ZXDU58 B121DC Power System
Product Description
Product Version: V2.0R01M05
ZTE CORPORATIONNo. 55, Hi-tech Road South, ShenZhen, P.R.ChinaPostcode: 518057Tel: +86-755-26771900Fax: +86-755-26770801URL: http://support.zte.com.cnE-mail: [email protected]
LEGAL INFORMATIONCopyright © 2014 ZTE CORPORATION.
The contents of this document are protected by copyright laws and international treaties. Any reproduction or
distribution of this document or any portion of this document, in any form by any means, without the prior written
consent of ZTE CORPORATION is prohibited. Additionally, the contents of this document are protected by
contractual confidentiality obligations.
All company, brand and product names are trade or service marks, or registered trade or service marks, of ZTE
CORPORATION or of their respective owners.
This document is provided “as is”, and all express, implied, or statutory warranties, representations or conditions
are disclaimed, including without limitation any implied warranty of merchantability, fitness for a particular purpose,
title or non-infringement. ZTE CORPORATION and its licensors shall not be liable for damages resulting from the
use of or reliance on the information contained herein.
ZTE CORPORATION or its licensors may have current or pending intellectual property rights or applications
covering the subject matter of this document. Except as expressly provided in any written license between ZTE
CORPORATION and its licensee, the user of this document shall not acquire any license to the subject matter
herein.
ZTE CORPORATION reserves the right to upgrade or make technical change to this product without further notice.
Users may visit the ZTE technical support website http://support.zte.com.cn to inquire for related information.
The ultimate right to interpret this product resides in ZTE CORPORATION.
Revision History
Revision No. Revision Date Revision Reason
R1.0 2014-03-03 First edition
Serial Number: SJ-20140210154807-001
Publishing Date: 2014-03-03 (R1.0)
SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential
ContentsAbout This Manual ......................................................................................... I
Chapter 1 System Overview ...................................................................... 1-11.1 System Introduction............................................................................................ 1-1
1.2 System Features ................................................................................................ 1-2
1.3 Technical Specifications...................................................................................... 1-2
1.4 Design Standards............................................................................................... 1-4
Chapter 2 Structure and Components...................................................... 2-12.1 System Structure................................................................................................ 2-1
2.2 AC/DC Distribution Components ......................................................................... 2-2
2.3 ZXD1500 Rectifier .............................................................................................. 2-3
2.4 Centralized Supervision Unit ............................................................................... 2-5
2.5 Signal Interfaces on the SIB Board ...................................................................... 2-7
Chapter 3 ZXD1500 (V4.0) Rectifier Specifications ................................ 3-13.1 AC Input Over/Under-Voltage Protection.............................................................. 3-1
3.2 PFC Output Over/Under-Voltage Protection ......................................................... 3-2
3.3 Output Over-Voltage Protection........................................................................... 3-2
3.4 Output Over-Current Protection........................................................................... 3-3
3.5 Over-Temperature Protection and Fan Speed Control........................................... 3-3
Appendix A Alarm List .............................................................................. A-1
Appendix B Electrical Connection Diagram ........................................... B-1
Glossary .......................................................................................................... I
I
SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential
This page intentionally left blank.
II
SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential
About This ManualPurpose
This manual applies to the ZXDU58 B121 (V2.0R01M05) DC power system (the ZXDU58B121 (V2.0R01M05) for short). The ZXDU58 B121 (V2.0R01M05) system provides powerfor -48 V communication equipment.
This manual describes the structure and characteristics the ZXDU58 B121 (V2.0R01M05).
Intended Audience
This manual is intended for:
l Planning engineersl Maintenance engineers
What Is in This Manual
This manual contains the following chapters/appendixes:
Chapter/Appendix Summary
1, System Overview Describes the appearance, dimensions, system features, and
technical specifications.
2, Structure and Components Describes the system structure , AC/DC Distribution
Components, the ZXD1500 (4.0) rectifier, the Centralized
Supervision Unit (CSU) and the Signal Interface Board (SIB).
3, ZXD1500 (V4.0) Rectifier
Specifications
Describes the input features, output features, over-temperature
protection and fan speed control of the ZXD1500 (V4.0) rectifier.
