Webinar_ProtectiveDevCoord1

Embed Size (px)

Citation preview

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    1/39

    Arc Flash with EasyPower

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    2/39

    Topics:

    EasyPower, LLC

    Molded-case Circuit Breaker vsLow Voltage Power Circuit

    Breakers Coordination of MCCBs

    Transformer Damage Curves

    Transformer Protection TCC Clipping & Tick Marks

    I2T Settings What and Why?

    Questions2

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    3/39

    Molded Case Circuit Breakers vs LowVoltage Power Circuit Breakers

    Designed, Built and Tested to MeetDifferent Standards:

    MCCBs & ICCBs UL489

    LVPCBs UL1066 (ANSI C37)

    In general:

    MCCBs Switchboards

    LVPCBs Switchgear (Drawout)

    EasyPower, LLC 3

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    4/39

    Comparison

    Characteristic MCCB LVPCB

    Maintenance No user-serviceableparts

    Can be inspected andmaintained, including

    contacts, arc-chutes,etc.

    Short-Time Duty Cycle Not Required (But canbe tested)

    Carry Fault Current fortwo 30-cycle periods

    Short Circuit Testpower factor

    15 to 20% (> 20kA) 15% max

    Instantaneous Trip Required Not Required

    Normal Use Switchboards (UL891) Switchgear (ANSIC37.20.1)

    Cont Current Rating 80% (unless 100%

    rated)

    Always 100%

    EasyPower, LLC 4

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    5/39

    Look at Short Circuit Example

    EasyPower, LLC 5

    3 PHASE Fault Total Fault Currents Equipment DutiesBus Name Bus kV Sym Amps X/R Ratio Mult Factor Asym Amps Equip Type Duty Amps

    SUB 8A 0.480 39609.5 6.89 1.35 53629.1 LVPCBMCCB 10-20 kAMCCB > 20 kA

    39890.246332.142129.4

    Calculated SC

    Current= pf of 14.4%

    Adjusted Duty de-rated

    So, 42 kA LVPCB OK, 42 kA MCCB NOT OK

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    6/39

    Impact on Coordination: Short-time withstand rating allows

    LVPCB to stay closed, allowing

    downstream equipment to clear fault.

    Lack of short-time rating means thatMCCB must have instantaneous trip to

    trip breaker at the short circuitwithstand rating

    Newer MCCBs may be tested for short-

    time withstand. EasyPower, LLC 6

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    7/39

    Coordinating MCCBs and LVPCBs

    In general, MCCBs in series will often not coordinatewith each other due to instantaneous trip elements.

    Coordination is much more reliable with LVPCBs IFthe proper trip units and settings are used.

    EasyPower, LLC 7

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    8/39

    Short-time Withstand

    Improves Coordination Specify LVPCBs with no instantaneous or switchable

    Will coordinate with downstream MCCBs

    Use Short-time delay to coordinate between mainand feeder breakers

    Can also use Zone Selective Interlocking withLVPCBs.

    EasyPower, LLC 8

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    9/39

    MCCBs in Series General case do not coordinate

    May coordinate below certain levels offault current.

    Easypower, LLC 9

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    10/39

    Easypower, LLC 10

    Typical MCCBCoordination

    Overlapindicatescoordinationproblem

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    11/39

    Easypower, LLC 11

    TypicalLVPCB

    Coordination

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    12/39

    Selective Coordination of

    MCCBs In 2005 NEC required selective

    coordination of emergency power

    systems This spurred MCCB manufacturers to

    improve testing and documentation ofMCCB coordination

    Fuses, if applied per manufacturersinstructions (2:1) have been shown tocoordinate by test

    12

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    13/39

    Two techniques to coordinate

    MCCBs Use upstream breaker with high short-

    circuit withstand rating and set

    instantaneous above actual maximumfault current available

    Use MCCBs that are tested combination

    and shown to coordinate up to certainfault current

    EasyPower, LLC 13

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    14/39

    Series Coordination of MCCBsValid only by test

    Test data shows MCCBs will coordinateeven though curves overlap on TCC

    Limited to same manufacturer

    Tracked in EasyPower Library Data

    EasyPower, LLC 14

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    15/39

    EasyPower, LLC 15

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    16/39

    Set Option in PDC Options

    EasyPower, LLC 16

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    17/39

    EasyPower, LLC 17

    SeriesCoordinationTest Data in

    EasyPower

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    18/39

    Coordination Time Intervals

    Low Voltage Breakers and Trip Units TCCs include all breaker operating time

    and tolerances as long as they do nottouch, they should coordinate

    Relay curves show only nominal relay

    operate time need to allow additionaltime separation

    Traditionally we have used 0.3 to 0.4

    seconds EasyPower, LLC 18

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    19/39

    CTI Limits Number of Relays

    in Series Since we must allow this CTI between

    each pair of relays, clearing times get

    very slow when we have more than twoor three relays in series.

