4
18 YCME / YHME Series 2 Modular screw chillers and heat pumps YCME/YHME 0162HE to 0222HE A complete range from 160 kW up to 224 kW Modular concept Provide flexibility and achieve reliability Up to 8 modules in one water system brings important benefits. Achieve reliability Full redundancy – Safety first. Should a module fail, the remaining modules maintain operational continuity. Fully configurable units Increase the versatility Up to 60 different options and accessories make our chiller as unique as the project needs. Some of the most interesting are: Dual pump option Heat recovery option Sound attenuation compressor enclosure Example of module configurations

YCME / YHME Series 2 Modular screw chillers and heat pumps · 2019. 8. 28. · Modular screw chillers and heat pumps YCME/YHME 0162HE to 0222HE A complete range from 160 kW up to

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: YCME / YHME Series 2 Modular screw chillers and heat pumps · 2019. 8. 28. · Modular screw chillers and heat pumps YCME/YHME 0162HE to 0222HE A complete range from 160 kW up to

18

YCME / YHME Series 2Modular screw chillers and heat pumpsYCME/YHME 0162HE to 0222HEA complete range from 160 kW up to 224 kW

Modular conceptProvide flexibility and achieve reliabilityUp to 8 modules in one water system brings important benefits.

Achieve reliabilityFull redundancy – Safety first. Should a module fail, the remaining modules maintain operational continuity.

Fully configurable unitsIncrease the versatilityUp to 60 different options and accessories make our chiller as unique as the project needs.

Some of the most interesting are:

Dual pump option

Heat recovery option

Sound attenuation compressor enclosureExample of module configurations

Page 2: YCME / YHME Series 2 Modular screw chillers and heat pumps · 2019. 8. 28. · Modular screw chillers and heat pumps YCME/YHME 0162HE to 0222HE A complete range from 160 kW up to

YORK® AIR-CONDITIONING PRODUCTS

19

Modular screw chillers and heat pumpsYCME/YHME 0162HE to 0222HE

Manufacturer reserves the rights to change specifications without prior notice.

Widest operating range at highest efficiencyYCME/YHME Cooling operating rangeChilled water outlet temperature: -10°C to +30°CAmbient temperature: -15°C to +46°C

YHME Heating operating rangeHot water outlet temperature: +35°C to +55°CAmbient temperature: -10°C (WB) to +15.5°C (WB)

Two operating modes selectable at commissioning allow the installation’s performance to focus on either high efficiency or high accuracy outlet water temperature. Ambient temperature

High water temperature (option)

Standard

Brine (Low 3 option under development)

Brine(Low 1 option) (low 2 option)

-15

+30

+15

+5

-5

-10

+46 °C

°C

Chille

d w

ater

out

let t

empe

ratu

re

YCME Air-cooled Chiller Performance DataIndividual modules YCME0162HE YCME0182HE YCME0202HE YCME0222HE

Cooling capacity kW 159.6 179.6 204.5 224.4

Total power input kW 51.32 57.75 65.34 71.01

SEER 4.11 4.13 4.12 4.12

ŋs, c 161 162 162 162

Sound power level dB(A) 96 97 98 99

Dimensions (H x W x D) mm 2450 x 1955 x 2290 2450 x 1955 x 3230

Operating weight kg 1300 1340 1590 1680

Chilled Water Outlet (std, options Low / High) °C +5°C ~ +15°C, with Options -10°C ~ +5°C / +15°C ~ +30°C

Ambient Air Temperature °C -15°C ~ +46°C

Electrical Power Supply 3N - 400V 50Hz

YHME Air-cooled Heat Pump Performance DataIndividual modules YHME0162HE YHME0182HE YHME0202HE YHME0222HE

Cooling capacity kW 149.7 169.6 194.6 209.5

Total power input kW 51.09 57.88 65.97 70.3

Heating capacity kW 145.4 145.4 185.5 185.5

Total power input kW 51.56 51.56 65.32 65.32

SCOPMeet Ecodesign requirements

ŋs, h

Sound power level dB(A) 96 97 98 99

Dimensions (H x W x D) mm 2450 x 1955 x 2290 2450 x 1955 x 3230

Operating weight kg 1400 1420 1680 1760

Chilled Water Outlet (std, options Low / High) °C +5°C ~ +15°C, with Options -10°C ~ +5°C / +15°C ~ +30°C

Heated Water Outlet °C +35°C ~ +55°C

Ambient Air Temperature (Cool / Heat) °C -15°C ~ 46°C / -9.5 (DB), -10 (WB) ~ +21 (DB), +15.5 (WB)

Electrical Power Supply 3N - 400V 50Hz

Net values at Eurovent nominal conditions:Cooling capacities in kW given for 7°C water leaving temperature ∆t 5°C and 35°C ambient temperature.Heating capacities in kW given for 45°C water leaving temperature and 7°C ambient temperature.Ecodesign figures are calculated following variable outlet approach.For Ecodesign calculations, please contact your JCI representative.Sound Pressure: measured at 1.5m height, and at 1m distance from the control panel.The above data is based on Johnson Control’s selection software YORKworks 18.06. Please refer to the latest version of the software for specific projects.

Page 3: YCME / YHME Series 2 Modular screw chillers and heat pumps · 2019. 8. 28. · Modular screw chillers and heat pumps YCME/YHME 0162HE to 0222HE A complete range from 160 kW up to

20

Dimensions and hydraulic connections

YCME/YHME 0162-0182

All dimensions in mm. Drawings not a scale. Size Hydraulic connections

YCME/YHME 0162-0182 2” 1/2 Victaulic Ø 76.1 mm

Page 4: YCME / YHME Series 2 Modular screw chillers and heat pumps · 2019. 8. 28. · Modular screw chillers and heat pumps YCME/YHME 0162HE to 0222HE A complete range from 160 kW up to

YORK® AIR-CONDITIONING PRODUCTS

21

YCME/YHME 0202-0222

YCME/YHME 0162HE to 0222HE

All dimensions in mm. Drawings not a scale. Size Hydraulic connections

YCME/YHME 0202-0222 2” 1/2 Victaulic Ø 76.1 mm