75
Enclosed Top Mount #4083 PREREQUISITE BIDDING REQUIREMENTS Any manufacturer submitting a proposal or bid, to these specifications; shall meet the following conditions. The manufacturer of the apparatus herein specified; shall be wholly owned (100%) and managed by a Company, Corporation, and/or Parent Company that is wholly based, and permanently resides in the United States of America. The Company, Corporation, and/or Parent Company, and all assets belonging to such; shall be wholly owned and managed (100%) by the entities specified above. Any proposal, bid, or response to these specifications by any foreign based, owned, or managed (in part or in whole) Company, Corporation, and/or Parent Company; shall be cause for immediate rejection. Any proposal, bid, or response to these specifications by any Company, Corporation, and/or Parent Company, that is owned, operated, managed, or held in contract; in part or wholly by a partnership or other agreement; shall be cause for immediate rejection. Exceptions to these conditions will not be allowed under any circumstances. NFPA 1901-2009 The National Fire Protection Association “Standard for Automotive Fire Apparatus, 2009 edition, is hereby adopted and made a part of these specifications, the same as if it were written out in full detail, with the exception of the section dealing with "Equipment Recommended for Various Types of Apparatus". Bidders shall provide the equipment requested herein and the buyer shall supply the rest before the apparatus is put into service. It is the intent of the purchaser to purchase an apparatus that meets 100% of the minimum standards defined and outlined in NFPA 1901-2009 edition. There are to be no exceptions to this requirement. Page 1 of 75

 · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

PREREQUISITE BIDDING REQUIREMENTS

Any manufacturer submitting a proposal or bid, to these specifications; shall meet the following conditions.

The manufacturer of the apparatus herein specified; shall be wholly owned (100%) and managed by a Company, Corporation, and/or Parent Company that is wholly based, and permanently resides in the United States of America.

The Company, Corporation, and/or Parent Company, and all assets belonging to such; shall be wholly owned and managed (100%) by the entities specified above.

Any proposal, bid, or response to these specifications by any foreign based, owned, or managed (in part or in whole) Company, Corporation, and/or Parent Company; shall be cause for immediate rejection.

Any proposal, bid, or response to these specifications by any Company, Corporation, and/or Parent Company, that is owned, operated, managed, or held in contract; in part or wholly by a partnership or other agreement; shall be cause for immediate rejection.

Exceptions to these conditions will not be allowed under any circumstances.

NFPA 1901-2009

The National Fire Protection Association “Standard for Automotive Fire Apparatus, 2009 edition, is hereby adopted and made a part of these specifications, the same as if it were written out in full detail, with the exception of the section dealing with "Equipment Recommended for Various Types of Apparatus". Bidders shall provide the equipment requested herein and the buyer shall supply the rest before the apparatus is put into service. It is the intent of the purchaser to purchase an apparatus that meets 100% of the minimum standards defined and outlined in NFPA 1901-2009 edition. There are to be no exceptions to this requirement.

STATEMENT OF EXCEPTIONS

The proposed apparatus as described in this specification document and all related material with the bid package shall meet or exceed all applicable sections for the category of apparatus as defined by NFPA 1901 newest edition, unless specifically noted within this specification or other official documents associated with this bid.

Should any area, section or portion of the apparatus not meet the intent and applicable requirements, a clearly defined listing or explanation of what and why compliance was not achieved shall be provided to the purchaser at the time of delivery.

VEHICLE STABILITY

Page 1 of 55

Page 2:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

The apparatus shall comply with the requirements of NFPA 1901, newest edition, as it applies to vehicle stability. The particular apparatus as described in the specification provided within the bid package shall be classified into one of the following categories:

The apparatus shall go through actual tilt table testing. This shall be determined by the apparatus manufacturer

The apparatus shall be equipped with rollover stability control systems as defined in section 4.13.1.2 of NFPA 1901, newest edition

The apparatus shall be deemed a similar apparatus and meeting the intent of section 4.13.1.1.2 of NFPA 1901, newest edition

CONSTRUCTION DOCUMENTATION

The contractor shall supply, at the time of delivery, at least one copy of the following documents:

1. The manufacturers record of apparatus construction details, including the following information:

a. Owners name and address b. Apparatus manufacturer, model, and serial number c. Chassis make, model, and serial number d. GAWR of front and rear axles e. Front tire size and total rated capacity in pounds (kg) f. Rear tire size and total rated capacity in pounds (kg) g. Chassis weight distribution in pounds with water and manufacturer mounted

equipment (front and rear) h. Engine make, model, serial number, rated horsepower and related speed, and

governed speed i. Type of fuel and fuel tank capacity j. Electrical system voltage and alternator output in amps k. Battery make, model, and capacity in cold cranking amps (CCA) l. Chassis transmission make, model, and serial number; and if so equipped,

chassis transmission PTO(s) make, model, and gear ratio m. Pump make, model, rated capacity in gallons per minute (liters per minute

where applicable), and serial number n. Pump transmission make, model, serial number, and gear ratio o. Auxiliary pump make, model, rated capacity in gallons per minute (liters per

minute where applicable), and serial number p. Water tank certified capacity in gallons or liters q. Aerial device type, rated vertical height in feet (meters), rated horizontal reach

in feet (meters), and rated capacity in pounds (kilograms) r. Paint manufacturer and paint number(s) s. Company name and signature of responsible company representative

2. Certification of slip resistance of all stepping, standing, and walking surfaces

3. If the apparatus has a fire pump, a copy of the following shall be provided: pump manufacturers certification of suction capability, apparatus manufacturers approval for stationary pumping applications, engine manufacturers certified

Page 2 of 55

Page 3:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

brake horsepower curve showing the maximum governed speed, pump manufacturers certification of the hydrostatic test, and the certification of inspection and test for the fire pump

4. If the apparatus has an aerial device, the certification of inspection and test for the aerial device, and all the technical information required for inspections to comply with NFPA 1914, Standard for Testing Fire Department Aerial Devices

5. If the apparatus has a fixed line voltage power source, the certification of the test for the fixed power source

6. If the apparatus is equipped with an air system, test results of the air quality, the SCBA fill station, and the air system installation

7. Weight documents from a certified scale showing actual loading on the front axle, rear axle(s), and overall fire apparatus (with the water tank full but without personnel, equipment, and hose)

8. Written load analysis and results of the electrical system performance tests

9. When the apparatus is equipped with a water tank, the certification of water tank capacity

OPERATION AND SERVICE DOCUMENTATION

The contractor shall supply, at time of delivery, at least two sets of complete operation and service documentation covering the completed apparatus as delivered and accepted.

The documentation shall address at least the inspection, service, and operations of the fire apparatus and all major components thereof.

The contractor shall also provide documentation of the following items for the entire apparatus and each major operating system or major component of the apparatus:

1. Manufacturers name and address2. Country of manufacture3. Source of service and technical information4. Parts and replacement information5. Descriptions, specifications, and ratings of the chassis, pump, and aerial

device 6. Wiring diagrams for low voltage and line voltage systems to include the

following information: representations of circuit logic for all electrical components and wiring, circuit identification, connector pin identification, zone location of electrical components, safety interlocks, alternator-battery power distribution circuits, and input/output assignment sheets or equivalent circuit logic implemented in multiplexing systems

7. Lubrication charts 8. Operating instructions for the chassis, any major components such as a

pump or aerial device, and any auxiliary systems 9. Precautions related to multiple configurations of aerial devices, if applicable 10. Instructions regarding the frequency and procedure for recommended

maintenance

Page 3 of 55

Page 4:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

11. Overall apparatus operating instructions 12. Safety considerations 13. Limitations of use 14. Inspection procedures 15. Recommended service procedures 16. Troubleshooting guide 17. Apparatus body, chassis, and other component manufacturers warranties 18. Special data required by this standard 19. Copies of required manufacturer test data or reports, manufacturer

certifications, and independent third-party certifications of test results 20. A material safety data sheet (MSDS) for any fluid that is specified for use on

the apparatus

The contractor shall deliver with the apparatus all manufacturers operations and service documents supplied with components and equipment that are installed or supplied by the contractor.

NFPA REQUIRED MANUALS

The construction, operation, and service documentation shall be provided on a CD-ROM. These manuals shall be written in a "step by step" format for ease of reference. There shall be two (2) copies of the CD provided with the apparatus as standard.

BODY STRUCTURAL INTEGRITY TEN (10) YEAR WARRANTY

The body shall be free of structural or design failure or workmanship for a period of ten (10) years or 100,000 miles starting thirty (30) days after the original invoice date.

STAINLESS STEEL TEN (10) YEAR LIMITED PLUMBING WARRANTY

The stainless steel plumbing shall be free from corrosion perforation for a period of ten (10) years starting thirty (30) days after the original invoice date.

BASIC NINETY (90) DAY LIMITED WARRANTY ON OEM PURCHASED PARTS

The apparatus shall be free of defects in material and workmanship for a period of ninety (90) days starting thirty (30) days after the original invoice date.

STANDARD ONE (1) YEAR WARRANTY

The apparatus shall be free of defects in material and workmanship for a period of one (1) year starting thirty (30) days after the original invoice date.

PAINT LIMITED WARRANTY

The apparatus body and pump house shall be free of blistering, peeling and any other adhesion defect caused by defective manufacturing methods or paint material selection for exterior surfaces for a period of three (3) years starting thirty (30) days after the original invoice date.

Paint on the body interior, or Line-X on pump panels, if applicable, is covered only under the Smeal Standard One Year Limited Warranty.

Page 4 of 55

Page 5:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

CORROSION LIMITED WARRANTY

The body exterior paint shall be warranted against corrosion perforation for a period of ten (10) years starting thirty (30) days after the original invoice date.

OVERALL HEIGHT

The overall height of the vehicle shall be approximately 130" from the ground. This measurement shall be taken with the tires properly inflated with the apparatus in the unloaded condition. The actual measurement shall be taken at the highest point of the apparatus.

VEHICLE TOP SPEED

The vehicle’s top speed shall be 68 MPH

OVERALL LENGTH

The overall length of the vehicle shall be approximately 379" (31' 7").

MISCELLANEOUS EQUIPMENT, PUMPERS

Miscellaneous equipment, as defined in the newest edition of NFPA 1901, sections 5.8.2 and 5.8.3, shall be the responsibility of the purchaser. The apparatus shall be designed and manufactured in such a manner as to provide ample enclosed space for which to store such equipment.

POLYPROPYLENE FOAM CELL

There shall be one (1) 30 gallon polypropylene foam cell(s) incorporated into the polypropylene water tank. If a foam system is not present on the unit, this foam cell {will/shall} be available for future use with a foam system.

There shall be one (1) pressure/vacuum vent installed on the foam tank.

There shall be one (1) drain hose connected to the foam cell. The drain shall have a 1/4 turn valve installed inside the pump house and it shall drain below the frame rail of the chassis.

