GeneralSpecifications
Yokogawa Electric Corporation2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan
Model FLXA212-Wire AnalyzerPROFIBUS PA Communication
GS 12A01A02-72E
n GeneralPROFIBUS is a vendor-independent and open fieldbus based on the international standard IEC61158 and IEC61784. It covers a wide range of applications in manufacturing and process automation fields.Vendor-independence and openness allow communication between devices of different manufactures with no special interface adjustment.FLXATM21 PROFIBUS PA model offers more flexible instrumentation through a higher level communication capability and proposes the cost reduction by multidrop wirings with fewer cables.
In the FLXA21 Human Machine Interface (HMI), 2-wire type analyzer FLXA21 offers easy touch screen operation and simple menu structure in 12 languages. Menus of display, execution and setting are displayed in a selected language.The analyzer FLXA21 automatically recognizes the installed sensor module and prepares the necessary menus for right configuration.For immediate measurement, the FLXA21 offers quick setup functionality. The quick setup screen appears when the analyzer is powered. Only a few setups – date/time, language, basic sensor configurations and output – will start the measurement.
The FLXA21 offers the best accuracy in measurement with temperature compensation functionality and calibration functionality. Sensor diagnostics and sensor wellness indication make measurement reliable. Logbook of events and diagnostic data is a useful information source for maintenance.
n Features• Interoperability PROFIBUSPAspecificationsgranttheinteroperabilityofthefieldinstrumentswithoutpreparingdesignatedsoftwarefortheinstrument.
•Multi-sensingfunction FLXA21PROFIBUSPAmodel,hasthreeindependentAIfunctionblocks.
• Alarm function FLXA21 PROFIBUS PA model securely supports variousalarmfunctions,suchashigh/lowalarm,noticeofblockerror,etc.basedonPROFIBUSspecifications.
•Self-diagnosticfunction Areliableself-diagnosticfunctionbasedontheNAMURNE107standarddetectsfailuresinthehardwareofpH/ORPsensor,conductivitysensor,andcommunications.
•2kindsofmeasurements;pH/ORP,Conductivity(SC)•SimpleHMImenustructurein12languages• Quick setup menu for immediate measurement•Indicationofsensorwellness
• Supported tools DTM for FieldMate EDD for SIEMENS SIMATIC PDM
GS 12A01A02-72E©CopyrightFeb2015
10thEditionJul.06,2021
FLEXA,FLXAaretrademarksorregisteredtrademarksofYokogawaElectricCorporation.Allothercompanyandproductnamesmentionedinthisdocumentaretrademarksorregisteredtrademarksoftheirrespectivecompanies.WedonotuseTMor®marktoindicatethosetrademarksorregisteredtrademarksinthisdocument.
2
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 12A01A02-72E
nGeneralSpecifications1. Basic■ MeasurementObject/SensorType
• pH/Oxidation-reductionPotential(pH/ORP)• Conductivity(SC)Note: Theavailablemeasurementobjectdependsona
sensormoduleinstalledontheanalyzer.■ AnalyzerStructure
Module structure●CompositionofAnalyzerOne(1)HousingassemblyOne(1)Sensormodule
2. Measurement2-1. pH/Oxidation-reductionPotential(pH/ORP)■ InputSpecificationDualhighimpedanceinput(≥1012Ω)
■ InputRangepH: -2to16pHORP: -1500to1500mVrH: 0to100rHTemperature:
Pt1000: -30 to 140 ºCPt100: -30 to 140 ºC6k8: -30to140ºCPTC10k: -30 to 140 ºCNTC8k55: -10to120ºC3k Balco: -30 to 140 ºCPTC500: -30to140ºC
■ Performance(Accuracy)(Thespecificationsareexpressedwithsimulatedinputs.)pH
Linearity: ±0.01pHRepeatability:±0.01pHAccuracy:±0.01pH
ORPLinearity: ±1mVRepeatability:±1mVAccuracy:±1mV
TemperaturewithPt1000,6k8,PTC10k,NTC8k55,3kBalco,
PTC500Repeatability:±0.1ºCAccuracy:±0.3ºC
withPt100Linearity: ±0.4ºCRepeatability:±0.1ºCAccuracy:±0.4ºC
2-2. Conductivity(SC)■ InputSpecificationTwoorfourelectrodesmeasurementwithsquarewaveexcitation,usingmax60m(200ft)cable(WU40/WF10)andcellconstantsfrom0.005to50.0cm-1
■ InputRangeConductivity:
min.: 0µS/cmmax.: 200mSx(Cellconstant) (overrange2000mS/cm)
Resistivity:min.: 0.005kΩ/(Cellconstant)max.: 1000MΩxcm
Temperature:Pt1000: -20to250ºCPt100: -20 to 200 ºCNi100: -20 to 200 ºCNTC8k55: -10to120ºCPb36(JISNTC6k): -20to120ºC
■ Performance(Accuracy)(Thespecificationsareexpressedwithsimulatedinputs.)Conductivity
Morethan2µSxKcm-1to200mSxKcm-1
Accuracy:±0.5%ofreading1µSxKcm-1to2µSxKcm-1
Accuracy:±1%ofreadingResistivity
0.005kΩ/Kcm-1tolessthan0.5MΩ/Kcm-1
Accuracy:±0.5%ofreading0.5MΩ/Kcm-1to1MΩ/Kcm-1
Accuracy:±1%ofreadingTemperature
withPt1000,Pb36,Ni100Accuracy:±0.3ºC
withPt100,NTC8k55Accuracy:±0.4ºC
Temperature compensationNaCltable: ±1%Matrix: ±3%
Stepresponse: 90%(<2decades)in7seconds(ofreadingonthedisplay)
Note: "K"meanscellconstant. YOKOGAWAprovidesconductivitysensorsofwhich
cellconstantsare0.1to10cm-1.
3. Electrical■ OutputSignalDigitalcommunicationsignalbasedonPROFIBUSPAprotocol.
■ CommunicationRequirements:SupplyVoltage: 9to32VDCCurrentDraw: 24mA(max)BusconnectionandFieldbuscabletypeaccordingtorecommendationbasedonIEC1158-2.
■ FunctionalSpecifications:FunctionalspecificationsforPROFIBUScommunicationconformtothePROFIBUSPAVer3.02.GSDfile: Theactualfilecanbedownloadedfrom
www.profibus.com■ FunctionBlock:ThreeAIblocks
■ DisplayLCDwithatouchscreen: Black/White:213x160pixelsContrastadjustmentavailableonthetouchscreenMessagelanguage: 12(English,Chinese,Czech,French,
German, Italian,Japanese,Korean,Polish,Portuguese,RussianandSpanish)
Oneanalyzerhasall12languages.Note: Descriptionforaselectionoflanguageand
languagenamesarewritteninEnglish.Note: OnlyEnglishalphabetandnumericareavailable
foratagnumber,anadditionaldescriptionforeachvalueonthedisplayscreenandpasswords.
Note: Onlyformessagelanguageonthescreen,12languagesareprovided.
Jul.06,2021-00
3
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 12A01A02-72E
4. Mechanicalandothers■ HousingCase: Plastic(Polycarbonate)Casecolor:Silvergray(equivalenttoMunsell
3.2PB7.4/1.2)Window: Polycarbonate(flexible)Protection:IP66(exceptCanada),NEMAType 4X
(USA),CSAType3S/4X(Canada)■ Plate
Main name plate: inside case coverRegulationplate:onthecaseoutside
■ CableandTerminalCable size:
Outer diameter:6to12mm(suitableforM20cablegland)3.4to7mm(groundingcable)
Terminalscrewsize:M4 torqueofscrewup:1.2N•mWire terminal: Pinterminal,ringterminalandspade
terminalcanbeusedforanalyzer’spowersupplyterminalsandsensorterminals.
Pinterminal:pindiameter:max.1.9mm Ringandspadeterminal:width:max.7.8mm
■ CableEntry3holes,M20cableglandx3pcs,Sleevex1pc(forgroundingcableline)Note: Cableglandandplugaredeliveredwithananalyzer,
butnotassembledintotheanalyzer.■ MountingMountinghardware(option): •Universalmountingkit(Note) •Pipeandwallmountinghardware •PanelmountinghardwareNote: Thiskitcontainsthepipeandwallmounting
hardwareandthepanelmountinghardware.Hood(option): • Stainless steel • Stainlesssteelwithurethanecoating • Stainlesssteelwithepoxycoating
■ StainlessSteelTagPlateWhentheadditionalcode“/SCT”withatagnumberisspecified,thetagplateonwhichthetagnumberisinscribedisdeliveredwiththeanalyzer.Tagplateishangingtype.
■ ConduitAdapterUsingoptionaladapter • G1/2(quantity:4) • 1/2NPT (quantity:4) •M20x1.5 (quantity:4)Theseconduitadaptersaredeliveredwithananalyzer,butnotassembledintotheanalyzer.
■ SizeofHousingCase144x144x151mm(WxHxD)(withoutcablegland)
■ WeightApprox.1kg
■ AmbientOperatingTemperature-20to+55ºC
■ StorageTemperature-30 to +70 ºC
■ Humidity10to90%RHat40ºC(Non-condensing)
n RegulatoryCompliance■ Safety,EMCandRoHSComplianceSafety: UL61010-1 UL61010-2-030 CAN/CSA-C22.2No.61010-1 CAN/CSA-C22.2No.61010-2-030 EN61010-1 EN61010-2-030EMC: EN61326-1ClassA,Table2(Forusein
industriallocations) EN61326-2-3 EN61326-2-5 RCM:EN61326-1ClassA,Table2 KoreaElectromagneticConformity
Standard Class A 한국 전자파적합성 기준
RoHS: ENIEC63000(Style3.06andlater)Installation altitude: 2000 m or lessCategorybasedonIEC61010:I(Note1)PollutiondegreebasedonIEC61010:2(Note2)Note1:Installationcategory,calledover-voltagecategory,
specifiesimpulsewithstandvoltage. Equipmentwith"CategoryI"(ex.twowire
transmitter)isusedforconnectiontocircuitsinwhichmeasuresaretakentolimittransientover-voltagestoanappropriatelylowlevel.
Note2:Pollutiondegreeindicatesthedegreeofexistenceofsolid,liquid,gasorotherinclusionswhichmayreducedielectricstrength.Degree2isthenormalindoorenvironment.
InformationoftheWEEEDirective Thisproductispurposelydesignedtobe
usedinalargescalefixedinstallationsonlyand,therefore,isoutofscopeoftheWEEEDirective.TheWEEEDirectivedoesnotapply. TheWEEEDirectiveisonlyvalidintheEU.
Jul.06,2021-00
4
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 12A01A02-72E Jul.06,2021-00
■ ExplosionProtectedTypeCompliance
Item Description ‘Type’inMScode
Europe(ATEX)
[Intrinsicsafety“ia”]ApplicableStandard: ENIEC60079-0,EN60079-11CertificateNo: DEKRA11ATEX0109XMarking/Rating: II1GExiaIICT4Ga,FISCOfielddeviceAmbientTemperature: -20to55°CPowerSupply/Signals: Seethecontroldrawing.Electricalparameters: Seethecontroldrawing.Dielectricstrength: 500Va.c.r.m.s.between -Supplyterminalsandtheearthterminal -theterminalsofMeasuringModulesexcludingPH,SCandISCandtheearthterminal -SupplyterminalsandtheterminalsofMeasuringModules -theterminalsofMeasuringModule1andtheterminalsofMeasuringModule2 700Vd.c.between -theterminalsofPH,SCandISCMeasuringModulesandtheearthterminalSpecificconditionsofuse: Electrostaticchargesonthenon-metallicorcoatedpartsofthetwowireanalyzershallbeavoided.
