Upload
battinapati-shiva
View
23
Download
2
Embed Size (px)
DESCRIPTION
Crompton
Citation preview
1© ZIV Aplicaciones y Tecnología S. A.
Distance Protection
2© ZIV Aplicaciones y Tecnología S. A.
PROTECTION FUNCTIONS
Function Description21+21N Distance protection for phase and ground faults
50Sup Overcurrent for distance monitoring
Load encroachment logic
Protection schemes for distance elements
Fuse failure detector
Close onto fault logic
Remote breaker open detector
Dead Line Detector
68/78 Power swing blocking and/or tripping (out of step t ripping)
25 Synchronism check
79 3-pole/1-pole recloser
50BF Breaker failure protection
3© ZIV Aplicaciones y Tecnología S. A.
Function Description46 Open phase detector
49 Thermal image protection
50F Three phase instantaneous overcurrent elements (A,B ,C)
50N Three ground instantaneous overcurrent elements
50Q Three negative sequence instantaneous elements
51F Three phase time delay overcurrent elements (A,B,C)
51N Three ground time delay overcurrent elements
51Q Three negative sequence time delay overcurrent elem ents
67 Phase directional unit (A,B,C)
67N Ground directional unit
67Q Negative sequence directional unit
Protection schemes for 67N/67Q
PROTECTION FUNCTIONS
4© ZIV Aplicaciones y Tecnología S. A.
Function Description50STUB Stub bus protection
59 Three phase overvoltage elements (A,B,C)
27 Three phase undervoltage elements (A,B,C)
59N Two ground overvoltage elements
81M Three overfrequency elements
81m Three underfrequency elements
81D Three rate of frequency change elements
Single/three pole tripping for 21+21N and 67N/67Q
Suitable for cables and overheadlines with series capacitor compensation
Mutual coupling compensation for parallel lines
PROTECTION FUNCTIONS
5© ZIV Aplicaciones y Tecnología S. A.
DescriptionBreaker supervision
Fault locator (compensates for load flow and mutual coupling)
Trip masks for distance zones or for auxiliary units
Programmable logic (executed each 2 ms)
Oscillography with analog and digital signals
Records: events, fault reports and metering logs
Measurement
Control
Communications
User interface (alphanumeric display and keypad/pro grammable push bottons for operations or commands)
Integrated simulator
ADITIONAL FUNCTIONS
6© ZIV Aplicaciones y Tecnología S. A.
4 x V + 5 x I ó 5 x V + 8 x I (depending on the mod el)
1 alarm output (watchdog)
Digital inputs (all programmable):
10 in 2 U box
22 in 3 U box
34 in 4 U box
37 in 6 U box
Outputs (all programmable and strong: anyone can be used as trip / close output)
10 in 2 U box (4 can be fast for teleprotection)
23 in 3 U box (4 can be fast for teleprotection)
36 in 4 U box (4 can be fast for teleprotection)
44 in 6 U box (4 can be fast for teleprotection)
Connectors with ring lugs
INPUTS / OUTPUTS
7© ZIV Aplicaciones y Tecnología S. A.
5 distance zones (all reversible)
6 independent measuring elements for each zone
Impedance reaches, resistive reaches and time delay s independent for ground and phase units
Selectable characteristic independent for phase and ground faults:
Mho (dynamic and variable)
Quadrilateral
Both combined (AND / OR)
Reaches (Z1) and zero sequence compensation factors (K0=Z0/Z1) independent for each zone in module and a ngle
DISTANCE PROTECTION
8© ZIV Aplicaciones y Tecnología S. A.
Dynamic characteristic (memory action):
Variable characteristic (V1 action):
Advantages of polarizing with V1M:
Proper operation for zero voltage three phase faults and for voltage inversions (series compensation)
Proper operation for zero voltage single phase and two-phase faults
MHO CHARACTERISTIC
9© ZIV Aplicaciones y Tecnología S. A.