A, Alarm List Describes the alarm name, and the default alarm level and
output relays.
B, Electrical Connection Diagram Provides the electrical connection diagram of the ZXDU58
B121 (V2.0R01M05).
I
SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential
Conventions
This document uses the following typographical conventions.
Typeface Meaning
Danger: Indicates an imminently hazardous situation, which if not avoided,
will result in death or serious injury.
Warning: Indicates a hazard that, if not avoided, could result in serious
injuries, equipment damages or interruptions of major services.
Caution: Indicates a potential hazard that, if not avoided, could result in
moderate injuries, equipment damages or partial service interruption.
Note: Provides additional information about a certain topic.
II
SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential
Chapter 1System OverviewTable of Contents
System Introduction....................................................................................................1-1System Features ........................................................................................................1-2Technical Specifications .............................................................................................1-2Design Standards.......................................................................................................1-4
1.1 System IntroductionThe ZXDU58 B121 (V2.0R01M05) is an embeded DC power system. It provides -53.5 Vpower for communication equipment.
l Two-phase four-wire (L1/L2/N/PE) AC input, 127 V/220 V (phase voltage/line voltage),50 Hz/60 Hz.
l In full configuration, the ZXDU58 B121 (V2.0R01M05) is equipped with four ZXD1500(V4.0) rectifiers, which form a rated output current of 120 A (42 V - 58 V).
The ZXDU58 B121 (V2.0R01M05) is 6U in height and 19 inches in width. It will fit in a 19inches rack or cabinet. See Figure 1-1 for its appearance and dimensions.
Figure 1-1 Appearance and Dimensions of the ZXDU58 B121 (V2.0R01M05)
• Unit: mm
1-1
SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential
ZXDU58 B121 Product Description
1.2 System FeaturesThe ZXDU58 B121 (V2.0R01M05) system has the following features:
l A wide range of AC input line voltage (80 V - 300 V) makes the system suitable forareas with unstable sources.
l The ZXDU58 B121 (V2.0R01M05) chassis contains a power distribution unit,rectifiers, and a monitoring unit.
l The ZXDU58 B121 (V2.0R01M05) system supports multiple networking modes, suchas RS232 and RS485.
l Intelligent monitoring unit.l High reliability with Mean Time Between Failures (MTBF) ≥ 2.2 × 105 h.l Signal interfaces on the rear panel for monitoring.
1.3 Technical SpecificationsRefer to Table 1-1 for the technical specifications of the ZXDU58 B121 (V2.0R01M05).
Table 1-1 Technical Specifications
Item Description
Appearance dimensions 266 mm × 483 mm × 350 mm (H × W × D)
Model B121-CSUCSU
Software version V2.20
Rectifier ZXD1500 (V4.0) rectifier, at most four sets
Rated output l Rated output current: 120 A (42 V - 58 V)
l Rated output power: 6.4 kW (at 53.5 V)
System efficiency ≥ 90%
AC input mode Two-phase, four-wire (L1/L2/N/PE)
AC input voltage l Rated input voltage: 127 V/220 V (phase voltage/line
voltage)
l Range: 80 V - 300 V (line voltage)
AC input frequency l Rated frequency: 50 Hz/60 Hz
l Frequency range: 45 Hz - 66 Hz
AC input circuit
breaker
l One AC input branch
l 1×63 A/2P MCB
AC Surge Protection
Device
Class C, maximum discharge current: Imax = 40 kA (8/20µs)
AC distribution
Auxiliary AC output None
1-2
SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential
Chapter 1 System Overview
Item Description
DC output voltage l Rated output voltage: -53.5 V
l Range: -42 V to -58 V (The DC output voltage can be
adjusted through the CSU)
Battery input circuit
breakers
l Two battery input branches
l 2×100 A/1P MCBs
Load disconnection
modes
LLVD1 + LLVD2
DC output circuit
breakers
Six DC output branches:
l LLVD1 (F101 - F102): 2×40 A/1P MCBs
l LLVD2 (F201 - F204): 1×32 A + 2×10 A + 1×6 A /1P
MCBs
DC distribution
DC Surge Protection
Device
Maximum discharge current: Imax = 15 kA (8/20µs)
Communication
interface
l One RS232 communication interface
l One RS485 communication interface
Input/output relays l Four input relays
l Five output relays
l One CSU fault output relay
Supervision
interface
Environment
detection
l One flood alarm interface
l One door status alarm interface
l One smog status alarm interface
l One environment temperature interface
l One temperature control interface
l Two battery temperature interfaces
Operational
temperature
-5℃ to +45℃ (+15℃ to +25℃, recommended)
Storage temperature -40 ℃ to +70 ℃
Relative humidity 10% to 95% (non-condensing), 40% to 60% recommended
Altitude l 0 to 2000 m: 100% output power
l 2000 to 3000: The power derating percentage is 1% for
each 100 m increase in altitude above 2000 m.
