Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
Including sequential and exception tests
December 2012
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
2
Contents
Page
1. Purpose 3
2. Policy context 3
3. Brent’s Strategic Flood Risk Assessment 4
4. Brent’s Surface Water Management Plan 4
5. Area for Applying the Test 5
6. Findings 6
7. Changes to Wembley Area Action Plan 7
Appendices
A. Sequential Test 14
B. Site-specific Analysis 18
C. Brent’s Strategic Flood Risk Assessment (2007)
Extract - planning recommendations
34
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
3
1. Purpose
1.1 The National Planning Policy Framework (NPPF) requires Local Plans to apply a sequential, risk-
based approach to the locations of development in order to avoid flood risk. This document
fulfils these requirements by undertaking a sequential and, where appropriate, an exception test
for site proposals in the Wembley Area Action Plan. It also incorporates policy
recommendations in Brent’s Strategic Flood Risk Assessment Level 1 (2007), Wembley
Masterplan Level 2 Strategic Flood Risk Assessment (2008) and the Surface Water Management
Plan (2011).
1.2 All forms of flood risk are considered including:
• Fluvial – flooding from Wealdstone Brook
• Surface water flooding
• Ground water flooding
1.3 This document proposes changes and additions to the Wembley Area Action Plan in light of the
flood risk analysis and policy recommendations.
2. Policy Context
2.1 The National Planning Policy Framework (NPPF) (March 2012) requires Local Plans to apply a
sequential, risk-based approach to the locations of development in order to avoid flood risk. The
aim of the Sequential Test is to steer new development to areas with the lowest probability of
flooding. Development should not be allocated or permitted if there are reasonably available
sites appropriate for the proposed development in areas with a lower probability of flooding.
Where new development is exceptionally necessary in such areas, policy aims to make it safe
without increasing flood risk elsewhere and where possible, reducing flood risk overall.
2.2 Brent’s Strategic Flood Risk Assessment (SFRA) level 1 acknowledges that in areas like the
London Borough of Brent, restricting ‘more vulnerable’ development from areas designated as
Zone 3a (high probability of flooding) may heavily compromise the viability of existing
communities within the Borough. Where a local planning authority has identified that there is a
strong planning based argument for a development to proceed that does not meet the
requirements of the Sequential Test, it will be necessary for the Council to demonstrate that the
Exception Test can be satisfied. This document provides the analysis for the Sequential and
Exception Tests using the methodology and guidance set out in the NPPF Technical Guidance
(March 2012).
2.3 For the Exception Test to be passed:
• it must be demonstrated that the development provides wider sustainability benefits to the
community that outweigh flood risk, informed by a Strategic Flood Risk Assessment where
one has been prepared; and
• a site-specific flood risk assessment must demonstrate that the development will be safe for
its lifetime taking account of the vulnerability of its users, without increasing flood risk
elsewhere, and, where possible, will reduce flood risk overall.
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
4
3. Brent’s Strategic Flood Risk Assessment
3.1 Brent’s Strategic Flood Risk Assessment (SRFA) Level 1 (2007) provides a spatial overview of the
risks posed by flooding (from various sources) across the borough. The SFRA should be used by
the Council to inform the application of the Sequential Test. A Level 2 SFRA (2008) has been
prepared for the Wembley Masterplan Area which assesses flood risk on the sites in more detail.
3.2 When considering the suitability of sites for future development, the SFRA (2007) states:
It is considered unreasonable to restrict future development within areas that may have
suffered a localised flooding incident in years past. It is essential however not to overlook the
potential risk of localised flooding during the design process. Whilst the incidents that have
been identified will typically not result in widespread damage or disruption, a proactive
approach to risk reduction through design can mitigate the potential for damage, both to the
development itself and elsewhere. Specific development control recommendations have been
provided accordingly.
3.3 The SFRA provides an assessment of flood risk in Wembley. It says:
Wembley is situated to the West of the Borough bordering the River Brent in the South and
Wealdstone Brook to the East.
A number of properties in the area are in the Flood Risk Zone 3a, High Probability of River
Brent and Wealdstone Brook. There are some areas falling within Zone 2, Medium
Probability.
The majority of the Wembley Area belongs to Zone 1, Low Probability.
Even though the flood outline is relatively narrow, the number of properties affected by a
Zone 3a and 2 event could be high as the area is densely developed. The area near the
confluence of the Wealdstone Brook and River Brent near Tokyngton has been identified as a
problem area for combined sewer flooding.
Overview of Development Pressure
Wembley is a major city centre and Opportunity Area of the Borough for regeneration which
enjoy good transport links. High density residential developments are encouraged in the
Town Centre to promote regeneration objectives. Key development centres are in the
Wembley Park/Stadium area east of the town centre. As a major visitor centre and venue for
national and international sports events, the area is under tremendous pressure for
development.
4. Brent’s Surface Water Management Plan
4.1 Brent’s Surface Water Management Plan outlines the preferred surface water management
strategy for the London Borough of Brent and includes consideration of flooding from sewers,
drains, groundwater and runoff from land, small watercourses and ditches that occurs as a result
of heavy rainfall.
4.2 The Plan identifies Critical Drainage Areas (CDA) where multiple sources of flood risk (surface
water, groundwater, sewer, river) cause flooding in one or more Local Flood Risk Zones (LFRZ). A
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
5
LFRZ is defined as a discrete area of flooding that does not exceed the national criteria for a
‘Flood Risk Area’ but still affects houses, businesses or infrastructure.
4.3 In Wembley, the areas particularly susceptible to overland flow are formed by the river valleys of
the Wealdstone Brook and River Brent. Several stretches of the main line (Wembley Stadium),
are susceptible to surface water flooding and, if flooded, will impact services into and out of
London.
4.4 Most of the WAAP site proposals are within the Wembley Stadium Critical Drainage Area which
several areas of surface water ponding within the CDA affecting commercial property and critical
infrastructure. Critical Infrastructure affected- 2 x Electrical Installation. Sites W3, W4 and W6
are within a LFRZ.
4.5 Wembley is not an area where surface water flooding is likely to be caused by pluvial, sewer and
groundwater flooding.
4.6 The SWMP sets out recommendations for borough wide planning policies with the aim of
reducing surface water runoff. The Wembley Area Action Plan section of this document shows
how these recommendations have been incorporated.
4.7 From 2013 all new developments will be required to submit information to Brent’s SUDS
Approval Board (SAB) which has a duty to ensure that all new developments have incorporated
SUDS to deal with the surface water run off from the development.
5. Area for Applying the Test
5.1 This document applies the sequential test to each site proposal in the Wembley Area Action Plan
that falls within Flood Zones 2 and 3 and, where necessary, the exception test.
5.2 The geographical area of search over which the sequential test will be applied is restricted to the
Wembley Growth Area, defined in Core Strategy policy CP7, and taken forward by the Wembley
Area Action Plan.
5.3 Similarly, the source of reasonably available alternative sites for comparison includes any sites
within the Wembley Growth Area that are known to the council and that are available and
suitable for delivering growth. Specifically, these are sites W1-W31 in the Wembley Area Action
Plan. Some sites are not appropriate for certain uses; for example residential use in the
Strategic Industrial Location (sites W29-31) or retail outside the town centre (sites W14-W19
and W25-W31). When comparing sites, only those capable of accommodating the same use
class(es) will be considered ‘available’.
5.4 The reason for limiting the geographical area of search for the sequential test and the source of
alternative sites to the Growth Area is because Wembley is designated as an Opportunity Area in
the London Plan with targets for growth including 11,000 new jobs and 11,500 new homes.
London Plan Policy 2.13 requires the borough to develop detailed proposals for the Wembley
Opportunity Area in order to deliver these strategic targets.
5.5 London Plan Table A1.1 Opportunity Areas sets out the following policy direction for Wembley:
New housing and leisure-related development should be integrated with the iconic and
world-class stadium and other facilities, including the Arena and Conference Centre.
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
6
Supported by upgrades to the three stations, improved public transport will play a key role in
managing heavy demand for mass movement, links between the stations and the strategic
leisure facilities should be improved. Development should contribute to the regeneration,
vitality and viability of Wembley as a town centre, including its expansion eastwards.
Proposals should enhance permeability and connectivity to the wider hinterland and the
potential to locate a civic facility including a school adjacent to Olympic Way should be
explored.
5.6 In order to deliver this growth in Wembley all available suitable sites must be considered. It is
not appropriate to consider sites outside of Wembley Growth Area for comparison because they
do not form part of the Growth Area and cannot contribute to meeting the identified growth.
5.7 The source used for comparing flood risk between sites is the council’s Site Specific Allocations
PPS25 Sequential Test (June 2010), Strategic Flood Risk Assessment Level 2: Wembley
Masterplan Area (November 2008) and associated map.
6. Findings
6.1 The council has a proactive approach to risk reduction when considering the suitability of sites
for future development in the Wembley Area Action Plan, in line with the recommendations of
the SFRA.
6.2 The table in Appendix A compares each of the Wembley Area Action Plan proposals sites (W1-
W31) with any reasonably available sites in the Wembley Growth Area with a lower probability
of flooding that would be appropriate to the type of land use proposed.
6.3 The analysis shows that the majority of available sites in the Wembley Area Action Plan are in
Flood Zone 1 where all development uses are permitted and therefore the sequential test is not
necessary. For all sites however, it is essential that sustainable drainage techniques are
stipulated as a development control recommendation to reduce the runoff from the site,
thereby not exacerbating existing localised drainage problems nearby. This is a key
recommendation of the Level 1 SFRA (section 6.4.8).
6.4 Detailed analysis was carried out on the remaining eight sites which fall partly or wholly into
flood zones 2 and 3 shown at Appendix B.
6.5 Three of the sites (W13, W15, W27) are in flood zones 1 and 2. The analysis found that there are
no reasonably available alternative sites wholly in Flood Zone 1, but there is low flood risk
vulnerability as the proposed uses are compatible with flood zones 1 and 2.
6.6 Four of the sites (W14, W16, W21, W26) are in flood zones 1-3. The analysis found that there
are no reasonably available alternative sites in zones 1 and 2. More vulnerable uses such as
residential, residential care homes, certain community facilities, education, student
accommodation and hotels require an Exception Test in flood zone 3a. None of the proposed
uses are compatible with flood zone 3b. An Exception Test was carried out for each of these
sites and included in the site specific analysis below.
6.7 One site (W25) is in flood zones 2-3. The analysis found that there are no reasonably available
alternative sites in zones 1 and 2. More vulnerable uses such as residential, residential care
homes, certain community facilities, education, student accommodation and hotels require an
Exception Test in flood zone 3a. None of the proposed uses are compatible with flood zone 3b.
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
7
An Exception Test was carried out for each of these sites and included in the site specific analysis
below.
6.8 Sites W3, W4 and W6 are in a Local Flood Risk Zone (LFRZ) in the Wembley Stadium Critical
Drainage Area (CDA) which has several areas of surface water flooding affecting property and
critical infrastructure. The SWMP identifies preferred options for mitigating flood risk in the
LFRZ which include Road side Rain Garden, Detention basins and Land Management practices.
There may be opportunities to alleviate surface water flooding as part of the development of
this site.
7. Changes to Wembley Area Action Plan
7.1 This section sets out additions and changes to the draft Wembley Area Action Plan in light of the
findings from the NPPF sequential and exception tests, Brent’s Strategic Flood Risk Assessment
Level 1 (2007), Wembley Masterplan Level 2 Strategic Flood Risk Assessment (2008) and the
Surface Water Management Plan (2011).
Proposed changes to Policy WEM35
7.2 In line with para 100 of the National Planning Policy Framework (NPPF) and in order to improve
the strategic approach to flood risk in policy WEM35, the following changes are suggested:
WEM35: Flood Risk
All proposed development in Flood Zones 2 and 3 will require a detailed Flood Risk Assessment
(FRA), in accordance with Section 6.7 of Brent’s Strategic Flood Risk Assessment.
Applications will be assessed against the site-specific flood risk mitigation requirements set out
for individual Site Proposals.
Development is not suitable in Flood Zone 3b.
Application of a site-level sequential approach will be expected to locate development towards
areas of lowest risk within the site. More vulnerable development will not usually be
appropriate in Flood Zone 3a. Where it is proposed in exceptional circumstances, an Exception
Test will be required.
Proposals within Flood Risk Zones 3a (High Probability and Climate Change) and 2 (Medium
Probability) will be required to pass the Sequential Test, and where a site is affected by Flood
Zone 3a, the Exception Test must be applied. Proposals will need to demonstrate how flood risk
is reduced by sequential layout of the site and form of development. All proposals for
development in Flood Zones 2 and 3a&b will require a full Flood Risk Assessment (FRA).
Proposals in Flood Zone 1 which are over 1 hectare in size will also require a site specific FRA.
Development proposals in the area above must demonstrate that there will be no net loss in
floodplain storage nor an increase in maximum flood levels, within adjoining properties as
recommended by Brent's Strategic Flood Risk Assessment Report Level 1 (2007).
Developments will be required to implement SUDS to ensure that runoff from the site (post
redevelopment) does not exceed Greenfield runoff rates.
In order to reduce surface water flood risk in the area, all major proposals will be required to
apply SUDS in accordance with Brent Surface Water Management Plan.
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
8
Developers will also be required to demonstrate whether there is sufficient capacity both on and
off site in the foul sewer network to support development. Where insufficient capacity exists
developers will be required to identify how any necessary upgrades will be delivered ahead of
the occupation of development.
Proposed changes to Chapter 10: Response to climate change
7.3 The SWMP sets out recommendations for borough wide planning policies with the aim of
reducing surface water runoff. The table below shows how the policy requirements have been
incorporated into the Wembley Area Action Plan, where appropriate.
SWMP Policy Requirement Wembley Area Action Plan
Wembley Central Critical Drainage Area Para 10.13 –
In most of the urban area, roads and land are
usually impermeable which can lead to surface
water flooding. Much of Wembley is prone to
surface water flooding. The Flood and Water
Management Act 2010 requires local
authorities across England and Wales to
develop, maintain, apply and monitor a
strategy for local flood risk management in
their areas. Brent Surface Water Management
Plan (BSWMP), which contains the
Preliminary Flood Risk Assessment and a Flood
Risk Management Plan, designates the
Wembley Stadium Critical Drainage Area (CDA)
which has several areas of surface water
flooding affecting property and critical
infrastructure. The SWMP identifies mitigation
measures which aims to help manage and
reduce surface water flood risk in Brent.
Wembley Stadium CDA Action - Encourage
uptake of green roofs in new developments.
WEM34
Wembley Stadium CDA Action – Encourage
permeable paving
WEM35
Wembley Stadium CDA Action - Identify
potential locations suitable for retrofitting
Road Side Rain Gardens, and where swales
and detention basins could be installed
Add text to 10.14:
Measures to alleviate surface water flooding
through SUDS will be required as part of the
development of sites W3-W4, W6-W20 and
W25-W29.
Ponds should be included as part of a wider
SuDS scheme for the redevelopment of this
area
Add “ponds” to para 10.14
Undertake further topographical survey to
determine the extent to which kerbs could
be altered
Add “re-profiling of ground levels” to para
10.14
Undertake further topographical survey to
determine the extent to which ground levels
could be changed
Add “re-profiling of ground levels” to para
10.14
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
9
A specific river corridor management policy
to provide flood defence, recreation,
amenity and biodiversity
WEM42
Development must achieve surface water
runoff at or below present greenfield runoff
rates
Add to policy WEM35
Development must be safe from flooding
over its whole lifetime, including for the
impacts of climate change, and should use
all opportunities to reduce flood risk overall
Add new para to supporting text:
10.16 Specific flood risk reduction measures
and Flood Risk Assessment requirements are
set out for each site proposal (chapters 12-16).
This includes recommendations from the SFRA,
SWMP and site-specific sequential
considerations. From 2013 all new
developments will be required to submit
information to Brent’s SUDS Approval Board
(SAB) which has a duty to ensure that all new
developments have incorporated SUDS to deal
with the surface water run off from the
development.
Add flood mitigation/ FRA recommendations
for each site proposal (chapters 12-16 – see
section 7.5 below).
Green Infrastructure within development
should protect existing floodplains and
provide an opportunity for linking habitats
and creating environmental highways
through the integration of SuDS through
urban areas
See above
SuDS should be used to control the rate and
volume of runoff. Pollution controls should
be incorporated within them to protect and
improve watercourse quality
See above
All developments exceeding 0.5 hectares
must include source control and/or natural
surface water storage options within the site
boundary; and design for greenfield run off
rates
See above
New developments should demonstrate that
during events that exceed the design
capacity of the surface water drainage
system excess water is safely stored or
conveyed from the site without adverse
impacts
See above
The long term management and
responsibility for the maintenance of any
new SuDS systems must be agreed with the
council (until such time as the SuDS Approval
Body is in place) prior to the granting of
planning permission
See above
All development pre commencement of See above
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
10
construction must submit and be approved
by Brent Drainage Section (LLFA) detailed
drainage design including storage
calculations for the attenuated flows and
flow restriction methods
All new properties within a fluvial flood zone
or local flood risk zone should have a
finished floor level at least 0.3m above
surrounding ground levels and be fitted with
flood resilience measures up to 0.5m above
finished floor level. (However this will not
negate other planning requirements, for
example to achieve inclusive access to new
development)
See above
Guidelines on the provision of onsite storage
including the AEP event and necessary
freeboard
Technical information as part of Flood Risk
Management Plan
Guidelines on the need for strategic
mitigation measures, particularly in
identified regeneration areas, required to
contribute to managing surface water flood
risk on a wider scale
WEM35, development management policies
Guidance on what is classed as permitted
development within a CDA or policy area
and any deviation from national guidance via
local development orders for example
Include in borough-wide development
management policy
Load-reduction targets must be achieved
when assessing the post-developed sites
SuDS treatment train
Part of site assessment criteria
7.4 In light of policy requirements from the SWMP and elsewhere, the following changes are
proposed for WAAP paragraphs 10.11-10.15 as well as an additional paragraph inserted as
10.16:
Flooding
10.11 There are two types of floods in the area, one is associated with the river when the actual
amount of river flow is larger than the amount that the channel can hold, and river will overflow
its banks and flood the areas alongside the river. Land adjacent to the Wealdstone Brook is the
area at risk of flooding. The map shows the areas at risk of flooding. Brent seeks to ensure that
all new development in flood risk areas is appropriately flood resilient and resistant and that
any residual risk can be safely managed.
10.12 As required by the National Planning Framework, the council has undertaken a sequential
approach should be used in areas known to be for sites at risk from any form of flooding
including fluvial and surface water flooding. Planning recommendations are provided for sites
at risk of flooding in the Site Proposals chapters. Inappropriate The council has a proactive
approach to risk reduction when considering the suitability of sites for future development in
the Wembley Area Action Plan, in line with the recommendations of the SFRA. New
development in areas at risk of flooding will be required to apply a site-level sequential test to
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
11
ensure should be avoided by directing development is steered away from areas at highest risk
and located in line with the NPPF flood risk vulnerability classification but where development is
necessary, making it safe without increasing flood risk elsewhere.
10.13 In most of the urban area, roads and land are usually impermeable which can lead to
surface water flooding. Much of Wembley is prone to surface water flooding. The Flood and
Water Management Act 2010 requires local authorities across England and Wales to develop,
maintain, apply and monitor a Brent’s Surface Water Management Plan (SWMP) provides a
strategy for local flood risk management in the borough. their areas. Brent Surface Water
Management Plan (BSWMP), which contains the Preliminary Flood Risk Assessment and a Flood
Risk Management Plan, The document identifies and designates a Critical Drainage Area (CDA)
for the Wembley Stadium area which has several areas of surface water flooding affecting
property and critical infrastructure. Three WAAP sites fall into a Local Flood Risk Zone (LFRZ).
aims to help manage and reduce surface water flood risk in Brent.
10.14 The Act also introduces the requirements for d Developers are required to construct
include sustainable urban drainage systems (SUDS) in their schemes. The SWMP identifies
specific SUDS measures for the Wembley Stadium CDA to relieve pressures on the drainage
system, reduce flood risk and the demand for fresh water. These include rainwater harvesting
and grey water recycling, can help relieve pressures on the drainage system, It can reduce flood
risk and the demand for fresh water. SUDS such as green roofs, filter strips and swales, storm
water storage tanks, permeable and porous pavements, re-profiling of ground levels, basins,
ponds, reed beds can help reduce the volume and speed of water flowing into drains and
eliminate surface water flooding. BSWMP favours the application of SUDS. Measures to
alleviate surface water flooding through SUDS will be required as part of the development of
sites W3-W4, W6-W20 and W25-W29. Specific SUDS requirements for sites in the LFRZ are set
out in the appropriate Site Proposals.
10.15 In addition, Most of the sewer network in the Wembley area is undersized. Careful
consideration must be given to issues of sewer flooding, both on and off site, as a result of new
development. Developers may be required to carry out studies to ascertain whether proposed
development will lead to overloading of the existing sewer infrastructure.
10.16 Specific flood risk reduction measures and Flood Risk Assessment requirements are set
out for each site proposal (chapters 12-16). This includes recommendations from the SFRA,
SWMP and site-specific sequential considerations. From 2013 all new developments will be
required to submit information to Brent’s SUDS Approval Board (SAB) which has a duty to
ensure that all new developments have incorporated SUDS to deal with the surface water run
off from the development.
Proposed changes to Chapters 12-16: Site Proposals
7.5 Key recommendations should be incorporated for each site affected by flooding. It is suggested
the following additional paragraphs are added or replace the section on flooding for Site
Proposals (chapters 12-16):
W3
Site W3 is in a Local Flood Risk Zone (LFRZ) in the Wembley Stadium Critical Drainage Area (CDA)
which has several areas of surface water flooding affecting property and critical infrastructure.
Brent’s Surface Water Management Plan (SWMP) identifies mitigation measures for the LFRZ
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
12
which include road side rain gardens, detention basins and re-profiling ground levels. Measures
to alleviate surface water flooding will be required as part of the development of this site.
W4
Part of Site W4 is in a Local Flood Risk Zone (LFRZ) in the Wembley Stadium Critical Drainage
Area (CDA) which has several areas of surface water flooding affecting property and critical
infrastructure. Brent’s Surface Water Management Plan (SWMP) identifies mitigation measures
for the LFRZ which include road side rain gardens, detention basins and re-profiling ground
levels. Measures to alleviate surface water flooding will be required as part of the development
of this site.
W6
Site W6 is in a Local Flood Risk Zone (LFRZ) in the Wembley Stadium Critical Drainage Area (CDA)
which has several areas of surface water flooding affecting property and critical infrastructure.
Brent’s Surface Water Management Plan (SWMP) identifies mitigation measures for the LFRZ
which include road side rain gardens, detention basins and re-profiling ground levels. Measures
to alleviate surface water flooding will be required as part of the development of this site.
W13
The site is in flood zones 1 and 2. All proposed development will require a detailed Flood Risk
Assessment (FRA), in accordance with Section 6.7 of the Brent Borough SFRA. The ‘sequential
approach’ at site level should be applied to steer more vulnerable development such as
residential, student accommodation, hotels, and certain community uses towards areas of
lowest risk within the site; north west area and southern edge. Density should be varied to
reduce the number of vulnerable units in high risk areas. Further site-specific details are set out
in the sequential test assessment for the WAAP.
W14
The site is in flood zones 1-3. All proposed development will require a detailed Flood Risk
Assessment (FRA), in accordance with Section 6.7 of the Brent Borough SFRA. While the council
considers that developing the site provides wider sustainability benefits to the community that
outweigh flood risk, a ‘sequential approach’ at site level should be applied to steer more
vulnerable development such as education, student accommodation and hotels uses towards
areas of lowest risk within the site; to the western area. None of the proposed uses are
compatible with flood zone 3b. Density should be varied to reduce the number of vulnerable
units in high risk areas. A minimum 8 metres buffer zone must be provided for the waterway
and development should contribute to the re-naturalisation of Wealdstone Brook. Further site-
specific details are set out in the sequential test assessment for the WAAP.
W15
The site is in flood zones 1 and 2. All proposed development will require a detailed Flood Risk
Assessment (FRA), in accordance with Section 6.7 of the Brent Borough SFRA. The ‘sequential
approach’ at site level should be applied to steer more vulnerable development such as
residential, and hotel uses towards areas of lowest risk within the site; area from north west to
south. Density should be varied to reduce the number of vulnerable units in high risk areas.
Further site-specific details are set out in the sequential test assessment for the WAAP.