ZSLESL ZL
V1IX ⋅⋅⋅⋅
IR⋅⋅⋅⋅
IZSL⋅⋅⋅⋅
IX ⋅⋅⋅⋅
IR⋅⋅⋅⋅
IZLZSR ⋅⋅⋅⋅++++ )(
V1F1
ZSR
F2
IF2
V2
IF1
F1
IrelayIF2F2V1
IF1=Irelay
F1V1F2V2
-jXC
MHO CHARACTERISTIC
10© ZIV Aplicaciones y Tecnología S. A.
V
φ
Ieq1
V
φ
1M
IX ⋅
IR ⋅)( cargaIIeqZSL φ−⋅
111 ZIeq ⋅
RFIF ⋅F F’
I
1M
IX ⋅
IR ⋅
F F’
Vφ φ
Vφ φ
φ φ
)( cargaIIZSL φφφφ −⋅
2
RFIF ⋅φφ
Z11⋅Iφφ
PHASE-GROUND FAULTS [ ] φφ VnZnKIIFop −⋅−⋅+= 1)10(0
MVFpol 1φ=
( ) ( )[ ] 90ºFpolargFopargº90 ≤−≤−
PHASE-PHASE FAULTSφφφφ VnZIFop −⋅= 1
MVFpol 1φφ=
MHO CHARACTERISTIC
11© ZIV Aplicaciones y Tecnología S. A.
QUADRILATERAL CHARACTERISTIC
θθθθ1
Zr
Directional unit
Reactance element (load and non homogeneity compensation)
Resistive limiters
12© ZIV Aplicaciones y Tecnología S. A.
REACTANCE ELEMENT
SINGLE PHASE TO GROUND FAULT
Z1SL Z1SRESLA ESRA
Z1SL Z1SRESLB ESRB
Z1SL Z1SRESLC ESRC
ZSN ZSN’ZN
Z1LF Z1LF’
Z1LF Z1LF’
Z1LF Z1LF’
ZN’
Ic
Ib
Ia
Ic’
Ib’
Ia’IFa
RF
RFIFaLFZIeqVa ⋅+⋅= 1 ( )100 −⋅+= KIIaIeq
VaVbVc
13© ZIV Aplicaciones y Tecnología S. A.
PHASE-PHASE (TO GROUND) FAULT
2/1 RFIFabLFZIeqVab ⋅+⋅= IbIaIabIeq −==
Z1SL Z1SRESLA ESRA
Z1SL Z1SRESLB ESRB
Z1SL Z1SRESLC ESRC
Z1LF Z1LF’
Z1LF Z1LF’
Z1LF Z1LF’
Ic
Ib
Ia
Ic’
Ib’
Ia’
VaVbVc
RF/2
RF/2 RgIFb
IFa
IFbIFaIFab −=
REACTANCE ELEMENT
14© ZIV Aplicaciones y Tecnología S. A.
IF RF⋅
VrIeq Z LF⋅ 1
Ieq
αααα
Z1FIeq ⋅IX ⋅
IR ⋅
RFIFLFZIeqVr ⋅+⋅= 1 RFIeq
IFLFZZr ⋅+= 1
ZrZ1LF
ααααZ1FX
R
RFIeq
IF ⋅ Fr
F
ERROR
F
Fr
REACTANCE ELEMENT
15© ZIV Aplicaciones y Tecnología S. A.
α α α α depends onLOAD FLOW
HOMOGENEITY
0≈αLOAD FLOW AND HOMOGENEOUS SYSTEM
FORWARD LOAD FLOW 0<αREVERSE LOAD FLOW 0>α
NO LOAD FLOW AND NON HOMOGENOUS SYSTEM
NO LOAD FLOW AND HOMOGENOUS SYSTEM
REACTANCE ELEMENT
( )Z1LF Z1SLα arg
Z1L Z1SL Z1SR
+=
+ +
16© ZIV Aplicaciones y Tecnología S. A.
LOAD FLOW AND HOMOGENOUS SYSTEM
F
Z1F
α
Fr
ZrZ1LF
R
X
Underreaching effect ( α>0) Overreaching effect ( α<0)
F
Z1F Fr
Zr
Z1LF
R
X
RFIeq
IF ⋅RF
Ieq
IF ⋅α
Ieq
Fpol
Avoid
Ieq
Fpol
Avoid
Fpol parallel to IF
2φIFpol =
pfIIFpol φφφφ −=
Single line to ground fault
Phase-phase fault (with or without ground)
pfIIFpol φφ −=
REACTANCE ELEMENT
17© ZIV Aplicaciones y Tecnología S. A.
NO LOAD FLOW AND NON HOMOGENOUS SYSTEM
Fpol NON parallel to IF (angle= α)
Faults at 100% γ = α
Zr
Z1LF
α
Z1F
X
R
RFIeq
IF ⋅
Ieq
Fpol
F
Fr
REACTANCE ELEMENT
( )Z1LF Z1SLα arg
Z1L Z1SL Z1SR
+=
+ +
γ
Tilting angle is introduced
( )Z1L Z1SLarg
Z1L Z1SL Z1SRγ
+=
+ +
18© ZIV Aplicaciones y Tecnología S. A.
⋅
Ieq1
Z11
α C1
C2
Fpol
Vφ
F
F’
α
⋅Ieq1
I φ
IX ⋅
IR ⋅
RF⋅IF
FopZ11
αC1
C2
Fpol
V
F
F’
α
⋅
I
φφI
φφ
φφ
IX ⋅
IR ⋅
Fop
2/IF RF⋅φφ
[ ] φφ VnZnKIIFop −⋅−⋅+= 1)10(0 φφφφ VnZIFop −⋅= 1
2φIFpol = pfIIFpol φφ −= pfIIFpol φφφφ −=
REACTANCE ELEMENT
PHASE-GROUND FAULTS PHASE-PHASE FAULTS
( ) ( )[ ] 180ºFpolargFoparg0 ≤−−≤ γ
19© ZIV Aplicaciones y Tecnología S. A.
Dynamic line (memory action):
Variable line (V1 action):
Advantages of polarizing with V1M:
Proper operation for zero voltage three phase faults and for voltage inversions (series compensation)
Proper operation for zero voltage single phase and two-phase faults
DIRECTIONAL UNIT
20© ZIV Aplicaciones y Tecnología S. A.
IX ⋅⋅⋅⋅
IR ⋅⋅⋅⋅
DIRECTIONAL UNIT
IX ⋅⋅⋅⋅
IR⋅⋅⋅⋅V1F1 IrelayIF2
F2V1
IF1=Irelay
F1V1 F2V2
IZSL⋅⋅⋅⋅
IZLZSR ⋅⋅⋅⋅++++ )(
ZSLESL ZL
V1
ZSR
F2
IF2
IF1
F1
-jXC
V2
21© ZIV Aplicaciones y Tecnología S. A.
( ) ( ) ( )[ ] ( )αα −≤−≤+− º90argargº90 FpolFop
DIRECTIONAL UNIT
PHASE-GROUND FAULTS PHASE-PHASE FAULTS
V
φ
Iφ
V
φ
1M
Iφ
IX ⋅
IR ⋅
α
)( cargaIIeqZSL φ−⋅
C3
F
V
I
V 1M
I
IX ⋅
IR ⋅
α
φ φ
φ φ
φ φ
φ φ
)( cargaIIZSL φφφφ −⋅
C3
F
φIFop= φφIFop=MVFpol 1φ= MVFpol 1φφ=
22© ZIV Aplicaciones y Tecnología S. A.
φφ VRGnIFop −⋅= RGnIFpol ⋅= φ φφφφ VRPnIFop −⋅= RPnIFpol ⋅= φφ
[ ])arg()arg( IeqnInbucle −−== φθθθ nθθ =
RESISTIVE LIMITER
PHASE-GROUND FAULTS PHASE-PHASE FAULTS
C4
V
F’
Z11⋅Ieq1
Ieq1
φ
IX ⋅
IR ⋅
F
Iφ
11θ
1bucθ
RFIF ⋅
1RGI ⋅φ
C4
V
F’Z11⋅
I
IX ⋅
IR ⋅
F
11θ
φφ
φφ
Iφφ 2
RFIF ⋅φφ
1RPI ⋅φφ
( ) ( ) ( )[ ] θθ ≤−≤+− FpolFop argargº90
23© ZIV Aplicaciones y Tecnología S. A.
QUADRILATERAL: PHASE-GROUND FAULTS
24© ZIV Aplicaciones y Tecnología S. A.
QUADRILATERAL: PHASE-PHASE FAULTS
25© ZIV Aplicaciones y Tecnología S. A.
Based on angle between Ia2 and Ia1 fault currents
For faults with zero sequence infeed uses phase undervoltage units
Allows:
Single pole tripping on single-phase-ground faults
Blocking leading phase on phase-phase-ground faults
For phase-phase-ground faults the lagging phase-ear th loop can not be blocked: helps phase-phase loop in some kind of faults
PHASE SELECTOR
26© ZIV Aplicaciones y Tecnología S. A.
( ) ( )f_1Iaarg2Iaarg −=φ
InIa ⋅> 05.02 %101
2 >Ia
IaInIa ⋅> 05.00 %8
1
0 >Ia
Ia
PHASE-PHASE FAULT GROUND FAULT
PHASE SELECTOR
27© ZIV Aplicaciones y Tecnología S. A.
PHASE-PHASE-GROUND FAULTS
Z1LF
Z1LF
RF
Rg
IFbIFa
RF
IFT
A
B
ZN
Va Vb
Ib
Ia
Z1LF
Z1LF
RF
IFbIFa
RF
IFT
A
B
ZN
Va Vb
Ib
Ia
ABG FAULT:AG unit overreachesBG unit underreaches
AG BG FAULT:AG and BG units operate correctly
The AB unit can be complemented with the BG unit
28© ZIV Aplicaciones y Tecnología S. A.
FAULT DETECTOR
Sequence currents increment detection ( ∆I0, ∆Ia1, ∆Ia2)
Sequence currents levels exceeded (I0, Ia2)
Sealed-in by operation of distance units, overcurre nt units, close onto fault detector and stub bus protection
Supervises the tripping produced by distance units, overcurrent units, close onto fault detector, stub bus protection and remote breaker open detector
Determines the fault inception time (allows the sel ection of prefault and postfault values: current and voltage)
29© ZIV Aplicaciones y Tecnología S. A.
FAULT DETECTOR
30© ZIV Aplicaciones y Tecnología S. A.
α1α1α1α1α2α2α2α2
R1R2
X
R
R: minimum Rloadα: minimum PF
LOAD ENCROACHMENT
31© ZIV Aplicaciones y Tecnología S. A.
Activation when:
Phase undervoltage units pick-up without
activation of fault detector
Input coming from MCB activates
Inhibited when any pole is open
Can block distance elements, weak infeed trip,
synchronism, dead line detector and voltage units
FUSE FAILURE DETECTOR
32© ZIV Aplicaciones y Tecnología S. A.
FUSE FAILURE DETECTOR
33© ZIV Aplicaciones y Tecnología S. A.
Detects what pole of the breaker has opened
Detection based on breaker contacts plus undercurre nt
detectors
Outputs used by phase selector, distance units, fau lt
detector, power swing detector, fuse failure detect or,
ground and negative sequence overcurrent units, rec loser,
etc
OPEN POLE DETECTOR
34© ZIV Aplicaciones y Tecnología S. A.
OPEN POLE DETECTOR
35© ZIV Aplicaciones y Tecnología S. A.
OPEN POLE DETECTOR
36© ZIV Aplicaciones y Tecnología S. A.
DISTANCE UNITS OPERATION
SINGLE PHASE UNITS
37© ZIV Aplicaciones y Tecnología S. A.
DISTANCE UNITS OPERATION
PHASE-PHASE UNITS
38© ZIV Aplicaciones y Tecnología S. A.
DEAD LINE DETECTOR
Operated based on undervoltage and undercurrent uni ts
Only applicable when the VT is on the line side
Allows detecting the breaker closing without the ne ed from
external contacts
Can be used to activate the close onto fault functi on
39© ZIV Aplicaciones y Tecnología S. A.
Activated with manual close or reclose commands:
internal or external
Phase overcurrent units with second harmonic
restraint ( inrush stabilization)
Zone 1 extension:
Always activated for close commands
Adjustable for reclose commands
CLOSE ONTO FAULT DETECTOR
40© ZIV Aplicaciones y Tecnología S. A.
CLOSE ONTO FAULT DETECTOR
41© ZIV Aplicaciones y Tecnología S. A.
X
R
Stable oscillation
Unstable oscillation
A
ZONE INT
ZONE MED
ZONE EXT
δ
ZB
ZA
ZL
Slow trip
Fast trip
T
POWER SWING DETECTOR
42© ZIV Aplicaciones y Tecnología S. A.
Selectable zones to be blocked
Unblocking of blocked distance zones when a fault is
detected:
Ground or phase-phase fault detection (phase select or)
Time the impedance remain inside the external zone
Tripping for unstable swings: slow/fast trip
POWER SWING DETECTOR
43© ZIV Aplicaciones y Tecnología S. A.
POWER SWING DETECTOR
44© ZIV Aplicaciones y Tecnología S. A.
Basic Scheme:
Stepped distance
Schemes without communication channel:
Zone 1 extension
Remote breaker open detector
DISTANCE PROTECTION SCHEMES
45© ZIV Aplicaciones y Tecnología S. A.
Schemes with communication channel:
Permissive underreach transfer trip ( PUTT)
Direct transfer trip ( DTT)
Permissive overreach transfer trip ( POTT)
Directional comparison unblocking ( DCUB)
Directional comparison blocking ( DCB)
User defined (programmable logic)
Binary information transmission (virtual inputs/out puts)
DISTANCE PROTECTION SCHEMES
46© ZIV Aplicaciones y Tecnología S. A.
DISTANCE PROTECTION SCHEMES
Complementary logics:
Echo and weak infeed trip logic
Transient blocking for current reversal (parallel lines)
47© ZIV Aplicaciones y Tecnología S. A.
STEPPED DISTANCE
Independent timers for phase and ground faults
Timers do not drop out for evolving faults
Blocking signals coming from:
Power swing detector
Fuse failure detector
Series compensated lines logic
48© ZIV Aplicaciones y Tecnología S. A.
STEPPED DISTANCE
49© ZIV Aplicaciones y Tecnología S. A.
ZONE 1 EXTENSION
Zone 1 extended to overreaching zone (zone 2 or 3)
Requires fast reclosing to restore the supply as fa st as
possible
Inhibited when the breaker opens; enabled again whe n
the breaker remains closed for a settable time
Avoids zone 1 extension when reclosing
50© ZIV Aplicaciones y Tecnología S. A.
ZONE 1 EXTENSION
51© ZIV Aplicaciones y Tecnología S. A.
PUTT
Carrier sending by zone 1 (underreaching)
Settable carrier time
Can be complemented by weak infeed logic (trip)
Optional carrier sending by open breaker
Blocking signals coming from:
Power swing detector
Digital input
52© ZIV Aplicaciones y Tecnología S. A.
PUTT
53© ZIV Aplicaciones y Tecnología S. A.
DTTSimilar to PUTT but with direct trip by carrier rec eption
Settable carrier time
Settable security time to avoid erroneous operation s
due to noise in the communication channel
Optional carrier sending by open breaker
Blocking signals coming from:
Power swing detector (only blocks carrier sending)
Digital input
54© ZIV Aplicaciones y Tecnología S. A.
DTT
55© ZIV Aplicaciones y Tecnología S. A.
POTTCarrier sending by overreaching zone
Settable carrier time
Can be complemented by weak infeed (echo or
echo+trip) and current reversal logics
Optional carrier sending by open breaker
Blocking signals coming from:
Power swing detector
Digital input
56© ZIV Aplicaciones y Tecnología S. A.
POTT
57© ZIV Aplicaciones y Tecnología S. A.
DCUBSimilar to POTT but allows instantaneous tripping f or a
time window (150 ms) even if the carrier is lost
Requires frequency-shifted PLC equipment
Settable carrier time
Can be complemented by weak infeed (echo or echo+tr ip) and current reversal logics
Optional carrier sending by open breaker
Blocking signals coming from:
Power swing detector
Digital input
58© ZIV Aplicaciones y Tecnología S. A.
DCUB
59© ZIV Aplicaciones y Tecnología S. A.
DCBCarrier sending by reverse zone (zone 4 or zone 5) or non-
directional overcurrent units (fast carrier sending )
Settable time delay for overreaching zone operation
Implicit current reversal logic
Carrier stop input / output
Blocking signals (inhibite tripping and generate ca rrier) coming from:
Power swing detector
Digital input
60© ZIV Aplicaciones y Tecnología S. A.
DCB
61© ZIV Aplicaciones y Tecnología S. A.
WEAK INFEED LOGIC
Selectable logic output: NON, ECHO or ECHO+TRIP
Settable security time to avoid erroneous echo send ings
due to noise in the communication channel
Implicit current reversal logic
Settable voltage threshold for weak infeed trip
Phase selector based on undervoltage units
Optional weak infeed trip blocking by fuse failure detector
62© ZIV Aplicaciones y Tecnología S. A.
WEAK INFEED LOGIC
63© ZIV Aplicaciones y Tecnología S. A.
CURRENT REVERSAL LOGIC
Can be applied in any permissive overreaching schem e
Blocking signal for overreaching zone is activated b y
reverse zone (zone 4 or zone 5) pick-up
Settable blocking time delay
64© ZIV Aplicaciones y Tecnología S. A.
CURRENT REVERSAL LOGIC
65© ZIV Aplicaciones y Tecnología S. A.
REMOTE BREAKER OPEN DETECTOR
Allows zone 2 instantaneous tripping once the remote
breaker is detected as open (three-phase):
Loss of load (undercurrent detectors)
Capacitive current detection (long lines)
( ) ( ) ( )[ ] ( )δφφδ +≤−≤− º90argargº90 VI
66© ZIV Aplicaciones y Tecnología S. A.
REMOTE BREAKER OPEN DETECTOR
67© ZIV Aplicaciones y Tecnología S. A.
OVERCURRENT UNITSPhase, ground and negative sequence / instantaneous and
time delayed
Selectable torque control: non-directional / forwar d / reverse
Selectable directional unit (torque control type)
Torque control disable input
Time delay reset input
Blocking signals coming from:
Digital input
Open pole detectors (ground and negative sequence units)
Series compensated lines logic
68© ZIV Aplicaciones y Tecnología S. A.
PHASE INSTANTANEOUS
OVERCURRENT UNITS
69© ZIV Aplicaciones y Tecnología S. A.
GROUND INSTANTANEOUS
OVERCURRENT UNITS
70© ZIV Aplicaciones y Tecnología S. A.
NEGATIVE SEQUENCE
INSTANTANEOUS OVERCURRENT UNITS
71© ZIV Aplicaciones y Tecnología S. A.
PHASE TIME-DELAYED
OVERCURRENT UNITS
72© ZIV Aplicaciones y Tecnología S. A.
GROUND TIME-DELAYED
OVERCURRENT UNITS
73© ZIV Aplicaciones y Tecnología S. A.
NEGATIVE SEQUENCE
TIME-DELAYED OVERCURRENT UNITS
74© ZIV Aplicaciones y Tecnología S. A.
Phase directional units:
Polarized by quadrature memory phase-phase voltage
Ground directional units:
Polarized by zero-sequence voltage
Polarized by current coming from an earth clamp
Negative sequence directional units:
Polarized by negative sequence voltage
Distance zone 2 can act as directional unit for o/c
Two setting options available in case of loss of po larization (can be applied to fuse failure ): blocking/permission
DIRECTIONAL UNITS
75© ZIV Aplicaciones y Tecnología S. A.
DIRECTIONAL UNITS
76© ZIV Aplicaciones y Tecnología S. A.
Polarization voltage compensator factor for ground and negative sequence directional units:
)67_00(_ 67_67 NANGKIVPOLF NCOMPN ∠⋅+−=
)67_22(_ 67_67 QANGKIVPOLF QCOMPQ ∠⋅+−=
Applications:
Increase polarization voltage: makes it higher than minimum level for polarization (strong zero/negative sequence sources)
Invert polarization voltage: compensates inversions in series compensated lines
DIRECTIONAL UNITS
77© ZIV Aplicaciones y Tecnología S. A.
ZA0 ZB0p x ZL0 (1-p) x ZL0
IF
I0
V0
ZA0 ZB0 ZL0
IF
I0
V0
-V0
I0
COMP_67NKI0 ⋅ ANG_67N
Forward
Reverse
)0(00 IZAV −⋅= 0)00(0 IZBZLV ⋅+=Forward fault Reverse fault
DIRECTIONAL UNITS
78© ZIV Aplicaciones y Tecnología S. A.
jXSL2 jmXL2-jXC
j(1-m)XL2 jXSR2
V2
I2 IF
I2
)2(22 jXCjXSLIV −−−−⋅⋅⋅⋅====−−−−
22 jXSLI ⋅⋅⋅⋅
)(2 jXCI −−−−⋅⋅⋅⋅
QCOMPKI 67_2 ⋅⋅⋅⋅FORWARD FAULT
Negative sequence voltage inversion if, with line side CT : XC>XSL2
Vpolarization CompensationXCK QCOMP >>>>67_
DIRECTIONAL UNITS
79© ZIV Aplicaciones y Tecnología S. A.
jXSL2 jXL2-jXC
jXSR2
V2
I2IF
REVERSE FAULT
I2
)22(22 jXSRjXLIV ++++⋅⋅⋅⋅====−−−−
QCOMPKI 67_2 ⋅⋅⋅⋅
¡Attention with reverse faults!: do not overcompensate Vpolarization
2267_ XSRXLK QCOMP ++++<<<<
DIRECTIONAL UNITS
80© ZIV Aplicaciones y Tecnología S. A.
For ground or negative sequence directional O/C (67 N/67Q)
Permissive underreach transfer trip (PUTT)
Direct transfer trip (DTT)
Permissive overreach transfer trip (POTT)
Directional comparison unblocking (DCUB)
Directional comparison blocking (DCB)
User defined (programmable logic)
Echo and week infeed tripping
Transient blocking for current reversal
O/C PROTECTION SCHEMES
81© ZIV Aplicaciones y Tecnología S. A.
OPEN PHASE DETECTOROnly operates with series faults (broken conductor)
Independent from load current (I2/I1 ratio)
82© ZIV Aplicaciones y Tecnología S. A.
Includes logic to check voltages on both sides of t he breaker. Setting options that allow reclose or manu al close:
Dead line/live bus
Live line/dead bus
Dead line/dead bus
In case of live line/live bus three conditions can be checked:
Voltage magnitudes difference
Voltage angles difference
Frequency difference
Compensation for the breaker closing time
Synchronism for two breakers
SYNCHROCHECK UNIT
83© ZIV Aplicaciones y Tecnología S. A.
SYNCHROCHECK UNIT
84© ZIV Aplicaciones y Tecnología S. A.
Current detection levels and timers are independent for single and three phase trips
Breaker failure pick ups initiated by single pole t rips include phase segregated current detectors and time rs
Non overcurrent breaker failure detection ( trips from overvoltage, frequency, Buchholz etc)
Retrip command (single/three phase)
Initiation by external protection trip: single/thre e pole
Breaker arc detection
Supervision of two breakers
BREAKER FAILURE
85© ZIV Aplicaciones y Tecnología S. A.