Environment
specifications
Other requirements l The cabinet should be stable and erect.
l No conductive dusts or corrosive gases.
l No explosion hazard, no shake or jolt.
l No strong Electromagnetic Interference (EMI).
1-3
SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential
ZXDU58 B121 Product Description
1.4 Design StandardsEMC Standards
The ZXDU58 B121 (V2.0R01M05) system complies with the following ElectromagneticCompatibility (EMC) standards:
l EN55022l IEC61000-3-3; IEC61000-3-2; IEC61000-4-2; IEC61000-4-3; IEC61000-4-4;
IEC61000-4-6; IEC61000-4-8; and IEC61000-4-11
Safety Standards
The ZXDU58 B121 (V2.0R01M05) system is in compliance with the IEC/UL/EN 60950safety standards.
Other Standards
The ZXDU58 B121 (V2.0R01M05) system is also in compliance with the followingstandards:
l The Restriction of Hazardous Substances (RoHS) directive (2002/95/EC) of theEuropean Union.
l This device complies with Part 15 of the FCC Rules. Operation is subject to thefollowing two conditions: (1) This device may not cause harmful interference. (2)This device must accept any interference received, including interference that maycause undesired operations.
1-4
SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential
Chapter 2Structure and ComponentsTable of Contents
System Structure........................................................................................................2-1AC/DC Distribution Components ................................................................................2-2ZXD1500 Rectifier ......................................................................................................2-3Centralized Supervision Unit ......................................................................................2-5Signal Interfaces on the SIB Board.............................................................................2-7
2.1 System StructureThe ZXDU58 B121 (V2.0R01M05) consists of the ZXD1500 (V4.0) rectifiers, CentralizedSupervision Unit (CSU), Signal Interface Board (SIB), and AC/DC distribution unit.
For the layout of the components, see Figure 2-1.
Figure 2-1 System Composition of the ZXDU58 B121 (V2.0R01M05)
1. AC/DC distribution unit(Front view)
2. CSU
3. ZXD1500 (V4.0) rectifiers4. PE connection terminal5. Signal Interface Board
6. AC/DC distribution unit(Rear view)
2-1
SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential
ZXDU58 B121 Product Description
For a description of the components, refer to Table 2-1.
Table 2-1 System Composition of the ZXDU58 B121 (V2.0R01M05)
S.N. Component Description
1 AC/DC distribution unit Provide AC and DC power distribution. For the further
details, refer to 2.2 AC/DC Distribution Components.
2 Centralized Supervision Unit
(CSU)
Collects the power device operation data and manages
the power device. For the further details, refer to 2.4
Centralized Supervision Unit.
3 ZXD1500 (V4.0) rectifiers Converts AC power to DC power. For the further details,
refer to 2.3 ZXD1500 Rectifier.
4 Signal Interface Board (SIB) Provide supervision interfaces for supervision.
For the further details, refer to 2.5 Signal Interfaces on
the SIB Board.
2.2 AC/DC Distribution ComponentsFor the layout of the AC/DC distribution components, see Figure 2-2.
Figure 2-2 AC/DC Distribution Components
For a description of the components, refer to Table 2-2.
Table 2-2 AC/DC Distribution Components
Label Component Description
AC Output - -
2-2
SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential
Chapter 2 Structure and Components
Label Component Description
AC input circuit breaker Controls the connection and disconnection of AC
input power.