W16
The site is in flood zones 1-3. All proposed development will require a detailed Flood Risk
Assessment (FRA), in accordance with Section 6.7 of the Brent Borough SFRA. While the council
considers that developing the site provides wider sustainability benefits to the community that
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
13
outweigh flood risk, a ‘sequential approach’ at site level should be applied to steer more
vulnerable development towards areas of lowest risk within the site; to the north. None of the
proposed uses are compatible with flood zone 3b. Density should be varied to reduce the
number of vulnerable units in high risk areas. A minimum 8 metres buffer zone must be
provided for the waterway and development should contribute to the re-naturalisation of
Wealdstone Brook. Further site-specific details are set out in the sequential test assessment for
the WAAP.
W21
The site is in flood zones 1-3. All proposed development will require a detailed Flood Risk
Assessment (FRA), in accordance with Section 6.7 of the Brent Borough SFRA. While the council
considers that developing the site provides wider sustainability benefits to the community that
outweigh flood risk, a ‘sequential approach’ at site level should be applied to locate homes
towards area of lowest risk within the site; along Brook Avenue. The proposed use is not
compatible with flood zone 3b. Density should be varied to reduce the number of vulnerable
units in high risk areas. A minimum 8 metres buffer zone must be provided for the waterway
and development should contribute to the re-naturalisation of Wealdstone Brook. Further site-
specific details are set out in the sequential test assessment for the WAAP.
W25
The site is in flood zones 2-3. All proposed development will require a detailed Flood Risk
Assessment (FRA), in accordance with Section 6.7 of the Brent Borough SFRA. While the council
considers that developing the site provides wider sustainability benefits to the community that
outweigh flood risk, a ‘sequential approach’ at site level should be applied to steer more
vulnerable development such as residential uses towards areas of lowest risk within the site;
northern and southern areas. None of the proposed uses are compatible with flood zone 3b.
Density should be varied to reduce the number of vulnerable units in high risk areas. Further
site-specific details are set out in the sequential test assessment for the WAAP.
W26
The site is in flood zones 1-3. All proposed development will require a detailed Flood Risk
Assessment (FRA), in accordance with Section 6.7 of the Brent Borough SFRA. While the council
considers that developing the site provides wider sustainability benefits to the community that
outweigh flood risk, a ‘sequential approach’ at site level should be applied to steer more
vulnerable development such as residential, residential care homes, and certain community uses
towards areas of lowest risk within the site; western and southern areas. None of the proposed
uses are compatible with flood zone 3b. Density should be varied to reduce the number of
vulnerable units in high risk areas. Further site-specific details are set out in the sequential test
assessment for the WAAP.
W27
The majority of the site is in flood zone 1; however there are small sections of flood zone 2
adjacent to the Wealdstone Brook. The buffer strip will remove the developable area of the site
wholly into flood zone 1.
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
14
Appendix A – Sequential Test
ID Name Type Existing use
Proposed / Potential use
Flood Zone
Known Surface / Ground Water Issues
Permissible Land Use (Sequential Test) Proposed Uses Compatible?
Site in FZ1?
Alternative site in FZ1?
Site in FZ 2?
Alternative site in FZ2?
Site in FZ3?
Alternative site in FZ3a?
Planning solution
Essential Infrastructure
Highly Vulnerable
More Vulnerable
Less Vulnerable
Water Compatible
W1 Wembley West End
Brownfield
Retail, residential and carpark
Mixed use - retail/residential /car park/bus lane
1 No ✓ yes Development in Zone 1 should consider the requirements of SFRA Section 6.4.8.
W2 London Road
Brownfield
Retail, office, takeaway, restaurant
Mixed use – retail, town centre uses
1 No ✓ yes Development in Zone 1 should consider the requirements of SFRA Section 6.4.8.
W3 Chiltern Line Cutting North
Brownfield
Railside embankments
Mix use retail, residential, office & open space
1 Yes LFRZ
✓ yes Development in Zone 1 should consider the requirements of SFRA Section 6.4.8. Mitigation requirements for LFRZ in SWMP.
W4 Wembley High Road/ Chiltern Line Cutting South
Brownfield Office
Mixed use - hotel & retail
1 Yes LFRZ
✓ yes Development in Zone 1 should consider the requirements of SFRA Section 6.4.8. Mitigation requirements for LFRZ in SWMP.
W5 Copland School & Brent House
Brownfield Office, petrol filling station & residential
Mixed use - residential/ office/retail
1 No ✓ yes Development in Zone 1 should consider the requirements of SFRA Section 6.4.8.
W6 South Way Site
Brownfield
Vacant Mixed use including retail, Pubs, bars, cafes, residential and student accommodation
1 Yes LFRZ
✓ yes Development in Zone 1 should consider the requirements of SFRA Section 6.4.8. Mitigation requirements for LFRZ in SWMP.
W7 Mahatma Gandhi House
Brownfield
Office Residential or office use
1 No ✓ yes Development in Zone 1 should consider the requirements of SFRA Section 6.4.8.
W8 Land West of Stadium
Brownfield
Under construction
Mixed use – retail, leisure, housing, student accommodation, hotel
1 No ✓ yes Development in Zone 1 should consider the requirements of SFRA Section 6.4.8.
W9 York House
Brownfield
Office Mixed use 1 No ✓ yes Development in Zone 1 should consider the requirements of SFRA Section 6.4.8.
W10 Dexion House
Brownfield
Office Mixed use - retail, office, leisure, residential, student accommodation and hotel
1 No ✓ yes Development in Zone 1 should consider the requirements of SFRA Section 6.4.8.
W11 Malcolm Brownfield Cleared site Mixed use - retail, 1 No ✓ yes Development in Zone 1
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
15
ID Name Type Existing use
Proposed / Potential use
Flood Zone
Known Surface / Ground Water Issues
Permissible Land Use (Sequential Test) Proposed Uses Compatible?
Site in FZ1?
Alternative site in FZ1?
Site in FZ 2?
Alternative site in FZ2?
Site in FZ3?
Alternative site in FZ3a?
Planning solution
Essential Infrastructure
Highly Vulnerable
More Vulnerable
Less Vulnerable
Water Compatible
House office, leisure, residential, hotel and community use.
should consider the requirements of SFRA Section 6.4.8.
W12 North West Lands
Brownfield
Demolition and construction site
Mixed use - Civic centre, retail, office, leisure, residential, student accommodation, hotel and community use.
1 No ✓ yes Development in Zone 1 should consider the requirements of SFRA Section 6.4.8.
W13 Stadium Retail Park
Brownfield
Retail Mixed use - retail, office, leisure, student accommodation, hotel and community use with a limited amount of residential.
1,2 No ✓
No highly vulnerable uses proposed on site
yes no no Yes no N/A Land use in Zone 2 should be restricted to ‘water-compatible’, ‘less vulnerable’ and ‘more vulnerable’ category, or essential infrastructure, with reference to SFRA section 6.4.7
W14 Arena House
Brownfield
Vacant Mixed use - offices, education, student housing or hotel
1 No ✓ yes Development in Zone 1 should consider the requirements of SFRA Section 6.4.8.
W14 Crescent House
Brownfield
Education Mixed use - offices, education, student housing or hotel
1,2,3 No Exception Test required for education, student accommodation, hotels in 3a; None of the uses are compatible with 3b
yes no yes no yes no Development within Zone 3a should be restricted to ‘less vulnerable’ land uses with regard to SFRA sections 6.4.4-6. ‘More vulnerable’ land uses should be steered towards zones 1&2
W15 Apex & Karma House
Brownfield
Industrial and office units
Mixed use - Residential, commercial, workspace
1,2 No ✓
No highly vulnerable uses proposed on site
yes no yes no no N/A Land use in Zone 2 should be restricted to ‘water-compatible’, ‘less vulnerable’ and ‘more vulnerable’ category, or essential infrastructure, with reference to SFRA section 6.4.7
W16 1 Olympic Way
Brownfield
Office Mixed use to include office
1,2,3 No Partly. Any ‘more vulnerable’ uses proposed as part of mixed use scheme will be subject to an Exception Test
yes no yes no yes no Development within Zone 3a should be restricted to ‘less vulnerable’ land uses with regard to SFRA sections 6.4.4-6. ‘More vulnerable’ land uses should be steered towards zones 1&2
W17 Olympic Way Office
Brownfield
Office Mixed use – Office, hotel, residential, cafes, restaurants, bars, open space
1 No ✓ yes Development in Zone 1 should consider the requirements of SFRA Section 6.4.8.
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
16
ID Name Type Existing use
Proposed / Potential use
Flood Zone
Known Surface / Ground Water Issues
Permissible Land Use (Sequential Test) Proposed Uses Compatible?
