22
The copyright is in Takashi Yagisawa Translation Start Date: August 8 th , 2018 http://wingshome.co.jp/introduction_e.html WINGS CORPORATION Japan Doc. No. : WD14-001E Sheet 116 of 138 Rev. No. : E0 Title: Introduction of the inspection and testing for the industrial valves 8. Function test (PERFORMANCE INSPECTION) This commentary for mainly operating tests and actual temperature of the actuator with the valve (low temperature and high temperature) test. Others, Fire Test etc are also available but I will omit it. 8.1 Operation test of valve with actuator Actuators are mainly classified as electric, pneumatic, and hydraulic by operating methods. In the selection (sizing) of the actuator, it is general that the maximum design differential pressure is used as a reference. Pressure inspection (PRESSURE INSPECTION) will be implemented in accordance with paragraph 5 of this article. However, the High-Pressure Closure Test uses a test pressure (API 598, JPI-7S-39, etc.) 1.1 times the maximum design differential pressure and operates with the actuator. For the valves with actuators, perform the following function tests according to the operation method. (refer to JPI-7R-68.) 8.1.1 Motor Operated Actuator (1) Operation inspection: It is electrically operated fully open and fully closed, operation is smooth, limit switch, torque switch, etc. are functioning. Also, the opening indication must be accurate when fully open or fully closed. In addition, measure the current at startup and running, and be within the range of specifications. (2) Opening and Closing Time Test: Full opening / closing within the prescribed time. (3) Manual operation inspection: If equipped with manual operation function, switch to manual operation and operate smoothly. (4) Withstand voltage: Test voltage (motor rated voltage × 2 + 1,000 V) is applied for 1 minute between the stator winding of the motor (motor) and earth and there is no abnormality. However, in principle, it is not carried out when the actuator manufacturer carries out the certificate. Which may cause deterioration. (5) Insulation resistance test: Set to 100 MΩ or more at DC 500 V between each terminal of the motor and the electrical components and the earth.

WINGS CORPORATION Doc. No. : WD14-001E Japan Rev. No. : E0wingshome.co.jp/introduction/section8_e.pdf · 2018. 10. 16. · Also, low temperature tests at temperatures below -196 °

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

  • The copyright is in Takashi Yagisawa

    Translation Start Date: August 8th, 2018

    http://wingshome.co.jp/introduction_e.html

    WINGS CORPORATION

    Japan

    Doc. No. : WD14-001E

    Sheet 116 of 138

    Rev. No. : E0

    Title: Introduction of the inspection and testing for the

    industrial valves

    8. Function test (PERFORMANCE INSPECTION)

    This commentary for mainly operating tests and actual temperature of the actuator with the valve (low

    temperature and high temperature) test.

    Others, Fire Test etc are also available but I will omit it.

    8.1 Operation test of valve with actuator

    Actuators are mainly classified as electric, pneumatic, and hydraulic by operating methods. In the selection

    (sizing) of the actuator, it is general that the maximum design differential pressure is used as a reference.

    Pressure inspection (PRESSURE INSPECTION) will be implemented in accordance with paragraph 5 of this

    article. However, the High-Pressure Closure Test uses a test pressure (API 598, JPI-7S-39, etc.) 1.1 times the

    maximum design differential pressure and operates with the actuator.

    For the valves with actuators, perform the following function tests according to the operation method. (refer

    to JPI-7R-68.)

    8.1.1 Motor Operated Actuator

    (1) Operation inspection: It is electrically operated fully open and fully closed, operation is smooth, limit

    switch, torque switch, etc. are functioning. Also, the opening indication must be accurate when fully open or

    fully closed.

    In addition, measure the current at startup and running, and be within the range of specifications.

    (2) Opening and Closing Time Test: Full opening / closing within the prescribed time.

    (3) Manual operation inspection: If equipped with manual operation function, switch to manual operation

    and operate smoothly.

    (4) Withstand voltage: Test voltage (motor rated voltage × 2 + 1,000 V) is applied for 1 minute between the

    stator winding of the motor (motor) and earth and there is no abnormality. However, in principle, it is not

    carried out when the actuator manufacturer carries out the certificate. Which may cause deterioration.

    (5) Insulation resistance test: Set to 100 MΩ or more at DC 500 V between each terminal of the motor and

    the electrical components and the earth.

    http://wingshome.co.jp/introduction_e.html

  • The copyright is in Takashi Yagisawa

    Translation Start Date: August 8th, 2018

    http://wingshome.co.jp/introduction_e.html

    WINGS CORPORATION

    Japan

    Doc. No. : WD14-001E

    Sheet 117 of 138

    Rev. No. : E0

    Title: Introduction of the inspection and testing for the

    industrial valves

    Note:

    An explosion-proof standard is set for valves with actuators installed in the plant when they are used in an

    atmosphere of flammable gas. Attach the actuator with the structure specified in the explosion-proof grade

    of the purchase specification (regulation of IEC 60079). These grades are listed on the nameplate of the

    actuator and it is necessary to check whether there is any difference from the certificate.

    The following is a reference example of explosion proof symbol.

    For reference, Name Plate indication

    http://wingshome.co.jp/introduction_e.html

  • The copyright is in Takashi Yagisawa

    Translation Start Date: August 8th, 2018

    http://wingshome.co.jp/introduction_e.html

    WINGS CORPORATION

    Japan

    Doc. No. : WD14-001E

    Sheet 118 of 138

    Rev. No. : E0

    Title: Introduction of the inspection and testing for the

    industrial valves

    http://wingshome.co.jp/introduction_e.html

  • The copyright is in Takashi Yagisawa

    Translation Start Date: August 8th, 2018

    http://wingshome.co.jp/introduction_e.html

    WINGS CORPORATION

    Japan

    Doc. No. : WD14-001E

    Sheet 119 of 138

    Rev. No. : E0

    Title: Introduction of the inspection and testing for the

    industrial valves

    http://wingshome.co.jp/introduction_e.html

  • The copyright is in Takashi Yagisawa

    Translation Start Date: August 8th, 2018

    http://wingshome.co.jp/introduction_e.html

    WINGS CORPORATION

    Japan

    Doc. No. : WD14-001E

    Sheet 120 of 138

    Rev. No. : E0

    Title: Introduction of the inspection and testing for the

    industrial valves

    8.1.2 Pneumatic Operated Actuator

    (1) Operation inspection: It is fully open and fully closed by pneumatic pressure, operation is smooth, limit

    switch, torque switch, etc. are functioning. Also, the opening indication must be accurate when fully open or

    fully closed.

    In addition, in the case of a single operation by a combination with a spring, the air is stopped and the state

    of air pressure disappears, and a fully closed or full open test by a spring return is performed.

    (2) Opening and Closing Time Test: Full opening / closing within the prescribed time.

    (3) Manual operation inspection: If equipped with manual operation function, switch to manual operation

    and operate smoothly.

    (4) Cylinder leakage inspection: Pressurize the cylinder part to the specified air pressure and have no leakage

    from each part of the cylinder.

    8.1.3 Hydraulic Operated Actuator

    (1) Operation inspection: It is fully open and fully closed by pneumatic pressure, operation is smooth, limit

    switch, torque switch, etc. are functioning. Also, the opening indication must be accurate when fully open or

    fully closed.

    (2) Opening and Closing Time Test: Full opening / closing within the prescribed time.

    (3) Manual operation inspection: If equipped with manual operation function, switch to manual operation

    and operate smoothly.

