What is Backflow?
Back Siphonage
Back Pressure
Vacuum on supply
Downstream pressure higher than supply
“Backflow” means flow upstream, that is in a direction contrary to the intended normal direction of flow, within or from a water fitting
Flow of water Backflow
www.arrowvalves.co.uk copyright 2006-20123
Backflow Example
Bath (1st floor)
Sink (ground floor)
The above diagram shows a bath with a submerged shower head
Shower head
If negative pressure should occur, dirty bath water could be sucked back into the pipework and be discharged from the sink as water used for hand washing,
drinking etcA Double Check Valve fitted to the shower hose would prevent the bath water
reaching the sink and contaminating it
Double Check Valve model ED235
Further (secondary) backflow protection should also be provided (see later slide)
www.arrowvalves.co.uk copyright 2006-20124
Fluid Categories
European Fluid Category 5
European Fluid Category 4
European Fluid Category 3
EuropeanFluid Category 2
EuropeanFluid Category 1
Class 1Schedule A Risk
Class 2Schedule B Risk
Class 3Schedule C Risk
Previous UKClassification
European/New UKClassification
WholesomeWater
Air Gap – AA AB Pipe Interrupter - DC
RPZ – BAPipe Interrupter - DB
Double Check – ED
Single Check – EB
No Protection Required(Except Secondary, at times)
Backflow Prevention Examples(Used in Building Services)
www.arrowvalves.co.uk copyright 2006-20125
Types of Backflow ProtectionPoint of Use Protection
“The provision of zone or whole site backflow protection should be in addition to individual requirements at points of use and within the system”
G15.25
Appliances of different types e.g. a washing machine and dishwasher, must have their own protection, preventingcross contamination
www.arrowvalves.co.uk copyright 2006-20126
Types of Backflow ProtectionZone Protection
“Any taps and fittings used for supplying water for non-domestic applications, such as commercial, horticultural, agricultural or industrial purposes should be provided with
a. backflow protection devices appropriate to the downstream fluid category; and
b. where appropriate, a zone protection system” G15.18
Where several appliances of the same type and same Fluid Category are used within a commercial building, water suppliers may accept single protection for multiple appliances.
www.arrowvalves.co.uk copyright 2006-20127
Types of Backflow ProtectionSecondary Backflow Protection
“A whole-site or zone backflow prevention device should be provided on the supply or distributing pipe, such as a single check valve or double check valve, or other no less effective backflow prevention device, according to the level of risk as judged by the Water Undertaker…”
G15.24
Whole site backflow protection should be
provided on supply pipes to two or more separately
occupied premises
Arrow Valves Branch Valve model BRV – Servicing, Double Check & Drain Tap
with Solder Union connections
www.arrowvalves.co.uk copyright 2006-20128
Fluid Category 3 ProtectionDouble Check Valve
ED Double Check ValveCategory 3 protection
ED is “non-verifiable” meaning there are no test
points provided. EC is verifiable but none is approved and since
protection is still Fluid Category 3, there is no
benefit.
Applications –
Exceptionally low head-loss ED Device (Model ED132)
Stainless Steel - exceptionally low head-loss – Model ED316
Double Check Valve - model ED235. For fluid category 3 protection on
shower hoses. Flow limiter option
No Tools RequiredSupply to flats (whole site)Separate floors (secondary)Numerous others
www.arrowvalves.co.uk copyright 2006-20129
Filling Heating Systems
Accessories available include Expansion Vessels (EVCP), Expansion Vessel Isolators (BVEV) and Air Dirt Removers (ADR), Water Meter (WMV3P)
Fills and pressurises “non-house” heating systems with output greater than 45 kW
Automatically fill “house” heating
systems or “non-house”
heating systems less than 45 kW
output
Fluid Category 3 (heating permanent connection)
Fluid Category 4
Optional wall mounting brackets (Model AFBRA)
Filling Valve – CA Device with Pressure Reducing Valve and
inlet/outlet servicing valves
Model CA297PRV
“Autofill” – Fluid Category 4Model AFS
“Autofill” – Fluid Category 3Model AFCA
www.arrowvalves.co.uk copyright 2006-201210
Filling Heating Systems – Fluid Category 5