SincetheenclosureoftheModelFLXA202ismadeofaluminium,ifitismountedinanareawheretheuseofEPLGa(category1G)equipmentisrequired,itshallbeinstalledsuchthat,evenintheeventofrareincidents,ignitionsourcesduetoimpactandfrictionsparksareexcluded.
On-siteassembling: SeeUse’sManualIM12A01A03-01EN.Installationanderection:Seethecontroldrawing.Maintenance and Repair: Warning:Amodificationoftheequipmentwouldnolongercomplywiththeconstructiondescribedinthe
certificatedocumentation. OnlypersonnelauthorizedbyYokogawaElectricCorporationcanrepairtheequipment.
ControlDrawing: Referto(1)
-CB
International(IECEx)
[Intrinsicsafety“ia”]ApplicableStandard: IEC60079-0,IEC60079-11CertificateNo: IECExDEK11.0044XMarking/Rating: ExiaIICT4Ga,FISCOfielddeviceAmbientTemperature: -20to55°CPowerSupply/Signals: Seethecontroldrawing.Electricalparameters: Seethecontroldrawing.Dielectricstrength: 500Va.c.r.m.s.between -Supplyterminalsandtheearthterminal -theterminalsofMeasuringModulesexcludingPH,SCandISCandtheearthterminal -SupplyterminalsandtheterminalsofMeasuringModules -theterminalsofMeasuringModule1andtheterminalsofMeasuringModule2 700Vd.c.between -theterminalsofPH,SCandISCMeasuringModulesandtheearthterminalSpecificconditionsofuse: Electrostaticchargesonthenon-metallicorcoatedpartsofthetwowireanalyzershallbeavoided.
SincetheenclosureoftheModelFLXA202ismadeofaluminium,ifitismountedinanareawheretheuseofEPLGa(category1G)equipmentisrequired,itshallbeinstalledsuchthat,evenintheeventofrareincidents,ignitionsourcesduetoimpactandfrictionsparksareexcluded.
On-siteassembling: SeeUse’sManualIM12A01A03-01EN.Installationanderection:Seethecontroldrawing.Maintenance and Repair: Warning:Amodificationoftheequipmentwouldnolongercomplywiththeconstructiondescribedinthe
certificatedocumentation. OnlypersonnelauthorizedbyYokogawaElectricCorporationcanrepairtheequipment.
ControlDrawing: Referto(1)
5
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 12A01A02-72E
Item Description ‘Type’inMScode
UnitedStates(FM)
[Intrinsicallysafe/Nonincendive]ApplicableStandard: FM3600,FM3610,FM3611,FM3810,NEMA250,ANSI/ISA60079-0,
ANSI/ISA60079-11,ANSI/UL121201,ANSI/ISA61010-1CertificateNo: FM20US0046XMarking/Rating: ISCLI,DIV1,GPABCDCLI,ZN0,AExiaIIC
NICLI,DIV2,GPABCDCLI,ZN2IIC FISCOfielddevice
T4:forambienttemperature:-20to55°CEnclosure: Type 4XPowerSupply/Signals: Seethecontroldrawing.Battery: No replaceable batteryElectricalparameters: Seethecontroldrawing.Dielectricstrength: 500VAC,r.m.s.between -Supplyterminalsandtheearthterminal -theterminalsofMeasuringModulesexcludingPH,SCandISCandtheearthterminal -SupplyterminalsandtheterminalsofMeasuringModules -theterminalsofMeasuringModule1andtheterminalsofMeasuringModule2 700VDCbetween -theterminalsofPH,SCandISCMeasuringModulesandtheearthterminalSpecificconditionsofuse: Seethecontroldrawings.On-siteassembling: SeeUse’sManualIM12A01A03-01EN.Installationanderection: Seethecontroldrawing.Maintenance and Repair: Warning:Amodificationoftheequipmentwouldnolongercomplywiththeconstructiondescribedinthe
certificatedocumentation. OnlypersonnelauthorizedbyYokogawaElectricCorporationcanrepairtheequipment.
ControlDrawing: Referto(3)
-CD
Canada(CSA)
[Intrinsicallysafe/Nonincendive]ApplicableStandard: C22.2No.0,CAN/CSA-C22.2No.94,C22.2No.213,CAN/CSA-C22.2
No.60079-0,CAN/CSA-C22.2No.60079-11,CAN/CSA-C22.2No.61010-1,CAN/CSA-C22.2No.61010-2-030
CertificateNo: 2425510Marking/Rating: ExiaIICT4Ga,FISCOfielddevice
Intrinsically safe for Class I, Division 1, Groups A, B, C, D, T4 Nonincendive for Class I, Division 2, Groups A, B, C, D, T4
AmbientTemperature: -20to55°CAmbientHumidity: 0–100%(NoCondensation)Enclosure: IP66,NEMA4XPowerSupply/Signals: Seethecontroldrawing.Battery: No replaceable batteryElectricalparameters: Seethecontroldrawing.Dielectricstrength: 500VAC,r.m.s.between -Supplyterminalsandtheearthterminal -theterminalsofMeasuringModulesexcludingPH,SCandISCandtheearthterminal -SupplyterminalsandtheterminalsofMeasuringModules -theterminalsofMeasuringModule1andtheterminalsofMeasuringModule2 700VDCbetween -theterminalsofPH,SCandISCMeasuringModulesandtheearthterminalSpecificconditionsofuse: Seethecontroldrawings.On-siteassembling: SeeUse’sManualIM12A01A03-01EN.Installationanderection: Seethecontroldrawing.Maintenance and Repair: Warning:Amodificationoftheequipmentwouldnolongercomplywiththeconstructiondescribedinthe
certificatedocumentation. OnlypersonnelauthorizedbyYokogawaElectricCorporationcanrepairtheequipment.