    (4) Leakage inspection: The specified pressure is applied to the hydraulic part, and there is no leakage from

    each part such as hydraulic piping.

    http://wingshome.co.jp/introduction_e.html

  • The copyright is in Takashi Yagisawa

    Translation Start Date: August 8th, 2018

    http://wingshome.co.jp/introduction_e.html

    WINGS CORPORATION

    Japan

    Doc. No. : WD14-001E

    Sheet 121 of 138

    Rev. No. : E0

    Title: Introduction of the inspection and testing for the

    industrial valves

    For reference only: The following is an example of formula for calculating actuator sizing.

    http://wingshome.co.jp/introduction_e.html

  • The copyright is in Takashi Yagisawa

    Translation Start Date: August 8th, 2018

    http://wingshome.co.jp/introduction_e.html

    WINGS CORPORATION

    Japan

    Doc. No. : WD14-001E

    Sheet 122 of 138

    Rev. No. : E0

    Title: Introduction of the inspection and testing for the

    industrial valves

    http://wingshome.co.jp/introduction_e.html

  • The copyright is in Takashi Yagisawa

    Translation Start Date: August 8th, 2018

    http://wingshome.co.jp/introduction_e.html

    WINGS CORPORATION

    Japan

    Doc. No. : WD14-001E

    Sheet 123 of 138

    Rev. No. : E0

    Title: Introduction of the inspection and testing for the

    industrial valves

    http://wingshome.co.jp/introduction_e.html

  • The copyright is in Takashi Yagisawa

    Translation Start Date: August 8th, 2018

    http://wingshome.co.jp/introduction_e.html

    WINGS CORPORATION

    Japan

    Doc. No. : WD14-001E

    Sheet 124 of 138

    Rev. No. : E0

    Title: Introduction of the inspection and testing for the

    industrial valves

    http://wingshome.co.jp/introduction_e.html

  • The copyright is in Takashi Yagisawa

    Translation Start Date: August 8th, 2018

    http://wingshome.co.jp/introduction_e.html

    WINGS CORPORATION

    Japan

    Doc. No. : WD14-001E

    Sheet 125 of 138

    Rev. No. : E0

    Title: Introduction of the inspection and testing for the

    industrial valves

    8.2 Low- and High-Temperature Testings

    A test to confirm the function in a low temperature or high temperature environment close to the actual use

    condition of the valve is called a real temperature test. The actual temperature test must be carried out by

    presenting to the valve maker the test procedure including application status, quantity to be purchased and

    amount of leakage in purchase specifications. In the absence of these requirements, the valve manufacturer

    does not normally perform real temperature test.

    8.2.1 Low temperature test

    For the low temperature test, the minimum design temperature of the valve is from -50 ° C to -196 ° C for

    BS 6364: Valve for cryogenic service, from -30 ° C to -196 ° C for Shell MESC SPE 77/200: 2007 VALVE

    IN LOW TEMPERATURE AND CRYOGENIC SERVICES . Also, low temperature tests at temperatures

    below -196 ° C are not common as they require special testing equipment.

    (1) Test facility (Test Rig Arrangement)

    Reference examples of test equipment are shown below.

    · The line on the pressurizing side needs to be approved in Japan as a high pressure gas production facility.

    · All piping must be designed to have sufficient strength under low temperature environment by using

    stainless steel pipe, fitting, flange, high pressure connecting jig. In addition, it is necessary to confirm that

    leakage of piping system is less than allowable leakage amount by helium pressure applied pressure before

    http://wingshome.co.jp/introduction_e.html

  • The copyright is in Takashi Yagisawa

    Translation Start Date: August 8th, 2018

    http://wingshome.co.jp/introduction_e.html

    WINGS CORPORATION

    Japan

    Doc. No. : WD14-001E

    Sheet 126 of 138

    Rev. No. : E0

    Title: Introduction of the inspection and testing for the

    industrial valves

    testing.

    · For temperature measurement, measure the temperature of the test site, the vicinity of Disc inside the valve,

    the body surface and Stuffing Box portion.

    · The test pressure shall be measured at two places, the pressurizing side and the exit side, and at least the

    test pressure at the pressurizing side must be recorded continuously. Please calibrate the pressure gauge and

    use range according to applicable standards.

    · Check the valve leakage amount with a flow meter provided on the outlet side or a small amount of leakage

    with a measuring cylinder in water.

    · It is recommended that test data (pressure, temperature, flow meter leakage, helium detector leakage etc.)

    be recorded over time. It is now easier to digitally record using a data logger.

