PRESENTATION ON PRESENTATION ON PLANT CONTROLS & INST. OVERVIEW
OF GGSR - BATHINDA (CPP)GGS (C )
OWNER : M/S HMELPMC : M/S EIL
BHEL-PE&SD
GGSR CPP- PLANT OVERVIEW
C&I DESIGN OVERVIEW- INSTRUMENTATION
APPLICATION DESIGN PHILOSOPHY
HAZARDOUS AREA PROTECTION INTRINSIC SAFE CONCEPT & EX-PROOF FOR SOV/ HIGHER VOLTAGE
PROCESS PARAMETER MONIROING & SMART TRANSMITTER (4-20mA), 2oo3 SENSORS CONTROL
( )FOR CRTICAL LOOPS
INSTRUMENT FOR ALARM/SHUTDOWN SEPARATE SMART TRANSMITTER (4-20mA), (SWITCHES ARE AVOIDED FOR RELIABILITY)(SWITCHES ARE AVOIDED FOR RELIABILITY).
CONTROL VALVES WITH SMART POSIT’NR WITH INTEGRAL I/P
FUEL FLOW MEASUREMENT MASS FLOW METERFUEL FLOW MEASUREMENT MASS FLOW METER
FUEL TANKS LEVEL MEASUREMENT RADAR LEVEL TRANSMITTER
PROCESS SWITCHES NOT USED
TEMPERATURE MONITOING Pt-100, 3-WIRE RTDs & K-TYPE T/C
TEMPERATURE CONTROL TEMP TRANSMITTERS
Cont’d….
C&I DESIGN OVERVIEW
• INSTRUMENTATION POWER SUPPLY
APPLICATION POWER SUPPLY RATINGAPPLICATION POWER SUPPLY RATING
FIELD TRANSMITTERS 24V DC, LOOP POWERED FROM CONTROL SYSTEM
MASS FLOW METERS & RADAR LEVEL TRANSMITTERS
110V AC UPS
SOLENOID VALVES 110V AC UPS POWERED FROM DCS RELAY LOGICSOLENOID VALVES 110V AC UPS, POWERED FROM DCS RELAY LOGIC
CONTROL VALVES 24V DC, LOOP POWERED FROM CONTROL SYSTEM
ANALYSERS 110V AC UPS
MOV INDICATIONS 24V DC POWERED FROM CONTROL SYSTEM
MOV OPEN/CLOSE COMMANDS 24V DC POWERED FROM ACTUATOR
PUMP INDICATIONS 24V DC POWERED FROM CONTROL SYSTEM
PUMP START/STOP COMMANDS 240V AC/220V DC POWERED FROM SWITCHBOARD
C&I DESIGN OVERVIEW – CONTROL SYSTEM
• maxDNA DCS IS PROVIDED FOR COMPLETE CPP CONTROL & MONITORING FROM MAIN CONTROL ROOM& MONITORING FROM MAIN CONTROL ROOM
• FUNCTIONSo PROCESS MONITORING o PROCESS MONITORING o PUMP & MOV OPERATIONS, SEQUENCE CONTOL OPERATIONSo CONTROL VALVES OPERATIONS & SUB-PKG MONITORING
• INTERLOCK & SHUT DOWN SYSTEM – PART OF maxDNA DCS • DEDICATED SYSTEMS ARE PROVIDED FOR
o GAS TURBINE - MARK-VIo HRSG & UB FIRING SYSTEM - BMS PLC with BACK UP CONTROL DESKo VIBRATION SYSTEMS FOR GT & STo PACKAGE SYSTEM FOR HSD CENTRIFUGE, COMPRESSED AIR SYSTEM,
A/C,
ABOVE SUB-SYSTEMS ARE INTEGRATED WITH PLANT DCS
…
REDUNDANCYREDUNDANCYPROCESSOR - 1:1POWER SUPPLY - 1:1COMMUNICATION NETWOK - 1:1I/O MODULES – 1:1 (CRITICAL)
CPP DCS –OPERATOR INTERFACECPP DCS OPERATOR INTERFACE
•• OPERATOR STATIONS –9 Nos IN CONTROL ROOMo PROVIDED FOR OPERATOR INTERFACEo FOR PLANT START-UP MONITORING CONTROL & SHUTDOWNo FOR PLANT START UP, MONITORING, CONTROL & SHUTDOWNo TO VIEW PROCESS PARAMETERS, ALARMS, TRENDS, SET POINTSo DRIVES OPERATION– A/M SELECTION, START/ STOP & SEQUENCE
CONTROL
DISTRIBUTION OF OPERATOR STATIONSDISTRIBUTION OF OPERATOR STATIONS
FOR HRSG - 2 NosFOR UB 2NosFOR UB - 2NosFOR STEAM TURBINES - 2 NosFOR BOP SYSTEMS - 2 NosPLANT SUPERVISOR 1 NOPLANT SUPERVISOR - 1 NO
Cont’d….