WATER TANK

The water tank shall have a capacity of 1000 U.S. gallons. Certification of the tank capacity shall be recorded on the manufacturer's record of construction and shall be provided to the purchaser upon delivery of the apparatus.

UPF POLY TANK CONSTRUCTION

The UPF Poly-Tank ® IIE shall be constructed of 1/2" thick PT2E™ polypropylene sheet stock. This material shall be a non-corrosive stress relieved thermoplastic, black in color, and U.V. stabilized for maximum protection.

BOOSTER TANK

Page 5 of 55

Page 6:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

The booster tank shall be of a specific configuration and shall be so designed to be completely independent of the body and compartments. All joints and seams shall be nitrogen welded and tested for maximum strength and integrity. The top of the booster tank shall be fitted with removable lifting eyes designed with a 3 to 1 safety factor to facilitate easy removal.

TANK BAFFLES

The transverse swash partitions shall be manufactured of 3/8" PT2E™ polypropylene (natural in color) and extend from approximately 4" off the floor to just under the cover. The longitudinal swash partitions shall be constructed of 3/8" PT2E polypropylene (natural in color) and extend to the floor of the tank through the cover to allow for positive welding and maximum integrity. All partitions shall be equipped with vent and air holes to permit movement of air and water between compartments. The partitions shall be designed to provide maximum water flow. All swash partitions shall interlock with one another and be welded to each other as well as to the walls of the tank.

TANK SUMP

There shall be one (1) sump in the bottom of the water tank. The sump shall be constructed of 1/2" polypropylene and shall be located in the left front quarter of the tank. On all tanks that require a front suction, a 4" schedule 40 polypropylene pipe shall be installed that will incorporate a dip tube from the front of the tank to the sump location. The sump shall be used as a combination clean-out and drain. All tanks shall have an anti-swirl plate located approximately 2" above the sump to pre-vent air from being entrained in the water while pumping.

TANK FILL CONNECTION

All tank fill couplings shall be backed with flow deflectors to break up the stream of water entering the tank, and shall be capable of withstanding sustained fill rates of up to 1,000 GPM.

TANK LID

The tank lid shall be constructed of 1/2" thick PT2E™ polypropylene to incorporate a multi three-piece locking design that allows for individual removal and inspection if necessary. The tank lid shall be recessed 3/8" from the top of the tank and shall be welded to both sides and longitudinal partitions for maximum integrity. Each one of the lids shall have hold downs consisting of 2" polypropylene dowels spaced a maximum of 30" apart. These dowels shall extend through the covers and shall assist in keeping the covers rigid under fast filling conditions. A minimum of two lifting dowels shall be drilled and tapped 1/2" x 13" to accommodate the lifting eyes.

LIFETIME TANK WARRANTY

The tank shall have a lifetime warranty from UPF.

Page 6 of 55

Page 7:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

WATER TANK FILL TOWER

The tank shall have a combination vent and manual fill tower marked "Water Fill." The fill tower shall be constructed of 1/2" PT2E polypropylene and shall be a minimum dimension of 8" x 8" at the outer perimeter. The tower shall be located in the left front corner of the tank. The tower shall have a 1/4" thick removable polypropylene screen and a PT2E polypropylene hinged-type cover.

UPF TANK OVERFLOW

The tank shall be equipped with a minimum of a 6" schedule 40 polypropylene overflow/air vent pipe. The pipe shall be installed in the fill tower and extend through the tank and dump to the rear of the rear axle.

TANK DRAIN VALVE

One (1) 1" quarter-turn tank drain valve shall be provided under the tank sump. The valve shall be attached to poly reducer bushings and terminate out the bottom of the water tank below the truck and shall be controlled at the valve location.

ENCLOSED TOP MOUNT

A fully enclosed cab module shall be provided to accommodate the firefighters, and provide enclosed top-mount operation of the pump system. The modular cab shall be "stand-alone", totally separate from the apparatus body and from the chassis cab.

The modular cab shall have tow (2) full height crew access doorways, with hinged doors provided with upper level sliding windows.

Cab entrances are to be in compliance with NFPA standards handrails.

The exterior and interior steps and floor covering/plating’s are to be in compliance with NFPA for slip resistance and heights from ground as well as intermediate steps.

CONSTRUCTION MATERIALS

The crew cab structural components shall be fabricated of .190" smooth aluminum plate, including: front full width vertical panels, full height driver's and passenger's forward cab sides with outboard corners, driver's and passenger's full height rear cab sides, rear cab full width panels, and the entire roof cap with back-sloped front.

The crew cab fabricated outer door panels shall be constructed of .125" smooth sheet aluminum. The following crew cab components shall be fabricated of or plated with .125" polished 4-way aluminum treadplate C-102 pattern: interior crew cab transverse floor/walkway, interior doorway step wells, interior crew cab pump enclosure, removable pump access door, and optionally specified recessed seating cavity.

All specified aluminum treadplate step and walk surfaces shall incorporate an NFPA

Page 7 of 55

Page 8:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

approved non-slip pattern.

All crew cab screw type fasteners shall be stainless steel "low profile" button socket head cap screws, equipped with Ny-Lok stainless steel hex nuts.

CONSTRUCTION METHODS

The entire crew cab module shall be precision machine fabricated "concealed-bolted-construction," and properly reinforced without the use of angles or structural shapes. Bolted construction shall allow for individual removal of each and every fabricated component, in the event of damage. Flanged areas of individual fabricated crew cab components shall be located inside the crew cab area so that their screw type fasteners are not visible from the exterior.

The entire roof cap. full width and full length, shall also be of all-bolted construction to allow for easy replacement in the event of damage from overhead hazards.

The size of fasteners and their spacing shall provide for maximum structural integrity and no leakage in mating flanged area between fasteners. All nuts shall be Ny-Lok, designed to prevent loosening. NOTE: Hex head, truss head, Phillips pan head, or other large profile fasteners are not to be used for assembly of fabricated sheet metal components.

Driver's and passenger's forward crew cab corners shall be full height of crew cab sides, with integral 45-degree beveled outboard front corners, and rear double flange forming the forward crew cab vertical door jamb.

The upper front of the crew cab shall "slope-back" at a 45-degree angle, full width of the cab, for streamline appearance and to allow for forward-and-up visibility window.

CREW CAB ACCESS DOOR WAYS, TWO (2) EACH

Driver's and passenger's side crew cab doorways shall be furnished, minimum size of 99" high x 28" wide, each provided with following specified flush-fit vertically hinged crew door and interior doorway step well. NOTE: The top of doorway opening shall be within four (4) inches of the roof cap height, to allow for maximum entry/exit head room. DOORWAY VERTICAL SCUFF PLATES

The rear "trailing-edge" doorway jambs shall be lined, full height and full depth (also wrapping around the exterior door jamb corner), with a single piece machine polished stainless angular trim molding for paint protection.

OVERHEAD DRIP PROTECTION

Full length machine polished extruded aluminum drip moldings shall be furnished, bolted in position immediately above crew cab doorway openings, extending from forward outboard corner to rear of roof cap. Drip moldings shall be drilled/fitted prior to and installed after final painting.

Page 8 of 55

Page 9:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

HAND RAILS, INTERIOR AND EXTERIOR

Interior door liner angle-mounted and exterior trailing doorway vertically mounted 1-1/4" diameter non-slip tubular hand rails are to be furnished, with chrome plated bolt-on brackets and surface mount gaskets. CREW ACCESS DOORS

Driver's and passenger's side "flush" vertically hinged crew cab access doors shall be furnished, outer door panels fabricated of smooth sheet aluminum, minimum of 2" thick, with U-formed flanged perimeter. Specified inner door liners are to be bolt-on easily removable, using low-profile machine screws and Nut-Serts imbedded in perimeter door flange

Polished stainless steel full height piano hinges are to be bolted to the door and to the forward "leading-edge" flange of doorway, using stainless screws and removable Ny-Lok nuts. Hinge leaf fastener holes and corresponding door jamb mounting holes are to be included in the CAD engineering, to assure precision fit of door in opening, and replacement repeatability.

3M dielectric insulating polyester film barrier tape must be provided on the mating surfaces of: hinge to door and hinge to doorway jamb.

Crew access doors are each to be provided with a stainless steel spring loaded top door jamb mounted door prop, with stainless steel restraint stop-nut. Door props are to be bolted to reinforced inner plates, not to removable door liners.

DOOR WINDOW

Tempered glass window units shall be provided, at least 20" wide x 32" high, located in the upper portion of the crew cab doors.

The window units shall have black anodized extruded aluminum exterior window frame with interior perimeter clamp-ring surround. Window unit exterior underside flange shall be silicone seal-caulked prior to installation in the window cut-out of the door outer panel. Permanent window units shall have outboard "tinted" (62% light transfer medium gray) tempered glass window panel with vinyl glazing weather-stripping, and continuous formed extrusions with minimum 3" radius corners.

NOISE ISOLATION

Interior cavity of cab crew doors, between outer door panel and removable inner liner, shall be packed with foam soundproofing material.

DOOR LATCHES, 2-POINT ROTARY SLAM, LOCKING STYLE

Each crew cab door shall be equipped with two (1-upper and 1-lower) FVMSS-approved rotary-slam latch mechanisms, connected with mechanical adjustable rods to a single door latch actuator. Door latch actuator shall be of the paddle style, with exterior and opposing lockable interior paddle handles.

Page 9 of 55

Page 10:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

WEATHER STRIPPING, REPLACEABLE

Clip-on hollow core neoprene rubber weather stripping shall be installed on perimeter doorway jambs, nylon reinforced web-strap type door stop bolted to door and doorway jamb. INTERIOR STEP WELLS, 2-LEVEL

Driver's side and passenger's side interior dual level step wells shall be provided, at least 28" wide x 11" deep (front-to-rear), evenly dividing the step height from exterior running board step level to the interior upper floor/walk-way.

The vertical step risers shall be outboard sloping, providing maximum lower stepping surface depth and minimum upper step well depth, while also maintaining maximum interior crew cab floor width (side-to-side). The top step surfaces shall meet NFPA requirements for slip-resistance.

Step surface, back riser, and step well sides shall be bolted in position and easily removable.

STEP LIGHTS

Two (2) each step well mounted 12-volt shielded light fixtures shall be furnished and activated with parking brake.

INTERIOR FLOOR, WALKWAY

The interior crew cab floor shall be at least 69" side-to-side, extending between interior floor level driver's side step riser and passenger's side step riser. Floor plating shall be bolted to the specified crew cab sub-frame cross channels, so as to be no more than 1-1/2" above the chassis frame rails. The top standing and walkway surfaces shall meet NFPA requirements for slip-resistance. The interior crew cab floor risers, inner door liners, recessed seat housings, step wells, and pump enclosure shall all be fabricated of natural finish non-painted scuff resistant material.

All fabrications and/or overlays must be bolted in position and easily removable.

NOTE: Permanently welded interior tread-plate overlays or step well and floor fabrications are not acceptable.