AC Input
AC input connection
terminals (L1/L2/PE)
Connect AC input L1/L2 cables and PE cable.
AC SPD AC surge protection
device
Provides surge protection for the AC input power.
DC Output DC output circuit breaker Controls the connection and disconnection of a DC
output circuit.
l LLVD1 load groups are labeled as F101 - F102
(DC output 1, 2).
l LLVD2 load groups are labeled as F201 - F204
(DC output 3, 4, 5, 6).
DC output (+)
DC output (-48V)
DC output connection
terminals
Connect the DC load.
Battery Input Battery input circuit
breakers
Controls the connection and disconnection of a
battery circuit.
BATT (-)
BATT (+)
Battery input connection
terminals
Connect two battery packs.
DC Surge
Arrester
DC surge protection
device
Provides surge protection for a DC circuit.
2.3 ZXD1500 RectifierThe ZXD1500 (V4.0) rectifiers convert AC to DC, provide power to the loads and chargethe batteries.
AppearanceFor the appearance of a ZXD1500 (V4.0) rectifier, see Figure 2-3.
2-3
SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential
ZXDU58 B121 Product Description
Figure 2-3 ZXD1500 (V4.0) Rectifier
1. Indicators2. Grille
3. Handle4. Stop pin
5. Input/output integratedsocket
Indicators
The indicators indicate the working state of the rectifier. For a description of the status ofthese indicators, refer to Table 2-3.
Table 2-3 Indicators Description
Designation Description Status Indication
IN Input Lit (green) AC input is normal.
OUT Output Lit (green) DC output is normal.
CL Current limit Lit (yellow) Current limit has occurred (the rectifier output
current has reached the current limit).
ALM Alarm Lit (red) An alarm has occurred.
Note:
When the rectifier is in sleep mode, only the IN indicator is lit.
Input/Output Integrated Socket
The input/output integrated socket of the rectifier is shown in Figure 2-4. It is used for theconnection to the DC power system.
2-4
SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential
Chapter 2 Structure and Components
Figure 2-4 Input/Output Integrated Socket
The pins of the socket are defined in Table 2-4.
Table 2-4 Pins Description
Pin No. Signal Description
1 OUTPUT 48V+ DC output +
3 OUTPUT 48V- DC output -
11 REMOTE l High–level input (amplitude at 5 V): to turn off the rectifier.
l Low–level input or high resistance: to turn on the rectifier.
12 ALARM l Low–impedance output: startup process, internal
fault/alarm or overheat status of the rectifier.
l High–impedance output: normal status.
13 COM Common end for the control signals.
14 ON-LINE Rectifier online signal: Directly connected to the COM signal on
the MAIN board.
15 PWM An input pulse signal with the amplitude of 5 V is required.
16 SHARE-BUS Current equalizing bus.
17 FOUT Output signal: Frequency/Current = 1.5 kHz/15 A.
26 AC input PE Protection ground.
27 AC input N Neutral
28 AC input L Live
2.4 Centralized Supervision UnitThe Centralized Supervision Unit (B121-CSU) manages the power distribution unit,rectifiers and batteries of the ZXDU58 B121 (V2.0R01M05) system.
Functions
l Collects the operational data and monitors the operation of the system.l Provides alarm and necessary protection if the system is operating abnormally.
2-5
SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential
ZXDU58 B121 Product Description
l Sends data to the background Supervision Center (SC) and receives the commandsfrom the SC. In this way, the system can be monitored remotely.
StructureFor the CSU structure, see Figure 2-5.
Figure 2-5 Centralized Supervision Unit (B121-CSU)
1. LCD screen2. Indicators3. Reset button
4. Buttons5. Handle6. Power switch
7. Fastening screw8. (Rear) Interface
IndicatorsThe indicators indicate the current operational status of the CSU. For a description of theCSU indicators, refer to Table 2-5.
Table 2-5 CSU Indicators
Designation Description Status Indication
PWR Power Lit (green) Power is applied to the CSU.
RUN Run Flashing (green) CSU is operating normally.