CPP DCS –OPERATOR INTERFACECPP DCS OPERATOR INTERFACE
• ENGINEERING STATIONS –2 NosG G S O S oso FOR PLANT GRAPHICS MODIFICATIONS/ NEW GRAPHICS BUILDINGo FOR APPLICATION SOFTWARE MODIFICATIONS
LOGICS / SEQUENCE CONTROL MODIFICATIONSo LOGICS / SEQUENCE CONTROL MODIFICATIONSo VALIDATTION OF LOGICS BEFORE DOWNLOADING INTO DPU.
• HISTORIAN STATION 1 No• HISTORIAN STATION –1 Noo FOR HISTORIAN DATA COLLECTION & ARCHIVING.o DATA QUERY FOR TRIP ANALYSIS/ REPORTS.o DATA STORAGE INTERVAL IS PROGRAMMABLEo ARCHIVAL STORAGE TO CD-ROM.
• maxLINK STATION –2 Noo FOR INTERFACING - MARK VI, BMS PLCs, VIBRATION MONITORING SYS
DATA TRANSFER TO DCS OPERATOR STATIONS FROM OTHER SYSo DATA TRANSFER TO DCS OPERATOR STATIONS FROM OTHER SYSCont’d….
CPP DCS – PANEL MOUNTED SYSTEMSCPP DCS PANEL MOUNTED SYSTEMS
• DISTRIBUTED PROCESS UNIT (DPU)o PERFORMS DATA ACQUISION , DATA PROCESSING & CONTROLSo ACQUISITION OF TREND INFORMATIONo LOGGING OF SOEo CONTINUOUS SCANNING OF I/O MODULESo EXECUTION OF PREDEFINED LOGICS
•maxNET & ETHERNET SWITCHESmaxNET & ETHERNET SWITCHESHIGH SPEED NETWORK FOR CONNECTING DPUs, OPERATOR/ENGG STATIONS, PRINTERS.
• SEQUENCE OF EVENT RECORDING (SOE)o SOE FUNCTION IS INTEGRAL IN DCS. o TIME STAMPING WITH “1 mSEC” RESOLUTIONo TIME STAMPING WITH 1 mSEC RESOLUTIONo SOE SIGNALS ARE TAGGED IN MAIN DATABASE
Cont’d….
CPP DCS – PANEL MOUNTED SYSTEMSCPP DCS PANEL MOUNTED SYSTEMS
• HART MANAGEMENT SYSTEM (HMS)o PROVIDED FOR C&I MAINTENANCE PURPOSEo ALL TRASMITTERS & CONTROL VALVES ARE CONNECTEDo REMOTE ACCESS OF EACH FIELD INSTS. FOR PERIODIC CALIBRATION o AUTOMATIC GENERATION OF INSTRUMENT DATABASE
- MAKE/ MODEL, DATE OF CONNECTION, DATE OF LAST CALIBRATION & NEXT CALIBRATION etc.& C O etc
- CALIBRATION PROCEDURE, HISTORY RECORDSo ON LINE INSTRUMENT STATUS MONITORING
•MASTER CLOCK SYSTEM
o PROVIDED FOR TIME SYNCRONISATION WITH ALL THE CONTROL SYSTEMS
o CONNECTED TO PLANT DCS, STG SYSTEM, MARK VI, PLCs, VMSo UNIFIED TIME IS REQUIRED FOR MANAGEMENT REPORTING, TRIP o UNIFIED TIME IS REQUIRED FOR MANAGEMENT REPORTING, TRIP
ANALYSIS, DATA LOGGING etc.Cont’d….