Dose & Fill – Model DF
“Midi-Fill” DigitalModel MFD
Advanced Pressurisation Unit
• Weekly self test – BMS alerts to avoid heating system shutdown
• Anti-seize daily pump pulse
• Integral water meter and excessive filling alarms
• No annual testing
Features –
• All the features of the “Midi-Fill” Digital plus –
• Low chemical BMS warning
• Manual internal dosing facility
• External dosing facility – replaces need for dosing pot
Features –
“Midi-Fill” Digital with Automatic
Dosing
www.arrowvalves.co.uk copyright 2006-201211
Fluid Category 4 ProtectionRPZ Valve / BA Device
RPZ Option B
Upstream Isolating Valve, Strainer, RPZ, downstream
Isolating Valve
Compact RPZ ValveModel BA3T
Applications• Clothes washing machines
• Dishwashing machines
• Fire fighting equipment
• Printing and photographic equipment
• Water treatment
• Water softening
• Vehicle washing and many more
Reduced Pressure Zone (RPZ) Valves – also known as
BA device. Mechanical backflow preventer for Fluid
Category 4 backpressure and backsiphonage protection
Standpipe
Freestanding watering point incorporating
BA device
Model SPBA
Installation requirements
Tamperproof environmentAdequate rear clearanceAccess height 0.3 m min 1.5 m max
www.arrowvalves.co.uk copyright 2006-201212
Insulation Jacket
Model BTJAC
Drip Tray
Model BTDT1Wall mounting
bracketsModel BTBRA
Wall Cover
Model BTCAB3
Fluid Category 4 ProtectionAF Air Gap
Based on diagram G15.31.2
SgV
Outlet
Air Gap
“Pent-A-Boost” Fixed speed
Compact Domestic Booster
model BTAF
Incorporating type AF air gap
Variable speed also available
Shown with optional insulation
jacket
Primarily to boost the supply pressure to Penthouse Suites and similar tall buildings
requiring individual booster sets
Applications
• Tall buildings (3 storey+) e.g. Penthouse suites
• Boosting low pressure
• “Combi” boilers and showers
• Drinking (“wholesome”) water – use optional jacket
Supplied as a complete package ready for installation
www.arrowvalves.co.uk copyright 2006-201213
Fluid Category 5 ProtectionAB Air Gap
Based on diagram G15.31.2
SgV
Outlet
Air Gap
Weir Overflow
“Boost-A-Break” Fixed speed
Break Tank and Booster Setmodel BTAB
Incorporating type AB air gap
Variable speed also available
Suitable for all backflow prevention
applications
Primarily to provide Fluid Category 5 backflow protection and to boost water
pressure for high flow applications
Wall mounting brackets
Model BTBRA
Wall Cover
Model BTCAB3
Floor cabinet
Model BTCAB1
Drip Tray
Model BTDT1
Applications
Non-domestic Hose Union taps e.g.
• Waste bin washing• Wash-down• Irrigation
• Laboratories• Rain water
• Baths / Showers – Healthcare
• Bed pan washers
www.arrowvalves.co.uk copyright 2006-201214
Fluid Category 5 ProtectionAB Air Gap
“Midi-Break”
Break Tank & Booster Set model BTMIDI
Incorporating type AB air gap
Stainless steel housing provides neat and hygienic
installation
Three models –
Midi-1, Midi-2A and Midi-3A
Applications – Healthcare premises (baths with shower hoses, clothes and dishwashing
machines) Bidet washing Sinks with hoses
Non-domestic Hose Union taps Vegetable washing
Wall mounted Break Tank & Booster Set
Primarily to provide Fluid Category 5 backflow protection and to boost water
pressure for high flow applications
BTDT3 - Stainless steel drip tray for “Midi-Break”
BTCAB4 - Wall Cover for “Midi-Break”Wall mounting brackets included
www.arrowvalves.co.uk copyright 2006-201215
Fluid Category 5 ProtectionCare Shower
Applications – Healthcare (assisted bathing)
Nursing homes Veterinary Dog grooming Medical Mortuary
Butchery Bidet Toilet (paperless)
Thermostatically controlled shower – Electric Shower & Booster Pump
package (model CSABATLF)
Supplies instantaneous hot water to an accurate maximum temperature
Fluid Category 5 backflow protection
Meets BEAB Care Mark Requirements as safe for use by elderly, young or sick
www.arrowvalves.co.uk copyright 2006-201216
Ablution Plant – FC5
Toiletry (paperless), animal washing, butchery
Assists with multi-cultural facilities
Fluid Category 5 backflow protection
Consists of -
• Break Tank with Type AB air gap• Booster Pump • Storage Heater • TMV
Applications –
Safe hot water with Fluid Category 5
backflow protection – Model BTHW
Fluid Category 5 ProtectionAblution Plant
www.arrowvalves.co.uk copyright 2006-201217