12 of 50
Question Response
EXTERIOR
EXTERIOR WALLS
Roof Plan reference
Elevation
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action RESTITCH
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
Deficiency STONE: CHIPPED/SPALLED/BROKEN PIECES
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 13 of 50
Question Response
EXTERIOR
EXTERIOR WALLS
Elevation
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
Deficiency STONE: OPEN JOINTS
Roof Plan reference
Elevation
Deficiency Quantity 20
Quantity Uom L.F.
Potential Action REPOINT
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 14 of 50
Question Response
EXTERIOR
EXTERIOR WALLS
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
EXTERIOR SOFFITS Does not Exist
LOADING DOCK Does not Exist
LOUVER Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
PARAPETS Inspected
Material Type(s) Masonry
Replacement Quantity 2,500
Replacement Uom C.F.
InspectedInstance on All Facades
Instance Condition 2 - Between Good and Fair
Instance Quantity 2,500
Instance Quantity Uom C.F.
Deficiency BRICK: OPEN JOINTS
Roof Plan reference
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 - Facade D
Violations No violations recorded.
PLAZA DECK Does not Exist
ROOF Inspected
Roofing Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 15 of 50
Question Response
EXTERIOR
ROOF
Roofing
Replacement Quantity 9,000
Replacement Uom S.F.
ROOF HATCH/SMOKE HATCH Does not Exist
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
ROOF BARRIER Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
ROOF CAGE Does not Exist
ROOF FENCE Does not Exist
ROOFING Inspected
InspectedInstance on Modified Bitumen: All Roofs
Instance Condition 4 - Between Fair and Poor
Instance Quantity 9,000
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 2020
Source of Installation Custodial Staff
Deficiency MODIFIED BITUMEN: ROOFING: DELAMINATION
Roof Plan reference
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENTREMOVAL
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 (Above Room 304A)
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 16 of 50
Question Response
EXTERIOR
ROOF
Roofing
ROOFING
Violations No violations recorded.
Deficiency MODIFIED BITUMEN: ROOFING: MAJOR ACTIVE ROOFLEAKS IN INSTRUCTIONAL SPACE
Roof Plan reference
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENTREMOVAL
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 - Room 304A (Picture Taken) Roof 2 - Exit Stair 6E (C/D)Similar.
Violations No violations recorded.
ROOFING DRAINS Does not Exist
Specialties Inspected
BULKHEAD/PENTHOUSE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
CUPOLA/ SPIRES/ TOWERS Does not Exist
DORMER Does not Exist
DUNNAGE STEEL Does not Exist
SKYLIGHT/ROOF VENT Does not Exist
ROOF/GRAVITY TANK Does not Exist
STAIRS/RAMPS: EXTERIOR Inspected
BUILDING CHEEK/FLANK WALLS Inspected
Condition 5 - Poor
Deficiency STONE: DETERIORATED COPING STONE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 17 of 50
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
BUILDING CHEEK/FLANK WALLS
Roof Plan reference
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade D
Violations No violations recorded.
Deficiency STONE: OPEN JOINTS
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 18 of 50
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
BUILDING CHEEK/FLANK WALLS
Deficiency Photo1
Facade D
Violations No violations recorded.
Deficiency STONE: CRACKS/SPALLING - MAJOR
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade D
Violations No violations recorded.
Deficiency STONE: BULGING/DISPLACED
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 19 of 50
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
BUILDING CHEEK/FLANK WALLS
Roof Plan reference
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade D
Violations No violations recorded.
Deficiency BRICK: DETERIORATED COPING STONE
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 20 of 50
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
BUILDING CHEEK/FLANK WALLS
Deficiency Photo1
Facade B
Violations No violations recorded.
Deficiency BRICK: CRACKS/SPALLING - MAJOR
Roof Plan reference
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade B
Violations No violations recorded.
Deficiency STONE: DETERIORATED JOINTS AT COPING STONES
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 21 of 50
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
BUILDING CHEEK/FLANK WALLS
Roof Plan reference
Deficiency Quantity 10
Quantity Uom L.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade B
Violations No violations recorded.
Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR
Roof Plan reference
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 22 of 50
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
BUILDING CHEEK/FLANK WALLS
Deficiency Photo1
Facade B
Violations No violations recorded.