Site in FZ1?
Alternative site in FZ1?
Site in FZ 2?
Alternative site in FZ2?
Site in FZ3?
Alternative site in FZ3a?
Planning solution
Essential Infrastructure
Highly Vulnerable
More Vulnerable
Less Vulnerable
Water Compatible
W18 Wembley Retail Park
Brownfield
Retail, restaurant
Residential 1 No ✓ yes Development in Zone 1 should consider the requirements of SFRA Section 6.4.8.
W19 Stadium Car Park
Brownfield
Car park Mixed use including leisure
1 No ✓ yes Development in Zone 1 should consider the requirements of SFRA Section 6.4.8.
W20 Cottrelll House
Brownfield
Residential, office and restaurant
Mixed use - residential, retail, commercial and community facilities
1 No ✓ yes Development in Zone 1 should consider the requirements of SFRA Section 6.4.8.
W21 21-31 Brook Avenue
Brownfield
Residential Residential 1,2,3 No Partly. An Exception Test is required for residential uses in 3a. Residential is not compatible with Zone 3b
yes no yes no yes no Development within Zone 3a should be restricted to ‘less vulnerable’ land uses with regard to SFRA sections 6.4.4-6. ‘More vulnerable’ land uses should be steered towards zones 1&2
W22 Wembley Park Station Car Park
Brownfield
Car park Residential 1 No ✓
yes Development in Zone 1 should consider the requirements of SFRA Section 6.4.8.
W23 The Torch/ Kwik Fit
Brownfield
Public house, Kwik Fit
Mixed use – residential, retail
1 No ✓ yes Development in Zone 1 should consider the requirements of SFRA Section 6.4.8.
W24 Town Hall Brownfield Listed building with administrative, political and ceremonial roles
Mixed use - office/residential/ community
1 No ✓ yes Development in Zone 1 should consider the requirements of SFRA Section 6.4.8.
W25 Amex House
Brownfield
Industry Mixed use - residential/ industry
2,3 No Partly. An Exception Test is required for residential uses in 3a. None of the uses are compatible with Zone 3b
No no yes no yes no Development within Zone 3a should be restricted to ‘less vulnerable’ land uses with regard to SFRA sections 6.4.4-6. ‘More vulnerable’ land uses should be steered towards zones 1&2
W26 Watkin House
Brownfield Car repair garages, industrial, storage and ancillary office buildings.
Office, leisure, residential, managed affordable workspace, community use
1,2,3 No Partly. An Exception Test is required for residential, residential
yes no yes no Yes no Development within Zone 3a should be restricted to ‘less vulnerable’ land uses with regard to SFRA sections 6.4.4-6. ‘More vulnerable’ land uses
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
17
ID Name Type Existing use
Proposed / Potential use
Flood Zone
Known Surface / Ground Water Issues
Permissible Land Use (Sequential Test) Proposed Uses Compatible?
Site in FZ1?
Alternative site in FZ1?
Site in FZ 2?
Alternative site in FZ2?
Site in FZ3?
Alternative site in FZ3a?
Planning solution
Essential Infrastructure
Highly Vulnerable
More Vulnerable
Less Vulnerable
Water Compatible
care homes, and some community facilities uses in 3a. None of the uses are compatible with Zone 3b
should be steered towards zones 1&2
W27 Euro Car Parts
Brownfield
Retail, industrial Mixed use - office, leisure, residential, student accommodation, managed affordable workspace, hotel and community use
1,2 No ✓
No highly vulnerable uses proposed on site
yes no yes no no N/A The proposed buffer strip will remove the developable area of the site wholly into flood zone 1. Development in Zone 1 should consider the requirements of SFRA Section 6.4.8.
W28 First Way Brownfield
Industrial/retail /warehouses /waste facility
residential/offices/leisure
1 No ✓ yes Development in Zone 1 should consider the requirements of SFRA Section 6.4.8.
W29 Second Way
Brownfield
Light industry, offices, storage
Offices, light industry, storage and distribution, some transport related functions, utilities and wholesale markets.
1 No ✓ yes Development in Zone 1 should consider the requirements of SFRA Section 6.4.8.
W30 Drury Way
Brownfield
Builder's storage yard and depot
Industrial and employment uses
1 No ✓ yes Development in Zone 1 should consider the requirements of SFRA Section 6.4.8.
W31 Great Central Way
Brownfield
Vacant site Industrial, warehousing or other business uses
1 No ✓ yes Development in Zone 1 should consider the requirements of SFRA Section 6.4.8.
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
18
Appendix B - Site-Specific Analysis
Site: W13 Stadium Retail Park
Key
Flood Zone 2 Flood Zone 3 Site Boundary/Reference
Medium Probability of flooding High Probability of flooding
Site Information
Area of Site (Ha): 1.1 hectares
Flood Zone(s) 1,2
Proposed Land Use: Mixed use development with predominantly commercial uses,
including retail, office, leisure, student accommodation, hotel
and community use with a limited amount of residential.
Vulnerability Classification of uses: Highly vulnerable: none
More vulnerable: student accommodation, hotels, some
community uses, residential
Less vulnerable: office, leisure
Sequential Test: More vulnerable uses are compatible with Flood Zones 1&2
Less vulnerable uses are compatible with Flood Zones 1&2
Overview of Flood Risk from SFRA Level 2: Wembley Masterplan Area
• Source of Flooding – Wealdstone Brook
• The site is not situated in the immediate vicinity of the river
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
19
• Approx 70% of the site lies in Flood Zone 2 with a medium probability of flooding. The remainder is
in Flood Zone 1
• The site is offered a degree of protection in the form of the bordering wall
• Flood depths are shallow and the speed of the flood waters will be negligible
• Water is unlikely to inundate the site for any longer than approximately 6 hours
• Risk to life will be low under normal operating conditions
Planning Recommendations from SFRA Level 2: Wembley Masterplan Area
• Refer to Appendix C for Strategic Flood Risk Assessment SFRA) Level 1 (2007) recommendations for
Future Development within Zone 2 Medium Probability and Zone 1 Low Probability
• All proposed development will require a detailed Flood Risk Assessment (FRA), in accordance with
Section 6.7 of the Brent Borough SFRA
• The ‘sequential approach’ at site level should be applied to steer development towards areas of
lowest risk within the site
• Density should be varied to reduce the number of vulnerable units in high risk areas
• A positive reduction in the risk of flooding within the Borough must be demonstrated as an outcome
of the proposed development
• Floor levels must be situated above the 1 in 100 year fluvial predicted maximum flood level plus
climate change, incorporating an allowance for freeboard (refer to section 6.8 of the SFRA)
• Implement SUDS to ensure that runoff from the site (post redevelopment) does not exceed
Greenfield runoff rates. Any SUDS design must take due account of groundwater and geological
conditions (refer Section 6.9 of the SFRA)
• To ensure the safety of the residents and employees during a flood, access and egress routes must
be designed to meet Environment Agency defined criteria, as set out in Appendix D of the SFRA
• Ensure that there is no net loss in floodplain storage as a result of the proposed development
• It must be demonstrated that the proposed development does not result in an increase in maximum
flood levels, within adjoining properties
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
20
Site: W14 Crescent House
Key
Site Information
Area of Site (Ha): 0.37 hectares
Flood Zone(s) 1,2,3
Proposed Land Use: Offices, education, student housing or hotel
Vulnerability Classification of uses: Highly vulnerable: none
More vulnerable: education, student accommodation, hotels
Less vulnerable: office
Sequential Test: More vulnerable uses are compatible with Flood Zones 1&2
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
21
Less vulnerable uses are compatible with Zones 1,2&3a
An Exception Test is required for ‘more vulnerable’ uses in 3a
None of the proposed uses are compatible with Zone 3b
Exception Test • Developing the site to deliver new jobs and homes in the
Wembley Growth Area provides wider sustainability
benefits to the community that outweigh flood risk
• Any development on W13 must meet the planning
requirements set out below in order to meet the second
part of the exception test
Overview of Flood Risk
• Source of Flooding – Wealdstone Brook
• The majority of the site is situated within Flood Zone 2 Medium Probability.