CREW CAB SUB-FRAME

A crew cab sub-frame shall be furnished, bolted to and removable from the chassis frame rails. Sub-frame shall consist of multiple low-profile 3" iron transverse channels welded to two (2) longitudinal 5/16" plate steel fabricated Z-iron chassis frame liners. The sides of frame liners are to be precision machined and bolted to the side web of both chassis frame rails, allowing easy removal of the entire crew cab module from the chassis. Sub-frame assembly shall be prime painted and color coat painted to match the chassis frame rails or the fire pump system. The inboard Z-iron and outboard chassis frame rail mating

Page 10 of 55

Page 11:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

surfaces shall be coated with ECK corrosion preventative prior to final installation of the sub-frame assembly. The crew cab sub-frame assembly shall be bolted to and provide support for the crew cab front panel, forward cab sides, rear cab sides, optionally specified hose cartridge tunnel, interior forward seat housing, and interior crew cab floor and doorway step well fabrications. Sub-frame's low profile design shall allow for maximum interior crew cab stand-up and walk-through headroom while providing for minimum exterior overall crew cab height.

"CURB-VIEW" LOWER DOOR WINDOWS

Tempered glass window units shall be provided matching width to upper windows, by at least 20" high, located: one (1) in the lower portion of each of the crew cab doors.

Window unit construction shall match the specified upper door window units, with black anodized extruded aluminum exterior window frame with interior perimeter clamp-ring surround, silicone seal-caulked prior to installation, with "tinted" tempered glass window panel with vinyl glazing weatherstripping. Tinted glass shall be 62% light transfer medium gray

CREW CAB INTERIOR DOOR LINER

The specified crew cab door liner(s) shall be constructed of .125" polished 4-way aluminum treadplate, so as to provide a scuff resistant non-painted surface. Liner is to be bolted in position and easily removable for service of the internal door latch mechanisms.

CREW DOOR CONSPICUITY

NFPA approved conspicuity material shall be provided, at least 96 sq. in, located on the lower interior crew cab door skin.

FRONT WINDOW, FORWARD & UP FACING

One (1), 16" x 68" front upper crew cab window shall be furnished, located immediately below roof cap, above chassis cab, on the “back-sloped” front panel. Window glass must be of a DOT compliant (forward facing) safety style laminate, installed using rubber window setting channel or a black anodized extruded aluminum frame.

FORWARD SIDE CREW CAB WINDOWS

The Crew Cab forward side panels shall be equipped with two (2) each, one (1) driver side and one (1) passenger side, upper level vertical window units. Window units are to be only 7” narrower than the front corner side panel width and the same height as upper door windows, provided with tinted glass panels and 3" radius corners.

REAR SIDE CREW CAB WINDOWSThe Crew Cab rear side panels shall be equipped with two (2) each, one (1) driver side and one (1) passenger side, upper level rectangular window units. Window units to be only 7” narrower than the rear cab side, by maximum height available from top of exterior side pump panel to roof cap (at least 28" tall), provided with tinted glass panels and 3"

Page 11 of 55

Page 12:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

radius corners.

CREW CAB REAR WINDOW

A rear Crew Cab window unit shall be furnished, installed immediately below the roof cap, equipped with "tinted" tempered or safety glass. Window shall be same type as side cab, measuring minimum 80" wide x 12" tall.

SCUFF PROTECTION, BELOW SPEEDLAYS

Exterior driver's and passenger's side forward crew cab corners, below the speed-lay hose beds, shall be over-laid with polished 4-way aluminum treadplate. Overlay shall wrap-around the outboard corner fabrication, inboard to the chassis cab width.

CREW CAB SPEED-LAY PROVISION

A transverse tunnel shall be furnished immediately to rear of crew cab front wall, above chassis frame.

Tunnel shall accommodate specified removable speed-lay trays.

POLISHED STAINLESS SURROUNDS

Polished stainless steel scuff plating shall be provided, completely surrounding the driver and passenger side tunnel openings, to protect side panels during hose deployment and installation of cartridge hose beds. Scuff plates shall have mitered joints cut to a radius to prevent injury to personal or cleaning equipment.

SPEED-LAY HOSE RESTRAINT, VINYL END FLAP

The open ends of the specified speed-lay hosebed cavities shall be equipped with a top opening single piece vinyl coated nylon "flap", equipped with two (2) pull-tight strap/buckle fasteners sewn to flap cover and bolted aluminum slide-extrusion with beaded bottom seam. Design shall allow for convenient removal for replacement. Vinyl end flaps shall be designed to secure (during travel) the packed hose and attached nozzle.

SPEED-LAY HOSE TRAYS

Two (2) removable speed-lay hose trays shall be provided, fabricated of 3/16" smooth aluminum.

Hose beds shall be located transverse through forward crew cab corners, at average waist level.

Each modular speed-lay hosebed cartridge shall accommodate 200 ft. each of 1-3/4" double jacket fire hose.

The cartridges shall each be provided with: four (4) vertical end hand holes, four (4) top outboard horizontal hand holes, perforated floor for hose ventilation, and nylon cavity runners/guides.

Page 12 of 55

Page 13:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

CEILING LINER MATERIAL, VINYL COVERED FOAM

The interior crew cab ceiling shall be lined with perforated black vinyl covered 3/4" foam cushion sound dampening material. Vinyl cushion material to be spray adhesive installed on underside flat metal surfaces and trimmed with black coated aluminum fabrications, bolted in position and removable. Roof bow covers shall be provided, to hold the individual ceiling liner panels in position and provide mounting panels for the specified interior crew cab overhead light fixtures. WALL LINER MATERIAL, VINYL COVERED FOAM

The crew cab interior walls shall be lined with perforated black vinyl covered 3/4" foam cushion material. Vinyl cushion material to be attached with spray adhesive, installed on all flat metal surfaces, including: full width and height of front panel (around pass-through) and full height and width of side panels (around windows). All interior vinyl cushion material corner seams shall be covered with black coated aluminum fabrications, bolted in position and removable.

Where ceiling liner is a matching perforated vinyl cushion material, black coated aluminum fabrications shall be provided, that retain the ceiling liner material and completely cover the roof support bows.

The doorway surround jambs shall be trimmed, on the interior of crew cab, with treadplate aluminum fabrications. Interior doorway trim fabrications shall cover the door hinge fasteners and wiring looms.

COMBO AIR CONDITIONER-HEATER

A Red Dot R-2300-2P or equal 17,700 BTU Cooling/32,000 BTU Heating combination heater and air conditioner evaporator shall be furnished, complete with: engine coolant heater lines extending from engine compartment to heater core, air conditioning refrigerant lines extending from chassis air conditioning system to evaporator.

STEP WELL HEATERS

For optimum heating, combination evaporator/heater core units with air ducts and multiple 12-volt squirrel cage fans, dual evaporators, and condensation drains shall be installed under specified cab steps.

CONSOLE AND DASH MOUNTED VENTS

Four (4) 6" diameter swiveling vents shall be installed around control console and along bottom of rear window to provide warm or air conditioned air for cab heat, cooling, and defrost. Ventilation tubing and duct work shall be completely concealed from view.

CONCEALED HEAT AND A/C LINES

Refrigerant / heater coolant hoses and air ducts, where inside crew cab, shall be fully enclosed inside black (to match interior wall liner) vinyl coated aluminum fabrications.

Page 13 of 55

Page 14:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

PANEL MOUNTED CONTROLS

Cooling and heating temperature shall be controlled by interior crew cab instrument panel mounted heater/air conditioning controls.

HEATER LINES

Hot water heater to be piped to chassis engine cooling system "down stream" of interior chassis cab heater. Heater lines shall extend from exterior chassis cab heater to specified crew cab heater and return to engine. GATE VALVES

Heater lines to be gated to prevent loss of engine coolant in the event of ruptured cooling line and also to allow shut down of heating system during summer time operations.

CREW CAB DEFROSTER FANS, TWO (2) EACH

Two (2), metal caged 12-volt adjustable ceiling fans shall be furnished, with fan mounted switch, located so as to de-fog rear and rear side windows.

REAR FACING SCBA SEATS, FOUR (4) EACH

Four (4) each, rear facing SCBA seats shall be provided at front of crew cab.

Bostrum "SecureAll" Tanker 400CT "black" Durawear covered recessed SCBA back crew seats shall be provided, mounted to a platform above the specified speed-lay module.

The seats shall include: overhead head rest, occupant sensor, tapered bottom cushion, sculptured back rest cushions, and SecureALL quick-release tank retainer with yellow grab-bar seat cushion recessed trigger.

The individual seat assemblies shall be evenly spaced within the mounting area, so as to provide for comfortable 29"+ wide seating positions.

Red (contrasting color) DOT approved vinyl retractable lap style seat belt assemblies are to be furnished, for each seating position.

PUMP COMPARTMENT INTEGRAL WITH CREW CAB

The pump compartment/enclosure shall be located "mid-ship" of the vehicle, integral with rear section of the crew cab, fully enclosed on front, rear, both sides, and top (inside crew cab). Driver's side and passenger's side exterior pump panels to be recessed from crew cab sides to allow for discharge outlet and suction inlet extensions, adapters, and closures to remain within 102" overall width of vehicle.

Access to the interior pump compartment is to be provided through specified interior crew cab pump access door.

Pump panel runningboards are to be provided; drivers and passenger's sides, at a level

Page 14 of 55

Page 15:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

to be "in-line" with the apparatus body rub rails.

BLEEDER VALVE AND DRAIN VALVE CONTROL PANELS

The passenger side and driver side gated discharge outlets and suction inlets bleeder valves shall be back side mounted to a brushed stainless steel horizontal full width bolt-on riser panel, located immediately above the pump panel runningboards. Bleeder and drain valve controls shall be located evenly spaced, in a single horizontal row, on the exterior side of the riser panels.

The top portion of the driver and passenger side exterior pump panels, below the crew cab side window units, shall be fabricated of brushed stainless steel, bolted in position and easily removable. This header panel is to be of the minimum height necessary to accommodate overhead pump panel light fixtures.

REMOVABLE SIDE PUMP ACCESS PANELS.Driver and Passenger sides of pump module shall incorporate brushed stainless steel removable panels, removal of which allows for total pump access, above and below the chassis frame levels, and full width of the pump module.

The removable side panels shall be located above and interlock with the driver and passenger side bleeder and drain valve control panels. Each removable side panel shall be held in place by four (4) outboard corner mounted chrome plated quick release push-button trigger latches, and shall be equipped with two (2) chrome plated grab handles to aid in the removal and re-installation of the panel. Removable side panels shall mate "flush" with the horizontal bleeder/drain riser panel and overhead header panel, and overlay onto brushed stainless steel side flanges thus eliminating the possibility of dissimilar metals corrosion.

Removal of the passenger and driver side trigger-latched panels shall provide an unobstructed opening of at least 36" wide by 34" tall, allowing access to and removal of all side discharge and suction gate valves and fittings.

Specified suction and discharge closures and elbow adapters shall allow for disassembly for complete removal of overlay inserts.

All discharge outlet and suction inlet holes are to be concentric/custom-fit around extension fittings. Trims rings shall not be acceptable

FULL-WIDTH INTERIOR PUMP CONTROL PANEL

A top-mount pump control console will be furnished, located above midship mounted fire pump, approximately 82" side-to-side width.

Pump control console lower plane shall slope down towards operator's standing position, and shall have a glare-free surface. The specified pump gauge panel to be located above and to the rear of pump control console.

The upper back plane of the pump control panel shall accommodate the specified "opening" instrument panel, and lower forward plane shall be stationary so as to facilitate

Page 15 of 55

Page 16:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

installation of the specified inlet/outlet/drain valve and pump manual controls.

PUMP CONSOLE HANDRAIL & REMOVABLE PUMP ACCESS DOOR

One (1), tilt-out/removable double panel interior pump compartment access door shall be furnished, recessed into and "flush" with the vertical front surface of the pump compartment.

Removable door shall be at least 40" wide x 35" high, fabricated of .125" polished 4-way aluminum treadplate, U-formed construction with: large polished stainless steel D-ring door handle and 2-point latch and bottom door locator pins.

Door shall tilt-out for visual inspection and be removable for unobstructed interior access to fire pump and its related plumbing.

HORIZONTAL HANDRAIL

A knurled hand rail with chrome plated end brackets shall be furnished, mounted horizontally below leading edge of pump control console. PUMP CONTROLS AND LOCATIONS & IDENTIFICATION

All specified pump discharge and suction controls are to be mounted on the top-mount pump control console, so as to permit operation of the pump from one central location. All of the specified discharge valve manual and power operated valve control consoles shall be evenly spaced on the same horizontal line, immediately below and in-line with their respective discharge pressure gauge/instrument.

Any optionally specified, remote toggle switch activated gated pump suction controls, with "open" indicator lights, shall be prominently grouped together on the pump control console, for ease of identification.

All discharge valve and suction valve mechanical control rod linkages, extending from the control handle to the valve lever, are to be heavily cadmium plated solid cold rolled steel, equipped with adjustable threaded/jam-nut clevis or swivel ball joints on each end. Control linkages shall not require lubrication, and are to be warranted for a period of 25-years.

NOTE: Flexible control cables, wires, and other less positive methods of valve movement are not acceptable. The specified discharge and suction manifolds shall be designed to allow "line-of-sight" pathways from valve control to the valve levers, negating the need for bendable floppy devices requiring lubrication and exclusive source replacement.

All controls and inlets, drain valve controls, bleeder valve controls, and all other pump related accessory controls shall be properly identified with nameplates describing function and operation of each control.

SEALED ENVIROMENT CONTROL CONSOLE

Page 16 of 55

Page 17:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

Design and construction of the pump control panel and gauge panel shall prevent exposure to the interior pump compartment, thereby preventing air, noise, and moisture contamination into the fully enclosed crew cab/operator's control area.

NOTE: Discharge and/or suction controls which require slotted openings (gasketed or not) in the control panel for travel of the valve control handle, are not be acceptable.

TOP MOUNT VALVE CONTROLS, CLASS-1

Six (6) Class 1 model 100984, Top Mount Lever Style push-pull valve controls, with "twist-to-lock" round grab handles shall be furnish, to include recessed identification name plates.

DISCHARGE CONTROL NAME PLATES

The specified individual discharge control engraved color coded identification name plate’s nomenclature shall, describe: the physical location of outlet, the size of hose to be attached, and the type of discharge. Where an outlet is Foam Capable, the name plate shall so describe.

DISCHARGE OUTLET NAME PLATES

Individual Discharge Outlet name plates are to be provided adjacent to the outlet or hosebed. Outlet name plates are to be of the same color as the discharge valve control name plate, pressure instrument/gauge name plate, and the bleeder valve control name plate. PRINTED NAME PLATES The specified identification tags (name plates) shall consist of permanently encapsulated UV resistant printing, attached to the pump panels, operator’s panel, and body panels where designated. All discharge related name plates are to be color coded as specified below.

NAME TAG SURROUND BEZELS

The individual identification name plates shall be perimeter surrounded by chrome plated trim bezels. Nomenclature is to be printed black on white and surrounding chrome bezels are to have top and bottom color imprinted to match color of control and respective gauge. FIRE PUMP SYSTEM

WATEROUS SINGLE-STAGE 1250 GPM 'FULL-BODY' PUMP, PTO DRIVEN

A 1250 gallon per minute, Waterous Model CSPA-1250, Class A, PTO driven single-stage centrifugal iron pump body - rear pump transmission drive, fire pump shall be furnished, mounted "mid-ship" of the vehicle immediately ahead of the compartments and water tank. Pump transmission to be Waterous "PA" chain-drive, to provide smooth quiet transmission of power. The pump transmission ratio, in combination with the chassis transmission mounted PTO ratio shall allow the pump to deliver the percentage of rated

Page 17 of 55

Page 18:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

capacity at discharge pressures indicated below, during stationary pumping operations, while the drive engine is running in it's peak performance range/RPM: 100 percent of rated capacity at 150 pounds net pressure 100 percent of rated capacity at 165 pounds net pressure 70 percent of rated capacity at 200 pounds net pressure 50 percent of rated capacity at 250 pounds net pressure

In addition to stationary pumping, the specified pump drive system shall allow for "Pump & Drive" operations, at less than rated capacity. MANUFACTURER HYDRO TESTThe pump shall be tested by Waterous, hydrodynamically at above pressure and capacities, and for 10 minutes hydrostatically at a pressure of 500 psig. Certification by Waterous shall be provided in delivery manual. Apparatus Manufacturer's pump performance test to be performed after construction. Factory certification to be provided in delivery manual. PUMP INSTRUCTION MANUALS/CDTwo (2), Waterous instruction manuals, one (1) in digital CD format, and one (1) printed with 3-ring binder, shall be provided upon delivery of the apparatus. Manuals to be pump model and serial number specific, to include but not be limited to operation instructions, maintenance (lubrication), and illustrated parts break-down.

PUMP TEST DATA PLATE

The pump shall be provided with a metal plate giving the rated flow at "capacity" and "pressure" test pressures, together with the RPM of the engine at those pressures and deliveries, and mounted in clear view of the pump operator's panel. Test plate shall also indicate pump serial number, engine governed speed, and pump mode of operation for all four individual pump rating tests.

SEPARABLE IMPELLER SHAFT

A separable impeller shaft shall be furnished to allow removal or disassembly of the pump transmission, separate from the pump body. ADDITIONAL FEATURES

Additional pump features shall include: dual-suction bronze replaceable impeller and impeller seal rings, stainless steel impeller shaft grease lubricated front and oil lubricated rear bearings, horizontally split main pump body, and all moving parts which come into contact with water to be bronze or stainless steel.

PUMP LUBRICATION

One grease zerk shall be installed on driver's side exterior pump panel, piped with clear nylon 3/16" tubing to the front impeller shaft bearing cap. Grease zerk to be provided with removable dust cap, bearing end cap equipped with relief device to discharge excess grease.

Page 18 of 55

Page 19:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

PUMP FLUID CAPACITY PLATE

A permanently mounted metal plate shall be furnished, located inside driver's compartment, specifying the quantity and type of the pump system fluids (where applicable) as used in this apparatus. Additional information to be provided for pump accessory equipment fluids not listed, and so designated by Customer.

PTO & PTO DRIVELINE

The Waterous "PA" chain style pump transmission shall be driven by a heavy duty Chelsea "hot shift" (or Muncie equivalent) gear style PTO and Spicer Driveline. The pump/PTO shall be engaged with a cab console mounted illuminated rocker switch shift.

Spicer 1300 series Driveline components to be furnished to facilitate pump removal, components shall include: pump and PTO end yokes, slip stub shafts, slip yokes, and cross-and-bearings. Driveline to be high speed balanced.

PUMP SEALS

"Mechanical" pump seal assemblies to be furnished, with the specified full-body centrifugal pump, self-adjusting type, maintenance free.

INDICATOR LIGHTS - PUMP SHIFT

The specified PTO pump system shall be provided with the following indicator lights: Two (2), green indicator lights shall be provided in the driving compartment as follows: one (1) of the lights shall be energized when the pump drive has been engaged and shall be marked "Pump Engaged". The second light shall be energized when both the pump drive has been engaged and the chassis transmission is in neutral and shall be marked "OK to stationary pump." One (1) green and one (1) red indicator light shall be provided on the pump operator's panel. The green light shall be energized when the chassis transmission is in neutral, pump, and the parking brake are engaged. The green light shall be positioned adjacent to, and preferably above, the throttle and shall be marked "OK to Stationary Pump." The red light shall be engergized when the pump is engaged and the chassis transmission is not in neutral or the park brake is not applied and shall be located adjacent to, and preferably above, the throttle, and shall be marked "Pump and Roll Mode."

ENGINE COOLER/HEAT EXCHANGER CONTROL VALVE

The customer's furnished heat exchanger shall be controlled from the pump operator's position, with a Class-1 1/4-turn 3/8" ball valve control on pump control panel. A gate valve is to be provided, mounted on the operator's pump panel, properly labeled to identify its operation. Piping from the fire pump to the heat exchanger, and return (to pump Master Drain suction port), shall be provided by the installer (customer), using high

Page 19 of 55

Page 20:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

pressure line. Pressure line (from pump discharge) to be gated, with a Class-1 1/4-turn 3/8" ball valve control on pump control panel, with instructional nameplate.

PUMP DRAIN MANIFOLD

Waterous manifold drain valve, with bronze body and stainless plunger shall be furnished mounted on pump transmission and operated by a push-pull cable with chrome plated T-handle control on pump panel. Drain valve shall be piped with high pressure nylon tubing, to low points of pump suction and discharge cavities to allow simultaneous draining through a single drain valve.

INTAKE RELIEF VALVE, 2-1/2" STAINLESS STEEL

A Class 1 model 107819 stainless steel pump suction intake relief valve shall be furnished, installed inside pump compartment, flange bolted or threaded to suction cavity of the fire pump. Valve to be of the pre-set (to 125 psi) adjustable bypass design, to dump below the vehicle excessive inlet water pressure. Relief valve to be accessible for future adjustment of bypass pressure.

PRESSURE GOVERNOR & MONITORING DISPLAY, FRC PUMPBOSS

Fire Research PumpBoss series PBA401-D00 pressure governor and monitoring display kit shall be installed. The kit shall include a control module, intake pressure sensor, discharge pressure sensor, and cables. The control module case shall be waterproof and have dimensions not to exceed 6 3/4" high by 4 5/8". The control knob shall be 2" in diameter with no mechanical stops, have a serrated grip, and a red idle push button in the center. It shall not extend more than 1 3/4" from the front of the control module. Inputs for monitored engine information and outputs for engine control shall be on the J1939 databus. Inputs from the pump discharge and intake pressure sensors shall be electrical

The following continuous displays shall be provided:Engine RPM; shown with four daylight bright LED digits more than 1/2" highCheck engine and stop engine warning LEDsEngine oil pressure; shown on a dual color (green/red) LED bar graph displayEngine coolant temperature; shown on a dual color (green/red) LED bar graph displayTransmission Temperature: shown on a dual color (green/red) LED bar graph displayBattery voltage; shown on a dual color (green/red) LED bar graph displayPressure and RPM operating mode LEDsPressure / RPM setting; shown on a dot matrix message displayThrottle ready LED.

The dot-matrix message display shall show diagnostic and warning messages as they occur. It shall show monitored apparatus information, stored data, and program options when selected by the operator. All LED intensity shall be automatically adjusted for day and night time operation.The program shall store the accumulated operating hours for the pump and engine to be displayed with the push of a button. It shall monitor inputs and support audible and visual warning alarms for the following conditions:

High Battery VoltageLow Battery Voltage (Engine Off)

Page 20 of 55

Page 21:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

Low Battery Voltage (Engine Running)High Transmission TemperatureLow Engine Oil PressureHigh Engine Coolant TemperatureOut of Water (visual alarm only)No Engine Response (visual alarm only).

The program features shall be accessed via push buttons located on the front of the control module. There shall be a USB port located at the rear of the control module to upload future firmware enhancements.

The governor shall operate in two control modes, pressure and RPM. No discharge pressure or engine RPM variation shall occur when switching between modes. A throttle ready LED shall light when the interlock signal is recognized. The governor shall start in pressure mode and set the engine RPM to idle. In pressure mode the governor shall automatically regulate the discharge pressure at the level set by the operator. In RPM mode the governor shall maintain the engine RPM at the level set by the operator except in the event of a discharge pressure increase. The governor shall limit a discharge pressure increase in RPM mode to a maximum of 30 psi. Other safety features shall include recognition of no water conditions with an automatic programmed response and a push button to return the engine to idle.

The pressure governor and display shall be programmed to interface with a Cummins engine.

PRIMER PERFORMANCE REQUIREMENTS

The pump shall be capable of taking suction and discharging water with a lift of 10 ft. in not more than 30 seconds with the pump dry, through 20 ft. of suction hose of appropriate size. It shall be capable of developing a vacuum of 22" at an altitude of up to 1000 ft.

WATEROUS VPOS PUMP PRIMER

A high capacity positive displacement self lubricating priming system shall be furnished, consisting of: a Waterous VPO "oil-less" rotary vane priming pump with 12-volt electric motor drive, and a manual/electric priming valve assembly with remote pump operator's panel mounted pull/spring-return control. Priming pump shall be mounted beneath fire pump. Priming valve assembly to be self draining, located on top of pump.

HEAT ENCLOSURE, ALUMINUM

A removable heater casing is to be provided, completely enclosing the under side of the fire pump compartment module. Heater casing side and end panels are to be fabricated entirely of natural finish smooth sheet aluminum, bolted to and easily removable from the bottom perimeter of the pump module. So as to allow maximum ground clearance, the heater casing shall be the minimum depth required to enclose the pump transmission, horizontal engine exhaust system, and all pump accessories. Two (2) individual smooth aluminum slide-out bottom panels are to be provided, criss-cross reinforced with drain holes and ¼-turn butterfly clamp latch, removal of which allows for inspection of and

Page 21 of 55

Page 22:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

access to the fire pump and chassis components. NOTE: A center bottom slide-out panel brace shall be provided, off-set to one side so as to not obstruct the pump transmission lubricating fluid drain. PUMP WARRANTY

The specified Waterous fire pump and Waterous accessories shall carry a Waterous five (5) year warranty covering defective parts only.

STAINLESS STEEL TUBULAR PUMP SUCTION INLET AUXILIARY PIPING

Suction manifolds, where not part of and integral with the pump manufacturer's pump intake castings, shall be fabricated of "tubular" stainless steel ONLY, schedule 10 or schedule 40 wall thickness. All auxiliary side threaded taps and/or Victaulic risers shall be "coped" to conform to radius of larger size waterway, so as to provide unsurpassed flow characteristics.

NOTE: Due to the poor flow characteristics, a suction manifold fabricated of square or rectangular tubing with flat-mount weld spuds and/or riser pipes for auxiliary suction taps, is not an acceptable substitute to a tubular manifold.

Heavy wall threaded stainless steel pipe and pipe fittings shall be used, wherever possible, upstream of the specified 2-1/2" suction valves.

All suction manifolds and fittings, and suction valves, tubing's, and hoseline assemblies shall be pressure tested after installation.

PUMP SUCTION INLETS Following specified pump manifold inlets shall be equipped with zinc die cast screens so as to provide cathode protection for pump waterways.

All intakes shall be provided with suitable closures capable of withstanding 500 psi, threaded caps shall be chrome plated brass, rocker lug 3" and smaller, long handled larger than 3".

SUCTION INLET VALVE STANDARDS (WHERE OPTIONALLY SPECIFIED)

Following optionally specified 3" or larger gated intakes (except the tank-to-pump intake) shall include a remote controlled valve mechanism that shall not permit changing the position of the flow regulating element of the valve from full close to full open, or vice versa, in less than 3 seconds. Where air type actuators are employed, they shall include dual (2-each) adjustable needle valve restrictors, bench set/tested, so as to facilitate the slow movement. Where manual gear or electric gear style actuators are employed, the crank or motor shall regulate movement speed.

SHORT SUCTION TUBE

The specified side pump suction inlet(s) shall be of minimum length to allow for exterior stacking of adapters or preconnected hose.

Page 22 of 55

Page 23:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

INLET BLEEDER VALVES

Where specified, each gated intake shall be equipped with a bleeder valve located inside pump compartment (inside rear compartment-for rear suctions), upstream gate valve, with remote bleeder control in close proximity to the intake. The gated inlet bleeders shall consist of: 3/4" high pressure flexible hose assemblies extending between suction valve and bleeder valve, 3/4" cast bronze or stainless steel bleeder valve, exterior bleeder valve control handle, and an engraved or printed identification label. Bleeder controls for side gated inlets are to be located below the inlet, in a single row immediately above the runningboard/floor level. Bleeder controls for optionally specified rear inlets are to be located below the inlet, above the tailboard level. The bleeder valves shall be Class-1 model 115639 “lift-handle” style equipped with chrome plated lever control handles, which are in the down position when closed.

HOSE THREADS

Where specified, all screw-on/off threads shall be NST (National Standard Threads), all "sexless" couplings shall be Storz. SELF BLEEDING SUCTION CAPS

The specified "threaded" suction caps shall be the VLH Class-1, Trident or equivalent which incorporates a cross-machined thread design to automatically relief stored pressure in the line during un-capping.

VALVES - AKRON HEAVY DUTY 8800/8600 SERIES

All ball valves shall be Akron Brass in-line valves, dual directional flow style; suitable for suction and/or discharges.. The Akron valves shall be the 8800 or 8600 series heavy-duty style with flow optimizing stainless steel ball and a simple polymer two-seat design.

The specified Akron valves shall not require lubrication of their dual polymer seats or any other internal waterway components, and must be capable of swinging out of the waterway for in-line maintenance.

6" GATED MASTER SUCTION, 6" NST CAPPED, OPERATOR'S PANEL CONTROL

A passenger's side gated 6" pump suction intake is to be provided with: 6" NST 500 psi chrome plated long handle cap, 6" removable zinc strainer, 6" NST male x 6" ASA flanged extension nipple (inlet extending through pump panel), bronze bleeder valve located inboard pump panel with exterior control handle, 6" Weco butterfly style gate valve with "slow operating" paddle type air actuator, operator's panel valve control console with guarded toggle switch and "OPEN" indicator light, and appropriate interior pump compartment 6" ASA flanged pump intake fitting. Suction inlet is to have a minimum extension outboard of the pump panel so as to allow for preconnected soft suction hose.

SUCTION INTAKE RELIEF VALVE - INBOARD PASSENGER SIDE PUMP PANEL

A Class-1 adjustable stainless steel suction intake relief valve shall be furnished, enclosed inboard the passenger's side pump panel. Intake relief valve to be located

Page 23 of 55

Page 24:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

upstream of the above specified butterfly style gate valve, "sandwiched" between gate valve and specified external inlet fitting. Intake relief valve shall be mounted so as to self-drain and dump excessive suction inlet pressure below the pump compartment.

6" NON-GATED MASTER SUCTION, 6" NST CAPPED

A driver's side 6" pump suction intake to be provided with: 6" NST 500 psi chrome plated brass long handled cap, 6" removable zinc strainer, 6" NST cast iron threaded intake fitting extension, and appropriate cast iron interior pump compartment mounted threaded intake fitting. Inlet shall have minimum extension outboard the pump panel.

2-1/2" GATED SUCTION, 2-1/2" NST PLUGGED, REMOTE CONTROL

An Akron driver's side gated 2-1/2" pump suction intake to be provided with: 2-1/2" NST male chrome plated rocker lug plug type cap with chain, 2-1/2" NST chrome plated rocker lug swivel female with internal strainer, bronze bleeder valve with outboard control knob, 2-1/2" full flow Akron 1/4-turn ball style bronze suction valve with air cylinder actuator located inboard pump panel, minimum 2-1/2" i.d. threaded pipe and elbows between valve and pump intake fitting, and remote valve control console with guarded toggle air valve and "OPEN" indicator light.

TANK-TO-PUMP CONNECTIONS

3-1/2" WATEROUS SUCTION VALVE, HIGH-FLOW

A 3-1/2" full-flow Waterous tank-to-pump 1/4-turn valve to be furnished with chrome plated bronze ball, spring loaded seal assembly, and inlet hose connection. The gated suction line/piping from specified tank sump to the tank-to-pump valve shall be furnished with reusable screw-banded flexible "hump hose" connection and 4" i.d. stainless steel piping enclosed within the fire pump compartment. Tank-to-pump suction line design and size shall allow a flow rate of at least 700 GPM. (200 GPM in excess of NFPA minimum requirement).

NOTE: Plastic or PVC tubing is not an acceptable alternative to stainless steel piping. TANK-TO-PUMP CHECK VALVE

Waterous bronze tank-to-pump suction check valve to be furnished, integral with fire pump main body casting, full-flow design to prevent obstruction of suction waterway (available on CS and CM pumps only). Check valve shall prevent high capacity "back-flow" of water from the pump-to-tank, if the tank suction valve is inadvertently left open.

TANK REFILL

One (1), gated 1-1/2" tank fill discharge line, from pressure side of fire pump to water tank to be provided with: tank fill spud located at top front of water tank, high pressure wire reinforced 1-1/2" hose with reusable threaded end couplings, 1-1/2" NRS bronze screw-type valve and pump operator's panel mounted screw type control knob. Tank fill valve to be of the screw-type so that it can be throttled and used as a bypass or pump cooling line. Control nameplate to read: "TANK FILL - PUMP COOLING".

Page 24 of 55

Page 25:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

INDUSTRIAL PUMP DISCHARGE OUTLET CONTROLS AND ACTUATORS

All discharge valves shall have operating controls and actuators that allow the valve to be positioned incrementally from closed to full open, and locked in any selected position. Each valve control is to be adjacent to its respective pressure instrument.

Each of the specified 3" diameter or larger discharge valves are to have an operating mechanism which shall not permit changing the position of the flow regulating element of the valve from full close to full open, or vice versa, in less than 3 seconds. DISCHARGE OUTLET BLEEDERS

Each of the following specified gated discharges shall be equipped with a "discharge outlet bleeder". The outlet bleeders shall consist of: 3/4" high pressure flexible hose assemblies extending between discharge valve and bleeder valve, 3/4" cast bronze or stainless steel bleeder valve mounted interior of pump compartment (inside rear compartment-for rear discharges), and an exterior bleeder valve control handle with color coded (to match corresponding discharge outlet) engraved or printed identification label. Bleeder controls for side discharges are to be located below the outlet, in a single row immediately above the runningboard/floor level. Bleeder controls for optionally specified rear discharges are to be located below the outlet, above the tailboard level. The bleeder valves shall be rotating quarter-turn style equipped with rectangular chrome plated control handles, which are horizontal when closed.

HOSE THREADS

Where specified, all screw-on/off threads shall be NST (National Standard Threads), all "sexless" couplings shall be Storz.

PUMP FITTINGS & "ROUND TUBULAR" S/S DISCHARGE MANIFOLD

The above specified fire pump shall be provided with high-tensile closed grain cast iron "bolt-on" left and/or right side discharge fittings (upstream of discharge valves only) and cast iron "bolt-on" left side, right side, and/or front/rear large diameter suction intake adapters, as provided and flow/pressure tested by the fire pump manufacturer.

A stainless steel "round tubular" discharge manifold shall be furnished, flange bolted or Victaulic clamped to and easily removable from, the fire pump's large diameter discharge outlet taps.

NOTE: Due to the likelihood of high pressure deformation (regardless of wall thickness), manifolds fabricated of square or rectangular tubing's, are not acceptable

The tubular manifolds main waterway shall be commensurate in diameter to feed the quantity and size of auxiliary discharge line "branches". So as to provide unsurpassed flow characteristics, all auxiliary branch reducers shall be concentric bell reducers, and all couplings and risers shall be "coped" to conform to the radius of the larger size feed waterway. Flat-mount weld spuds and non-coped risers welded to rectangular fabrications and end plates are not acceptable.

All stainless steel welding shall be TIG, to assure proper penetration and conformity with

Page 25 of 55

Page 26:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

original tubing and weld fitting outside diameters. All elbows shall be smooth sweep weld fittings.. See following specifications describing the number/size/locations of outlet gate valves to be furnished.

Heavy wall threaded pipe and pipe fittings shall be used, wherever possible, downstream of the specified side outlet and top deluge discharge valves.

All flexible discharge lines and bleeder lines, downstream of respective valves, shall be reinforced high pressure hose assemblies with stainless steel or brass end fittings.

Pressure gauge tubing lines shall be clear polypropylene with brass fittings, manifold drain lines (that are not high pressure hose assemblies) shall be copper tubing.

All discharge manifolds and fittings, suction manifolds and fittings, discharge and suction valves, tubing's, and hoseline assemblies shall be pressure tested before and after installation.

PASSENGER SIDE 2-1/2" DISCHARGE

One (1), passenger's side 2-1/2" gated discharge to be provided with: 2-1/2" NST chrome plated brass rocker lug cap with chain, 2-1/2" NST male x 2-1/2" NST rocker lug swivel female 45 degree chrome plated brass elbow outlet extension, 2-1/2" NST male chrome plated brass outlet adapter, 3/4" bleeder valve and hose assembly, 2-1/2" i.d. stainless steel pipe nipple, 2-1/2" Akron 8000 series ball style 1/4-turn full flow bronze bodied self-locking discharge valve (located inside pump enclosure), and push-pull chrome "locking-style" discharge control handle located on the pump operator's control panel.

3" GATED OUTLET, 4" NST x 5" STORZ x 2-1/2" NST OUTLET WITH ELBOW

There shall be an LDH discharge outlet with a 3" Akron Hand Wheel crank operated valve, installed on the passenger side of the apparatus, terminating with 2-1/2" chrome rocker lug cap, 2-1/2" NST male x 5" Storz adapter, 5" Storz 30 degree elbow x 4" NST female outlet adapter, 4" NST male threaded outlet. This discharge outlet shall be actuated with a crank control, and hand wheel with position indicator at the pump operator's control panel. REAR DRIVER SIDE 2-1/2" DISCHARGE

One (1), rear (driver's side) 2-1/2" gated discharge to be provided with: 2-1/2" NST chrome plated brass rocker lug cap with chain, 2-1/2" NST male x 2-1/2" NST rocker lug swivel female 30 degree chrome plated brass elbow extension, 2-1/2" NST male chrome plated brass outlet adapter, 3/4" bleeder valve with exterior remote control, 2-1/2" i.d. stainless steel pipe or wire reinforced hose assembly with 2-1/2" stainless end fittings, 2-1/2" Akron 8000 series ball style 1/4-turn full flow bronze bodied self-locking discharge valve (located inside pump enclosure),and a push-pull locking control with color coded nameplate located on the pump operator's control panel.

DRIVER SIDE 2-1/2" DISCHARGE

Page 26 of 55

Page 27:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

One (1), driver's side 2-1/2" gated discharge to be provided with: 2-1/2" NST chrome plated brass rocker lug cap with chain, 2-1/2" NST male x 2-1/2" NST rocker lug swivel female 45 degree chrome plated brass elbow outlet extension, 2-1/2" NST male chrome plated brass outlet adapter, 3/4" bleeder valve and hose assembly, 2-1/2" i.d. stainless steel pipe nipple, 2-1/2" Akron 8000 series ball style 1/4-turn full flow bronze bodied self-locking discharge valve (located inside pump enclosure), and push-pull chrome "locking-style" discharge control handle located on the pump operator's control panel.

SELF-BLEEDING DISCHARGE CAPS, AND ELBOWS

Where specified, the rocker lug discharge caps and outlet elbow extensions are to be VLH, Class-1, Trident, or equivalent which incorporates a cross-machined thread design to automatically relieve stored pressure in the line during uncapping/unthreading.

FIRE PUMP MODULE, MIDSHIP OF APPARATUS, INDEPENDENT OF BODY

FORWARD SPEEDLAY 2" DISCHARGE

One (1), forward horizontal speed-lay 2" gated discharge to be provided with: 1-1/2" NST male outlet x 2" inlet 90 degree bronze or stainless steel discharge swivel, hoseline bleeder valve, 2" i.d. stainless steel pipe or wire reinforced hose with 2" stainless end fittings, 2" Akron 8000 series ball style 1/4-turn full flow bronze bodied self-locking discharge valve (located inside pump compartment), and push-pull chrome "twist-to-lock" discharge control handle with recessed color coded nameplate located on the pump operator's control panel.

BACK SPEEDLAY 2" DISCHARGE

One (1), back horizontal speed-lay 2" gated discharge to be provided with: 1-1/2" NST male outlet x 2" inlet 90 degree bronze or stainless steel discharge swivel, hoseline bleeder valve, 2" i.d. stainless steel pipe or wire reinforced hose with 2" stainless end fittings, 2" Akron 8000 series ball style 1/4-turn full flow bronze bodied self-locking discharge valve (located inside pump compartment), and push-pull chrome "twist-to-lock" discharge control handle with recessed color coded nameplate located on the pump operator's control panel.

TRANSVERSE SPEEDLAY HOSEBEDS, IN FORWARD SECTION OF CREW CAB:

Please refer to the Crew Cab section of detailed specifications, for the "SPEEDLAY HOSEBEDS" configuration.

ISOLATED TUBULAR DISCHARGE MANIFOLD, FOR FUTURE FOAM CAPABILITY

A flanged bolt-on tubular stainless steel "isolated" pump discharge foam manifold is to be furnished, configured to feed multiple designated discharge lines that can, with the addition of a direct discharge foam system, become foam capable.

REMOVABLE MANIFOLD SECTION

Page 27 of 55

Page 28:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

The tubular discharge manifold is to include a removable section of tubing, at least 15-inches upstream of the specified meter receptacle, designed to be replaced by a future installed check valve. The tubular manifold is to also be provided with a riser receptacle, which will accommodate a flow meter device, a bottom fitting tap for the remote manifold drain valve, and multiple flanged ports for use with discharge valves designated as future foam lines.

FOAM MANIFOLD CAPACITY

Discharge foam manifold is to be of adequate size/capacity to handle flows up to 850 gallons per minute.

TUBULAR MANIFOLD DRAIN

A 3/4" quarter-turn bronze drain valve, with chrome plated control handle and recessed name tag, is to be furnished, located on a side pump panel immediately above the running board/rub rail level.

Manifold drain line is to extend from a bottom tap on the tubular discharge (future foam) manifold, with positive "gravity-drain" to the panel mount drain valve, assuring complete drainage of the manifold downstream upstream of the manifold fed discharge valves.

ACCOMMODATONS FOR FOAM CONTROL CONSOLE AND LIQUID LEVEL INDICATOR

The specified pump operator's control panel is to be configured so as to allow for the future installation of a foam system control console. The space is to be easily accessible from the pump operator's standing position. Mounting space is to also be provided, on the specified gauge and instrument panel, of installation of an additional matching brand liquid level indicator.

ACCOMMODATIONS FOR DC MOTOR DRIVEN FOAM PUMP

A fabricated stainless steel platform is to be provided, installed inside the pump module, in a location conducive for installation of a 12-volt DC motor-driven direct discharge foam injection system. The platform is to be bolted in position and removable.

PUMP MOUNTING, FULL-BODY MID-SHIP PUMP WITH PTO-DRIVE

The specified full body midship pump system, with its integral pump transmission, shall be independently mounted on a "pump house" subframe which itself is to be bolted to and easily removable from the chassis frame rails. The subframe shall consist of a two (2) each 5/16” steel plate fabricated Z-irons which rest on the top flange of the chassis frame rails; and are sandwich bolted to the outboard chassis frame webs. This design shall provide for a “rigid” mount of the pump house, and perfect horizontal and vertical alignment with the apparatus body, runningboards always remaining in alignment with apparatus body rubrails. The pump house is to be located no more than one (1) inch forward of apparatus body, and two (2) inches rearward of the chassis cab. Pump mount brackets are to be placed at the same relative angle as engine/transmission and the rear axle.

Page 28 of 55

Page 29:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

Pump mounting brackets and pump house subframe shall be primer painted and urethane painted to match pump or chassis frame rails.