ControlDrawing: Referto(2)
Jul.06,2021-00
6
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 12A01A02-72E Jul.06,2021-00
Item Description ‘Type’inMScode
UnitedStates(FM)
[Nonincendive]ApplicableStandard: FM3600,FM3611,FM3810,NEMA250,ANSI/UL121201,ANSI/ISA61010-1CertificateNo: FM20US0046XMarking/Rating: NICLI,DIV2,GPABCDZN2IICT4:forambienttemperature:-20to55°CEnclosure: Type 4XPowerSupply/Signals: Seethecontroldrawing.Battery: No replaceable batteryElectricalparameters: Seethecontroldrawing.Dielectricstrength: 500VAC,r.m.s.between -Supplyterminalsandtheearthterminal -theterminalsofMeasuringModulesexcludingPH,SCandISCandtheearthterminal -SupplyterminalsandtheterminalsofMeasuringModules -theterminalsofMeasuringModule1andtheterminalsofMeasuringModule2 700VDCbetween -theterminalsofPH,SCandISCMeasuringModulesandtheearthterminalSpecificconditionsofuse: Seethecontroldrawings.On-siteassembling: SeeUse’sManualIM12A01A03-01EN.Installationanderection: Seethecontroldrawing.Maintenance and Repair: Warning:Amodificationoftheequipmentwouldnolongercomplywiththeconstructiondescribedinthe
certificatedocumentation. OnlypersonnelauthorizedbyYokogawaElectricCorporationcanrepairtheequipment.
ControlDrawing: Referto(3)
-DD
Canada(CSA)
[Nonincendive]ApplicableStandard: C22.2No.0,CAN/CSA-C22.2No.94,C22.2No.213,CAN/CSA-C22.2
No.61010-1,CAN/CSA-C22.2No.61010-2-030CertificateNo: 2425510Marking/Rating: NonincendiveforClassI,Division2,GroupsA,B,C,D,T4AmbientTemperature: -20to55°CAmbientHumidity: 0–100%(NoCondensation)Enclosure: IP66,NEMA4XPowerSupply/Signals: Seethecontroldrawing.Battery: No replaceable batteryElectricalparameters: Seethecontroldrawing.Dielectricstrength: 500VAC,r.m.s.between -Supplyterminalsandtheearthterminal -theterminalsofMeasuringModulesexcludingPH,SCandISCandtheearthterminal -SupplyterminalsandtheterminalsofMeasuringModules -theterminalsofMeasuringModule1andtheterminalsofMeasuringModule2 700VDCbetween -theterminalsofPH,SCandISCMeasuringModulesandtheearthterminalSpecificconditionsofuse: Seethecontroldrawings.On-siteassembling:SeeUse’sManualIM12A01A03-01EN.Installationanderection:Seethecontroldrawing.Maintenance and Repair: Warning:Amodificationoftheequipmentwouldnolongercomplywiththeconstructiondescribedinthe
certificatedocumentation. OnlypersonnelauthorizedbyYokogawaElectricCorporationcanrepairtheequipment.
ControlDrawing: Referto(2)China(NEPSI)
[Intrinsicsafety“ia”]ApplicableStandard: GB3836.1-2010,GB3836.4-2010,GB3836.20-2010CertificateNo: GYJ18.1051XMarking/Rating: ExiaIICT4Ga,FISCOfielddeviceAmbientTemperature: -20to55°CControlDrawing: Referto(4)
-CH
Korea(KOSHA)
[Intrinsicsafety“ia”]ApplicableStandard: NoticeofMinistryofLaborNo.2016-54CertificateNo: 15-AV4BO-0160XMarking/Rating: ExiaIICT4,FISCOfielddeviceAmbientTemperature: -20to55°CControlDrawing: Referto(4)
-EG
7
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 12A01A02-72E Jul.06,2021-00
■ ControlDrawings(1) ATEXandIECEx Intrinsicsafety“ia”
Yokogawa Electric Corporation
Model
FLXA21
Title Control draw
ing (FOU
ND
ATION
Fieldbus / PROFIBU
S PA type)
No.
IKE039-A32
Page1
Revision0
Date
2019-10-18
N
otes: 1.
The associated apparatus must be a linear source or a FISCO
power supply.
2.Sensor 1 m
ay be simple apparatus or intrinsically safe apparatus.
3.W
hen accessing the display window
or other non-metallic parts of the enclosure of FLXA21,
take the following m
easures to minim
ize the risk of explosion from electrostatic discharges, in
addition to avoiding any actions that cause the generation of electrostatic charges, such as rubbing w
ith a dry cloth.
To avoid electrostatic charge on the operator, -
Earth the operator through a wrist-strap, or
-O
perate FLXA21 on the conductive floors, wearing anti-static w
ork clothes and electrostatic safety shoes, or
-N
eutralize the operator and FLXA21 by a static elimination bar w
hich has a metal part
earthed through resistor from 100k
to 100M.
In case that those measures cannot be taken or static electricity cannot be suppressed, bring a
gas detector and make sure there is no ignition capable atm
osphere around FLXA21 before the operation.