EQU Charge equalization Lit (green) Battery equalized charge is in-process.
COMM Communication Flashing (yellow) CSU is communicating with the
connected PC.
ALM Alarm Flashing (red) An alarm or fault has occurred.
Buttons
l The RST button is used to restart the CSU.l Users can perform querying and setting operations through the buttons laid on the
front panel of the CSU. For the function description of the buttons, refer to Table 2-6.
Table 2-6 Button Function
Button Function
▲ Turns pages (or items) upwards / increases values.
▼ Turns pages (or items) downwards / decreases values.
2-6
SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential
Chapter 2 Structure and Components
Button Function
Esc Exits and returns to the upper-level interface.
Enter Confirms the current menu items/saves the current parameter
setting/enters the lower-lever interface.
▲ + Enter Displays help information.
2.5 Signal Interfaces on the SIB BoardThe Signal Interface Board (SIB) provides external communication interfaces and signalinterfaces. For the layout of the interfaces on the SIB and pin configuration of theinterfaces, see Figure 2-6. For a description of the interfaces, refer to Table 2-7.
Figure 2-6 SIB
Table 2-7 Signal Interface Description
Interface Description
Battery temperature sampling interfaces and environment detection interfaces
X4 Battery 1 temperature Connects to temperature sensor of battery pack 1
2-7
SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential
ZXDU58 B121 Product Description
Interface Description
X5 Battery 2 temperature Connects to temperature sensor of battery pack 2
X12 Temperature control Used for low temperature disconnection function
X23 Flood alarm Connects to flood detect sensor
X24 Smoke alarm Connects to smoke detect sensor
X25 Ambient temperature Connects to environment temperature sensor
X26 Door status alarm Connects to door entrance detect sensor
Communication Interfaces
X21 RS485 interface The interface for RS485 communication
X22 RS232 interface The interface for RS232 communication
Input/output relay interfaces
X13 Input relay 1 and 2
X14 Input relay 3 and 4
The four input relays can be customized by the user for alarm
input.
The default alarm status of the input relays in the CSU are
“close”.
X15 Output relay for CSU
fault
This output relay is reserved for CSU fault.
X16 Output relay 1
X17 Output relay 2
X18 Output relay 3
X19 Output relay 4
X20 Output relay 5
l The output relays 1 to 5 correspond to the software codes
A1 to A5 in the CSU.
l For the default output relays for the alarms, refer to the
Alarm List.
l Users can customize these output relays for alarm output.
2-8
SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential
Chapter 3ZXD1500 (V4.0) RectifierSpecificationsTable of Contents
AC Input Over/Under-Voltage Protection ....................................................................3-1PFC Output Over/Under-Voltage Protection ...............................................................3-2Output Over-Voltage Protection..................................................................................3-2Output Over-Current Protection..................................................................................3-3Over-Temperature Protection and Fan Speed Control ................................................3-3
3.1 AC Input Over/Under-Voltage ProtectionFor the AC input over/under-voltage protection and power decrease control, refer to Table3-1 and see Figure 3-1.
Table 3-1 AC Input Over/Under-Voltage Protection and Power Control
AC Input Voltage Protection and Power Control
≤ 70 V Auxiliary power supply startup
≤ 80 V The post-DC/DC conversion circuit and the pre-PFC circuit stop working.
80 V - 110 V Current limit Imax = (10 ± 2) A.
110 V - 150 V Current limit Imax = (20 ± 2) A
150 V - 300 V Current limit Imax = (32 ± 1) A
≥ 300 V The post-DC/DC conversion circuit and the pre-PFC circuit stop working.
3-1
SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential
ZXDU58 B121 Product Description
Figure 3-1 AC Input Over/Under-Voltage Protection
l The protection function is implemented through hardware.l The precision of the voltage is ± 10 V and the hysteresis width is (15 ± 10) V.
3.2 PFC Output Over/Under-Voltage ProtectionThe PFC output over/under-voltage protection is as follows:
l When the PFC output voltage > 440 V DC, the post-DC/DC conversion circuit and thepre-PFC circuit stop working.
l When the PFC output voltage < 340 V DC, the post-DC/DC conversion circuit stopsworking.