PRESSURE GAUGES/INSTRUMENTS ALIGNED WITH DISCHARGE CONTROLS The following specified pump panel mounted discharge controls shall be located adjacent to or immediately below and inline with corresponding individual discharge pressure gauge. The control panel shall be configured in an organized manner, "user-friendly", side-to-side across the entire panel.

PUMP GAUGE & INSTRUMENT PANEL 12-VOLT LED LIGHTING

Multiple weatherproof Weldon model 2631 or equivalent 12-volt LED light fixtures shall be furnished, located overhead the pump gauge/instrument panel, lights to be installed beneath a protective metal light shield, illuminating the gauges, instruments, and controls. Lights shall be illuminated with panel mounted switch, identified with backlit nameplate.

SIDE PUMP PANEL LIGHTING

Multiple chrome plated 12-volt shielded pump panel light fixtures shall be furnished, located top outboard corners of side pump panel(s). Lights to be activated by setting of the vehicle’s Park Brake.

ENGINE INSTRUMENTATION

The engine instrumentation is to be included in the specified fire pump pressure control system "engine governor". Instrumentation shall be integral with the Governor Control.

HEATER, PUMP COMPARTMENT

HOT WATER TYPE HEATER, 30,000 BTU

A 30,000 BTU Badger R-255-0 or equivalent hot water type automotive heater to be furnished and installed inside the compartment, above the manifolds. Heater installation to include: gated engine coolant feed and return lines, dual 12-volt electric fans, and fan control located on operator's control panel. COLOR CODED DISCHARGE NAMEPLATES: NOMENCLATURE

Discharge name plates and/or control diagrams are to be permanently engraved into colored media or encapsulated color coded printing, as specified below. Name plate colors are to match the designated color of the individual outlets and pressure instruments.

Suction name plates are to be of the same single color, contrasting to the discharge colors

The name plate's nomenclature is to identify: physical location, size of hose to be attached, and type of discharge. Example: REAR PASSENGER SIDE 2-1/2" PRECONNNECT DISCHARGE

Page 29 of 55

Page 30:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

Color matching name plates are to be provided for: Discharge Outlet (or Hosebed Pre-Connect), Discharge Control, Discharge Pressure Instrument, and the Discharge Bleeder Control..Apparatus locations are to be identified as: FRONT (forward facing), PASSENGER SIDE (curb side facing), REAR (rearward facing), and DRIVER SIDE (street side facing).

On sides of apparatus, left-to-right locations are to be identified as FORWARD and REARWARD.

NOTE: The terms LEFT and RIGHT are not to be utilized, unless specifically instructed to do so by customer.

MASTER PUMP PRESSURE GAUGES

Master pump intake and pump discharge pressure indicating devices shall be located within 8" of each other, edge to edge, with the intake (suction) pressure indicating device to the left of the pump discharge pressure indicating device. A 4-1/2" diameter Class One LFP410 compound style pressure gauge to be furnished, registering 0 x 600 psi, black numerals on white background. Gauge to be piped to discharge volute of fire pump, equipped with a black permanently engraved identification nameplate installed below the gauge, to read: "DISCHARGE." A 4-1/2" diameter Class One LFP410 compound style pressure gauge to be furnished, registering -30 x 400 psi, black numerals on white background. Gauge to be piped to suction volute of fire pump, equipped with a black permanently engraved identification nameplate installed below the gauge, to read: "SUCTION."

TEST GAUGE PANEL

One (1), dual test plug assembly to be furnished, installed on specified gauge panel adjacent to respective pump suction and pump discharge gauge. Test plugs to be piped to pump suction cavity and discharge cavity using high pressure clear nylon tubing with brass fittings.

INDIVIDUAL DISCHARGE GAUGES

Six (6), 2-1/2" diameter Class One LFP210 compound style discharge pressure gauges to be furnished, registering 0 x 400 psi, black numerals on white background. Gauges to be located in a uniform manner no more than 6" from its respective discharge valve control. Each gauge and respective discharge valve control to be equipped with color coded permanently engraved identification nameplate to describe numerical sequence, location, type and size of outlet. All above specified pressure gauges to be analog style, liquid filled, vibration dampened, and capable of operations to -40 degrees F. The specified engine monitors, pump suction and discharge gauges, and individual gated

Page 30 of 55

Page 31:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

discharge pressure gauges shall be installed on the specified gauge panel. Pressure gauges to be piped to the individual discharge valves and pump suction and discharge volutes using high pressure clear nylon tubing with brass fittings.

WATER LEVEL INDICATOR - TANK VISION

One (1), FRC, "Tankvision" WLA200-A00 water tank level indicator to be furnished with: weatherproof encapsulated high intensity LED light indicator, tank level sending unit, and protected wiring loom. Water tank level indicator to be mounted on pump control panel. Tank level sensing unit to be located front of specified water tank to properly sense water capacity.

PUMP COMPARTMENT LIGHT

One (1), clear lens incandescent 6" round chrome plated surface mount 12-volt interior pump compartment light to be furnished, mounted beneath the ceiling of interior pump module. Light to be activated by light lens mounted push-button switch.

ALUMINUM BODY CONSTRUCTION

The apparatus body shall be fabricated from 1/8” 5052-H32, smooth aluminum sheet. The complete apparatus body shall be fabricated utilizing the break and bend techniques in order to form a strong, yet flexible, uni-body structure. The body shall be constructed with holding fixtures to ensure proper dimensioning. Each apparatus body shall is specific in design in order to meet the unique requirements of the purchasing fire department.

The side-facing rear wheel well areas {will/shall} be made of 1/8" aluminum Tread Brite material, which {will/shall} be fastened to the body and removable.

The main body compartments on each side, as well as the rear center compartment if applicable, shall contain a sweep out floor design. Each compartment shall be made to the most practical dimensions in order to provide maximum storage capacity for the fire department's equipment. The door opening threshold will be positioned lower than the compartment floor permitting easy cleaning of the compartments.

The flooring of all lower, main body compartmentation shall also have welded seams. All door jams, on both the top and the bottom, shall be welded as well.

The two (2) rear side compartments as well as the rear center compartment, if applicable, shall be welded to the rear deck support structure. This rear deck support structure is specially designed for the galvanized apparatus body substructure. A minimum of three (3) angles, which are 1/4” x 3”, shall run the entire width of the main rear deck from sweep-out to sweep-out. Each lower, rear compartment will be adequately stitch welded to the angles providing strength and durability to the entire apparatus body.

The body design shall include a “false wall” design in the lower portion of each lower, rear compartment. This is required in order to allow for easy accessibility to the rear electrical components found in the rear taillight cluster area.

The upper area of the apparatus body, directly above the side compartment door openings, a header is to be fabricated from smooth, aluminum sheet. This area shall be

Page 31 of 55

Page 32:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

free from any body seams and shall be painted the same color as the apparatus body. The height of the header may vary depending on the following factors: apparatus design, lettering requirements, scene lights and warning light requirements as well as various other options.

BODY SUB FRAME

To assure proper body alignment and clearance, the body sub frame shall be constructed in a positive holding fixture and fitted directly on the chassis.

The chassis frame rails shall be fitted with fiber reinforced rubber to isolate the body frame members from direct contact with chassis frame rails.

The main body sub frame shall be constructed from structural steel consisting of tubing, angles, channels, and flats. All structural steel shall be a minimum of 36,000 PSI Yield Strength. The sub frame shall run the full length of the body and shall be spaced the same width as the chassis frame rails. The main sub frame shall also be the integral support for the water tank. Vertical drop tubes shall be welded to the sub frame at the rear of the body.

A drop frame fabricated of steel tube and steel angles shall support the compartment area behind the rear axle. The rear drop frame shall be constructed using vertical drop tubes, welded to the main sub frame. All drop frame structures shall be welded directly to the body sub frame to allow the body to be a completely separate structure from the chassis.

After fabrication the sub frame shall be hot dip galvanized for maximum protection against corrosion.

BODY MOUNTING

The body sub frame shall be fastened to the chassis frame with spring loaded body mounts. Each mount shall be configured using a two-piece bracket. The brackets shall be fabricated of steel plates. The plates shall be painted to prevent any corrosion. Each mounting assembly shall utilizing two (2) plated bolts and two (2) heavy duty springs. The assembly design shall allow the body and sub frame to act as one (1) component, separate from the chassis. As the chassis frame twists under driving conditions, the spring mounting system shall limit any stress from being transferred into the body. The spring loaded body mounts shall also prevent frame side rail or body damage caused by unevenly distributed stress and strains due to load and chassis movement.

Body mountings that do not allow relief from chassis movement shall not be acceptable.

TANK MOUNTING

The water tank shall rest on the sub frame cross members which are spaced as required by the tank manufacturer.

The tank shall be isolated from the cross members through the use of hard rubber strips with a minimum Rockwell hardness of 60 durometer. Additionally, the tank shall be supported around the entire perimeter and captured both front and rear as well as side to side to prevent the tank from shifting during vehicle operations.

Page 32 of 55

Page 33:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

Although the tank shall be designed on a free floating suspension principle, it shall be required that the tank have adequate hold down restrains to minimize movement during vehicle operations.

The tank shall be completely removable without disturbing or dismantling the apparatus structure.

LEFT SIDE COMPARTMENTS

COMPARTMENT L1

There shall be a full height compartment located ahead of the rear wheel on the left side of the apparatus body. This compartment shall be designated as L1 within these specifications and any ensuing paperwork or drawings after contract execution. It shall be equipped with a roll-up door.

Door Opening - 37" Wide x 55" High

The compartment shall have a usable depth of 25-3/4" in the lower portion and 15-1/4" in the upper portion.

COMPARTMENT L2

A compartment shall be located above the rear wheel on the left side of the apparatus body. This compartment shall be designated as L2 within these specifications and any ensuing paperwork or drawings after contract execution. It shall be equipped with a roll-up door.

Door Opening - 61" Wide x 25-1/2" High

The compartment shall have a usable depth of 15-1/4".

COMPARTMENT L3

There shall be a full height compartment located behind the rear wheel on the left side of the apparatus body. This compartment shall be designated as L3 within these specifications and any ensuing paperwork or drawings after contract execution. It shall be equipped with a roll-up door.

Door Opening - 37" Wide x 55" High

The compartment shall be transverse in the lower portion and have a usable depth of 15-1/4" in the upper portion.

RIGHT SIDE COMPARTMENTS

COMPARTMENT R1

Page 33 of 55

Page 34:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

There shall be a full height compartment located ahead of the rear wheel on the right side of the apparatus body. This compartment shall be designated as R1 within these specifications and any ensuing paperwork or drawings after contract execution. It shall be equipped with a roll-up door.

Door Opening - 37" Wide x 55" High

The compartment shall have a usable depth of 25-3/4" in the lower portion and 15-1/4" in the upper portion.

COMPARTMENT R2

A compartment shall be located above the rear wheel on the right side of the apparatus body. This compartment shall be designated as R2 within these specifications and any ensuing paperwork or drawings after contract execution. It shall be equipped with a roll-up door.