Supply +, Supply –
FISCO field device, or the follow
ing parameters
U
i: 24 V
Ii: 250 mA
Pi: 1.2 W
Ci: 2.72 nF
Li: 0 mH
M
easuring Module 1
Type of M
easuring Module
pH, SC, D
OISC
SENCO
M
Uo
11.76 V11.76 V
5.36 V Io
116.5 mA
60.6 mA
106.16 mA
Po 0.3424 W
0.178 W0.1423 W
Co
100 nF100 nF
31 F
Lo 1.7 m
H8 m
H0.45 m
H
Non-hazardous Area
Hazardous Ares
Supply ++
Associated Apparatus
–Supply –
Housing Assem
bly
Measuring M
odule 1
FLXA21 Series Analyzer
Sensor 1 T
T
Terminators
Other
Field Devices
���������������������� �
����������������������������
���������������������
���������������
������������������������������������
8
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 12A01A02-72E
(2) FM Intrinsicsafety,NonincendiveM
odel: FLEX
A Series D
ate: April 17, 2015
Rev.2: D
ec. 26, 2019 D
oc. No.: IFM
039-A72 P.1
Yokogawa E
lectric Corporation
Control draw
ing (FOU
ND
ATION
Fieldbus / PROFIBU
S PA type) Installation for D
ivision 1 / Zone 0, 1 Applicable m
odels: FLXA21-D
-x-x-CD-xx-xx-F-..., FLXA21-D
-x-x-CD-xx-xx-P-…
Unclassified Location
Hazardous (Classified) Location
Class I, Division 1, G
roups A, B, C, D, or
Class I, Zone 0, 1, Group IIC
Temperature Class: T4
Measuring M
odule 1 (Note 8):
Type of M
easuring Module
pH, SC, D
O
ISCSEN
COM
Uo
11.76 V 11.76 V
5.36 VIo
116.5 mA
60.6 mA
106.16 mA
Po 0.3424 W
0.178 W
0.1423 WCo
100 nF 100 nF
31 F
Lo 1.7 m
H
8 mH
0.45 mH
Specific condition of use -
Precautions shall be taken to minim
ize the risk of non-metallic parts and painted parts of
the enclosure. When the equipm
ent is used in hazardous locations, avoid any action which
generates electrostatic discharge such as rubbing with a dry cloth.
FLXA21 Analyzer
Supply +, Supply –(N
ote 5):
FISCO field device
or
U
i: 24 V
Ii: 250 mA
Pi: 1.2 W
Ci: 2.72nF
Li: 0 mH
Supply ++
Associated Apparatus(N
ote 4, 5) –
Supply –
Housing Assem
bly
Measuring M
odule 1Sensor 1 (N
ote 8)
TT
Terminators
Other
Field Devices
Model: FLE
XA Series
Date: A
pril 17, 2015 R
ev.3: Dec. 26, 2019
Doc. N
o.: IFM039-A
72 P.2
Yokogaw
a Electric C
orporation
Unclassified Location
Installation for Division 2 / Zone 2
Applicable models:
FLXA21-D-x-x-CD
-xx-xx-F-..., FLXA21-D-x-x-CD
-xx-xx-P-…
FLXA21-D
-x-x-DD
-xx-xx-F-..., FLXA21-D-x-x-D
D-xx-xx-P-…
Hazardous (Classified) Location
Class I, Division 2, G
roups A, B, C, D, or
Class I, Zone 2, Group IIC,
Temperature Class: T4
Measuring M
odule 1(N
ote 8):
Type of Measuring M
odulepH
, SC, DO
ISC
SENCO
MU
o 11.76 V
11.76 V5.36 V
Io 116.5 m
A 60.6 m
A106.16 m
APo
0.3424 W
0.178 W0.1423 W
Co 4
F 4
F31
FLo
4.5 mH
19 m
H0.45 m
H
Supply ++
Control Equipment
(Note 9)
–Supply –
Housing Assem
bly
Measuring M
odule 1
FLXA21 Analyzer
Sensor 1 (N
ote 8)
TT
Terminators
Other
Field Devices
Supply +, Supply –(N
ote 9):
Ui: 24 V
Ci: 2.72 nF
Li: 0 m
H
Specific condition of use: -
Precautions shall be taken to minim
ize the risk of non-metallic parts and painted parts o f
the enclosure. When the equipm
ent is used in hazardous locations, avoid any action which
generates electrostatic discharge such as rubbing with a dry cloth.
Jul.06,2021-00
9
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 12A01A02-72E
Model: FLE
XA Series
Date: M
ay 29, 2017 R
ev. D
oc. No.: IFM
039-A72 P.3
Yokogaw
a Electric C
orporation
Notes:
1. N
o revision to this drawing w
ithout prior approval of FM.
2. Installation m
ust be in accordance with the N
ational Electric Code (NFPA 70),
ANSI/ISA-RP12.06.01 and relevant local codes.
3. FISCO
installation must be in accordance w
ith ANSI/U
L-60079-25. 4.
The associated apparatus must be FM
-approved. 5.
The associated apparatus must be a FISCO
power supply or a linear source m
eeting the follow
ing conditions. U
o (or Voc) ≤ Ui
Io (or Isc) ≤ Ii Po ≤ Pi Co (or Ca) ≥ Ci + Ccable Lo (or La) ≥ Li + Lcable
6. Control equipm
ent connected to the associated apparatus must not use or generate a voltage
which exceeds U
m of the associated apparatus.
7. The control draw
ing of the associated apparatus must be follow
ed when installing the
equipment.