    Example in which recording was observed using a data logger (values shown in the example when high temperature test was performed)

    · Place a safety valve on the pressurizing side and miss the pressure when abnormal pressurization occurs.

    http://wingshome.co.jp/introduction_e.html

  • The copyright is in Takashi Yagisawa

    Translation Start Date: August 8th, 2018

    http://wingshome.co.jp/introduction_e.html

    WINGS CORPORATION

    Japan

    Doc. No. : WD14-001E

    Sheet 127 of 138

    Rev. No. : E0

    Title: Introduction of the inspection and testing for the

    industrial valves

    · Stainless steel plate is used for the low temperature tank and it is structured to withstand the load of the

    target valve, and it is enclosed by the insulation material.

    Secure the height at which the coolant is immersed to the border with Bonnet's Extension section or to the

    tip of Bonnet Bolt.

    Sample of cold bath for large diameter valve Sample of cold bath for small caliber valve

    (2) Coolant (Coolant)

    · When carrying out at -196 ° C, use liquefied nitrogen.

    · When carrying out at less than -196 ° C, it is common to use gas vaporized liquefied nitrogen, industrial

    alcohol + liquefied nitrogen or industrial alcohol + dry ice, but a large amount of alcohol is dangerous,

    compliance with laws and regulations , It is necessary to fully consider safety assurance.

    (3) Test fluid (Test Fluid)

    It is recommended to use helium gas regardless of test temperature. However, with Shell MESC SPE 77/200,

    100% nitrogen gas or 99% nitrogen gas + 1% helium gas is allowed for the test temperature of -110 ° C or

    higher.

    (4) Test Temperature (Test Temperature)

    Depending on the design temperature, it will not test below the impact test temperature specified by Body /

    Bonnet / Cover material standard (ASTM, JIS etc.).

    http://wingshome.co.jp/introduction_e.html

  • The copyright is in Takashi Yagisawa

    Translation Start Date: August 8th, 2018

    http://wingshome.co.jp/introduction_e.html

    WINGS CORPORATION

    Japan

    Doc. No. : WD14-001E

    Sheet 128 of 138

    Rev. No. : E0

    Title: Introduction of the inspection and testing for the

    industrial valves

    Note:

    1) Main liquefied gas types and boiling points (° C)

    Ammonia - 33.4, Propane - 42.1, Propylene - 47.7, Hydrogen Sulfide - 61, Acetylene - 84, Ethane - 88.6,

    Ethylene - 103.5, Methane - 165.5, Oxygen - 183, Argon - 185.8, Nitrogen - 195.8, Hydrogen - -268.9.

    It should be noted that a liquefied gas which is a liquefied gas whose pressure exceeds 0.2 megapascals at a

    normal temperature and has a pressure of 0.2 megapascals or more at present or a temperature of 35 ° C. or

    less when the pressure becomes 0.2 megapascals , Under the High Pressure Gas Safety Act. in Japan.

    2) Main specifications of low temperature materials and impact test temperature:

    Material Standards Impact Test Temp.℃ Material Standards Impact Test Temp.℃

    ASTM A352 LCB -46 ASTM A350 LF2 CL.1 -46

    ASTM A352 LCC -46 ASTM A350 LF2 CL.2 -18

    ASTM A352 LC1 -59 ASTM A350 LF3 -101

    ASTM A352 LC2 -73 ASTM A350 LF5 -59

    ASTM A352 LC3 -101 ASTM A350 LF6 CL.1 -51

    ASTM A352 LC9 -196 ASTM A350 LF9 -73

    3) Main low temperature characteristics of austenitic stainless steel

    It is known that when austenitic stainless steel is held at -100 ° C. or lower for a long time, a part of the

    structure undergoes martensitic transformation. These austenitic stainless steel (mainly ASTM A351 Gr.

    CF8M / ASTM A182 Gr. F316) are often used for body material of cryogenic valve is deformed due to the

    martensitic transformation, is the cause of the seat leakage There. However, the influence of thermal

    deformation is also significant, and it is required to design in consideration of these phenomena.