RAILINGS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
STAIRS/RAMPS Inspected
Condition 5 - Poor
Deficiency STONE: OPEN JOINTS
Roof Plan reference
Deficiency Quantity 10
Quantity Uom L.F.
Potential Action REPOINT
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade B
Violations No violations recorded.
Deficiency CONCRETE: WORN-OUT TREAD/RISER/NOSING
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 23 of 50
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
STAIRS/RAMPS
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade C
Violations No violations recorded.
Deficiency STONE: WORN-OUT TREAD/RISER/NOSING
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 24 of 50
Question Response
EXTERIOR
STAIRS/RAMPS: EXTERIOR
STAIRS/RAMPS
Deficiency Photo1
Facade A
Violations No violations recorded.
WINDOWS Inspected
Replacement Quantity 5,000
Replacement Uom S.F.
EXTERIOR GUARDS Inspected
Condition 3 - Fair
Deficiency DETERIORATED/TORN-OUT/MISSING
Roof Plan reference
Elevation
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 25 of 50
Question Response
EXTERIOR
WINDOWS
EXTERIOR GUARDS
Deficiency Photo1
Facade A - Near AW5
Violations No violations recorded.
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
WINDOWS Inspected
Material Type(s) Aluminum
InspectedInstance on Aluminum - Double Hung: All Facades
Instance Condition 3 - Fair
Instance Quantity 5,000
Instance Quantity Uom S.F.
Installation Year 1999
Source of Installation Custodial Staff
Deficiency ALUMINUM - DOUBLE HUNG: INOPERABLE BALANCE
Roof Plan reference
Elevation
Deficiency Quantity 80
Quantity Uom EACH
Potential Action REPLACE BALANCES
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 26 of 50
Question Response
EXTERIOR Inspected
WINDOWS Inspected
WINDOWS
Deficiency Photo1 No photo recorded
Violations No violations recorded.
INTERIOR Inspected
POOLS Does not Exist
STRUCTURAL Inspected
COLUMNS/BEAMS/BEARING WALLS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
FLOOR STRUCTURE Inspected
Condition 3 - Fair
Deficiency CINDER CONCRETE ARCH: METAL PAN DETERIORATED,SPALLED
Deficiency Location/Instance Basement - Electrical Panel Room, Boiler Room
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 5
Deficiency Photo1
Basement - Electrical Panel Room
Violations No violations recorded.
Deficiency CONCRETE: CRACKS/SPALLED/REINFORCEMENT EXPOSED
Deficiency Location/Instance Basement - Electrical Panel Room, Boiler Room
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
Deficiency Photo1
Basement - Electrical Panel Room
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 27 of 50
Question Response
INTERIOR Inspected
STRUCTURAL
FOUNDATION WALLS Inspected
Material Type(s) Concrete, Masonry
Condition 5 - Poor
Deficiency CONCRETE: WATER INFILTRATION IN NON- INSTRUCTIONALSPACE
Deficiency Location/Instance Basement - Boiler Room
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action INSTALL WATERPROOFING
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 5
Deficiency Photo1
Basement - Boiler Room
Violations No violations recorded.
Deficiency BRICK: OPEN JOINTS
Deficiency Location/Instance Basement - Electrical Panel Room, Boiler Room
Deficiency Quantity 120
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 5
Deficiency Photo1
Basement - Electrical Panel Room
Violations No violations recorded.
Deficiency BRICK: WATER INFILTRATION IN INSTRUCTIONAL SPACE
Deficiency Location/Instance Basement - Staff Toilet Room, Exit Stair 7F (A/B) to Courtyard,Cafeteria, Multipurpose Room
Deficiency Quantity 400
Quantity Uom S.F.
Potential Action INSTALL WATERPROOFING
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 28 of 50
Question Response
INTERIOR
STRUCTURAL
FOUNDATION WALLS
Deficiency Photo1
Basement - Staff Toilet Rooms
Violations No violations recorded.
Deficiency BRICK: CRACKED/SPALLED
Deficiency Location/Instance Basement - Electrical Panel Room, Custodian Storage/Toilet Room
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action RESTITCH
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 5
Deficiency Photo1
Basement - Electrical Panel Room
Violations No violations recorded.
ROOF STRUCTURE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
VAULTS-BUNKERS Inspected
Foundation Walls Inspected
Condition 3 - Fair
Deficiency OPEN JOINTS
Deficiency Location/Instance Basement - Ash Hoist Vault
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 5
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 29 of 50
Question Response
INTERIOR
STRUCTURAL
VAULTS-BUNKERS
Foundation Walls
Deficiency Photo1
Basement - Ash Hoist Vault
Violations No violations recorded.
Slab Structure Inspected
Condition 3 - Fair
Deficiency CINDER CONCRETE ARCH: METAL PAN DETERIORATED,SPALLED
Deficiency Location/Instance Basement - Ash Hoist Vault
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 5
Deficiency Photo1
Basement - Ash Hoist Vault
Violations No violations recorded.
Vault/Ash Hoist Doors and Framing Inspected
Condition 5 - Poor
Deficiency WATER INFILTRATION
Deficiency Location/Instance Basement - Ash Hoist Vault
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 30 of 50
Question Response
INTERIOR
STRUCTURAL
VAULTS-BUNKERS
Vault/Ash Hoist Doors and Framing
Deficiency Photo1
Basement - Ash Hoist Vault
Violations No violations recorded.
AUDITORIUM Does not Exist
CAFETERIA Inspected
InspectedInstance on Basement (1500 SF)
Ceiling
InspectedInstance on Basement (1500 SF)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
Not RequiredInstance on Basement (1500 SF)
Fixed Equipment
Does not ExistInstance on Basement (1500 SF)
Floor Finish
InspectedInstance on Basement (1500 SF)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Sliding-folding Partition
Does not ExistInstance on Basement (1500 SF)
Stage
Does not ExistInstance on Basement (1500 SF)
Walls
InspectedInstance on Basement (1500 SF)
Condition 3 - Fair
Deficiency WALL PADDING: DETERIORATED
Deficiency Location/Instance Center columns
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 31 of 50
Question Response
INTERIOR
CAFETERIA
Walls
Deficiency Photo1
Center columns
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK
Deficiency Location/Instance Near Stair CD
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Near Stair CD
Violations No violations recorded.
Window Curtains/Shades/Blinds
Does not ExistInstance on Basement (1500 SF)
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK
Deficiency Location/Instance Room 304A
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 32 of 50
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Ceiling
Deficiency Photo1
Room 304A
Violations No violations recorded.
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance Rooms 202,304A, Main Entrance Lobby
Deficiency Quantity 4
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Room 202
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Rooms 204,304,306A, Corridor near Rooms 302,303, and others
Deficiency Quantity 400
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 33 of 50
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish
Deficiency Photo1
Room 306A
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Corridor near Room 307
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Corridor near Room 307
Violations No violations recorded.
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Main Entrance Vestibule
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 34 of 50
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
Walls Inspected
Main Entrance Vestibule
Violations No violations recorded.
Specialties Does not Exist
GYMNASIUM Does not Exist
INTERIOR DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
INTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
KITCHEN Inspected
InspectedInstance on Basement (500 SF)
Ceiling
InspectedInstance on Basement (500 SF)
Condition 4 - Between Fair and Poor
Deficiency METAL PAN: DAMAGED/MISSING
Deficiency Location/Instance Near entrance
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near entrance
Violations No violations recorded.
Door(s)
InspectedInstance on Basement (500 SF)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on Basement (500 SF)
Condition 5 - Poor
Deficiency CONCRETE: CRACKS
Deficiency Location/Instance Storage Room
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 35 of 50
Question Response
INTERIOR
KITCHEN
Floor Finish
Deficiency Photo1
Storage Room
Violations No violations recorded.
Deficiency CERAMIC TILE: BROKEN/MISSING TILES
Deficiency Location/Instance Near entrance
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near entrance
Violations No violations recorded.
Walls
InspectedInstance on Basement (500 SF)
Condition 2 - Between Good and Fair
Deficiency CERAMIC TILE: BROKEN/ MISSING
Deficiency Location/Instance Near entrance
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 36 of 50
Question Response
INTERIOR
KITCHEN Inspected
Walls
Deficiency Photo1
Near entrance
Violations No violations recorded.
LIBRARY Inspected
InspectedInstance on Room 305
Built-in Furnishing
Does not ExistInstance on Room 305
Ceiling
InspectedInstance on Room 305
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
InspectedInstance on Room 305
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on Room 305
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Near Circulation Desk
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Circulation Desk
Violations No violations recorded.