• Small areas adjoining the watercourse fall within Flood Zone 3a High Probability
• The remainder is in Flood Zone 1
• The site is not offered any form of protection from raised formal defences
• The depth of flooding across much of the site is likely to be minimal
• Floodwaters will inundate the site for a short period, not exceeding 12 hours
• The potential risk to life is considered negligible
• The potential risk of groundwater flooding within the site is considered negligible
Planning Recommendations from SFRA Level 2: Wembley Masterplan Area
• Refer to Appendix C for Strategic Flood Risk Assessment SFRA) Level 1 (2007) recommendations for
Future Development within Zone 3b Functional Floodplain (Undeveloped Areas), Zone 2 Medium
Probability and Zone 1 Low Probability
• All proposed development will require a detailed Flood Risk Assessment (FRA), in accordance with
Section 6.7 of the Brent Borough SFRA
• The ‘sequential approach’ at site level should be applied to steer development towards areas of
lowest risk within the site
• Density should be varied to reduce the number of vulnerable units in high risk areas
• Development should be avoided in the small area of the site that is situated in Flood Zone 3
• A positive reduction in the risk of flooding within the Borough must be demonstrated as an outcome
of the proposed development
• Floor levels must be situated above the 1 in 100 year fluvial predicted maximum flood level plus
climate change, incorporating an allowance for freeboard (refer to section 6.8 of the SFRA)
• Within Flood Zone 3a High Probability, self contained basements that do not have internal access to
higher floors within the building should not be permitted. Self contained basements that do have
internal access to higher floors within the building may be permitted, however sleeping
accommodation should not be provided at basement level
• Implement SUDS to ensure that runoff from the site (post redevelopment) does not exceed
Greenfield runoff rates. Any SUDS design must take due account of groundwater and geological
conditions (refer Section 6.9 of the SFRA)
• To ensure the safety of the residents and employees during a flood, access and egress routes must
be designed to meet Environment Agency defined criteria, as set out in Appendix D of the SFRA
• Ensure that there is no net loss in floodplain storage as a result of the proposed development
• It must be demonstrated that the proposed development does not result in an increase in maximum
flood levels, within adjoining properties
• A minimum 8 metres buffer zone must be provided for the waterway
• The development should contribute to the re-naturalisation of Wealdstone Brook
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
22
Site: W15 Apex and Karma House
Key
Flood Zone 2 Flood Zone 3 Site Boundary/Reference
Medium Probability of flooding High Probability of flooding
Site Information
Area of Site (Ha): 1.1 hectares
Flood Zone(s) 1,2
Proposed Land Use: Mixed use development with hotel, residential, commercial
including affordable workspace
Vulnerability Classification of uses: Highly vulnerable: none
More vulnerable: hotels, residential
Less vulnerable: office, general industry
Sequential Test: More vulnerable uses are compatible with Flood Zones 1&2
Less vulnerable uses are compatible with Flood Zones 1&2
Overview of Flood Risk from SFRA Level 2: Wembley Masterplan Area
• Source of Flooding – Wealdstone Brook
• The site is not situated in the immediate vicinity of the river
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
23
• Approx 30% of the site lies in Flood Zone 2 with a medium probability of flooding. The remainder is
in Flood Zone 1
• floodwaters will inundate the site for a short period, not exceeding 12 hours
• The potential risk to life is considered negligible
• The site is not offered any form of protection from raised formal defences
• The potential risk of groundwater flooding within the site is considered negligible
Planning Recommendations from SFRA Level 2: Wembley Masterplan Area
• Refer to Appendix C for Strategic Flood Risk Assessment SFRA) Level 1 (2007) recommendations for
Future Development within Zone 2 Medium Probability and Zone 1 Low Probability
• All proposed development will require a detailed Flood Risk Assessment (FRA), in accordance with
Section 6.7 of the Brent Borough SFRA
• The ‘sequential approach’ at site level should be applied to steer development towards areas of
lowest risk within the site
• Density should be varied to reduce the number of vulnerable units in high risk areas
• A positive reduction in the risk of flooding within the Borough must be demonstrated as an outcome
of the proposed development
• Implement SUDS to ensure that runoff from the site (post redevelopment) does not exceed
Greenfield runoff rates. Any SUDS design must take due account of groundwater and geological
conditions (refer Section 6.9 of the SFRA)
• Floor levels must be situated above the 1 in 100 year fluvial predicted maximum flood level plus
climate change, incorporating an allowance for freeboard (refer to section 6.8 of the SFRA)
• It must be demonstrated that the proposed development does not result in an increase in maximum
flood levels, within adjoining properties
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
24
Site: W16 1 Olympic Way
Key
Site Information
Area of Site (Ha): 0.68 hectares
Flood Zone(s) 1,2,3
Proposed Land Use: Redevelopment should re-provide office floor space.
Vulnerability Classification of uses: Highly vulnerable: none
More vulnerable: none identified but could form part of
mixed use development
Less vulnerable: office
Sequential Test: Less vulnerable uses are compatible with Zones 1,2&3a
More vulnerable uses are compatible with Flood Zones 1&2
More vulnerable uses will be subject to an Exception Test
The proposed use is not compatible with Zone 3b
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
25
Exception Test • Developing the site to deliver new jobs and homes in the
Wembley Growth Area provides wider sustainability
benefits to the community that outweigh flood risk
• Any development on W13 must meet the planning
requirements set out below in order to meet the second
part of the exception test
Overview of Flood Risk
• Source of Flooding – overland flow that has exceeded the capacity of the adjacent Wealdstone Brook
• The majority of the site is situated within Flood Zone 2 Medium Probability
• Small areas adjoining the watercourse fall within Flood Zone 3 High Probability
• The remainder is in Flood Zone 1
• The site is not offered any form of protection from raised formal defences
• Floodwaters will inundate the site for a short period, not exceeding 12 hours
• Indicative flood depths at the site exceed 1000 mm in some areas
• The potential risk to life within inundated areas of the site is considered relatively high
• Development should be avoided in these areas
• The potential risk of groundwater flooding within the site is considered negligible
Planning Recommendations from SFRA Level 2: Wembley Masterplan Area
• Refer to Appendix C for Strategic Flood Risk Assessment SFRA) Level 1 (2007) planning
recommendations for Future Development within Zone 3b Functional Floodplain (Undeveloped
Areas), Zone 3a High Probability, Zone 2 Medium Probability and Zone 1 Low Probability
• Development should be avoided in the small area of the site that is situated in Flood Zone 3
• Wherever possible, development of the site should be steered towards areas of the site that are not
currently affected by flooding
• The ‘sequential approach’ at site level should be applied to steer development towards areas of
lowest risk within the site
• Density should be varied to reduce the number of vulnerable units in high risk areas
• All proposed development will require a detailed Flood Risk Assessment (FRA), in accordance with
Section 6.7 of the Brent Borough SFRA
• Development should be avoided in the small area of the site that is situated in Flood Zone 3
• A positive reduction in the risk of flooding within the Borough must be demonstrated as an outcome
of the proposed development
• Floor levels must be situated above the 1 in 100 year fluvial predicted maximum flood level plus
climate change, incorporating an allowance for freeboard (refer to section 6.8 of the SFRA)
• Within Flood Zone 3a High Probability, self contained basements that do not have internal access to
higher floors within the building should not be permitted. Self contained basements that do have
internal access to higher floors within the building may be permitted, however sleeping
accommodation should not be provided at basement level
• Implement SUDS to ensure that runoff from the site (post redevelopment) does not exceed
Greenfield runoff rates. Any SUDS design must take due account of groundwater and geological
conditions (refer Section 6.9 of the SFRA)
• To ensure the safety of the residents and employees during a flood, access and egress routes must
be designed to meet Environment Agency defined criteria, as set out in Appendix D of the SFRA
• Ensure that there is no net loss in floodplain storage as a result of the proposed development
• It must be demonstrated that the proposed development does not result in an increase in maximum
flood levels, within adjoining properties
• A minimum 8 metres buffer zone must be provided for the waterway
• The development should contribute to the re-naturalisation of Wealdstone Brook
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
26
Site: W21 21-31 Brook Avenue
Key
Site Information
Area of Site (Ha): 0.6 hectares
Flood Zone(s) 1,2,3
Proposed Land Use: Residential use and associated amenity space
Vulnerability Classification of uses: Highly vulnerable: none
More vulnerable: residential
Less vulnerable: none
Sequential Test: More vulnerable uses are compatible with Flood Zones 1&2
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
27
An Exception Test is required for ‘more vulnerable’ uses in 3a
The proposed use is not compatible with Zone 3b
Exception Test • Developing the site to deliver new jobs and homes in the
Wembley Growth Area provides wider sustainability
benefits to the community that outweigh flood risk
• Any development on W13 must meet the planning
requirements set out below in order to meet the second
part of the exception test
Overview of Flood Risk
• Source of Flooding – Wealdstone Brook
• Some of the site adjacent to Wealdstone Brook is in the functional flood plain (Zone 3b)
• Approximately half the site is in flood zone 1
• The site also includes areas within Flood Zone 3 High Probability and Flood Zone 2 Medium
Probability
Planning Recommendations
• Refer to Appendix C for Strategic Flood Risk Assessment SFRA) Level 1 (2007) planning
recommendations for Future Development within Zone 3b Functional Floodplain (Undeveloped
Areas), Zone 3b Functional Floodplain (Developed Areas), Zone 3a High Probability, Zone 2 Medium
Probability and Zone 1 Low Probability
• Encroachment into the Functional Flood Plain will not be permitted
• The ‘sequential approach’ at site level should be applied to steer development towards areas of
lowest risk within the site
• Density should be varied to reduce the number of vulnerable units in high risk areas
• Residential developments in Zone 3a should pass an Exception Test
• All proposed development will require a detailed Flood Risk Assessment (FRA), in accordance with
Section 6.7 of the Brent Borough SFRA including an assessment of flood extent, depth and speed
• A positive reduction in the risk of flooding within the Borough must be demonstrated as an outcome
of the proposed development
• Floor levels must be situated above the 1 in 100 year fluvial predicted maximum flood level plus
climate change, incorporating an allowance for freeboard (refer to section 6.8 of the SFRA).