    As for the martensitic transformation, treatment may be carried out in which transformation occurs in advance

    in liquefied nitrogen (-196 ° C.) at the stage of material or semi-processing to partially alleviate the risk of

    deformation. These processes are called sub-zero processing (SUB-ZERO TREATMENT), the valve

    manufacturer decides the processing standard and decides which part range to execute.

    (5) Test method

    1) Prior to testing

    Before conducting the low temperature test, perform the above-mentioned pressure test at the room

    temperature at the target valve and proceed the low-temperature test to the accepted valve. It is recommended

    to use nitrogen gas or helium gas as the test fluid in this case.

    When confirmed by water pressure, it is necessary to thoroughly dry the inside of the valve. In particular, it

    is difficult to remove water that has penetrated into packing and gaskets.

    Eliminate dust, dirt, oil and other foreign matter, and install the test fixture in a clean environment.

    Also, make sure that all bolts / nuts (Bonnet Bolting / Gland Bolting) are tightened with the prescribed torque

    before the low temperature test. The specified torque must be calculated and presented by the valve maker.

    http://wingshome.co.jp/introduction_e.html

  • The copyright is in Takashi Yagisawa

    Translation Start Date: August 8th, 2018

    http://wingshome.co.jp/introduction_e.html

    WINGS CORPORATION

    Japan

    Doc. No. : WD14-001E

    Sheet 129 of 138

    Rev. No. : E0

    Title: Introduction of the inspection and testing for the

    industrial valves

    2) Immersion in liquefied nitrogen (Cooling Down)

    - After installing the test fixture and moving to the low temperature bath, purge the piping system with helium

    and remove the internal moisture. For large valves, measure the dew point as necessary and confirm that no

    dew condensation occurs at low temperature.

    · Next, pressurize the piping system with helium of 0.2 MPa, and use a helium detector to check leakage

    from the connection. In this case, the amount of leakage shall be less than the allowable leakage amount

    described in the purchasing specifications.

    · When it is confirmed that there is no moisture and leakage, inject liquefied nitrogen into the low

    temperature bath.

    Note:

    Since liquefied nitrogen boils until the cold bath and the valve cools down, oxygen in the low temperature

    tank and around it becomes oxygen deficient. Prepare an oxygen concentration meter, measure the oxygen

    concentration in the surroundings, ventilate so as not to suffocate, and take safety measures.

    3) Cryogenic Test Method

    Described with reference to BS 6364:

    · When liquefied nitrogen is filled up to the specified height, hold for at least 1 hour until measurement

    temperature stabilizes.

    * Shell In MESC SPE 77 / 300-2007, test can be started if it is kept for 5 minutes until it becomes stable and

    the temperature inside the valve becomes -190 ℃ or lower (test temperature is -196 ℃). For other test

    temperatures, it can be started when the temperature difference is 5% of the specified test temperature or 5 °

    C, whichever is higher.

    · Valve seat test pressure stage (Increment Test Pressure)

    BS 6364 pressurizes to the maximum pressure of 20 ° C of the Rating Pressure (Max. Allowable Working

    Pressure / MAWP) of each pressure (Nominal Pressure) at the following pressure stage.

    Nominal Pressure Class (PN) Increment Pressure (MPa)

    Class 150 (PN 20) 0.35

    Class 300 (PN 50) 0.75

    Class 600 (PN 100) 2.00

    For example, the rating press of ASME B 16.34 at 20 ° C of Body material CF 8 M,

    Class 150: 1.90 MPa, Class 300: 4.96 MPa, Class 600: 9.93 MPa.