Walls
InspectedInstance on Room 305
Condition 2 - Between Good and Fair
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 37 of 50
Question Response
INTERIOR
LIBRARY Inspected
Walls
Deficiency No deficiencies recorded
LOCKER ROOM Does not Exist
MULTI-PURPOSE ROOM Inspected
InspectedInstance on Basement (1600 SF)
Ceiling
InspectedInstance on Basement (1600 SF)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
Not RequiredInstance on Basement (1600 SF)
Fixed Equipment
InspectedInstance on Basement (1600 SF)
Condition 3 - Fair
Deficiency DAMAGED/MISSING
Deficiency Location/Instance Near entrance
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
Floor Finish
InspectedInstance on Basement (1600 SF)
Condition 2 - Between Good and Fair
Deficiency VINYL TILES: BROKEN/DETERIORATED/MISSING TILES
Deficiency Location/Instance Near Drinking Fountain
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Near Drinking Fountain
Violations No violations recorded.
Sliding-folding Partition
Does not ExistInstance on Basement (1600 SF)
Stage
Does not ExistInstance on Basement (1600 SF)
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 38 of 50
Question Response
INTERIOR
MULTI-PURPOSE ROOM Inspected
Walls
InspectedInstance on Basement (1600 SF)
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK
Deficiency Location/Instance Near windows
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Near windows
Violations No violations recorded.
Window Curtains/Shades/Blinds
Does not ExistInstance on Basement (1600 SF)
SCIENCE DEMO ROOM Does not Exist
SCIENCE LAB Does not Exist
SCIENCE PREP ROOM Does not Exist
SHOWER ROOM Does not Exist
STAIRS/RAMPS: INTERIOR Inspected
Do Letter Stair Signs Exist? Yes
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 5 - Poor
Deficiency METAL: DETERIORATED DOOR
Deficiency Location/Instance Stair AB/Basement
Deficiency Quantity 2
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 39 of 50
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Door(s)
Deficiency Photo1
Stair AB/Basement
Violations No violations recorded.
Partition Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Railings Inspected
Condition 3 - Fair
Deficiency METAL: DAMAGED
Deficiency Location/Instance Stair AB/Bulkhead
Deficiency Quantity 10
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
Stair AB/Bulkhead
Violations No violations recorded.
Stairs and Landings Inspected
Condition 2 - Between Good and Fair
Deficiency CONCRETE: CRACKS/SPALLING - MAJOR
Deficiency Location/Instance Stair CD/Basement
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 40 of 50
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Stairs and Landings
Deficiency Photo1
Stair CD/Basement
Violations No violations recorded.
Deficiency VINYL TILES: DETERIORATED SUBSTRATE
Deficiency Location/Instance Stair CD/2
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair CD/2
Violations No violations recorded.
Deficiency STONE: BROKEN/MISSING
Deficiency Location/Instance Stair AB/Basement
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair AB/Basement
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 41 of 50
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Stair CD/Basement
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair CD/Basement
Violations No violations recorded.
Deficiency METAL CLADDING: DETERIORATED
Deficiency Location/Instance Stair AB/Basement
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Stair AB/Basement
Violations No violations recorded.
Deficiency PLASTER: CRACKS/SPALLING - ACTIVE LEAK
Deficiency Location/Instance Stair AB/Basement,CD/Basement
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 42 of 50
Question Response
INTERIOR
STAIRS/RAMPS: INTERIOR
Walls
Deficiency Photo1
Stair AB/Basement
Violations No violations recorded.
TOILET ROOMS - STAFF Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 5 - Poor
Deficiency WOOD: DETERIORATED DOOR
Deficiency Location/Instance In Room 306A
Deficiency Quantity 1
Quantity Uom EACH
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
In Room 306A
Violations No violations recorded.
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stalls Inspected
Condition 5 - Poor
Deficiency RUST - MAJOR
Deficiency Location/Instance Basement
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 43 of 50
Question Response
INTERIOR
TOILET ROOMS - STAFF
Stalls
Deficiency Photo1
Basement
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency BRICK: CRACKS/SPALLING - ACTIVE LEAK
Deficiency Location/Instance Basement
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
Basement
Violations No violations recorded.
