Transcript
Page 1: Gendrive Series 2000 Gx5 - mtu-online-shop.com...Gendrive Series 2000 Gx5 for Power Generation Standard Backup Applications with water-to-air charge air cooling Power. Passion. Partnership

Gendrive

Series 2000 Gx5 for Power Generation Standard Backup Applicationswith water-to-air charge air cooling

Power. Passion. Partnership.

Dimensions and Masses

Engine Dimensions(LxWxH)mm(in) Mass,drykg(lbs)

12V 1835x1580x1570(72x62x62) 2570(5665)

16V 2180x1580x1580(86x62x62) 3180(7010)

18V 2350x1580x1600(93x62x63) 3580(7893)

Alldimensionsareapproximate,forcompleteinformationrefertotheinstallationdrawing.

EngineModel

Bore/stroke mm(in) 130/150(5.1/5.9)

Cylinderconfiguration 90°V

Displacement/cylinder l(cuin) 1.99(121)

Displacement,total l(cuin) 12V:23.9(1458),16V:31.8(1944),18V:35.8(2185)

Fuelspecification EN590,GradeNo.1-D/2-D(ASTMD975-00)

Applicationgroup Powerdefinition

StandbyPower(3D) Emergencyservice,fuelstoppower, Loadfactor:≤85%,Operatinghours:max.500h/year,

IFN Overload:Fuelstoppower(IFN)

PowerdefinitionaccordingtoISO3046(ratingsalsocorrespondtoSAEJ1995andSAEJ1349standardconditions).ConsultyourMTUdistributor/dealerfortheratingthatwillapplytoyourspecificapplication.Rated power is without fan drive. The power consumption of any fan drive has to be deducted during designing of a generator set.

Page 2: Gendrive Series 2000 Gx5 - mtu-online-shop.com...Gendrive Series 2000 Gx5 for Power Generation Standard Backup Applications with water-to-air charge air cooling Power. Passion. Partnership

2IStandardBackupApplications

193 referencetoemissionlevelinpricelist

Engine Type Rated power kW (bhp) at 1800 rpm (60Hz) Optimization

12V2000G45 780(1046) x x

12V2000G85 890(1194) x x

16V2000G45 1010(1354) x x

16V2000G85 1115(1495) x x

18V2000G85 1310(1757) x x

Fanpowerrequirementnotconsidered

US

EPA

Non

road

Tie

r 2

com

plia

nt (4

0 C

FR 8

9)

US

EPA

Sta

tiona

ry

EMER

G T

ier

2 (4

0 C

FR 6

0)

Standby Power (3D)

Engine Type Rated power kW (bhp) at 1500 rpm (50Hz) Optimization

12V2000G25 635(852) x

12V2000G65 765(1026) x

16V2000G25 890(1194) x

16V2000G65 975(1307) x

18V2000G65 1100(1475) x

FanpowerrequirementnotconsideredFu

el c

onsu

mpt

ion

optim

ized

319

Page 3: Gendrive Series 2000 Gx5 - mtu-online-shop.com...Gendrive Series 2000 Gx5 for Power Generation Standard Backup Applications with water-to-air charge air cooling Power. Passion. Partnership

MTU Friedrichshafen GmbH I MTU Asia Pte Ltd I MTU America Inc.Rolls-RoycePowerSystemsCompanies

www.mtu-online.com

Subj

ectt

och

ange

.|3

2391

61|

Edi

tion

01/

16|

EN

C2

016-

03.

StandardEquipment

StartingSystem Electricstarter(24VDC/2-pole)

FuelSystem Electronicallycontrolledhigh-pressureinjectionwithsingleunitinjectionpumps(EUP)

LubeOilSystem Forcedfeedlubricationsystemwithpistoncooling,lubeoilcirculationpumpwithsafetyvalve,lubeoilmulti-stage

filter,lubeoilheatexchanger

CombustionAirSystem Exhaustturbochargers,intercooler

CoolingSystem Coolantcirculationpumpandcoolantthermostatforjacketwaterandchargeaircoolingsystem

EngineMounting Setofenginemountingbracketsatenginefreeanddrivingend

EngineManagement IntegratedelectronicenginecontrolandmonitoringsystemADEC

OptionalEquipment

StartingSystem Redundantstartingsystemelectric/air;electric/electric;air/air

FuelSystem Fuelpre-filter,specialfuelpre-filterwithwaterseparator

LubeOilSystem Handpumpforlubeoilextraction,electricalintervalpre-lubricationpump

CombustionAirSystem Heavydutyairfilters

EngineMounting Resilientenginemounts(rubberelements),rigidenginemounting

Referenceconditions:–Intake-airtemperature:25°C(77°F)–Ambientairpressure:1bar(14.5psi)–Altitudeabovesealevel:100m(328ft)

Subjecttochangewithoutnotice.Customizationpossible.Enginesillustratedinthisdocumentmayfeatureoptionsnotfittedasstandard.


Recommended