The PFC output over/under-voltage protection is implemented through hardware. Theprecision of the voltage is ±10 V and the hysteresis width is (15 ± 10) V.
3.3 Output Over-Voltage ProtectionThe output over-voltage protection circuit prevents the DC output filter capacitor andpowered devices from damage due to voltage loop failure.
The output over-voltage protection threshold is (61 ± 1) V, which is unmodifiable. Whenthe output voltage exceeds (61 ± 1) V, the rectifier disables output and will not enable ituntil the fault is eliminated after power-off and the rectifier is restarted.
3-2
SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential
Chapter 3 ZXD1500 (V4.0) Rectifier Specifications
3.4 Output Over-Current ProtectionThe output over-current protection circuit prevents the rectifier from being damaged dueto the fault of output current limit circuit.
To avoid over-current protection prior to current limit protection, the response ofover-current protection is set to be slower than current limit protection, and the over-currentprotection threshold is set to be higher than the maximum current limit threshold.
The over-current protection threshold of the rectifier is (36 ± 2) A.
The output over-current protection is a kind of backup protection and is configured as"unrecoverable". It does not act generally; however, once the over-current protectionis activated, the function will not recover until the fault is eliminated and the rectifier isrestarted.
3.5 Over-Temperature Protection and Fan SpeedControl
According to the temperature of the radiator, the fan may work at full speed or half speed.
l When the temperature is over 50 °C, the fan works at full speed.l When the temperature is below 50 °C, the fan works at half speed.
The radiator temperature may keep increasing when the fan is faulty or it is working atfull speed. Therefore, a negative temperature coefficient thermistor is used to prevent therectifier from being damaged due to over-temperature. The over-temperature protectionis as follows:
l When the temperature exceeds the temperature protection threshold, the post-DC/DCconversion circuit stops working.
l When the temperature is below the temperature protection threshold, the post-DC/DCconversion circuit starts to work.
3-3
SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential
ZXDU58 B121 Product Description
This page intentionally left blank.
3-4
SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential
Appendix AAlarm ListTable A-1 lists the alarms that can be detected by the B121-CSU (SV2.20) supervisionunit, and describes their default alarm levels and output relays.
l A1 - A5 refer to 5 output relays for the alarms.l Multiple alarms can share one output relay. Each alarm cannot correspond to multiple
output relays but one output relay only. “0” means that no output relay is assignedto an alarm. When an alarm is reported, it indicates that problems occur on thecorresponding output relay.
l Except for “Total Alarm” and “Start GEN”, the output relay of an alarm will not takeeffect when its alarm level is set to “Mask”.
Table A-1 Alarm List
S.N. Alarm Name AlarmLevel
OutputRelay
Alarm Description
1 Total Alarm Mask A1 The CSU detects that an alarm occurred.
AC Related
2 AC Aux SW Off Minor A2 The AC auxiliary switch is Off.
3 AC Main SW Off Major A2 The AC input air switch is Off.
4 AC Power Off Major A2 The mains supply is cut off and there is no
standby AC input available.
5 ACArrester Brk. Minor A2 The surge arrester is faulty.
6 AC Under-Vol Minor A2 The AC input voltage is lower than ACVol.Min.
7 AC Over-Vol Minor A2 The AC input voltage is higher than ACVol.Max.
8 AC Phase Lost Minor A2 AC input phase lost.
9 AC Current Over Minor A2 The AC input current is higher than the preset
maximum AC current.
SMR Related
10 SMR Alarm Minor A3 A rectifier is faulty. If one rectifier is faulty, it
is a minor alarm; if two or more rectifiers are
faulty at the same time, it is a major alarm.
11 SMR Abnormal Minor A3 The rectifier is activated but has no output.
DC and Battery Related
A-1
SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential
ZXDU58 B121 Product Description
S.N. Alarm Name AlarmLevel
OutputRelay
Alarm Description
12 DC Under-Vol Minor A4 The DC output voltage is lower than DCVol.Min.
13 DC Over-Vol Minor A4 The DC output voltage is higher than DCVol.Max.
14 DC Loop Break Minor A4 The DC output branch n is disconnected.
15 Bat Loop Break Minor A4 The battery branch n is disconnected.
16 Bat Under-Vol Major A4 The battery voltage is lower than BatVol Min.
17 Bat Over-Temp Minor A4 The temperature of battery n is higher than
Bat. Temp.Max.