• Within Flood Zone 3a High Probability, self contained basements that do not have internal access to
higher floors within the building should not be permitted. Self contained basements that do have
internal access to higher floors within the building may be permitted, however sleeping
accommodation should not be provided at basement level
• Implement SUDS to ensure that runoff from the site (post redevelopment) does not exceed
Greenfield runoff rates. Any SUDS design must take due account of groundwater and geological
conditions (refer Section 6.9 of the SFRA)
• To ensure the safety of the residents during a flood, access and egress routes must be designed to
meet Environment Agency defined criteria, as set out in Appendix D of the SFRA
• Ensure that there is no net loss in floodplain storage as a result of the proposed development
• Flow routes should not be obstructed
• It must be demonstrated that the proposed development does not result in an increase in maximum
flood levels, within adjoining properties
• A minimum 8 metres buffer zone must be provided for the waterway
• The development should contribute to the re-naturalisation of Wealdstone Brook
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
28
Site: W25 Amex House
Key
Site Information
Area of Site (Ha): 0.5 hectares
Flood Zone(s) 2,3
Proposed Land Use: Mixed use development, including residential, office and
managed affordable workspace for creative industries
Vulnerability Classification of uses: Highly vulnerable: none
More vulnerable: residential
Less vulnerable: office, general industry
Sequential Test: Less vulnerable and more vulnerable uses are compatible with
Flood Zone 2
More vulnerable uses require an Exception Test for zone 3a
None of the proposed uses are compatible with zone 3b
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
29
Exception Test • Developing the site to deliver new jobs and homes in the
Wembley Growth Area provides wider sustainability
benefits to the community that outweigh flood risk
• Any development on W13 must meet the planning
requirements set out below in order to meet the second
part of the exception test
Overview of Flood Risk
• Source of Flooding – Wealdstone Brook
• Approximately half the site lies in flood zone 2 and half in flood zone 3
• Some parts adjacent to the watercourse could lie in the Functional Flood Plain
Planning Recommendations from Site Specific Allocations PPS25 Sequential Test (June 2010)
• Refer to Appendix C for Strategic Flood Risk Assessment SFRA) Level 1 (2007) planning
recommendations for Future Development within Zone 3b Functional Floodplain (Undeveloped
Areas), Zone 3a High Probability and Zone 2 Medium Probability
• Encroachment into the Functional Flood Plain will not be permitted
• The ‘sequential approach’ at site level should be applied to steer development towards areas of
lowest risk within the site
• Density should be varied to reduce the number of vulnerable units in high risk areas
• Residential developments in Zone 3a should pass an Exception Test
• Highly vulnerable development should be avoided within this site
• All proposed development will require a detailed Flood Risk Assessment (FRA), in accordance with
Section 6.7 of the Brent Borough SFRA including an assessment of flood extent, depth, speed and
whether the existing buildings are permeable to flood waters
• A positive reduction in the risk of flooding within the Borough must be demonstrated as an outcome
of the proposed development
• Floor levels must be situated above the 1 in 100 year fluvial predicted maximum flood level plus
climate change, incorporating an allowance for freeboard (refer to section 6.8 of the SFRA)
• Within Flood Zone 3a High Probability, self contained basements that do not have internal access to
higher floors within the building should not be permitted. Self contained basements that do have
internal access to higher floors within the building may be permitted, however sleeping
accommodation should not be provided at basement level
• Implement SUDS to ensure that runoff from the site (post redevelopment) does not exceed
Greenfield runoff rates. Any SUDS design must take due account of groundwater and geological
conditions (refer Section 6.9 of the SFRA)
• To ensure the safety of the residents and employees during a flood, access and egress routes must
be designed to meet Environment Agency defined criteria, as set out in Appendix D of the SFRA
• Ensure that there is no net loss in floodplain storage as a result of the proposed development
• Flow routes should not be obstructed
• It must be demonstrated that the proposed development does not result in an increase in maximum
flood levels, within adjoining properties
• A buffer zone must be provided for the waterway
• The development should contribute to the re-naturalisation of Wealdstone Brook
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
30
Site: W26 Watkin Road
Key
Site Information
Area of Site (Ha): 1.5 hectares
Flood Zone(s) 1,2,3
Proposed Land Use: Mixed use development including office, leisure, residential,
managed affordable workspace, and community use. Extra
care housing or family housing could form part of any housing
mix.
Vulnerability Classification of uses: Highly vulnerable: none
More vulnerable: residential, residential care homes, some
community facilities
Less vulnerable: offices, general industry, leisure
Sequential Test: Less vulnerable and more vulnerable uses are compatible with
Flood Zone 2
More vulnerable uses require an Exception Test for zone 3a
None of the proposed uses are compatible with zone 3b
Exception Test • Developing the site to deliver new jobs and homes in the
Wembley Growth Area provides wider sustainability
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
31
benefits to the community that outweigh flood risk
• Any development on W13 must meet the planning
requirements set out below in order to meet the second
part of the exception test
Overview of Flood Risk
• Source of Flooding – overland flow that has exceeded the capacity of the adjacent Wealdstone Brook
• Most of the site lies in Flood Zone 2 with a medium probability of flooding. Some parts adjacent to
the watercourse lie in Flood Zone 3
• Some low areas adjoining the river are affected by Zone 3b Functional Floodplain
• floodwaters will inundate the site for a short period, not exceeding 12 hours
• The site has no protection from raised formal defences
• The potential risk of groundwater flooding within the site is considered negligible
• The potential risk to life within inundated areas (zones 3a and 3b) is considered relatively high.
