1
Emerson Climate Technologies December 27, 2012 Compressor Information Inputs Results Compressor Model: Refrigerant: Condensing Temperature (°F): Evaporator Temperature (°F): Phase: Frequency (Hz): Volts: Compressor Superheat (°F): Evaporator Superheat (°F): Total Subcooling (F): Return Gas Temperature (°F): Power (W): Net Refrigeration Effect (Btu/hr): Isentropic Efficiency (%): Current (Amps): Evaporator EER (Btu/Wh): Compressor Capacity (Btu/hr): Compressor EER (Btu/Wh): Refrigerant Flow Rate (lb/hr): Liquid Temp. (°F): ZR190KCE-TFD 460 60 3 R-134a 130.0 45.0 65.0 20 20 15 127,000 127,000 11.24 11.24 2,010.0 67.3 115.0 11,300 21.4 Discharge Temp. (°F): Application: Air Conditioning Note: Net Refrigeration Capacity is the amount of useful cooling delivered to refrigerated space. Rating Conditions 20 °F Superheat 15 F Subcooling 95 °F Ambient Air Over 176.0 Discharge Temperature Estimation Accuracy ± 10 °F. Condenser Heat Rejection (Btu/hr): 165,567 RLA (MCC/1.4) (Amps): MCC (Amps): 27.9 39.0 179.0 25.0 LRA: RLA (MCC/1.56) (Amps): NA HP: 2012 Emerson Climate Technologies, Inc.

ZR190KCE-TFD

Embed Size (px)

DESCRIPTION

Copeland 190

Citation preview

  • Emerson Climate Technologies December 27, 2012

    Compressor Information

    Inputs

    Results

    Compressor Model:

    Refrigerant:

    Condensing Temperature (F):

    Evaporator Temperature (F):

    Phase:

    Frequency (Hz):

    Volts:

    Compressor Superheat (F):

    Evaporator Superheat (F):

    Total Subcooling (F):Return Gas Temperature (F):

    Power (W):

    Net Refrigeration Effect (Btu/hr):

    Isentropic Efficiency (%):

    Current (Amps):

    Evaporator EER (Btu/Wh):

    Compressor Capacity (Btu/hr):

    Compressor EER (Btu/Wh):

    Refrigerant Flow Rate (lb/hr):

    Liquid Temp. (F):

    ZR190KCE-TFD

    460

    60

    3

    R-134a

    130.0

    45.0

    65.0

    20

    20

    15

    127,000

    127,000

    11.24

    11.24

    2,010.0

    67.3

    115.0

    11,300

    21.4

    Discharge Temp. (F):

    Application: Air Conditioning

    Note: Net Refrigeration Capacity is the amount of useful cooling delivered to refrigerated space.

    Rating Conditions20 F Superheat15 F Subcooling95 F Ambient Air Over

    176.0

    Discharge Temperature Estimation Accuracy 10 F.

    Condenser Heat Rejection (Btu/hr): 165,567

    RLA (MCC/1.4) (Amps):

    MCC (Amps):

    27.9

    39.0 179.0

    25.0

    LRA:

    RLA (MCC/1.56) (Amps):

    NAHP: