96
1 © ZIV Aplicaciones y Tecnología S. A. Distance Protection

ZLV

Embed Size (px)

DESCRIPTION

Crompton

Citation preview

Page 1: ZLV

1© ZIV Aplicaciones y Tecnología S. A.

Distance Protection

Page 2: ZLV

2© ZIV Aplicaciones y Tecnología S. A.

PROTECTION FUNCTIONS

Function Description21+21N Distance protection for phase and ground faults

50Sup Overcurrent for distance monitoring

Load encroachment logic

Protection schemes for distance elements

Fuse failure detector

Close onto fault logic

Remote breaker open detector

Dead Line Detector

68/78 Power swing blocking and/or tripping (out of step t ripping)

25 Synchronism check

79 3-pole/1-pole recloser

50BF Breaker failure protection

Page 3: ZLV

3© ZIV Aplicaciones y Tecnología S. A.

Function Description46 Open phase detector

49 Thermal image protection

50F Three phase instantaneous overcurrent elements (A,B ,C)

50N Three ground instantaneous overcurrent elements

50Q Three negative sequence instantaneous elements

51F Three phase time delay overcurrent elements (A,B,C)

51N Three ground time delay overcurrent elements

51Q Three negative sequence time delay overcurrent elem ents

67 Phase directional unit (A,B,C)

67N Ground directional unit

67Q Negative sequence directional unit

Protection schemes for 67N/67Q

PROTECTION FUNCTIONS

Page 4: ZLV

4© ZIV Aplicaciones y Tecnología S. A.

Function Description50STUB Stub bus protection

59 Three phase overvoltage elements (A,B,C)

27 Three phase undervoltage elements (A,B,C)

59N Two ground overvoltage elements

81M Three overfrequency elements

81m Three underfrequency elements

81D Three rate of frequency change elements

Single/three pole tripping for 21+21N and 67N/67Q

Suitable for cables and overheadlines with series capacitor compensation

Mutual coupling compensation for parallel lines

PROTECTION FUNCTIONS

Page 5: ZLV

5© ZIV Aplicaciones y Tecnología S. A.

DescriptionBreaker supervision

Fault locator (compensates for load flow and mutual coupling)

Trip masks for distance zones or for auxiliary units

Programmable logic (executed each 2 ms)

Oscillography with analog and digital signals

Records: events, fault reports and metering logs

Measurement

Control

Communications

User interface (alphanumeric display and keypad/pro grammable push bottons for operations or commands)

Integrated simulator

ADITIONAL FUNCTIONS

Page 6: ZLV

6© ZIV Aplicaciones y Tecnología S. A.

4 x V + 5 x I ó 5 x V + 8 x I (depending on the mod el)

1 alarm output (watchdog)

Digital inputs (all programmable):

10 in 2 U box

22 in 3 U box

34 in 4 U box

37 in 6 U box

Outputs (all programmable and strong: anyone can be used as trip / close output)

10 in 2 U box (4 can be fast for teleprotection)

23 in 3 U box (4 can be fast for teleprotection)

36 in 4 U box (4 can be fast for teleprotection)

44 in 6 U box (4 can be fast for teleprotection)

Connectors with ring lugs

INPUTS / OUTPUTS

Page 7: ZLV

7© ZIV Aplicaciones y Tecnología S. A.

5 distance zones (all reversible)

6 independent measuring elements for each zone

Impedance reaches, resistive reaches and time delay s independent for ground and phase units

Selectable characteristic independent for phase and ground faults:

Mho (dynamic and variable)

Quadrilateral

Both combined (AND / OR)

Reaches (Z1) and zero sequence compensation factors (K0=Z0/Z1) independent for each zone in module and a ngle

DISTANCE PROTECTION

Page 8: ZLV

8© ZIV Aplicaciones y Tecnología S. A.

Dynamic characteristic (memory action):

Variable characteristic (V1 action):

Advantages of polarizing with V1M:

Proper operation for zero voltage three phase faults and for voltage inversions (series compensation)

Proper operation for zero voltage single phase and two-phase faults

MHO CHARACTERISTIC

Page 9: ZLV

9© ZIV Aplicaciones y Tecnología S. A.

ZSLESL ZL

V1IX ⋅⋅⋅⋅

IR⋅⋅⋅⋅

IZSL⋅⋅⋅⋅

IX ⋅⋅⋅⋅

IR⋅⋅⋅⋅

IZLZSR ⋅⋅⋅⋅++++ )(

V1F1

ZSR

F2

IF2

V2

IF1

F1

IrelayIF2F2V1

IF1=Irelay

F1V1F2V2

-jXC

MHO CHARACTERISTIC

Page 10: ZLV

10© ZIV Aplicaciones y Tecnología S. A.

V

φ

Ieq1

V

φ

1M

IX ⋅

IR ⋅)( cargaIIeqZSL φ−⋅

111 ZIeq ⋅

RFIF ⋅F F’

I

1M

IX ⋅

IR ⋅

F F’

Vφ φ

Vφ φ

φ φ

)( cargaIIZSL φφφφ −⋅

2

RFIF ⋅φφ

Z11⋅Iφφ

PHASE-GROUND FAULTS [ ] φφ VnZnKIIFop −⋅−⋅+= 1)10(0

MVFpol 1φ=

( ) ( )[ ] 90ºFpolargFopargº90 ≤−≤−

PHASE-PHASE FAULTSφφφφ VnZIFop −⋅= 1

MVFpol 1φφ=

MHO CHARACTERISTIC

Page 11: ZLV

11© ZIV Aplicaciones y Tecnología S. A.

QUADRILATERAL CHARACTERISTIC

θθθθ1

Zr

Directional unit

Reactance element (load and non homogeneity compensation)

Resistive limiters

Page 12: ZLV

12© ZIV Aplicaciones y Tecnología S. A.

REACTANCE ELEMENT

SINGLE PHASE TO GROUND FAULT

Z1SL Z1SRESLA ESRA

Z1SL Z1SRESLB ESRB

Z1SL Z1SRESLC ESRC

ZSN ZSN’ZN

Z1LF Z1LF’

Z1LF Z1LF’

Z1LF Z1LF’

ZN’

Ic

Ib

Ia

Ic’

Ib’

Ia’IFa

RF

RFIFaLFZIeqVa ⋅+⋅= 1 ( )100 −⋅+= KIIaIeq

VaVbVc

Page 13: ZLV

13© ZIV Aplicaciones y Tecnología S. A.

PHASE-PHASE (TO GROUND) FAULT

2/1 RFIFabLFZIeqVab ⋅+⋅= IbIaIabIeq −==

Z1SL Z1SRESLA ESRA

Z1SL Z1SRESLB ESRB

Z1SL Z1SRESLC ESRC

Z1LF Z1LF’

Z1LF Z1LF’

Z1LF Z1LF’

Ic

Ib

Ia

Ic’

Ib’

Ia’

VaVbVc

RF/2

RF/2 RgIFb

IFa

IFbIFaIFab −=

REACTANCE ELEMENT

Page 14: ZLV

14© ZIV Aplicaciones y Tecnología S. A.

IF RF⋅

VrIeq Z LF⋅ 1

Ieq

αααα

Z1FIeq ⋅IX ⋅

IR ⋅

RFIFLFZIeqVr ⋅+⋅= 1 RFIeq

IFLFZZr ⋅+= 1

ZrZ1LF

ααααZ1FX

R

RFIeq

IF ⋅ Fr

F

ERROR

F

Fr

REACTANCE ELEMENT

Page 15: ZLV

15© ZIV Aplicaciones y Tecnología S. A.

α α α α depends onLOAD FLOW

HOMOGENEITY

0≈αLOAD FLOW AND HOMOGENEOUS SYSTEM

FORWARD LOAD FLOW 0<αREVERSE LOAD FLOW 0>α

NO LOAD FLOW AND NON HOMOGENOUS SYSTEM

NO LOAD FLOW AND HOMOGENOUS SYSTEM

REACTANCE ELEMENT

( )Z1LF Z1SLα arg

Z1L Z1SL Z1SR

+=

+ +

Page 16: ZLV

16© ZIV Aplicaciones y Tecnología S. A.

LOAD FLOW AND HOMOGENOUS SYSTEM

F

Z1F

α

Fr

ZrZ1LF

R

X

Underreaching effect ( α>0) Overreaching effect ( α<0)

F

Z1F Fr

Zr

Z1LF

R

X

RFIeq

IF ⋅RF

Ieq

IF ⋅α

Ieq

Fpol

Avoid

Ieq

Fpol

Avoid

Fpol parallel to IF

2φIFpol =

pfIIFpol φφφφ −=

Single line to ground fault

Phase-phase fault (with or without ground)

pfIIFpol φφ −=

REACTANCE ELEMENT

Page 17: ZLV

17© ZIV Aplicaciones y Tecnología S. A.

NO LOAD FLOW AND NON HOMOGENOUS SYSTEM

Fpol NON parallel to IF (angle= α)

Faults at 100% γ = α

Zr

Z1LF

α

Z1F

X

R

RFIeq

IF ⋅

Ieq

Fpol

F

Fr

REACTANCE ELEMENT

( )Z1LF Z1SLα arg

Z1L Z1SL Z1SR

+=

+ +

γ

Tilting angle is introduced

( )Z1L Z1SLarg

Z1L Z1SL Z1SRγ

+=

+ +

Page 18: ZLV

18© ZIV Aplicaciones y Tecnología S. A.

Ieq1

Z11

α C1

C2

Fpol

F

F’

α

⋅Ieq1

I φ

IX ⋅

IR ⋅

RF⋅IF

FopZ11

αC1

C2

Fpol

V

F

F’

α

I

φφI

φφ

φφ

IX ⋅

IR ⋅

Fop

2/IF RF⋅φφ

[ ] φφ VnZnKIIFop −⋅−⋅+= 1)10(0 φφφφ VnZIFop −⋅= 1

2φIFpol = pfIIFpol φφ −= pfIIFpol φφφφ −=

REACTANCE ELEMENT

PHASE-GROUND FAULTS PHASE-PHASE FAULTS

( ) ( )[ ] 180ºFpolargFoparg0 ≤−−≤ γ

Page 19: ZLV

19© ZIV Aplicaciones y Tecnología S. A.

Dynamic line (memory action):

Variable line (V1 action):

Advantages of polarizing with V1M:

Proper operation for zero voltage three phase faults and for voltage inversions (series compensation)

Proper operation for zero voltage single phase and two-phase faults

DIRECTIONAL UNIT

Page 20: ZLV

20© ZIV Aplicaciones y Tecnología S. A.

IX ⋅⋅⋅⋅

IR ⋅⋅⋅⋅

DIRECTIONAL UNIT

IX ⋅⋅⋅⋅

IR⋅⋅⋅⋅V1F1 IrelayIF2

F2V1

IF1=Irelay

F1V1 F2V2

IZSL⋅⋅⋅⋅

IZLZSR ⋅⋅⋅⋅++++ )(

ZSLESL ZL

V1

ZSR

F2

IF2

IF1

F1

-jXC

V2

Page 21: ZLV

21© ZIV Aplicaciones y Tecnología S. A.

( ) ( ) ( )[ ] ( )αα −≤−≤+− º90argargº90 FpolFop

DIRECTIONAL UNIT

PHASE-GROUND FAULTS PHASE-PHASE FAULTS

V

φ

V

φ

1M

IX ⋅

IR ⋅

α

)( cargaIIeqZSL φ−⋅

C3

F

V

I

V 1M

I

IX ⋅

IR ⋅

α

φ φ

φ φ

φ φ

φ φ

)( cargaIIZSL φφφφ −⋅

C3

F

φIFop= φφIFop=MVFpol 1φ= MVFpol 1φφ=

Page 22: ZLV

22© ZIV Aplicaciones y Tecnología S. A.

φφ VRGnIFop −⋅= RGnIFpol ⋅= φ φφφφ VRPnIFop −⋅= RPnIFpol ⋅= φφ

[ ])arg()arg( IeqnInbucle −−== φθθθ nθθ =

RESISTIVE LIMITER

PHASE-GROUND FAULTS PHASE-PHASE FAULTS

C4

V

F’

Z11⋅Ieq1

Ieq1

φ

IX ⋅

IR ⋅

F

11θ

1bucθ

RFIF ⋅

1RGI ⋅φ

C4

V

F’Z11⋅

I

IX ⋅

IR ⋅

F

11θ

φφ

φφ

Iφφ 2

RFIF ⋅φφ

1RPI ⋅φφ

( ) ( ) ( )[ ] θθ ≤−≤+− FpolFop argargº90

Page 23: ZLV

23© ZIV Aplicaciones y Tecnología S. A.

QUADRILATERAL: PHASE-GROUND FAULTS

Page 24: ZLV

24© ZIV Aplicaciones y Tecnología S. A.

QUADRILATERAL: PHASE-PHASE FAULTS

Page 25: ZLV

25© ZIV Aplicaciones y Tecnología S. A.

Based on angle between Ia2 and Ia1 fault currents

For faults with zero sequence infeed uses phase undervoltage units

Allows:

Single pole tripping on single-phase-ground faults

Blocking leading phase on phase-phase-ground faults

For phase-phase-ground faults the lagging phase-ear th loop can not be blocked: helps phase-phase loop in some kind of faults

PHASE SELECTOR

Page 26: ZLV

26© ZIV Aplicaciones y Tecnología S. A.

( ) ( )f_1Iaarg2Iaarg −=φ

InIa ⋅> 05.02 %101

2 >Ia

IaInIa ⋅> 05.00 %8

1

0 >Ia

Ia

PHASE-PHASE FAULT GROUND FAULT

PHASE SELECTOR

Page 27: ZLV

27© ZIV Aplicaciones y Tecnología S. A.

PHASE-PHASE-GROUND FAULTS

Z1LF

Z1LF

RF

Rg

IFbIFa

RF

IFT

A

B

ZN

Va Vb

Ib

Ia

Z1LF

Z1LF

RF

IFbIFa

RF

IFT

A

B

ZN

Va Vb

Ib

Ia

ABG FAULT:AG unit overreachesBG unit underreaches

AG BG FAULT:AG and BG units operate correctly

The AB unit can be complemented with the BG unit

Page 28: ZLV

28© ZIV Aplicaciones y Tecnología S. A.

FAULT DETECTOR

Sequence currents increment detection ( ∆I0, ∆Ia1, ∆Ia2)

Sequence currents levels exceeded (I0, Ia2)

Sealed-in by operation of distance units, overcurre nt units, close onto fault detector and stub bus protection

Supervises the tripping produced by distance units, overcurrent units, close onto fault detector, stub bus protection and remote breaker open detector

Determines the fault inception time (allows the sel ection of prefault and postfault values: current and voltage)

Page 29: ZLV

29© ZIV Aplicaciones y Tecnología S. A.

FAULT DETECTOR

Page 30: ZLV

30© ZIV Aplicaciones y Tecnología S. A.

α1α1α1α1α2α2α2α2

R1R2

X

R

R: minimum Rloadα: minimum PF

LOAD ENCROACHMENT

Page 31: ZLV

31© ZIV Aplicaciones y Tecnología S. A.

Activation when:

Phase undervoltage units pick-up without

activation of fault detector

Input coming from MCB activates

Inhibited when any pole is open

Can block distance elements, weak infeed trip,

synchronism, dead line detector and voltage units

FUSE FAILURE DETECTOR

Page 32: ZLV

32© ZIV Aplicaciones y Tecnología S. A.

FUSE FAILURE DETECTOR

Page 33: ZLV

33© ZIV Aplicaciones y Tecnología S. A.

Detects what pole of the breaker has opened

Detection based on breaker contacts plus undercurre nt

detectors

Outputs used by phase selector, distance units, fau lt

detector, power swing detector, fuse failure detect or,

ground and negative sequence overcurrent units, rec loser,

etc

OPEN POLE DETECTOR

Page 34: ZLV

34© ZIV Aplicaciones y Tecnología S. A.

OPEN POLE DETECTOR

Page 35: ZLV

35© ZIV Aplicaciones y Tecnología S. A.

OPEN POLE DETECTOR

Page 36: ZLV

36© ZIV Aplicaciones y Tecnología S. A.

DISTANCE UNITS OPERATION

SINGLE PHASE UNITS

Page 37: ZLV

37© ZIV Aplicaciones y Tecnología S. A.

DISTANCE UNITS OPERATION

PHASE-PHASE UNITS

Page 38: ZLV

38© ZIV Aplicaciones y Tecnología S. A.

DEAD LINE DETECTOR

Operated based on undervoltage and undercurrent uni ts

Only applicable when the VT is on the line side

Allows detecting the breaker closing without the ne ed from

external contacts

Can be used to activate the close onto fault functi on

Page 39: ZLV

39© ZIV Aplicaciones y Tecnología S. A.

Activated with manual close or reclose commands:

internal or external

Phase overcurrent units with second harmonic

restraint ( inrush stabilization)

Zone 1 extension:

Always activated for close commands

Adjustable for reclose commands

CLOSE ONTO FAULT DETECTOR

Page 40: ZLV

40© ZIV Aplicaciones y Tecnología S. A.

CLOSE ONTO FAULT DETECTOR

Page 41: ZLV

41© ZIV Aplicaciones y Tecnología S. A.

X

R

Stable oscillation

Unstable oscillation

A

ZONE INT

ZONE MED

ZONE EXT

δ

ZB

ZA

ZL

Slow trip

Fast trip

T

POWER SWING DETECTOR

Page 42: ZLV

42© ZIV Aplicaciones y Tecnología S. A.

Selectable zones to be blocked

Unblocking of blocked distance zones when a fault is

detected:

Ground or phase-phase fault detection (phase select or)

Time the impedance remain inside the external zone

Tripping for unstable swings: slow/fast trip

POWER SWING DETECTOR

Page 43: ZLV

43© ZIV Aplicaciones y Tecnología S. A.

POWER SWING DETECTOR

Page 44: ZLV

44© ZIV Aplicaciones y Tecnología S. A.

Basic Scheme:

Stepped distance

Schemes without communication channel:

Zone 1 extension

Remote breaker open detector

DISTANCE PROTECTION SCHEMES

Page 45: ZLV

45© ZIV Aplicaciones y Tecnología S. A.

Schemes with communication channel:

Permissive underreach transfer trip ( PUTT)

Direct transfer trip ( DTT)

Permissive overreach transfer trip ( POTT)

Directional comparison unblocking ( DCUB)

Directional comparison blocking ( DCB)

User defined (programmable logic)

Binary information transmission (virtual inputs/out puts)

DISTANCE PROTECTION SCHEMES

Page 46: ZLV

46© ZIV Aplicaciones y Tecnología S. A.

DISTANCE PROTECTION SCHEMES

Complementary logics:

Echo and weak infeed trip logic

Transient blocking for current reversal (parallel lines)

Page 47: ZLV

47© ZIV Aplicaciones y Tecnología S. A.

STEPPED DISTANCE

Independent timers for phase and ground faults

Timers do not drop out for evolving faults

Blocking signals coming from:

Power swing detector

Fuse failure detector

Series compensated lines logic

Page 48: ZLV

48© ZIV Aplicaciones y Tecnología S. A.

STEPPED DISTANCE

Page 49: ZLV

49© ZIV Aplicaciones y Tecnología S. A.

ZONE 1 EXTENSION

Zone 1 extended to overreaching zone (zone 2 or 3)

Requires fast reclosing to restore the supply as fa st as

possible

Inhibited when the breaker opens; enabled again whe n

the breaker remains closed for a settable time

Avoids zone 1 extension when reclosing

Page 50: ZLV

50© ZIV Aplicaciones y Tecnología S. A.

ZONE 1 EXTENSION

Page 51: ZLV

51© ZIV Aplicaciones y Tecnología S. A.

PUTT

Carrier sending by zone 1 (underreaching)

Settable carrier time

Can be complemented by weak infeed logic (trip)

Optional carrier sending by open breaker

Blocking signals coming from:

Power swing detector

Digital input

Page 52: ZLV

52© ZIV Aplicaciones y Tecnología S. A.

PUTT

Page 53: ZLV

53© ZIV Aplicaciones y Tecnología S. A.

DTTSimilar to PUTT but with direct trip by carrier rec eption

Settable carrier time

Settable security time to avoid erroneous operation s

due to noise in the communication channel

Optional carrier sending by open breaker

Blocking signals coming from:

Power swing detector (only blocks carrier sending)

Digital input

Page 54: ZLV

54© ZIV Aplicaciones y Tecnología S. A.

DTT

Page 55: ZLV

55© ZIV Aplicaciones y Tecnología S. A.

POTTCarrier sending by overreaching zone

Settable carrier time

Can be complemented by weak infeed (echo or

echo+trip) and current reversal logics

Optional carrier sending by open breaker

Blocking signals coming from:

Power swing detector

Digital input

Page 56: ZLV

56© ZIV Aplicaciones y Tecnología S. A.

POTT

Page 57: ZLV

57© ZIV Aplicaciones y Tecnología S. A.

DCUBSimilar to POTT but allows instantaneous tripping f or a

time window (150 ms) even if the carrier is lost

Requires frequency-shifted PLC equipment

Settable carrier time

Can be complemented by weak infeed (echo or echo+tr ip) and current reversal logics

Optional carrier sending by open breaker

Blocking signals coming from:

Power swing detector

Digital input

Page 58: ZLV

58© ZIV Aplicaciones y Tecnología S. A.

DCUB

Page 59: ZLV

59© ZIV Aplicaciones y Tecnología S. A.

DCBCarrier sending by reverse zone (zone 4 or zone 5) or non-

directional overcurrent units (fast carrier sending )

Settable time delay for overreaching zone operation

Implicit current reversal logic

Carrier stop input / output

Blocking signals (inhibite tripping and generate ca rrier) coming from:

Power swing detector

Digital input

Page 60: ZLV

60© ZIV Aplicaciones y Tecnología S. A.

DCB

Page 61: ZLV

61© ZIV Aplicaciones y Tecnología S. A.

WEAK INFEED LOGIC

Selectable logic output: NON, ECHO or ECHO+TRIP

Settable security time to avoid erroneous echo send ings

due to noise in the communication channel

Implicit current reversal logic

Settable voltage threshold for weak infeed trip

Phase selector based on undervoltage units

Optional weak infeed trip blocking by fuse failure detector

Page 62: ZLV

62© ZIV Aplicaciones y Tecnología S. A.

WEAK INFEED LOGIC

Page 63: ZLV

63© ZIV Aplicaciones y Tecnología S. A.

CURRENT REVERSAL LOGIC

Can be applied in any permissive overreaching schem e

Blocking signal for overreaching zone is activated b y

reverse zone (zone 4 or zone 5) pick-up

Settable blocking time delay

Page 64: ZLV

64© ZIV Aplicaciones y Tecnología S. A.

CURRENT REVERSAL LOGIC

Page 65: ZLV

65© ZIV Aplicaciones y Tecnología S. A.

REMOTE BREAKER OPEN DETECTOR

Allows zone 2 instantaneous tripping once the remote

breaker is detected as open (three-phase):

Loss of load (undercurrent detectors)

Capacitive current detection (long lines)

( ) ( ) ( )[ ] ( )δφφδ +≤−≤− º90argargº90 VI

Page 66: ZLV

66© ZIV Aplicaciones y Tecnología S. A.

REMOTE BREAKER OPEN DETECTOR

Page 67: ZLV

67© ZIV Aplicaciones y Tecnología S. A.

OVERCURRENT UNITSPhase, ground and negative sequence / instantaneous and

time delayed

Selectable torque control: non-directional / forwar d / reverse

Selectable directional unit (torque control type)

Torque control disable input

Time delay reset input

Blocking signals coming from:

Digital input

Open pole detectors (ground and negative sequence units)

Series compensated lines logic

Page 68: ZLV

68© ZIV Aplicaciones y Tecnología S. A.

PHASE INSTANTANEOUS

OVERCURRENT UNITS

Page 69: ZLV

69© ZIV Aplicaciones y Tecnología S. A.

GROUND INSTANTANEOUS

OVERCURRENT UNITS

Page 70: ZLV

70© ZIV Aplicaciones y Tecnología S. A.

NEGATIVE SEQUENCE

INSTANTANEOUS OVERCURRENT UNITS

Page 71: ZLV

71© ZIV Aplicaciones y Tecnología S. A.

PHASE TIME-DELAYED

OVERCURRENT UNITS

Page 72: ZLV

72© ZIV Aplicaciones y Tecnología S. A.

GROUND TIME-DELAYED

OVERCURRENT UNITS

Page 73: ZLV

73© ZIV Aplicaciones y Tecnología S. A.

NEGATIVE SEQUENCE

TIME-DELAYED OVERCURRENT UNITS

Page 74: ZLV

74© ZIV Aplicaciones y Tecnología S. A.

