3
AN 0032/A July 2008 Copyright © 2008 by AC Technology www.lenze-actech.com -508-278-900 For general information only. Content subject to change without notice. Application Note Input and output reactors serve very different purposes. Simply put, an input reactor protects the drive and an out- put reactor protects the motor. However, there are a few more details to determine the correct application. Input (Line) Reactors An input or line reactor helps protect a variable frequency drive (VFD) from input power line disturbances that could cause nuisance tripping or damage to the drive. An input (line) reactor also reduces the harmonics that the VFD generates back onto the line. Line reactors are sized based on the HP and voltage ratings of the drive in use. Lenze- AC Tech uses 3% or 5% reactors. Input (line) reactors should be used in these circumstances: The input line power is prone to have disturbances such as surges, spikes, transients, etc. The supply line power is very stiff (greater than 0 times the kVA rating of the connected VFD). Where harmonic distortion is a concern. (IEEE-59 Harmonic Control in Electrical Power Systems) Line reactors are connected in series between the input source and the VFD Controller. Refer to Figure for proper wiring installation. The reactor should be mounted as close to the drive as possible. Input Fuse Input Fuse Input Fuse Controller A1 A2 Motor B1 B2 C1 C2 Input Line Reactor Figure : Input (Line) Reactor 3% Impedance Line Reactors 3% impedance line reactors should be used to reduce power line transient voltages caused by capacitor switching, line notching, DC Bus over-voltage tripping and inverter over-current and over-voltage conditions. They improve the true input power factor and reduce cross-talk between drives. The input (line) reactor offers some protection to the drive in short-circuit conditions. If the supply transformer kVA rating is greater than ten times the drive kVA rating, then a line reactor is recommended to minimize damage to the drive in case the supply transformer ever shorts out. This line impedance is dependent on the short-circuit rating for the drive and on the supply power distribution transformer. Specifically, the line impedance must be greater than or equal to the ratio of the supply source transformer’s rating to the drive’s short circuit rating. For example, let’s say you have a 00kVA, 460V, 20A power transformer for your source and install a 3% line reactor in front of an MC series drive*. This means for the simplest calculation, the available short-circuit current would be 20A/.03 = 4000Amps. This is less than the MC series 5000A rating so the 3% line reactor would work fine. You can make this same calculation by determining the current of the supply transformer and the line reactor impedance. * The source transformer's impedance is not included because the difference in size makes it negligible. . 2. 3. When to Use a Line or Load Reactor Protecting the Drive or the Motor

When to Us a Line or Load Reactor

Embed Size (px)

DESCRIPTION

LineLoad Reactor

Citation preview

Page 1: When to Us a Line or Load Reactor

� AN0032/A� July2008Copyright©2008byACTechnology www.lenze-actech.com �-508-278-9�00 Forgeneralinformationonly.Contentsubjecttochangewithoutnotice.

Application Note

Inputandoutputreactorsserveverydifferentpurposes.Simplyput,aninputreactorprotectsthedriveandanout-putreactorprotectsthemotor.However,thereareafewmoredetailstodeterminethecorrectapplication.

Input (Line) Reactors

Aninputorlinereactorhelpsprotectavariablefrequencydrive(VFD)frominputpowerlinedisturbancesthatcouldcausenuisancetrippingordamagetothedrive.Aninput(line)reactoralsoreducestheharmonicsthattheVFDgeneratesbackontotheline.LinereactorsaresizedbasedontheHPandvoltageratingsofthedriveinuse.Lenze-ACTechuses3%or5%reactors.Input(line)reactorsshouldbeusedinthesecircumstances:

Theinputlinepowerispronetohavedisturbancessuchassurges,spikes,transients,etc.

Thesupplylinepowerisverystiff(greaterthan�0timesthekVAratingoftheconnectedVFD).

Whereharmonicdistortionisaconcern.(IEEE-5�9HarmonicControlinElectricalPowerSystems)

LinereactorsareconnectedinseriesbetweentheinputsourceandtheVFDController.RefertoFigure�forproperwiringinstallation.Thereactorshouldbemountedasclosetothedriveaspossible.

Input Fuse

Input Fuse

Input Fuse

Controller

A1 A2

MotorB1 B2

C1 C2

Input Line Reactor

Figure�:Input(Line)Reactor

3% Impedance Line Reactors

3%impedancelinereactorsshouldbeusedtoreducepowerlinetransientvoltagescausedbycapacitorswitching,linenotching,DCBusover-voltagetrippingandinverterover-currentandover-voltageconditions.Theyimprovethetrueinputpowerfactorandreducecross-talkbetweendrives.

Theinput(line)reactorofferssomeprotectiontothedriveinshort-circuitconditions.IfthesupplytransformerkVAratingisgreaterthantentimesthedrivekVArating,thenalinereactorisrecommendedtominimizedamagetothedriveincasethesupplytransformerevershortsout.Thislineimpedanceisdependentontheshort-circuitratingforthedriveandonthesupplypowerdistributiontransformer.Specifically,thelineimpedancemustbegreaterthanorequaltotheratioofthesupplysourcetransformer’sratingtothedrive’sshortcircuitrating.

Forexample,let’ssayyouhavea�00kVA,460V,�20Apowertransformerforyoursourceandinstalla3%linereactorinfrontofanMCseriesdrive*.Thismeansforthesimplestcalculation,theavailableshort-circuitcurrentwouldbe�20A/.03=4000Amps.ThisislessthantheMCseries5000Aratingsothe3%linereactorwouldworkfine.Youcanmakethissamecalculationbydeterminingthecurrentofthesupplytransformerandthelinereactorimpedance.

*Thesourcetransformer'simpedanceisnotincludedbecausethedifferenceinsizemakesitnegligible.

�.

2.

3.

WhentoUseaLineorLoadReactorProtectingtheDriveortheMotor

Lori
Technicon IEC-Website-800 Number
Page 2: When to Us a Line or Load Reactor

2 AN0032/A� July2008Copyright©2008byACTechnology www.lenze-actech.com �-508-278-9�00 Forgeneralinformationonly.Contentsubjecttochangewithoutnotice.

Application Note

5% Impedance Line Reactors

5%impedancelinereactorshavethesamebenefitsasthe3%reactorsplustheyprovidemaximumharmonicmiti-gationwithoutaddedcapacitance.Theseharmonicsignalsproducedistortionlevelsthatmaynotbeacceptableforcertainhighfrequencyornoisesensitiveequipment.UseofthemwillhelptocomplywiththeIEEE5�9Standardandreducemotoroperatingtemperatureandmotornoise.

Multiple Input (Line) Reactors

Inapplicationsinvolvingmultipledrivesinparallel,havingmorethanoneVFDconnectedtoacommonpowerlinerequiresonelinereactorperdrive.IndividualreactorswillprovideproperfilteringandoptimumsurgeprotectionforeachVFDandreducecrosstalkbetweeneachunit.AsinglereactorconnectedtomultipleVFDsdoesnotprovideadequateprotection,filteringorreduceharmonicdistortionwhenthesystemispartiallyloaded.

Eachlinereactor isconnectedinseriesbetweentheinputsourceandtheVFDController.RefertoFigure2forproperwiringinstallation.Eachsetofinputlinestothedriveshouldbeinitsownseparatesteelconduit.Thereactorshouldbemountedasclosetothedriveaspossible.

Input Fuse

Input Fuse

Input Fuse

Controller

A1 A2

MotorB1 B2

C1 C2

Input Fuse

Input Fuse

Input Fuse

Controller

A1 A2

MotorB1 B2

C1 C2

Input Line Reactors

Figure2:MultipleInput(Line)Reactors

Output (Load) Reactors

Anoutput(load)reactor,ontheotherhand,isusedtoprotectthemotorifthewiringdistancebetweentheVFDandmotorisverylong.ThedrivegeneratesahighfrequencyPWMthree-phaseoutputandnoisespikesaregeneratedontheleadingedgeofthesesignals.Thesenoisespikesgetamplifiedduetothelongcablelengthsandthead-ditionalcapacitanceofthecable.Theresultingvoltagecanexceedthemotor’speakvoltageratingwhereinsulationbreakdownoccurs.

Thegeneralruleofthumbisthatanoutputreactorshouldbeusedifthemotorwiringisover�00feet,butthisvaluevariesdependingonthemotor.IfthemotormeetstheNEMAMG-�Part3�standard,itispossibletohaveasmuchas300ftofcablingwithoutareactor.Ifitdoesnotmeetthestandard,themaximumcablelengthshouldbe�00ft.Also,ifthedistanceisbetween300and500ft,aloadreactormustbeinstalled.

Page 3: When to Us a Line or Load Reactor

3 AN0032/A� July2008Copyright©2008byACTechnology www.lenze-actech.com �-508-278-9�00 Forgeneralinformationonly.Contentsubjecttochangewithoutnotice.

Application Note

If thedistance isbetween500and�000ft,youwoulduseaspecial typeoffiltercalledadV/dTfilter,astheyprovidebetterprotectionattheseextremedistances.Thisalsovariesdependingonoutputcablespecs,shielding,powerconditions,andnoisesuppressionaswellasisolationtechniques.

LoadreactorsareconnectedinseriesbetweentheVFDControllerandthemotor.RefertoFigure3forproperwiringinstallation.Thereactorshouldbemountedasclosetothedriveaspossible.

Input Fuse

Input Fuse

Input Fuse

Controller

A1 A2

MotorB1 B2

C1 C2

Output Load Reactor

Figure3:OutputLoadReactor

Multiple Motors

Foranapplicationinvolvingmorethanonemotorbeingcontrolledbyasingledrive,asinglereactorcantypicallybeusedbetweentheVFDandthemotors.Notethateachmotorrequiresaseparatethermaloverloadforproperprotection.Thereactorshouldbesizedbasedonthetotalmotor/loadhorsepower.

TheloadreactorisconnectedinseriesbetweentheVFDControllerandthemotors.RefertoFigure4forproperwiringinstallation.Eachsetofmotorcablesshouldbeinaseparatesteelconduittoavoidnoiseandcrosstalkthatcancausenuisancetripping.Thereactorshouldbemountedasclosetothedriveaspossible.

Input Fuse

Input Fuse

Input Fuse

Controller

A1 A2

MotorB1 B2

C1 C2

Motor

Output Load Reactor

Figure4:Output(Load)Reactor&MultipleMotors

Lori
Technicon IEC-Website-800 Number