    MODEL A2097C/S 2 (50.8 mm) HIGH PERFORMANCE DRAINABLE FIXED MULLION LOUVER

    TEST DATA:

    For a 4 Foot by 4 Foot Unit. Tested with mill finish and no screen

    Free area = 8.84 ft2 (0.821 m2 Percent free area = 55.3% ) Free area velocity at the point of beginning water penetration

    (@ 0.01oz. / ft2

    Maximum recommended air intake velocity = 704 FPM (3.58 m/s)of free area based on a 15 minute interval test) = 904 FPM (4.59 m/s)Air volume @ 704 FPM free area velocity = 6223.4 CFM (2.94 m3

    Pressure drop @ 704 FPM intake velocity = 0.08 in. H/s)

    2

    Maximum recommended air exhaust velocity = 1759 FPM (8.94 m/s)O (19.4 Pa)Air Volume @ 1759 FPM free area velocity = 15549 CFM (7.34 m3

    Pressure drop @ 1759 FPM free area velocity = 0.50 in. H/s)

    2

    O (124.4 Pa)

    SUGGESTED SPECIFICATIONS:

    GENERAL: Furnish and install where indicated on the drawings C/S 2 (50.8 mm) HIGH

    PERFORMANCE DRAINABLE FIXED MULLION LOUVER MODEL A2097 as manufacturedby Construction Specialties, Inc. Cranford, New Jersey and Mississauga, Ontario. Complete detailsshall be submitted to the architect for approval prior to fabrication. Supplier must be a member of

    AMCA or BSRIA

    MATERIAL: Heads, sills and jambs to be one piece structural members of 6063-T6 alloy withintegral caulking slot and retaining beads. Mullions shall be sliding interlock with internal drain(s).Blades to be one piece extrusions with gutter(s) designed to catch and direct water to jamb and

    mullion drains. Extrusion thicknesses shall be as follows: Heads, Sills, jambs and blades:

    0.063(1.60 mm). Closed cell compression gaskets shall be provided between bottom of the

    mullion or jamb and the top of the sill to insure leak tight connections. All fasteners to be

    aluminum or stainless steel. All louvers to be furnished with 5/8 (15.87 mm) flattened expanded

    mesh, aluminum bird screen with a .055 (1.4 mm) thick extruded aluminum frame. Screens and

    screen frames to be standard mill finish.

    STRUCTURAL DESIGN: Structural supports shall be designed and furnished by the louvermanufacturer to carry a wind load of not less than_______ psf (Pascals). (Note: If this paragraph is

    omitted or if the design wind load is not specified, the louvers will be manufactured in self-supporting units up to a maximum of 5 (1524 mm) wide by 8 (2438 mm) high. Any additional

    structural supports required to adequately secure these units within the opening shall be theresponsibility of others.)

    TEST DATA: The louver manufacturer shall submit test data on a 4 x 4 (1.22 m x 1.22 m) unitshowing that the louver conforms to the following: (Based on a 15 min. test duration)

    Free area: 8.84 ft2 (0.821 m2)

    Free area velocity @ point of beginning water penetration (0.01 oz/ft 2 904 FPM (4.59 m/s))

    Intake pressure drop @ 0.01 oz ft2 0.13 in. H. free area velocity 2O (32.3 Pa)

    Exhaust pressure drop at 1000 FPM (5.09 m/s) free area velocity: 0.16 in. H2O (39.7 Pa)

    FINISH: All louvers shall be finished with C/S Powder Coat, a coating to be 1.5 to 3 mil. thick full

    strength 100% resin Fluoropolymer coating. Finish to allow zero VOCs to be emitted intofacility of application. Finish to adhere to a 4H Hardness rating. All finishing procedures shall beone continuous operation in the plant of the manufacturer. The coating shall meet or exceed all

    requirements of AAMA specification 2605-5 Voluntary Specification for High PerformanceOrganic Coatings on Architectural extrusions and Panels. The louver manufacturer shall supply anindustry standard 20-year limited warranty against failure or excessive fading

    of theFluoropolymer Powder Coat finish. This limited warranty shall begin on the date of material

    shipment.

    To download details and specifications visit www.c-sgroup.com. For technical and design assistance call 800-631-7379

    SECTION VIEW

    HEAD

    DRAINABLE

    SINGLE

    BLADE

    2"

    SILL

    JAMB

    MULLION

    PLAN VIEW

  • 8/3/2019 Www.c-sgroup.com Files Tech-center Louver Performance PDF a2097

    2/2

    Construction Specialties, Inc.

    Manufacturing & Sales Locationwww.c-sgroup.com

    Cranford, New Jersey

    49 Meeker Avenue 07016

    Telephone: (800) 631-7379

    Fax: (908) 272-2920

    Mississauga, Ontario

    895 Lakefront Promenade L5E 2C2

    Telephone: (888) 895-8955

    Fax: (905) 274-6241

    A member of the C/S Group of Companies

    For assistance with overseas requirements,call C/S International (908) 236-0800

    Copyright 2010. Construction Specialties, Inc., reserves the right to make

    design changes or to withdraw any design without notice.

    Water Penetration Statement

    AMCA defines the point of beginning water penetration as the free areavelocity at which the AMCA water test has yielded 0.01 or less ounces of

    water per square foot of louver free area during a 15-minute test period.

    Tests on non-drainable louvers have shown that the point of beginning

    water penetration for 4 and 6-inch deep louvers usually occurs at between

    600 and 800 FPM free area velocity. In addition, the total amounts of waterpenetration for non-drainable louvers significantly higher in comparison to

    drainable louvers when intake velocities exceed the 600 to 800 FPM range.