    unit: MPa

    Class 1st. Step 2nd. Step 3rd. Step 4th. Step 5th. Step 6th. Step

    150 0.35 0.70 1.05 1.40 1.75 1.90

    300 0.75 1.50 2.25 3.00 3.75 4.96

    600 2.00 4.00 6.00 8.00 9.93 N/A

    http://wingshome.co.jp/introduction_e.html

  • The copyright is in Takashi Yagisawa

    Translation Start Date: August 8th, 2018

    http://wingshome.co.jp/introduction_e.html

    WINGS CORPORATION

    Japan

    Doc. No. : WD14-001E

    Sheet 130 of 138

    Rev. No. : E0

    Title: Introduction of the inspection and testing for the

    industrial valves

    Shell MESC SPE 77/300-2007 では、(CF8M) unit: MPa

    Class LP seat 1st. 35%

    MAWP

    2nd. 70%

    MAWP

    3rd. 110%

    MAWP HP seat 100%

    150 0.2 / 0.7 0.665 1.33 2.09 1.90

    300 0.2 / 0.7 1.736 3.472 5.456 4.96

    600 0.2 / 0.7 3.476 6.951 10.923 9.93

    · Operation test

    In BS 6364, Open / Close is performed 20 times at each stage, and the operation torque of Open / Close is

    measured at the beginning and the end. The upper limit value of the operation torque is converted to 350 N

    in terms of the steering wheel operating force.

    In Shell MESC SPE 77 / 300-2007, perform opening / closing 90% at LP seat and 15 times at HP seat and

    measure the torque the first time at the first time. The upper limit value of the operation torque is converted

    to 350 N in terms of the steering wheel operating force.

    Operational tests exclude Check Valve.

    · Valve seat leak test (Incremental Pressure Seat Leakage Tests)

    At BS 6364, tests should be conducted at each pressure stage and below the allowable leakage below.

    Gate & Globe Valves: 100 mm 3 / s × DN.

    Check Valves: 200 mm 3 / s × DN.

    (Except for Check Valve, tightening torque shall be not more than the value determined by the valve maker.)

    Test Duration:

    unit: Minutes, Minimum

    Valve Sizes LP seat 3 Steps HP seat

    DN 15 -- 400 5 5 5

    DN 450 -- 600 5 5 10

    >DN 600 10 10 15

    For Shell MESC SPE 77 / 300-2007, tests should be conducted at each pressure stage and below the allowable

    leakage below.

    Gate & Globe Valves: 80 mm 3 / s × DN.

    Check Valves: 160 mm 3 / s × DN.

    (Except for Check Valve, tightening torque shall be not more than the value determined by the valve maker.)

    http://wingshome.co.jp/introduction_e.html

  • The copyright is in Takashi Yagisawa

    Translation Start Date: August 8th, 2018

    http://wingshome.co.jp/introduction_e.html

    WINGS CORPORATION

    Japan

    Doc. No. : WD14-001E

    Sheet 131 of 138

    Rev. No. : E0

    Title: Introduction of the inspection and testing for the

    industrial valves

    · Pressure resistance test (Shell Test)

    In BS 6364, there is no visual leakage from Gland part and Body / Bonnet Joint at each pressure stage, but

    there is no specific method and regulation of allowable leakage amount.

    For Shell MESC SPE 77 / 300-2007, conduct and check the leakage FE test from the Gland part and Body /

    Bonnet Joint at 100% MAWP pressure. The test method is also described in the leak test in Section 4.5.

    Test Duration:

    unit: Minutes, Minimum

    Valve Sizes Class 150 Class 300 Class 600

    DN 15 -- 40 10 10 10

    DN 50 -- 150 10 10 15

    DN 200 – 400 10 10 15

    DN 450 -- 600 10 10 15

    >DN 600 15 15 20

    Allowable Leakage Rate:

    Stem Seal Area;

    Class A (HS): ≦ 1.78 × 10 -8 × Stem Diameter (mm) Pa · m 3 / s

    Class B: ≦ 1.78 × 10 -7 × Stem Diameter (mm) Pa · m 3 / s

    Gasket Seal Area;

    Class A (HS): ≦ 1.78 × 10 -9 × Perimeter of the Gasket (mm) Pa · m 3 / s

    Class B: ≦ 1.78 × 10 -8 × Perimeter of the Gasket (mm) Pa · m 3 / s

    Note:

    1) After the low-temperature test, open the valve halfway, seal the pressure within about 0.2 MPa, leave it to

    room temperature naturally. If the valve is opened immediately after the cold test, dew condensation will

    occur due to the difference with room temperature, and it will contain moisture inside.