CONTROL OVERVIEW- MAIN EQPTs
SYSTEM/EQUIPMENT PRIMARY CONTROL SECONDARY MONITOINGMONITOING
GAS TURBINE Mark-VI CPP DCSSTEAM TURBINE CPP DCSSTEAM TURBINE CPP DCS ‐BACK PR. STEAM TURBINE CPP DCS ‐UBs‐FUEL,STEAM, WTR & CPP DCS ‐UBs FUEL,STEAM, WTR & DRN SYSTEMS
CPP DCS
UBs – BURNER CONTROLS BMS PLC CPP DCSHRSGs‐FUEL, STEAM, WTR & DRN SYSTEMS
CPP DCS ‐
HRSGs BURNER CONTROLS BMS PLC CPP DCSHRSGs‐BURNER CONTROLS BMS PLC CPP DCSGAS BOOSTER COMPRESSOR CPP DCS ‐
Cont’d….
CONTROL OVERVIEW- BOP SYSTEMS
SYSTEM/EQUIPMENT PRIMARY CONTROL & MONITORING
SECONDARY MONITOINGO O G
LCO SYSTEM‐STORAGE, FUEL FWDG for GTs, HRSGs & UBs
CPP DCS ‐
VANADIUM DOSING SYSTEM CPP DCS ‐
HSD SYSTEM‐STORAGE, FWDG for GTs CPP DCS ‐
HSD CENTRIFUGE CENTRIFUGE LCP CPP DCSHSD CENTRIFUGE CENTRIFUGE LCP CPP DCS
REFINERY GAS SYSTEM CPP DCS ‐
GD‐GFD SYSTEM CPP DCS ‐GD‐GFD SYSTEM CPP DCS ‐
STEAM SYSTEM‐VHP, HP, MP & LP CPP DCS ‐
CONDENSATE SYSTEM CPP DCS ‐
FEED WATER SYSTEM‐DEAE, BFPs CPP DCS ‐
STG, BPTG DRN & BLOWDOWN SYSTEM CPP DCS ‐
UTILITIES ‐POTABLE WATER, IA, PA, N2 CPP DCS ‐
Cont’d….
CONTROL OVERVIEW-BOP SYSTEMs
SYSTEM/EQUIPMENT PRIMARY CONTROL SECONDARY MONITOINGMONITOING
COOLING WATER SYSTEM CPP DCS ‐
DMWATER CIRCULATION CPP DCS ‐DM WATER CIRCULATION CPP DCS ‐
HP NITROGEN SYSTEM CNTRL PNL CPP DCS
HP LP DOSING SYSTEM CPP DCS ‐HP, LP DOSING SYSTEM CPP DCS
GAS BOOSTER COMPRESSOR CPP DCS ‐
PLANT FIRE & GAS SYSTEM DEDICATED PANEL IN CPP DCSPLANT FIRE & GAS SYSTEM DEDICATED PANEL IN CONTROL ROOM
CPP DCS
COMPRESSED AIR SYSTEM CNTRL PNL IN COMP. HOUSE
CPP DCSHOUSE
STEAM & WATER ANALYSIS SYSTEM for HRSG, UB & BOP
ANALYSER PNL IN SWAS ROOM
CPP DCS
FLUE GAS ANALYSIS – HRSG & UB CEMS PNL IN ANALYSERROOM
CPP DCS
PLANT DRIVE CONTROL PHILOSOPHY
FOLLOWING TYPES OF DRIVES ARE ENVISAGED IN CPPFOLLOWING TYPES OF DRIVES ARE ENVISAGED IN CPP:
o ELECTRICAL DRIVES:HT PUMPS - BFPs, CW PUMPS, FD FANS etc.LT PUMPS – FUEL FORWARDING PUMPS, DMW, DOSING PUMPSMOV (INTEGRAL ACTUATOR TYPE) STEAM SYS ISOLATIOMSMOVs (INTEGRAL ACTUATOR TYPE) - STEAM SYS ISOLATIOMS
o PNEUMATIC DRIVES:o PNEUMATIC DRIVES:CONTROL VALVESSOLENOID OPERATED VALVES
Cont’d….
PLANT DRIVE CONTROL PHILOSOPHY
TYPE OF DRIVE INDICATIONS IN DCS OPERATOR FUNCTIONS FROM DCSFROM DCS
HT PUMPS & LT PUMPS • READY TO START• PUMP RUNNING
• AUTO/MANUAL SELECTION• PUMP START COMMAND
• PUMP TRIPPED • PUMP STOP COMMAND
MOTOR OPERATED VALVES • READY TO START • AUTO/MANUAL SELECTION• VALVE OPENED• VALVE CLOSED
/• OPEN COMMAND• CLOSE COMMAND
CONTROL VALVES (REGULATING TYPE)
• VALVE POSITION IN%
• PROCESS VALUE • SET POINT • CONTROLLER AUTO/MANUAL• CONTROLLER OUTPUT IN %
ON‐OFF/ESD VALVES • VALVE OPENED • AUTO/MANUAL SELECTION• VALVE CLOSED
/• VALVE OPEN/CLOSE COMMAND
Cont’d….