8. W
hen installed in Division 1, Zone 0 or Zone 1, Sensor 1 m
ay be a simple apparatus or an
intrinsically safe apparatus meeting the conditions below.
W
hen installed in Division 2 or Zone 2, Sensor 1 m
ay be a simple apparatus or a nonincendive
field wiring apparatus m
eeting the conditions below, or alternatively, it may be equipm
ent suitable for D
ivision 2 or Zone 2 respectively, if a suitable wiring m
ethod other than nonincendive field w
iring is employed.
Ui (or Vm
ax) ≥ Uo
Ii (or Imax) ≥ Io
Pi ≥ Po Ci ≤ Co – Ccable Li ≤ Lo – Lcable
9. The control equipm
ent must be an FM
-approved FISCO pow
er supply, FNICO
power supply or
an associated nonincendive field wiring apparatus m
eeting the conditions below. Alternatively, it m
ay be general-purpose equipment, if a suitable w
iring method other than nonincendive field
wiring is em
ployed. U
o (or Voc) ≤ Ui
Co (or Ca) ≥ Ci + Ccable Lo (or La) ≥ Li + Lcable
10. WARN
ING
– POTEN
TIAL ELECTROSTATIC CH
ARGIN
G H
AZARD – W
HEN
THE
EQU
IPMEN
T IS USED
IN H
AZARDO
US LO
CATION
S, AVOID
ANY ACTIO
N W
HICH
G
ENERATE ELECTRO
STATIC DISCH
ARGE SU
CH AS RU
BBING
WITH
A DRY CLO
TH.
11. WARN
ING
– IN TH
E CASE WH
ERE THE EN
CLOSU
RE OF TH
E ANALYZER IS M
ADE O
F ALU
MIN
UM
, IF IT IS MO
UN
TED IN
ZON
E 0, IT MU
ST BE INSTALLED
SUCH
THAT, EVEN
IN
THE EVEN
T OF RARE IN
CIDEN
TS, IGN
ITION
SOU
RCES DU
E TO IM
PACT AND
FRICTIO
N SPARK
S ARE EXCLUD
ED
12. W
ARNIN
G – SU
BSTITUTIO
N O
F COM
PON
ENTS M
AY IMPAIR IN
TRINSIC SAFETY AN
D
SUITABITLITY FO
R DIVISIO
N 2 / ZO
NE 2.
Jul.06,2021-00
10
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 12A01A02-72E Jul.06,2021-00
(3) CSA Intrinsicsafety,NonincendiveM
odel: FLXA
21 / FLXA
202 D
ate: May 29, 2017
Rev.
Doc. N
o.: ICS032-A
72 P.1
Yokogawa E
lectric Corporation
Control draw
ing (FOU
ND
ATION
Fieldbus / PRO
FIBU
S PA type) Installation for Zone 0, 1 / D
ivision 1 Applicable m
odels: FLXA21-D
-x-x-CD-xx-xx-F-..., FLXA21-D
-x-x-CD-xx-xx-P-…
Non-hazardous Area
Hazardous Area
Class I, Zone 0, 1, Group IIC, or
Class I, Division 1, G
roups A, B, C, D
Temperature Class: T4
Measuring M
odule 1 (Note 6):
Type of M
easuring Module
pH, SC, D
O
ISC SEN
COM
U
o 11.76 V
11.76 V 5.36 V
Io 116.5 m
A 60.6 m
A 106.16 m
A Po
0.3424 W
0.178 W
0.1423 W
Co 100 nF
100 nF 31 μF
Lo 1.7 m
H
8 mH
0.45 m
H
Specific condition of use -
Electrostatic charges on the non-metallic or coated parts of the tw
o wire analyzer shall be
avoided.
Supply + + Associated Apparatus
(Note 3)
–Supply –
Housing Assem
bly
Measuring M
odule 1
FLXA21 Analyzer
Sensor 1 (N
ote 6)
T T Term
inators
Other
Field Devices
Supply +, Supply – (Note 3):
FISCO
field device
or
Ui: 24 V
Ii: 250 m
A
Pi: 1.2 W
Ci: 2.72nF
Li: 0 m
H
Model: FLX
A21 / FLX
A202
Date: M
ay 29, 2017 R
ev. D
oc. No.: IC
S032-A72 P.2
Yokogaw
a Electric C
orporation
Installation for Zone 2 / Division 2
Applicable models:
FLXA21-D-x-x-CD
-xx-xx-F-..., FLXA21-D-x-x-CD
-xx-xx-P-…
FLXA21-D
-x-x-DD
-xx-xx-F-..., FLXA21-D-x-x-D
D-xx-xx-P-…
Specific condition of use -
Electrostatic charges on the non-metallic or coated parts of the tw
o wire analyzer shall be
avoided. M
easuring Module 1 (N
ote 6):
Type of Measuring M
odule pH
, SC, DO
ISC
SENCO
M
Uo
11.76 V 11.76 V
5.36 V Io
116.5 mA
60.6 mA
106.16 mA
Po 0.3424 W
0.178 W
0.1423 W
Co
100 nF 100 nF
31 μF Lo
1.7 mH
8 m
H
0.45 mH
Non-hazardous Area
Hazardous Area
Class I, Zone 2, Group IIC, or
Class I, Division 2, G
roups A, B, C, D
Temperature Class: T4
Supply + +
Control Equipment
(Note 7)
–Supply –
Housing Assem
bly
Measuring M
odule 1
FLXA21 Analyzer
T T Term
inators
Other
Field Devices
Supply +, Supply – (Note 7):
U
i: 24 V
Ci: 2.72 nF
Li: 0 mH
Sensor 1 (N
ote 6)
11
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 12A01A02-72E Jul.06,2021-00
Model: FLX
A21 / FLX
A202
Date: M
ay 29, 2017 R
ev. D
oc. No.: IC
S032-A72 P.3
Yokogaw
a Electric C
orporation
Notes:
1. Installation m
ust be in accordance with the C
anadian Electric C
ode Part I (C22.1),
AN
SI/ISA-R
P12.06.01 and relevant local codes. 2.