    Especially true in industrial applications

    EasyPower, LLC

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    20/39

    Coordination Time Interval

    (CTI) Accounts For: Breaker Operating Time (2 to 8 cycles)

    Relay Overtravel (Electro-mechanical)

    Relay Error

    CT Error

    Lockout Relay Operate Time

    EasyPower, LLC

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    21/39

    What has changed? Newer Digital Relays have no overtravel

    and are extremely accurate can we

    reduce the CTI?Yes we can, but keep in mind:

    Still have breaker operate time and CT

    error CT Saturation must still be considered as

    well

    EasyPower, LLC

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    22/39

    EasyPower, LLC 22

    UPSTREAM DEVICE DOWNSTREAM DEVICE(TIMEINSECONDS)

    Electro-Mech. Relay Digital Relay Direct-Acting Trip Fuse

    Electro-Mech.Relay 0.30 0.25 0.20 0.20

    Digital Relay 0.25 0.20 0.15 0.20Direct-Acting Trip 0.20 .20 Separation Separation

    Fuse 0.30 .25 0.10 0.10

    TYPICAL COORDINATION TIMEINTERVALS

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    23/39

    Protecting Transformers Overloads

    Internal Faults

    Through Faults

    Transformer Damage Curves only dealwith through faults not internal faults,not overloads

    If you have an internal fault thetransformer is already damaged

    EasyPower, LLC

    f

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    24/39

    Transformer Protection ANSIDamage Curve Damage Curve for

    Through-Faults

    ANSI C57.109

    Oil Frequent vs

    Infrequent faults

    Mechanical

    Damage =Frequent Fault

    Mechanical

    Thermal

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    25/39

    ANSI C57.109Category Single-Phase

    (kVA)Three-Phase

    (kVA)Frequent

    Fault

    I 5 to 500 15 to 500 n/a

    II 501 to 1667 501 to 5000 10

    III 1668 to 10,000 5001 to 30,000 5

    IV Above 10,000 Above 30,000 5

    EasyPower, LLC

    Damage Curve Shape Varies Based onCategory, Transformer Impedance

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    26/39

    EasyPower LLC 26

    Protecting Delta-Wye

    Transformers Per-Unit Current Seen by Primary

    Protection Not the Same as Seen by

    Secondary Winding. Winding Damage on Through-Faults a

    function of current through any one

    winding. We must adjust damage curve or

    primary protection curve to compensate

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    27/39

    EasyPower LLC 27

    Protecting Delta-Wye Xfmr

    1 pu

    1 pu

    1 pu

    1 pu

    .58 pu

    1 pu

    1 pu

    Currents at Full Load -Normal

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    28/39

    EasyPower LLC 28

    Protecting Delta-Wye Xfmr Ignoring Load

    Current, PrimaryRelay or Fuse willsee only 58% of

    the per unit currentin the secondarywinding for groundfault on secondaryside.

    1 pu

    .58 pu

    .58 pu

    Currents For SLG Fault on Wye Side

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    29/39

    We Must Adjust Damage Curve

    Adjusted ForGround FaultSeen FromPrimary

    Applies Only for GroundFaults on Secondary onDelta-Wye Transformers

    Applies Only forPrimary Protection

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    30/39

    EasyPower LLC 30

    NEC Requirements for

    Transformer ProtectionNEC Table 450-3(A)Primary > 600V

    Primary Secondary

    Over 600V Over 600V 6% 400% 300% 250% 225% 125%

    Supervised Any 300% 250% N.R. N.R. N.R.

    6% 600% 300% 300% 250% 250%

    >6% 400% 300% 250% 225% 250%

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    31/39

    31

    Transformer Inrush

    Transformer PrimaryProtection Must Ride

    through Inrush Inrush hard to

    calculate, high inharmonics

    Assume 8 to 10 x FLCfor 0.1 sec

    Based on Self-CooledRating

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    32/39

    TCC Clipping and Tick Marks Intended to aid in understanding of

    impact of short circuit current on

    coordination Well look at why we want to use these

    features and how they behave in

    EasyPower

    EasyPower, LLC

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    33/39

    TCC Clipping and Tick Marks Consider TCC using manufacturers TCC

    and no tick marks

    Curve may extend to maximum faultcurrent grid line on TCC

    If we do not know what the maximum

    fault current through each device is, itis difficult to determine selectivity

    EasyPower, LLC

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    34/39

    TCC Tick Marks Tick Marks Can be Added to Indicate

    Maximum Fault Current Possible For

    Each Device Selected under Short Circuit tab for

    each protective device

    Can select cycle, 5 cycle, or 30 cycle

    EasyPower, LLC

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    35/39

    TCC Curve Clipping In addition to Tick Marks, we can stop

    (clip) TCC at the maximum fault

    current it can see.Also selected under Short Circuit tab

    for each protective device

    Can select cycle, 5 cycle, or 30 cycle

    EasyPower, LLC

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    36/39

    TCC Defaults EasyPower Defaults as delivered:

    TCC curves clipped cycle

    Tick Marks for each device cycle

    When TCC is opened or created, EasyPower faults every busand uses maximum current through each device to determineclipping and tick marks.

    But if a single bus is faulted tick marks and clipping canchange.

    EasyPower, LLC

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    37/39

    Last and Least I2

    t Function 480 V Trip Units Generally Have I2t

    function on Short-time and (sometimes)

    Ground FunctionCuts off the corner of Short-Time

    curve

    In = ON, Out = OFF Intent is to improve coordination with

    downstream fuses

    EasyPower, LLC

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    38/39

    Last and Least I2

    t Function In many situations, use of I2t function

    will increase arc-flash incident energy.

    Generally not necessary for coordinationwith other trip units or MCCBs.

    Not widely used.

    EasyPower, LLC

  • 7/27/2019 Webinar_ProtectiveDevCoord1

    39/39

    Question Future Topics

    E-mail Comments to

    [email protected] Thanks.

    mailto:[email protected]:[email protected]