18 1st Shut-down Major A4 When the battery voltage is lower than 1-ShutVol., the secondary loads are shut down.
19 2nd Shut-down Major A4 When the battery voltage is lower than 2-ShutVol., all the loads are shut down.
20 DCArrester Brk. Minor A4 The DC arrester is faulty.
21 DCBreaker Alarm Minor A4 The DC contactor of the DC loop n is faulty
(n ranges from 1 to 2)
22 Battery Fault Major A4 The battery cannot supply power online.
23 Bat Under-Temp Minor A4 The temperature of group N battery is less
than Bat Under-Temp.
24 Bat.Temp.Void Minor A4 The system is configured with batteries, but
battery temperature sensor is not properly
connected.
25 Bat.Discharge Minor A4 Battery discharge current is higher than
Bat.Discharge.
Environmental Related
26 Env Under-Temp Minor A5 Environment temperature is lower than
Env.Temp.Min.
27 Env Over-Temp Minor A5 The environment temperature is higher than
Env.Temp.Max.
28 Env Under-Hum Minor A5 The environment humidity is lower than
Env.Hum.Min.
29 Env Over-Hum Minor A5 The environment humidity is higher than
Env.Hum.Max.
30 Smoke Alarm Minor A5 The sensor detects the smoke.
31 Flood Alarm Minor A5 The sensor detects the entrance of water.
A-2
SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential
Appendix A Alarm List
S.N. Alarm Name AlarmLevel
OutputRelay
Alarm Description
32 Intrusion Alarm Minor A5 The sensor detects the intrusion of a foreign
object.
33 Door Magnet Alm Minor A5 The door with door magnet switch is opened.
34 Glass Broken Minor A5 The sensor detects broken glasses.
35 EnvUn.LostTouch Minor A5 The communication between the CSU and the
Environment Monitor Board (EMB) failed.
36 HeatExch.Alm Major A5 The heat exchanger is faulty.
37 Env.Temp.Void Minor A5 No valid battery temperature sensor is
configured.
38 Start GEN Mask 0 The generator has been activated.
A-3
SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential
ZXDU58 B121 Product Description
This page intentionally left blank.
A-4
SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential
Appendix BElectrical ConnectionDiagramFor the operating principle diagram of the ZXDU58 B121 (V2.0R01M05), see Figure B-1.
Figure B-1 Operating Principle Diagram of the ZXDU58 B121 (V2.0R01M05)
The components are described as follows.
l AC distribution unit: Connects AC input to the system and distributes AC power.l Rectifiers: Convert AC to DC.l DC distribution unit: Provides DC output to the loads and connects the batteries to
the system.l CSU: Controls and manages the system.l Batteries: Provide standby DC power to the loads when the mains is failure.
For the detailed electrical connection diagrams of the ZXDU58 B121 (V2.0R01M05), seeFigure B-2.
B-1
SJ-20140210154807-001|2014-03-03 (R1.0) ZTE Proprietary and Confidential
ZXDU58B121Pro
ductDescrip
tion
Figure B-2 Electrical Connection Diagram of the ZXDU58 B121 (V2.0R01M05)
B-2
SJ-20140210154807-001|2014-03-03(R1.0)
ZTEPro
prietary
andConfidential
GlossaryAC- Alternating Current
CSU- Centralized Supervision Unit
DC- Direct Current
EMB- Environment Monitor Board
EMC- Electromagnetic Compatibility
EMI- Electromagnetic Interference
LLVD- Load Low Voltage Disconnect
MCB- Miniature Circuit Breaker
MTBF- Mean Time Between Failures
PC- Personal Computer
PE- Protective Earth
PFC- Power Factor Correction
RoHS- Restriction of Hazardous Substances
SIB- Signal Interface Board
SPD- Surge Protection Device