PLANT DRIVE CONTROL PHILOSOPHYINDICATIONS/
COMDSMESSAGE FOR PLANT OPERATOR SIG.SOURCE
MOTOR DRIVEN PUMPS
LOCAL CONTROL STN (LCS)
- PUMP L/R SECTION- START/STOP IN LOCAL MODE
LCSSTN (LCS) START/STOP IN LOCAL MODE
READY TO START “START PERMISSIVE & MCC HEALTHY“FOR DCS OPERATION
SWITCH BOARD
MCC CKT OK+NO TH O/L + REM. SECT’D
/A/M ‐ SELECTION MANUAL- OPERATOR INITIATIONAUTO - THROUGH LOGIC SEQ.
DCS HMI
START/ STOP WHEN SELECTD IN MAN MODE DCS HMISTART/ STOP COMD.
WHEN SELECTD IN MAN. MODE DCS HMI
RUN INDICATION “DRIVE STARTED F/B” FOR OPERATOR INFORMATION
SWITCH BOARDOPERATOR INFORMATION BOARD
TRIP INDICATION “DRIVE TRIPPED ON THERMAL OVERLOAD” FOR OPERATOR
SWITCH BOARD
CRITICAL
INFORMATION & CORRECTIVE ACTION
Cont’d….
PLANT DRIVE CONTROL PHILOSOPHYINDICATIONS/
COMDSMESSAGE FOR PLANT OPERATOR SIG.SOURCE
MOTOR OPERATED VALVES (MOVS)
LOCAL CONTROL STN (LCS)
- L/R SECTION- START/STOP IN LOCAL MODE
LCSSTN (LCS) START/STOP IN LOCAL MODE
READY TO START “START PERMISSIVE & ACTR HEALTHY“FOR DCS OPERATION
ACTR ACTR CKT OK+NO TH O/L + REM. SECT’D + NO TRQ TRIPQ
A/M ‐ SELECTION MANUAL- OPERATOR INITIATIONAUTO - THROUGH LOGIC SEQ.
DCS HMI
OPEN/ CLOSE COMD.
WHEN SELECTD IN MAN. MODE DCS HMI
OPEN/ CLOSE “MOV STATUSF/B” FOR OPERATOR ACTROPEN/ CLOSE INDICATION
MOV STATUSF/B FOR OPERATOR INFORMATION
ACTR
Cont’d….
DRIVE CONTROL PHILOSPHY
INDICATIONS MESSAGE FOR PLANT OPERATOR SIGNAL SOURCESOU C
CONTROL VALVES (PNEUMATIC OPERATED)
A/M SELECTION MANUAL OPERATOR INITIATION DCS HMIA/M ‐ SELECTION MANUAL- OPERATOR INITIATION USE OF MANUAL LOADER
AUTO THROUGH PID & SET
DCS HMI
AUTO - THROUGH PID & SET POINT
CONTROL SET POINT
- BY OPERATOR TO MEET THE CONTROL REQTS.
- CONTROLLER NEEDS TO BE AUTO TO FOLLOW THE SET POINT
DCS HMI
AUTO TO FOLLOW THE SET POINT
VALVE POSITION “% OF VALVE OPENING “ FOR OPERATOR INFORMATION
POSITION TRAMITTER
Cont’d….
DRIVE CONTROL PHILOSPHY
INDICATIONS MESSAGE FOR PLANT OPERATOR SIGNAL SOURCESOU C
ON-OFF VALVES (SOLENOID OPERATED)
A/M SELECTION MANUAL OPERATOR INITIATION DCS HMIA/M ‐ SELECTION MANUAL- OPERATOR INITIATIONAUTO - THROUGH LOGIC SEQ.
DCS HMI
OPEN/ CLOSE WHEN SELECTD IN MAN MODE DCS HMIOPEN/ CLOSE COMD.