    In addition, there is a case where the valve seat leakage test and the pressure resistance test are performed

    again after returning to room temperature. In the Prototype Test, disassemble and check for damage of parts

    etc.

    http://wingshome.co.jp/introduction_e.html

  • The copyright is in Takashi Yagisawa

    Translation Start Date: August 8th, 2018

    http://wingshome.co.jp/introduction_e.html

    WINGS CORPORATION

    Japan

    Doc. No. : WD14-001E

    Sheet 132 of 138

    Rev. No. : E0

    Title: Introduction of the inspection and testing for the

    industrial valves

    2) Difference in polishing of Disc Seat face;

    The left side shows the general valve and the right shows the seat side of the low temperature valve. Surface

    roughness depends on production standard of each valve manufacturer.

    3) Precautions for Pressure Relief Hole of Cryogenic Valve:

    In the disc of Gate Valve for Cryogenic, a hole is drilled as shown in the left figure for preventing abnormal pressure rise.

    Therefore, when pressure is applied from the opposite side of the hole as shown in the left figure, it leaks to the primary side through a hole (Pressure Relief Hole). Normally, "High

    Pressure Side" or "Vent Hole Side" is displayed on the hole side of the valve.

    Even when piping, care must be taken in the sealing direction when fully closed.

    http://wingshome.co.jp/introduction_e.html

  • The copyright is in Takashi Yagisawa

    Translation Start Date: August 8th, 2018

    http://wingshome.co.jp/introduction_e.html

    WINGS CORPORATION

    Japan

    Doc. No. : WD14-001E

    Sheet 133 of 138

    Rev. No. : E0

    Title: Introduction of the inspection and testing for the

    industrial valves

    4) Location of “BackSeat” for Cryogenic Valves

    Fig. 1

    Normally, the position of BackSeat is the position shown in Fig.1, but Shell specifies Fig.2 or Fig.3. The reason is that liquefied gas enters the Cavity of Long Bonnet, and when using BackSeat it is the purpose of

    preventing the risk of abnormal boost. The disadvantage is that manufacturing precision is required, and if BackSeat leaks, repair becomes difficult. We will judge that the case of using BackSeat of valve after piping installation is extremely limited. In addition, since packing exchange during pressurization is prohibited, the

    author recommends the position in Fig.

    Length for

    Non Cold Box

    Rev. 1B

    Length for

    Cold Box

    Rev. 1B

    http://wingshome.co.jp/introduction_e.html

  • The copyright is in Takashi Yagisawa

    Translation Start Date: August 8th, 2018

    http://wingshome.co.jp/introduction_e.html

    WINGS CORPORATION

    Japan

    Doc. No. : WD14-001E

    Sheet 134 of 138

    Rev. No. : E0

    Title: Introduction of the inspection and testing for the

    industrial valves

    5) Long Bonnet length of cold valve

    The minimum length is specified as follows according to each standard and regulation.

    * BS 6364:

    The length below is the length from the center line of the valve diameter in the upper figure Fig.1.

    Note:

    The above Table 1 is the length when the valve body is installed in the Cold Box, and in the case of the Non

    Cold Box, it is stipulated as Min. 250 mm. (See Fig.1)

    *SHELL MESC SPE 77/200-2007:

    Note:

    In order to maintain the effect of the Vapor Space, the cold valve is a horizontal piping and the Stem is

    generally in a vertical attitude. With respect to the Stem vertical, the BS6364 is ± 15 degrees, the MESC SPE

    77/200 is ± 30 degrees Of the maximum allowable range.

    http://wingshome.co.jp/introduction_e.html

  • The copyright is in Takashi Yagisawa

    Translation Start Date: August 8th, 2018

    http://wingshome.co.jp/introduction_e.html

    WINGS CORPORATION

    Japan

    Doc. No. : WD14-001E

    Sheet 135 of 138

    Rev. No. : E0

    Title: Introduction of the inspection and testing for the

    industrial valves

    *MSS SP-134-2006a Valves for Cryogenic Service Including Requirements for Body/Bonnet Extensions:

    Note:

    The standard of the length is the Top of the Stuffing Box from the valve centerline line.