FISCO
installation must be in accordance w
ith CA
N/C
SA-C
22.2 No. 60079-25.
3. The associated apparatus m
ust be a FISCO
power supply or a linear source m
eeting the follow
ing conditions. U
o (or Voc) ≤ Ui
Io (or Isc) ≤ Ii Po ≤ Pi Co (or Ca) ≥ Ci + Ccable Lo (or La) ≥ Li + Lcable
4. C
ontrol equipment connected to the associated apparatus m
ust not use or generate a voltage w
hich exceeds Um
of the associated apparatus. 5.
The control drawing of the associated apparatus m
ust be followed w
hen installing the equipm
ent. 6.
When installed in Zone 0 or 1, or D
ivision 1, Sensor 1 may be a sim
ple apparatus or an intrinsically safe apparatus m
eeting the conditions below. W
hen installed in Zone 2 or Division 2, Sensor 1 m
ay be a simple apparatus or a
non-incendive field wiring apparatus m
eeting the conditions below, or alternatively, it m
ay be equipment suitable for Zone 2 or D
ivision 2 respectively, if a suitable wiring
method other than non-incendive field w
iring is employed.
Ui (or Vm
ax) ≥ Uo
Ii (or Imax) ≥ Io
Pi ≥ Po Ci ≤ Co – Ccable Li ≤ Lo – Lcable
7. The control equipm
ent must be a FISC
O pow
er supply, FNIC
O pow
er supply or an associated non-incendive field w
iring apparatus meeting the conditions below.
Alternatively, it m
ay be general-purpose equipment, if a suitable w
iring method other
than non-incendive field wiring is em
ployed. U
o (or Voc) ≤ Ui
Co (or Ca) ≥ Ci + Ccable Lo (or La) ≥ Li + Lcable
8. W
AR
NIN
G – PO
TEN
TIAL E
LEC
TRO
STATIC C
HA
RG
ING
HA
ZAR
D
AVERTISSEMEN
T – DAN
GER PO
TENTIEL D
E CHARG
ES ÉLECTROSTATIQ
UES
9. W
AR
NIN
G – SU
BSTITU
TION
OF C
OM
PON
EN
TS MAY
IMPA
IR IN
TRIN
SIC SA
FETY
AVERTISSEM
ENT – LA SU
BSTITUTIO
N D
E COM
POSAN
TS PEUT CO
MPRO
METTRE LA
SÉCURITÉ IN
TRINSÉQ
UE.
10. WA
RN
ING
– SUB
STITUTIO
N O
F CO
MPO
NE
NTS M
AY IM
PAIR
SUITA
BILITY
FOR
ZO
NE
2 / DIV
ISION
2. AVERTISSEM
ENT –LA SU
BSTITUTIO
N D
E COM
POSAN
TS PEUT REN
DRE CE M
ATÉRIEL IN
ACCEPTABLE POU
R LES EMPLACEM
ENTS D
E ZON
E 2 / DIVISIO
N 2.
(4) NEPSIandKOSHA Intrinsicsafety“ia”(RefertoApp.(1)ATEXandIECExControlDrawing)
12
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 12A01A02-72E
nModel&SuffixCodesModel Suffixcode Optioncode Description
FLXA21 ······················································································· ················· 2-Wire Analyzer
Powersupply -D ················· Always-D
Housing -P ················· Plastic
Display -D ················· Anti-glareLCD
Type -AB-AD-AG-CB-CD-CH-EG-DD
········································································································································
General purpose for CE, RCMGeneral purpose for CSAGeneralpurposeforKCISforATEX,IECEx(Note1)(Note2)ISforFM,CSA(Note1)IS for NEPSI(Note1)ISforKOSHA(Note1)NI for FM, CSA(Note3)
1st input -P1-C1
··································
pH/ORPConductivity(SC)
2nd input -NN ················· Withoutinput
Output(Note4) -P ················· PROFIBUSPA
— -N ················· Always-N
Languageset(Note5) -LA ················· Englishand11languages
Country -N ················· GlobalexceptJapan
— -NN ················· Always-NN
Option Mountinghardware
Hood
TagplateConduit adapter
/UM/U/PM/H6/H7/H8/SCT/CB4/CD4/CF4
Universalmountingkit(Note6)PipeandwallmountinghardwarePanelmountinghardwareHood,stainlesssteelHood,stainlesssteel+urethanecoatingHood,stainlesssteel+epoxycoatingStainlesssteeltagplateConduitadapter(G1/2x4pcs)Conduitadapter(1/2NPTx4pcs)Conduitadapter(M20x1.5x4pcs)
Notes:1: Type“-CB”,“-CD”,“-CH”,“-EG”areintrinsicsafety(IS).2: ProductregistrationisdonebyYokogawaTaiwanCorporationasanimporterinTaiwan.3: Type“-DD”isnonincendive(NI).4: TheFLXA21hasanotheroutputtypeof“4-20mA+HART”(suffixcode:-A).RefertoGS12A01A02-01E.5: Theselanguagesaremessagelanguagesontheanalyzer’sdisplay. OneanalyzerhasEnglishand11languages. Alllanguagesareasfollows;English,Chinese,Czech,French,German,Italian,Japanese,Korean,Polish,Portuguese,
RussianandSpanish.6: Theuniversalmountingkitcontainsthepipeandwallmountinghardware(/U)andthepanelmountinghardware(/PM).