WHEN SELECTD IN MAN. MODE DCS HMI
OPEN “VALVE IS FULLY OPENED F/B” FOR VALVE LIMIT INDICATION
/OPERATOR INFORMATION SWITCH
CLOSE “VALVE IS FULLY CLOSED F/B” FOR VALVE LIMIT INDICATION OPERATOR INFORMATION SWITCH
SIGNAL WIRING
ANALOG SIGNALS
FIELD RACK ROOM CONSOLE ROOMROOM
DPU
E/PAO
Cont’d….
SIGNAL WIRING
MCC SIGNALS
MCC RACK ROOM CONSOLE ROOM
DI
DPUMotor f/b
DO
Motor cmd
SIGNAL WIRING
MOV SIGNALS
FILED ACTR RACK ROOM CONSOLE ROOM
DI
DPUMOV f/b
DO
MOV cmd
PLANT CONTROL FUNCTIONSPLANT CONTROL FUNCTIONS
• BOP FUEL SYSTEMS• BOP FUEL SYSTEMS
o IMPLEMENTED IN PLANT DCSo CONTROL FUNCTIONSo CONTROL FUNCTIONS
- FUEL TANK LEVEL CONTROL- FUEL FORWARDING PUMP CONTROLS & AUTO CHANGEOVER
FILTER SYSTEM DP- FILTER SYSTEM DP- FUEL PRESSURE AND RECIRCULATION - FUEL FLOW MEASUREMENT
DRAIN SYSTEM CONTROL & MONITORING- DRAIN SYSTEM CONTROL & MONITORING- GAS ESD VALVE CONTROL- GAS SCRUBBER LEVEL CONTROL- GAS PRESSURE CONTROLS
Cont’d….
PLANT CONTROL FUNCTIONSPLANT CONTROL FUNCTIONS
• BOP WATER SYSTEMS• BOP WATER SYSTEMS
o IMPLEMENTED IN PLANT DCSo CONTROL FUNCTIONSo CONTROL FUNCTIONS
- DEARATOR LEVEL CONTROL- BFP CONTROLS FOR HRSG, UB & EXPORT
FEED CONTROL STATION- FEED CONTROL STATION- COOLING TOWER CONTROLS- CONDERSER COOLING WATER SYSTEM
AUX COILING WATER SYSTEM- AUX. COILING WATER SYSTEM- CONDERSATE STORAGE TANK LEVEL CONTROL- ST CONDENSER LEVEL CONTROL- CEP CONTROLS- BLOW DOWN SYSTEMS
Cont’d….
PLANT CONTROL FUNCTIONSPLANT CONTROL FUNCTIONS
• BOP STEAM SYSTEMS• BOP STEAM SYSTEMS
o IMPLEMENTED IN PLANT DCSo CONTROL FUNCTIONSo CONTROL FUNCTIONS
- VHP- TO - HP STEAM PRDS- HP - TO – MP STEAM PRDS
MP TO LP PRDS SYSTEM- MP – TO – LP PRDS SYSTEM- AUX. STEAM PRDS CONTROL- VHP/ HP HEADER VENT CONTROL
Cont’d….
PLANT CONTROL FUNCTIONSPLANT CONTROL FUNCTIONS
• HRSG CONTROLSSG CO O S
o IMPLEMENTED IN PLANT DCSo DEDICATED SYSTEM FOR BURNER CONTROLSo CONTROL FUNCTIONS
- DRUM LEVEL CONTROLS- SUPERHEAT STEAM TEMP. CONTROL- COMBUSTION CONTROL- DIVERTER CONTROL- MONITORING OF FEED WATER & STEAM PARAMETERSMONITORING OF FEED WATER & STEAM PARAMETERS- FLUE GAS PATH TEMP.- FUEL FLOW MESUREMENTSTEAM & WATER ANALYSIS pH CONDUCTIVITY SILICA- STEAM & WATER ANALYSIS – pH , CONDUCTIVITY, SILICA
- FULE GAS – NOX, SOX, CO MEASUREMENT- HRSG PROTECTION & TRIP LOGICSSCANNER & SEAL AIR FAN CONTROLS- SCANNER & SEAL AIR FAN CONTROLS
- DRAIN & VENT SYSTEMS Cont’d….