Development should be avoided in these areas
• The potential risk to life in Zone 2 is considered negligible
Planning Recommendations from Site Specific Allocations PPS25 Sequential Test (June 2010)
• Refer to Appendix C for Strategic Flood Risk Assessment SFRA) Level 1 (2007) planning
recommendations for Future Development within Zone 3b Functional Floodplain (Undeveloped
Areas), Zone 3b Functional Floodplain (Developed Areas), Zone 3a High Probability, Zone 2 Medium
Probability and Zone 1 Low Probability
• The ‘sequential approach’ at site level should be applied to steer development towards areas of
lowest risk within the site
• Density should be varied to reduce the number of vulnerable units in high risk areas
• ‘More vulnerable’ uses (residential, residential care homes, community facilities) should be located
away from Flood Zone 3
• Any ‘more vulnerable’ uses proposed in Flood Zone 3a will be subject to the Exception Test
• Highly vulnerable development should be avoided within this site
• Encroachment into the Functional Flood Plain (3b) will not be permitted
• All proposed redevelopment within Site W26 will require a detailed Flood Risk Assessment (FRA), in
accordance with Section 6.7 of the Brent Borough SFRA
• Throughout the site, (re)development must deliver a measurable reduction in flood risk. Risk
reduction measures for consideration should include SUDS to seek a reduction in the rate of runoff
from the site
• Within Flood Zone 3a High Probability, self contained basements that do not have internal access to
higher floors within the building should not be permitted. Self contained basements that do have
internal access to higher floors within the building may be permitted, however sleeping
accommodation should not be provided at basement level
• Threshold floor levels should be kept above predicted 1 in 100 year flood levels plus an allowance for
climate change (refer to section 6.8 of the SFRA)
• Loss of flood plain storage due to new development should be compensated
• Flow routes should not be obstructed
• Implement SUDS to ensure that runoff from the site (post redevelopment) does not exceed
Greenfield runoff rates
• Any SUDS design must take due account of groundwater and geological conditions (refer Section 6.9
of the SFRA)
• Safe dry access and egress should be provided (see Appendix D of the SFRA)
• A buffer zone must be provided for all culverted and open waterways
• The development should contribute to the re-naturalisation of Wealdstone Brook
Site: W27 Euro Car Parts
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
32
Key
Flood Zone 2 Flood Zone 3 Site Boundary/Reference
Medium Probability of flooding High Probability of flooding
Site Information
Area of Site (Ha): 1.35 hectares
Flood Zone(s) 1,2
Proposed Land Use: Mixed use development including office, leisure, residential,
student accommodation, managed affordable workspace,
hotel and community use.
Vulnerability Classification of uses: Highly vulnerable: none
More vulnerable: student accommodation, hotels, some
community uses, residential
Less vulnerable: office, leisure, general industry
Sequential Test: More vulnerable uses are compatible with Flood Zones 1&2
Less vulnerable uses are compatible with Flood Zones 1&2
Overview of Flood Risk
• Source of Flooding – Wealdstone Brook
• Approx 95% of the site lies in Flood Zone 1
• Sections close to the Wealdstone Brook are in Flood Zone 2 with a medium probability of flooding
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
33
Planning Recommendations
• Refer to Appendix C for Strategic Flood Risk Assessment SFRA) Level 1 (2007) planning
recommendations for Future Development within Zone 2 Medium Probability and Zone 1 Low
Probability
• All proposed development will require a detailed Flood Risk Assessment (FRA), in accordance with
Section 6.7 of the Brent Borough SFRA
• The ‘sequential approach’ at site level should be applied to steer development towards areas of
lowest risk within the site
• Density should be varied to reduce the number of vulnerable units in high risk areas
• A positive reduction in the risk of flooding within the Borough must be demonstrated as an outcome
of the proposed development
• A buffer zone must be provided for the waterway
• The development should contribute to the re-naturalisation of Wealdstone Brook
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
34
Appendix C - Strategic Flood Risk Assessment SFRA) Level 1 (2007)
Extract - planning recommendations
Future Development within Zone 3b Functional Floodplain (Undeveloped Areas)
Planning Recommendations – Allocation of Land for Future Development (relevant only following
the application of the Sequential Test) Areas of Functional Floodplain that are currently
undeveloped should be protected for flood storage purposes. Future development should be
restricted to water-compatible uses and essential infrastructure that has to be there (in accordance
with PPS25). Careful consideration should be given to the Council’s emergency response in times of
flood to ensure that public safety is not compromised.
Future Development within Zone 3b Functional Floodplain (Developed Areas)
It is important to recognise that, within Zone 3b Functional Floodplain, ‘previously developed land’
relates solely to existing buildings that are impermeable to flood water. The land surrounding
these buildings are important flow paths and/or flood storage areas that must be retained.
Planning Recommendations – Allocation of Land for Future Development (relevant only following
the application of the Sequential Test)
1. Future redevelopment of previously developed land within Zone 3b Functional Floodplain
(Developed Areas) will only be permitted within the footprint of an existing building that is
impermeable to flooding. Development must be restricted to ‘less vulnerable’ land uses. ‘More
vulnerable’ land uses must be actively discouraged, and should only be considered within sites of an
equivalent existing land use.
2. In all instances, it will be necessary to ensure that the requirements of the Exception Test are
satisfied. In planning terms, it must be demonstrated that “the development provides wider
sustainability benefits to the community that outweigh flood risk”. It should be recognised that
property situated within Zone 3b Functional Floodplain will be subject to frequent flooding, on
average, no less than once in every 20 years. There are clear sustainability implications to be
considered in this regard, and it is highly questionable whether insurance against flooding related
damages will be available in the longer term.
3. There should be a presumption against all building extensions (including outbuildings) within Zone
3b Functional Floodplain.
4. To satisfy the remaining criteria of the Exception Test, all development within Zone 3b Functional
Floodplain (existing developed areas only) should be designed in accordance with the development
control recommendations below.
Future Development within Zone 3a High Probability
Defended Areas within Zone 3a High Probability There are not many raised defences in the Borough
and few existing defences offer some degree of protection to the properties in Wembley and
Kingsbury areas. Whilst it is recognised that there is a government led commitment to the retention
of this system of defences, the statutory responsibility for flood defence remains with the individual
landowner. For this reason, all future development must assess (and mitigate) the residual risk of
flooding should the defences fail and/or fall into disrepair in future years. The assessment of flood
hazard (refer Section 5.3) has identified areas within which there may be a risk to life should these
raised defences fail in a catastrophic manner (i.e. the Rapid Inundation Zone). Where possible,
future development should be avoided in these areas. For all areas of Zone 3a High Probability
Wembley Area Action Plan: Flood Risk Analysis for Site Proposals
December 2012
35
situated behind raised defences, a suite of specific development control recommendations have
been provided, as detailed below.
Planning Recommendations – Allocation of Land for Future Development (relevant only following
the application of the Sequential Test)
1. Future development within Zone 3a High Probability should be restricted to ‘less vulnerable’ land
uses, in accordance with PPS25 (Appendix D) Table D2. ‘More vulnerable’ land uses, including
residential development, should be steered towards zones of lower flood risk (i.e. Zone 2 Medium
Probability or Zone 1 Low Probability) within which suitable land may be available in adjoining
character areas.
2. Where non-flood risk related planning matters dictate that ‘more vulnerable’ (residential)
development should be considered further, it will be necessary to ensure that the requirements of
the Exception Test are satisfied. In planning terms, it must be demonstrated that “the development
provides wider sustainability benefits to the community that outweigh flood risk”, and that “the
development is on developable previously developed land, or that there are no reasonable
alternative sites on previously developed land”.
3. To satisfy the remaining criteria of the Exception Test, all development within Zone 3a High
Probability should be designed in accordance with the development control recommendations
below
Future Development within Zone 2 Medium Probability
Planning Recommendations – Allocation of Land for Future Development (relevant only following
the application of the Sequential Test)
1. In accordance with PPS25, land use within Zone 2 Medium Probability should be restricted to the
‘water-compatible’, ‘less vulnerable’ and ‘more vulnerable’ category (including residential
development), or essential infrastructure, to satisfy the requirements of the Sequential Test
2. Where non-flood risk related planning matters dictate that ‘highly vulnerable’ development
should be considered further, it will be necessary to ensure that the requirements of the Exception
Test are satisfied. In planning terms, it must be demonstrated that “the development provides wider
sustainability benefits to the community that outweigh flood risk”, and that “the development is on
developable previously developed land, or that there are no reasonable alternative sites on
previously developed land”.
3. To satisfy the remaining criteria of the Exception Test, all development within Zone 2 Medium
Probability should be designed in accordance with the development control recommendations
below.
Future Development within Zone 1 Low Probability
Planning Recommendations – Allocation of Land for Future Development
There are generally no flood risk related constraints placed upon land use within Zone 1 Low
Probability (in accordance with PPS25), however it is important to recognise that future
development within this zone may adversely impact upon the existing flooding regime if not
carefully managed. Flooding related issues of a localised nature may also occur within Zone 1 Low
Probability. For this reason, all development should be carried out in accordance with the
development control recommendation below. Within ‘dry island’ areas that are surrounded by a
degree of flood risk, effective emergency planning measures should be in place to ensure that the
risk to life is minimised in case of flooding.