TOILET ROOMS - STUDENTS Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance 1st Floor - Boys
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 44 of 50
Question Response
INTERIOR
TOILET ROOMS - STUDENTS
Ceiling
Deficiency Photo1
1st Floor - Boys
Violations No violations recorded.
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stalls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LIFE SAFETY Inspected
F.D. HOLDING AREA Does not Exist
STEEL STAIRS Does not Exist
SITE Inspected
CONTAINERIZATION Does not Exist
Drainage System for Asphalt Inspected
Catch Basins/Manhole - Surrounded by asphalt Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Asphalt Covering Does not Exist
Drainage System for Concrete Does not Exist
Drainage System for Soil Does not Exist
DRINKING FOUNTAINS Does not Exist
FENCES Inspected
Condition 3 - Fair
Deficiency WROUGHT IRON: DAMAGED/DETERIORATED
Deficiency Location/Instance 4th Avenue
Deficiency Quantity 40
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 45 of 50
Question Response
SITE
FENCES
Deficiency Photo1
4th Avenue
Violations No violations recorded.
Deficiency WROUGHT IRON: RUST - MAJOR
Deficiency Location/Instance 4th Avenue
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
4th Avenue
Violations No violations recorded.
Deficiency CHAIN LINK: DAMAGED/DETERIORATED
Deficiency Location/Instance 13th Street, 14th Street
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
14th Street
Violations No violations recorded.
IRRIGATION SYSTEM Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 46 of 50
Question Response
SITE
IRRIGATION SYSTEM Does not Exist
PAVING Inspected
Student Non-Use Inspected
Gravel Exists? No
Asphalt Does not Exist
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Pavers Does not Exist
Student Use Inspected
Gravel Exists? Yes
Asphalt Inspected
Condition 4 - Between Fair and Poor
Deficiency CRACKS - MAJOR
Deficiency Location/Instance Schoolyard
Deficiency Quantity 500
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Schoolyard
Violations No violations recorded.
Concrete Does not Exist
Pavers Does not Exist
Site Sidewalks & Walkways Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Pavers Does not Exist
DOT Sidewalk Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 3 - Fair
Deficiency HEAVING
Deficiency Location/Instance 13th Street
Deficiency Quantity 50
Quantity Uom S.F.
Potential Action REPLACE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 47 of 50
Question Response
SITE
PAVING Inspected
DOT Sidewalk
Concrete
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
13th Street
Violations No violations recorded.
Deficiency DAMAGED CURBS
Deficiency Location/Instance 13th Street, 14th Street
Deficiency Quantity 50
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
14th Street
Violations No violations recorded.
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance 4th Avenue, 13th Street, 14th Street
Deficiency Quantity 250
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 48 of 50
Question Response
SITE
PAVING
DOT Sidewalk
Concrete Inspected
Deficiency Photo1
4th Avenue
Violations No violations recorded.
Pavers Does not Exist
PLAYGROUNDS Inspected
InspectedInstance on Schoolyard - West
Benches
Does not ExistInstance on Schoolyard - West
Fence
Does not ExistInstance on Schoolyard - West
Pavement
Does not ExistInstance on Schoolyard - West
Play Equipment
InspectedInstance on Schoolyard - West
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Safety Surfacing
InspectedInstance on Schoolyard - West
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Unpaved Area
Does not ExistInstance on Schoolyard - West
PLAYING SURFACE Does not Exist
RETAINING WALLS Inspected
Are there any Retaining Walls 6' OR higher facing publicstreet/sidewalk?
No
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
SEATING Inspected
Benches Inspected
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Metal/Wood/Plastic Does not Exist
Bleachers Does not Exist
SITE WALLS (NOT RETAINING WALLS) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 49 of 50
Question Response
SITE
STAIRS/RAMPS: EXTERIOR Inspected
Railings Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Site Cheek/flank Walls Inspected
Condition 2 - Between Good and Fair
Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR
Deficiency Location/Instance 14th Street
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
14th Street
Violations No violations recorded.
Stairs/ramps Inspected
Condition 2 - Between Good and Fair
Deficiency CAST IN PLACE CONCRETE: WORN-OUTTREAD/RISER/NOSERS
Deficiency Location/Instance 13th Street
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
13th Street
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
K124
PB/A&W Print Date: 9/13/2020Page 50 of 50