PLANT CONTROL FUNCTIONSPLANT CONTROL FUNCTIONS
• UB CONTROLS• UB CONTROLS
o IMPLEMENTED IN PLANT DCSo DEDICATED SYSTEM FOR BURNER CONTROLSo DEDICATED SYSTEM FOR BURNER CONTROLSo CONTROL FUNCTIONS
- DRUM LEVEL CONTROLSSUPERHEAT STEAM TEMP CONTROL- SUPERHEAT STEAM TEMP. CONTROL
- COMBUSTION CONTROL- FURNACE DRAFT CONTROLFD FAN & DAMPER CONTROL- FD FAN & DAMPER CONTROL
- MONITORING OF FEED WATER & STEAM PARAMETERS- FUEL FLOW MESUREMENT- STEAM & WATER ANALYSIS – pH , CONDUCTIVITY, SILICA- FULE GAS – NOX, SOX, CO MEASUREMENT- DRAIN & VENT SYSTEMS
Cont’d….
PLANT CONTROL FUNCTIONSPLANT CONTROL FUNCTIONS
• STEAM TURBINE CONTROLS• STEAM TURBINE CONTROLS
o IMPLEMENTED IN PLANT DCSo CONTROL FUNCTIONSo CONTROL FUNCTIONS
- TURBINE GOVERNOR- OVER SPEED CONTROL & PROTECTIONTERBINE PROTECTION & TRIP LOGICS- TERBINE PROTECTION & TRIP LOGICS
- LO SYSETM- MONITORING OF STEAM PARAMETERS
Cont’d….
PLANT CONTROL FUNCTIONSPLANT CONTROL FUNCTIONS
• MARK VI SYSTEM FOR GAS TURBINE• MARK VI SYSTEM - FOR GAS TURBINE
o DEDICATED CONTROL SYSTEM FOR GAS TURBINEo HMIs FOR OPERATOR INTERFACE o ENGG STATION FOR S/W MODIFICATIONSo CONTROL FUNCTIONS
- GAS TURBINE START UP CONTROLS- SPEED CONTROLS wrt TO LOAD- TURBINE FIRING TEMP CONTROLTURBINE FIRING TEMP. CONTROL- OVER-SPEED CONTROL- GT PROTECTION & SHUTDOWN INTERLOCKSFUEL 3 WAY VALVE CONTROL- FUEL 3- WAY VALVE CONTROL
COMMUNICATION SYSTEMCOMMUNICATION SYSTEM
• PUBLIC ADDRESS SYSTEM• PUBLIC ADDRESS SYSTEMo FOR TWO-WAY COMMUNICATION IN CPP FIELD & CONTROL ROOM.o MASTER CALL STATION IN CONTROL ROOMo FIELD CALL STATIONS IN STRATEGIC LOCATIONS.
- GT AREA- HRSG AREA- UB AREA- STEAM TURBINE AREA - FUEL PUMP HOUSE COOLING TOWER BFPS COMP AIR etcFUEL PUMP HOUSE, COOLING TOWER, BFPS, COMP. AIR etc.
• TELEPHONE SYSTEM
EPBAX BASED TELEPHONE SYSTEMo EPBAX BASED TELEPHONE SYSTEMo TELEPHONE IN CONTROL ROOM, OPERATOR ROOMS & OFFICE ROOMSo LOCAL ROOMS, SWAS ROOMS ARE PROVIDED WITH TELPHONES.
Cont’d….
PLANT COMMUNICATION SYSTEM
PLANT COMMUNICATION SYSTEM
DESIGN TEAM
EQUIPMENTS C&I DESIGN CONTROL IMPLEMENTATION
GAS TURBINE BHEL-HYD (GT DIV.) BHEL-HYD (GT DIV.)
MARK-VI BHEL-EDN (B’LORE) BHEL-EDN
STEAM TURBINE BHEL HYD (T&C) BHEL HYD (T&C)STEAM TURBINE BHEL-HYD (T&C) BHEL-HYD (T&C)
HRSG-FW & STEAM BHEL-TRY(HRSG DIV.) BHEL-EDN
HRSG-BMS BHEL-TRY(HRSG DIV.) BHEL-TRY(HRSG DIV.)( ) ( )
UB-FW & STEAM BHEL-TRY(HRSG DIV.) BHEL-EDN
UB-BMS BHEL-TRY(HRSG DIV.) BHEL-TRY(HRSG DIV.)
GBC BHEL-HYD (T&C) BHEL-EDN
FUEL- GT,HRSG & UB BHEL-HYD(PE & SD) BHEL-EDN
FW, STEAM & UTILITIES BHEL-HYD(PE & SD) BHEL-EDN
COMP. AIR SYSTEM BHEL-HYD(PE & SD) BHEL-HYD(PE & SD)& BHEL-EDN& BHEL EDN
CPP DCS BHEL-EDN BHEL-EDN