    Because of these characteristics, C/S recommends that drainable blade

    louvers be used for air intake applications whenever water entrainment mustbe minimized. In addition, we suggest that non-drainable louver air intakevelocities be held to 600 FPM through the free area. This will help to limit

    significant water penetration during times of average rain conditions.

    12 18 24 30 36 42 48 54 60

    0.30 0.46 0.61 0.76 0.91 1.07 1.22 1.37 1.52

    18 0.65 1.03 1.41 1.79 2.18 2.56 2.94 3.32 3.70

    0.46 0.06 0.10 0.13 0.17 0.20 0.24 0.27 0.31 0.34

    24 0.90 1.43 1.95 2.48 3.01 3.54 4.07 4.59 5.12

    0.61 0.08 0.13 0.18 0.23 0.28 0.33 0.38 0.43 0.48

    30 1.14 1.82 2.49 3.16 3.83 4.50 5.17 5.85 6.52

    0.76 0.11 0.17 0.23 0.29 0.36 0.42 0.48 0.54 0.61

    36 1.41 2.24 3.07 3.90 4.73 5.56 6.39 7.22 8.05

    0.91 0.13 0.21 0.29 0.36 0.44 0.52 0.59 0.67 0.75

    42 1.68 2.67 3.66 4.65 5.64 6.63 7.62 8.61 9.60

    1.07 0.16 0.25 0.34 0.43 0.52 0.62 0.71 0.80 0.89

    48 1.95 3.10 4.25 5.40 6.55 7.70 8.84 9.99 11.14

    1.22 0.18 0.29 0.39 0.50 0.61 0.72 0.82 0.93 1.04

    54 2.21 3.50 4.80 6.09 7.39 8.68 9.98 1 1.27 1 2.57

    1.37 0.20 0.33 0.45 0.57 0.69 0.81 0.93 1.05 1.17

    60 2.45 3.89 5.33 6.77 8.21 9.65 11.08 1 2.52 1 3.96

    1.52 0.23 0.36 0.49 0.63 0.76 0.90 1.03 1.16 1.30

    66 2.72 4.32 5.91 7.51 9.11 10.70 12.30 13.90 15.50

    1.68 0.25 0.40 0.54 0.69 0.84 0.98 1.13 1.28 1.42

    72 2.99 4.75 6.50 8.26 10.02 11.77 13.53 15.29 17.04

    1.83 0.27 0.43 0.59 0.75 0.91 1.07 1.23 1.39 1.55

    78 3.26 5.18 7.09 9.01 10.93 12.84 14.76 16.67 18.59

    1.98 0.30 0.47 0.64 0.82 0.99 1.16 1.33 1.51 1.68

    84 3.51 5.57 7.64 9.70 11.76 13.82 15.89 17.95 20.01

    2.13 0.50 0.50 0.69 0.88 1.06 1.25 1.44 1.62 1.81

    90 3.76 5.96 8.17 10.38 12.58 14.79 16.99 19.20 21.41

    2.29 0.34 0.54 0.74 0.94 1.14 1.34 1.54 1.74 1.94

    96 4.03 6.39 8.75 11.12 13.48 15.85 18.21 20.58 22.94

    2.44 0.58 0.58 0.79 1.00 1.22 1.43 1.64 1.86 2.07

    102 4.30 6.82 9.34 11.87 14.39 16.92 19.44 21.96 24.49

    2.59 0.39 0.61 0.84 1.07 1.29 1.52 1.75 1.97 2.20

    108 4.57 7.25 9.94 12.62 15.30 17.99 20.67 23.35 26.04

    2.74 0.41 0.65 0.89 1.13 1.37 1.61 1.85 2.09 2.33

    114 4.82 7. 65 10.48 13. 31 16.14 18. 97 21. 80 24.63 27. 46

    2.90 0.43 0.68 0.94 1.19 1.44 1.70 1.95 2.20 2.46

    120 5.06 8. 04 11.01 13. 98 16.96 19. 93 22. 91 25.88 28. 85

    3.05 0.45 0.72 0.99 1.25 1.52 1.79 2.05 2.32 2.59126 5.33 8. 46 11.59 14. 73 17.86 20. 99 24. 12 27.25 30. 39

    3.20 0.48 0.76 1.04 1.32 1.60 1.88 2.16 2.44 2.72

    132 5.60 8. 89 12.19 15. 48 18.77 22. 06 25. 35 28.64 31. 93

    3.35 0.50 0.79 1.09 1.38 1.67 1.97 2.26 2.55 2.85

    138 5.87 9. 33 12.78 16. 23 19.68 23. 13 26. 58 30.03 33. 48

    3.51 0.52 0.83 1.14 1.44 1.75 2.06 2.36 2.67 2.98

    144 6.12 9. 72 13.32 16. 92 20.51 24. 11 27. 71 31.30 34. 90

    3.66 0.54 0.86 1.18 1.50 1.82 2.14 2.46 2.78 3.10

    150 6.37 10. 11 13.85 17. 59 21.33 25. 07 28. 82 32.56 36. 30

    3.81 0.57 1 0.54 1.23 1.57 1.90 2.23 2.57 2.90 3.23

    156 6.64 10. 54 14.11 18. 34 22.23 26. 13 30. 03 33.93 37. 83

    3.96 0.59 1 0.97 1.28 1.63 1.98 2.32 2.67 3.02 3.36

    162 6.91 10. 97 15.03 19. 09 23.14 27. 20 31. 26 35.32 39. 38

    4.11 0.61 0.97 1.33 1.69 2.05 2.41 2.77 3.13 3.49

    PERFORMANCE DATA MODEL A2097

    HeightinInc

    hesandMeters

    Upper Numerals English Units/Lower Numerals Metric Units

    Width in Inches and Meters

    Intake

    Exhaust

    For a 48 X 48 sized louver