Phase directional units:

Polarized by quadrature memory phase-phase voltage

Ground directional units:

Polarized by zero-sequence voltage

Polarized by current coming from an earth clamp

Negative sequence directional units:

Polarized by negative sequence voltage

Distance zone 2 can act as directional unit for o/c

Two setting options available in case of loss of po larization (can be applied to fuse failure ): blocking/permission

DIRECTIONAL UNITS

Page 75: ZLV

75© ZIV Aplicaciones y Tecnología S. A.

DIRECTIONAL UNITS

Page 76: ZLV

76© ZIV Aplicaciones y Tecnología S. A.

Polarization voltage compensator factor for ground and negative sequence directional units:

)67_00(_ 67_67 NANGKIVPOLF NCOMPN ∠⋅+−=

)67_22(_ 67_67 QANGKIVPOLF QCOMPQ ∠⋅+−=

Applications:

Increase polarization voltage: makes it higher than minimum level for polarization (strong zero/negative sequence sources)

Invert polarization voltage: compensates inversions in series compensated lines

DIRECTIONAL UNITS

Page 77: ZLV

77© ZIV Aplicaciones y Tecnología S. A.

ZA0 ZB0p x ZL0 (1-p) x ZL0

IF

I0

V0

ZA0 ZB0 ZL0

IF

I0

V0

-V0

I0

COMP_67NKI0 ⋅ ANG_67N

Forward

Reverse

)0(00 IZAV −⋅= 0)00(0 IZBZLV ⋅+=Forward fault Reverse fault

DIRECTIONAL UNITS

Page 78: ZLV

78© ZIV Aplicaciones y Tecnología S. A.

jXSL2 jmXL2-jXC

j(1-m)XL2 jXSR2

V2

I2 IF

I2

)2(22 jXCjXSLIV −−−−⋅⋅⋅⋅====−−−−

22 jXSLI ⋅⋅⋅⋅

)(2 jXCI −−−−⋅⋅⋅⋅

QCOMPKI 67_2 ⋅⋅⋅⋅FORWARD FAULT

Negative sequence voltage inversion if, with line side CT : XC>XSL2

Vpolarization CompensationXCK QCOMP >>>>67_

DIRECTIONAL UNITS

Page 79: ZLV

79© ZIV Aplicaciones y Tecnología S. A.

jXSL2 jXL2-jXC

jXSR2

V2

I2IF

REVERSE FAULT

I2

)22(22 jXSRjXLIV ++++⋅⋅⋅⋅====−−−−

QCOMPKI 67_2 ⋅⋅⋅⋅

¡Attention with reverse faults!: do not overcompensate Vpolarization

2267_ XSRXLK QCOMP ++++<<<<

DIRECTIONAL UNITS

Page 80: ZLV

80© ZIV Aplicaciones y Tecnología S. A.

For ground or negative sequence directional O/C (67 N/67Q)

Permissive underreach transfer trip (PUTT)

Direct transfer trip (DTT)

Permissive overreach transfer trip (POTT)

Directional comparison unblocking (DCUB)

Directional comparison blocking (DCB)

User defined (programmable logic)

Echo and week infeed tripping

Transient blocking for current reversal

O/C PROTECTION SCHEMES

Page 81: ZLV

81© ZIV Aplicaciones y Tecnología S. A.

OPEN PHASE DETECTOROnly operates with series faults (broken conductor)

Independent from load current (I2/I1 ratio)

Page 82: ZLV

82© ZIV Aplicaciones y Tecnología S. A.

Includes logic to check voltages on both sides of t he breaker. Setting options that allow reclose or manu al close:

Dead line/live bus

Live line/dead bus

Dead line/dead bus

In case of live line/live bus three conditions can be checked:

Voltage magnitudes difference

Voltage angles difference

Frequency difference

Compensation for the breaker closing time

Synchronism for two breakers

SYNCHROCHECK UNIT

Page 83: ZLV

83© ZIV Aplicaciones y Tecnología S. A.

SYNCHROCHECK UNIT

Page 84: ZLV

84© ZIV Aplicaciones y Tecnología S. A.

Current detection levels and timers are independent for single and three phase trips

Breaker failure pick ups initiated by single pole t rips include phase segregated current detectors and time rs

Non overcurrent breaker failure detection ( trips from overvoltage, frequency, Buchholz etc)

Retrip command (single/three phase)

Initiation by external protection trip: single/thre e pole

Breaker arc detection

Supervision of two breakers

BREAKER FAILURE

Page 85: ZLV

85© ZIV Aplicaciones y Tecnología S. A.