    It differs from BS and MESC.

    * Other

    Although it seems that there is no regulation about the temperature of Stuffing Box when fluid of Cryogenic

    Service is flowed, in general, the temperature at which Packing section does not freeze is a standard.

    Regarding the verification of the temperature of the Stuffing Box, it is possible to perform temperature

    analysis using a method to obtain by experiment such as aeration method and recently using finite element

    method (FEM).

    FEM analysis example:

    http://wingshome.co.jp/introduction_e.html

  • The copyright is in Takashi Yagisawa

    Translation Start Date: August 8th, 2018

    http://wingshome.co.jp/introduction_e.html

    WINGS CORPORATION

    Japan

    Doc. No. : WD14-001E

    Sheet 136 of 138

    Rev. No. : E0

    Title: Introduction of the inspection and testing for the

    industrial valves

    8.2.2 High Temperature Test

    For the method of high temperature testing, there are a method of passing a heated steam or a high temperature

    gas through the inside of the valve and a method of winding and heating the outside of the valve with an

    electric heating coil or the like.

    Except for blowing out tests of safety valves, general valves are less frequently implemented except when

    specially requested for Prototype Test. Twenty years ago, we held a boiler test site at the Japan Valve

    Manufacturers Association, and there were cases in which function tests of high temperature / high pressure

    valves etc. of each company were carried out.

    In the above picture, a coil for local heating is wound around the bulb and a heat insulating material is attached.

    As for the test method, generally, when the temperature inside the valve falls within the specified temperature

    range, the operation, the valve seat leakage, and the withstanding pressure are checked as in the low

    temperature test. It is necessary to clarify each test method and specified leakage amount in the order

    specifications.

    http://wingshome.co.jp/introduction_e.html

  • The copyright is in Takashi Yagisawa

    Translation Start Date: August 8th, 2018

    http://wingshome.co.jp/introduction_e.html

    WINGS CORPORATION

    Japan

    Doc. No. : WD14-001E

    Sheet 137 of 138

    Rev. No. : E0

    Title: Introduction of the inspection and testing for the

    industrial valves

    For reference:

    Reference example of approximate calorie calculation

    (Class 150 - 6 "Calculation example in the case of Gate Valve CF8. The value varies depending on the

    manufacturer.)

    Condition: heating temperature 200 ° C., fluid: helium

    ① The amount of heat required for heating Helium in the valve:

    W 1 = 1.16 × C 1 × d 1 × V 1 × Δt

    C1: Helium specific heat = 1.25 kg * cal / (kg * ° C)

    d 1: Helium density = 0.178 kg / m 3

    V1: Valve volume roughly 0.006 m3

    ⊿t: Heating from 0 ° C to 200 ° C

    ∴ W1 about 0.31 W

    ② Heat quantity required for heating the valve body:

    W 2 = 1.16 × C 2 × d 2 × V 2 × Δt

    C2: Specific heat of stainless steel = 0.118 kg * cal / (kg * ° C)

    d 2 × V 2 = 110 kg (Body & Bonnet material weight)

    ⊿t: Heating from 0 ° C to 200 ° C

    ∴ W 2 about 3010 W

    ③ Heat radiation of valve surface:

    W 2 = A × Q

    A: Valve surface area about 0.68 m 3

    Q: Heat dissipation loss coefficient Without heat retention: 3400 W / m 3

    ∴ W3 about 2312 W

    Total power: The amount of electricity required for heating up to 200 ° C in 1 hour is about 5.3 kW

    Class 150 - 6 "For Gate Valve CF8:

    Under heating conditions up to 200 ° C in 5 hours, winding a heater of about 1.06 kW is a measure of the

    test.

    http://wingshome.co.jp/introduction_e.html