Jul.06,2021-00
13
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 12A01A02-72E
nDimensionsandMounting
44.9137
120.2
151
22.5 80
4-M6 depth 5For sensor 1 cable
For power supply
For grounding cable
137
80144
24.7
26.5
26.5
141144
FB4_01.ai
Unit: mm
ConduitAdapter(Optioncode:/CB4,/CD4,/CF4)
Adapter
49(1.93")
G1/2 screw (/CB4), 1/2 NPT screw (/CD4)M20x1.5 screw (/CF4)
Approx.55(2.2")
Packing
Unit: mm(inch)Nut
F0204.ai
Jul.06,2021-00
14
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 12A01A02-72E
(Note)Theuniversalmountingkit(/UM)containsthepipeandwallmountinghardware(/U)andthepanelmountinghardware(/PM).
Panelmountinghardware(Optioncode:/PM,/UM)
2-M5 length 35
185
178
100
195
135
Pan
el th
ickn
ess
1 to
12
Spacing panel cutout
4-M6 *
138+10
138
+1 0
FB4_03.ai
Unit: mm
*: Tighten the four screws to a torque of 2 N•m.
Wallmountinghardware(Optioncode:/U,/UM)
144 164
13
10070
144
224
200
50
15
For wall mounting3-ø10 holes
4-M6 *
FB4_02.ai
Unit: mm
*: Tighten the four screws to a torque of 2 N•m.
Note: Thewallonwhichtheanalyzerismountedshouldbestrongenoughtobeartheweightofmorethan8kg.
Pipemountinghardware(Optioncode:/U,/UM)
151
100
200
5017
4
144(205)
Pipe mounting (Horizontal) Pipe mounting (Vertical)
Pipe 50A(ø60.5)
M8 U-bolt
4-M6 *
FB4_04.ai
Unit: mm
*: Tighten the four screws to a torque of 2 N•m.
Jul.06,2021-00
15
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 12A01A02-72E
Stainlesssteelhood(Optioncode:/H6,/H7,/H8)184 220
(70)(100)
9144
144
7257
(50)
199
FB4_05.ai
Unit: mm
nWiringDiagrams
*2
*3
*4
n n n n n n n n n
+–
*1: Use a 2-wire shielded cable with an outside diameter of 6 to 12 mm.*2: Connect the analyzer to gland. (Class D ground: 100 ohm or less) Connect the grounding cable to the terminal of the power module inside. Use a cable with an outside diameter of 3.4 to 7 mm for the grounding line of the plastic housing. The minimum cross sectional area of the protective grounding cable should be 0.75 mm2.*3: Terminal numbers for each sensor module are shown below.*4: The terminal box may be necessary depending on the sensor cable length and the distance between the
analyzer and the sensor.
*1
WTB10 or BA10Terminal box
Coupler/Terminal
FLXA21 2-Wire AnalyzerPROFIBUS PA Communication
Sens
or
PH Module
SC Module
161519171318141211
PH
NC161514131211
SC
Jul.06,2021-00
16
All Rights Reserved. Copyright © 2015, Yokogawa Electric Corporation GS 12A01A02-72E
n InquirySpecificationsSheetforFLXA212-WireAnalyzer(PROFIBUSPACommunication)Makeinquiriesbyplacingcheckmarks()inthepertinentboxesandfillingintheblanks.1. GeneralInformation
Company name Contact Person; Department; Plant name; Measurement location; Purpose of use; Indication, Recording, Alarm, Control
2. MeasurementConditions(1)Processtemperature; to Normally [°C](2)Processpressure; to Normally [kPa](3)Flowrate; to Normally [l/min](4)Flowspeed; to Normally [m/s](5)Slurryorcontaminants; No, Yes(6)Nameofprocessfluid; (7)Componentsofprocessfluid; (8)Others;
3. InstallationSite(1)Ambienttemperature; to [°C](2)Location; Outdoors, Indoors(3)Others;
4. Requirements1st Input; pH/ORP Conductivity(SC)2nd Input; nWithout
4.1 pH/ORP(1)Measuringrange;pH0to14 ORP to mV (2)Systemconfigurationselection; Electrode, Holder,pHConverter,Cleaningsystem,Terminalbox, Accessories(3)Electrodecablelength; 3m, 5m, 7m, 10m, 15m, 20m, m(4)Electrodeoperatingpressure; 10 kPa or less, Morethan10kPa(5)Typeofholder; Guide pipe, Submersion, Flow-through, Suspension, Angledfloatingball,Verticalfloatingball(6)Cleaningmethod;Nocleaning,Ultrasoniccleaning,Jetcleaning,Brushcleaning(7)Sampletemperature;-5to105°C,-5to100°C,-5to80°C(8)Others;
4.2 Conductivity(1)Measuringrange; (2)Detector/sensor; SC4AJ Twoelectrodesystem(0.02cm-1)Twoelectrodesystem(0.1cm-1) SC8SG Twoelectrodesystem(0.01cm-1)Twoelectrodesystem(10cm-1), Fourelectrodesystem(10cm-1) SC210G Twoelectrodesystem(0.05cm-1)Twoelectrodesystem(5cm-1)(3)Detector/sensormountingmethod; SC4AJ Adaptermounting,Weldingsocket,Weldingclamp SC8SG Screw-in,Flow-through SC210G Screw-in,Flange,Flow-through,Screw-inwithgatevalve(4)Electrodecablelength; SC4AJ 3m, 5m, 10m, 20m SC8SG 5.5m, 10m, 20m SC210G 3m, 5m, 10m, 15m, 20m(5)Others;
Subjecttochangewithoutnotice.Jul.06,2021-00