BREAKER FAILURE

Page 86: ZLV

86© ZIV Aplicaciones y Tecnología S. A.

TRIP LOGIC

Can trip single pole for a single phase to ground f ault with:

Any distance zone

Accelarated overreaching zone

Instantaneous ground or negative sequence unit 1

Accelarated overreaching overcurrent units

Includes the following inputs:

Programmable trip

Trip Blocking

Pole n (n=A, B, C) trip blocking

Three pole trip preparation blocking

Page 87: ZLV

87© ZIV Aplicaciones y Tecnología S. A.

RECLOSER

Single/three pole reclose

4 reclosing modes: 1p, 3p, 1p/3p and dependent

Up to three reclose cycles

Can operate with external protections

Internal or external synchronism check

Programmable recloser initiation masks

Can control two breakers

Independent timers for single and three pole recloses

Page 88: ZLV

88© ZIV Aplicaciones y Tecnología S. A.

RECLOSER

Page 89: ZLV

89© ZIV Aplicaciones y Tecnología S. A.

Breaker supervision:

Excessive number of trips

Maintenance (accumulated kA 2)

Supervision of trip and/or close circuits (up to 6)

Pole discrepancy detector

SUPERVISION

Page 90: ZLV

90© ZIV Aplicaciones y Tecnología S. A.

BREAKER AND A HALF FUNCTIONALITY

B1

B2

L1

52-1

52-2

I1

I2

ILÍNE=I1+I2

L2

IA2 IB2 IC2

IA1 IB1 IC1VA VB VC

VSINC2

VSINC1

Page 91: ZLV

91© ZIV Aplicaciones y Tecnología S. A.

Programmable directional unit

Stub bus protection more secure for CT saturation

2 breaker failure units

2 synchrocheck units

2 coordinated reclosers

Supervision (accumulated kA N) for 2 breakers

BREAKER AND A HALF FUNCTIONALITY

Page 92: ZLV

92© ZIV Aplicaciones y Tecnología S. A.

CT-2

CT-1

WEAK SOURCE

STRONG SOURCE

I-2

I-LINEI-1

Directional unit more stable for CT saturation duri ng external faults (created with the programmable logic)

I-2 I-1

I-LINE

WITHOUT CT-1 SATURATION

NEW DIRECTIONAL UNIT

-90º<arg(I-1)-arg(I-2)<90º

ZL

I-2 I-1

I-LINE

WITH CT-1 SATURATION

NEW DIRECTIONAL UNIT

Page 93: ZLV

93© ZIV Aplicaciones y Tecnología S. A.

TI-2

TI-1

I-2

I-1

STUB BUS PROTECTION

89-L1

L1

WITHOUT CT SATURATION: I LINE=0

WITH CT SATURATION: I LINE≠0

2

21 −+− II

LÍNEAI

IMINα

Overcurrent unit only in operation when the line is olator opens

Retraint by through –fault current

ZONA DE OPERACIÓN

ZONA DE NO OPERACIÓN

Page 94: ZLV

94© ZIV Aplicaciones y Tecnología S. A.

BREAKER FAILURE

B1

B2

L1

52-1

52-2

I1

I2

L2

52-3

52-1 failure

B1 Open and intertrip

Detection with I1

52-2 failure

52-3 open and intertrip

Detection with I2

Page 95: ZLV

95© ZIV Aplicaciones y Tecnología S. A.

SYNCHROCHECK UNIT

Position 89-2

89-1

89-2

B1

B2

L1

L2

B1

B2

89-B1 89-B2

Position 89-B1 Position 89-B2

Breaker and a half Double busbar

52-B1

52-B2

52-0 52

VA VB VC

VSINC2

VSINC1

VSINC1 VSINC2

VA VB VC IN-1 IN-2

Page 96: ZLV

96© ZIV Aplicaciones y Tecnología S. A.

RECLOSER

Possibility for sequencial reclosing to avoid closing onto fault both breakers

Selection of the master and slave reclosers

Permission / blocking of the slave recloser when the master one is blocked

Blocking of the recloser associated to a manually open breaker

B1

B2

L1

52-1

52-2

I1

I2

L2

52-3