BREAKER FAILURE
86© ZIV Aplicaciones y Tecnología S. A.
TRIP LOGIC
Can trip single pole for a single phase to ground f ault with:
Any distance zone
Accelarated overreaching zone
Instantaneous ground or negative sequence unit 1
Accelarated overreaching overcurrent units
Includes the following inputs:
Programmable trip
Trip Blocking
Pole n (n=A, B, C) trip blocking
Three pole trip preparation blocking
87© ZIV Aplicaciones y Tecnología S. A.
RECLOSER
Single/three pole reclose
4 reclosing modes: 1p, 3p, 1p/3p and dependent
Up to three reclose cycles
Can operate with external protections
Internal or external synchronism check
Programmable recloser initiation masks
Can control two breakers
Independent timers for single and three pole recloses
88© ZIV Aplicaciones y Tecnología S. A.
RECLOSER
89© ZIV Aplicaciones y Tecnología S. A.
Breaker supervision:
Excessive number of trips
Maintenance (accumulated kA 2)
Supervision of trip and/or close circuits (up to 6)
Pole discrepancy detector
SUPERVISION
90© ZIV Aplicaciones y Tecnología S. A.
BREAKER AND A HALF FUNCTIONALITY
B1
B2
L1
52-1
52-2
I1
I2
ILÍNE=I1+I2
L2
IA2 IB2 IC2
IA1 IB1 IC1VA VB VC
VSINC2
VSINC1
91© ZIV Aplicaciones y Tecnología S. A.
Programmable directional unit
Stub bus protection more secure for CT saturation
2 breaker failure units
2 synchrocheck units
2 coordinated reclosers
Supervision (accumulated kA N) for 2 breakers
BREAKER AND A HALF FUNCTIONALITY
92© ZIV Aplicaciones y Tecnología S. A.
CT-2
CT-1
WEAK SOURCE
STRONG SOURCE
I-2
I-LINEI-1
Directional unit more stable for CT saturation duri ng external faults (created with the programmable logic)
I-2 I-1
I-LINE
WITHOUT CT-1 SATURATION
NEW DIRECTIONAL UNIT
-90º<arg(I-1)-arg(I-2)<90º
ZL
I-2 I-1
I-LINE
WITH CT-1 SATURATION
NEW DIRECTIONAL UNIT
93© ZIV Aplicaciones y Tecnología S. A.
TI-2
TI-1
I-2
I-1
STUB BUS PROTECTION
89-L1
L1
WITHOUT CT SATURATION: I LINE=0
WITH CT SATURATION: I LINE≠0
2
21 −+− II
LÍNEAI
IMINα
Overcurrent unit only in operation when the line is olator opens
Retraint by through –fault current
ZONA DE OPERACIÓN
ZONA DE NO OPERACIÓN
94© ZIV Aplicaciones y Tecnología S. A.
BREAKER FAILURE
B1
B2
L1
52-1
52-2
I1
I2
L2
52-3
52-1 failure
B1 Open and intertrip
Detection with I1
52-2 failure
52-3 open and intertrip
Detection with I2
95© ZIV Aplicaciones y Tecnología S. A.
SYNCHROCHECK UNIT
Position 89-2
89-1
89-2
B1
B2
L1
L2
B1
B2
89-B1 89-B2
Position 89-B1 Position 89-B2
Breaker and a half Double busbar
52-B1
52-B2
52-0 52
VA VB VC
VSINC2
VSINC1
VSINC1 VSINC2
VA VB VC IN-1 IN-2
96© ZIV Aplicaciones y Tecnología S. A.
RECLOSER
Possibility for sequencial reclosing to avoid closing onto fault both breakers
Selection of the master and slave reclosers
Permission / blocking of the slave recloser when the master one is blocked
Blocking of the recloser associated to a manually open breaker
B1
B2
L1
52-1
52-2
I1
I2
L2
52-3