Door Opening - 61" Wide x 25-1/2" High

The compartment shall have a usable depth of 15-1/4".

COMPARTMENT R3

There shall be a full height compartment located behind the rear wheel on the right side of the apparatus body. This compartment shall be designated as R3 within these specifications and any ensuing paperwork or drawings after contract execution. It shall be equipped with a roll-up door.

Door Opening - 37" Wide x 55" High

The compartment shall be transverse in the lower portion and have a usable depth of 15-1/4" in the upper portion.

REAR COMPARTMENT

COMPARTMENT T1

There shall be a single compartment located at the rear of the apparatus. This compartment shall be designated T1 within these specifications and any ensuing paperwork or drawings after contract execution. The compartment shall be equipped with a roll-up door.

Door Opening - 41" Wide x 41" High

The compartment shall have a usable depth of 28-1/2".

ROLL-UP DOORS ( SATIN FINISH )

Page 34 of 55

Page 35:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

Roll-up doors shall be ROM shutter type with 34 millimeter slats that roll onto a spool at the top of the compartment. Each slat shall be equipped with nylon end shoes to assure operation without the need of constant lubrication.

ROM ROLL UP DOOR HANDLES

The roll-up door shall be supplied with a full width handle for ease of opening with only one hand, allowing quick access to equipment and Nylon end shoes on every slat to assure operation without constant lubrication.

COMPARTMENT SCUFF PLATES

Anodized aluminum angle scuff plates shall be installed in the bottom sill area of all major equipment carrying compartments to reduce paint damage from equipment. The scuff plates shall be attached using a permanent bonding double sided tape.

STEPS

All steps shall have a surface area of at least 35 square inches and shall be able to withstand a load of at least 500 pounds. Steps shall be provided at any area that personnel may need to climb and shall be adequately lighted.

BOLT-ON STEPS

Three (3) Cast Product step(s) {will/shall} be installed on the left rear of the apparatus. These steps shall be used to gain access to the hose bed and hard hose storage. There shall be one (1) step on the right rear to gain access to the hard hose storage. The upper left step and right lower step {will/shall} be complete with integral lights.

COMPARTMENT VENTING

Each body compartment shall be properly vented in a manner that will reduce the amount of dirt and water that may enter the compartment. Venting shall be directly to the atmosphere rather than into another compartment which would only spread moisture throughout the body rather than dissipate it.

Additionally, each compartment shall be equipped with drain holes to allow standing water to exit the body without collecting.

HEAT DEFLECTOR SHIELD

Increased standards for emission have caused most exhaust temperatures to increase. To keep the exhaust heat from affecting anything stored in the body, a deflector shield shall be provided to aid in dissipating the heat.

REAR MODULAR GRIP STRUT REAR STEP

A grip strut running board shall be installed on the rear of the apparatus to form a full width step area. The ends of the running board shall be flush with the rub rail that is installed on the body to maintain a uniform appearance. The vertical outer-edge shall have an abraded finish.

Page 35 of 55

Page 36:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

All running boards shall be installed with sufficient support to form a sturdy, non-deflecting step area for personnel.

ULTRA STAINLESS™ MARUTEX® SCREWS

Stainless steel screws shall be provided throughout the body in locations such as: overlays, pump panels, and other numerous hardware mounting locations. In these locations the following screw specification shall apply.

The special ingredient in Ultra Stainless™ is Marutex®, which adds 2% molybdenum (moly) to 410 stainless. Moly is the significant component of 316 stainless that provides extra corrosion resistance. The moly is now added to 410 self drilling screws to produce Ultra Stainless™. This combination provides for unprecedented corrosion resistance combined with hardness for drilling.

Marutex® screws are tempered and quenched; regular T-140 self-drilling screws are case hardened. The additional carbon in Marutex® provides hardness for better drilling.

In certified testing the Marutex® screws have shown far superior corrosion resistance than that of 410 stainless, and 304 Bimetal screws. The screws were tested using two methods, the first was a 500 hour salt spray test, and the second was the European Air Pollution Test using the Kesterich method. In this test a combination of condensation water and atmosphere containing sulfur dioxide was sprayed on the screws. In both tests the Marutex® screws did not show any signs of rust, the 410 and 304 samples on the other hand did.

As part of quality control standards, samples from each batch of Ultra Stainless™ Marutex® screws shall be subject to a salt spray test for a minimum of 2500 hours. The test results shall be provided at any time upon request by the customer.

STEPPING, STANDING, WALKING SURFACES

All exterior surfaces designated by the manufacturer as stepping, standing, or walking areas shall be constructed of Grip Strut or Textured Treadbrite and shall provide a highly slip resistant surface, even when the surface is wet. All interior surfaces designated by the manufacturer as stepping, standing, or walking areas shall be slip resistant when the surface is dry.

The degree of slip resistance shall be in compliance with the intent of NFPA 1901 newest version.

TREADBRITE OVERLAYS

There shall be aluminum treadbrite overlays installed on the apparatus in those areas designated as walking areas. The treadbrite shall have .080" thickness

The top treadbrite overlay shall be mounted flush with the outer edges of the apparatus body.

A "J" channel shall be incorporated into the design in order to provide a rain gutter to further assist in preventing excessive moisture from getting into the compartments. The "J" channel shall be painted aluminum.

Page 36 of 55

Page 37:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

Overlays shall be totally insulated from the apparatus with nylon shoulder washers that extend into the hole that is drilled into the body. Stainless steel cap nuts shall be employed where bolts may damage equipment or cause injury. After painting and final construction overlays shall be additionally sealed at the edges with a caulking compound.

REAR WHEEL WELLS

The fenders shall be fitted with two (2) bolt-in shielding inner liner in the wheel well area for ease of cleaning and maintenance. There shall be sufficient clearance provided in the wheel wells to allow the use of tire chains when the apparatus fully loaded.

REAR ANODIZED ALUMINUM FENDERETTES

Two (2) anodized aluminum fenderettes shall be installed at the outboard edge of the rear wheel well area, one on each side. The fenderettes shall be fastened to tread plate wheel well.

REAR TOW EYE

One (1) rear tow eyes shall be installed directly below the rear of the chassis frame rails. The tow eye shall be capable of a 15,000 lb. straight pull rating.

HANDRAILS

Handrails shall be constructed of knurled aluminum of not less than 1-1/4" in diameter. All railing escutcheons and brackets shall be chrome plated, and shall be bolted to the body with stainless steel bolts. The lower bracket on all vertical handrails shall have a drain hole drilled in it at the lowest point. Handrails shall be provided in the following areas:

Horizontal rear handrail above the rear center compartment.

Left rear vertical hand rail from bottom of hose bed to just above the tail lights.

Right rear vertical hand rail from bottom of hose bed to just above the tail lights.

GROUND LADDERS

The ground ladders shall be stored beside the hose bed, to the right of the water tank. The ladders shall be stored vertically on their beam in an aluminum rack with poly scuff strips and extend into the pump house. The ladders shall be accessible through a hinged treadbrite door on the rear of the body.

ALUMINUM TUBES FOR PIKE POLE STORAGE

There {will/shall} be 2 aluminum tubes for storage of pike poles installed in the upper portion of the ladder storage compartment.

HOSE BED CAPACITY

HOSE BED

Page 37 of 55

Page 38:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

The hose bed shall be located above the water tank and shall have a capacity of 71 cubic feet. The inside of the hose bed shall be smooth aluminum and painted job color.

HOSE BED FLOORING

The floor of the hose bed compartment shall be constructed of Dura-Dek fiber reinforced plastic material. The flooring shall be fabricated of "T" beam pultrusions in parallel connected with cross slats that are first mechanically bonded and then epoxied, forming a large sheet.

The top portion of each "T" cross section shall measure 1-1/4" wide and 3/16" thick with beaded ends. The vertical portion shall be 3/8" thick, beading out at the bottom to a thickness of 1/2" and tall enough to result in an overall height of 1". The "T" sections shall be spaced 3/4" apart to allow for drainage and ventilation.

Each "T" beam shall be constructed utilizing a core of 250,000 continuous glass fiber strands that are high in resistance to tension, compression and bending. An outer sheath consisting of a continuous strand mat to prevent lineal splitting and shipping shall surround the core. The sheath shall also serve to draw the protective resin to the bar surface. Both reinforcements shall be pulled through an isophthalic polyester resin, treated with antimony trioxide for fire resistance, to form a solid length.

The flooring shall then be protected with a polyurethane coating to screen out ultraviolet rays. This bright white coating shall be baked on and shall provide a pleasing contrast when installed in the apparatus.

ALUMINUM HOSE BED PARTITION(S)

One (1) hose bed partition(s) shall be installed in the hose bed. The partition(s) shall be fabricated from ¼" smooth aluminum plate and an aluminum extrusion.

The partition(s) shall be mounted on hot-dipped galvanized slide rails at the front and rear of the hose bed.

The slide rails shall allow full movement of the partition along the width of the hose bed. Each hose bed partition shall have an oval shaped hand hold slot to assist in moving the partition. This shall provide the capability for variable hose load configurations and capacities.

ABRADED ADJUSTABLE HOSE BED DIVIDER

One (1) adjustable hose bed divider(s) shall have a maintenance free abraded finish.

VINYL HOSE BED COVER

There shall be a heavy duty 22 oz. Hypalon vinyl coated nylon hose bed cover installed on the apparatus. The front edge of the cover shall be retained in a "C" channel to prevent wind from lifting it, with Velcro on the sides. In addition the end flap shall be secured with a positive means to prevent unintentional deployment of the hose.

Page 38 of 55

Page 39:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

The cover shall be fastened at the sides with bungee and shall the rear flap shall be secured with quick release clips. The cover shall be black in color.

HARD SUCTION HOSE "V" TROUGH

There shall be one (1) hard suction hose "V" trough located above the left side high compartments with the capacity to storeone (1) 8' or one (1) 10' section of hard suction hose. The trough shall be fabricated of abraded aluminum plate. Velcro straps shall be supplied to hold the hard suction hose secure.

HARD SUCTION HOSE STORAGE

There shall be one (1) hard suction hose storage area located in the ladder compartment located at the rear of the apparatus. The storage area shall accommodate one (1) 10' or one (1) 12' section of hard suction hose.

CHARGE RECEPTACLE

A flush mount quick disconnect 12 volt DC charge receptacle shall be installed at the left side of the chassis cab by the driver's door.

AIR BRAKE REFILL INLET WITH CHECK VALVE

An air inlet shall be located near the driver's door. This fitting shall be connected to the air brake system "wet" tank to allow a remote air source to maintain a usable pressure in the chassis brakes. A check valve shall be provided as part of the system.

MANUAL EJECT

The Air Inlet shall be supplied with a manual eject.

WIRING HARNESSES

Wiring harnesses shall be the automotive type, engineered specifically for the builder's apparatus, and shall meet the following criteria. Under no circumstances shall diodes, resistors, or fusible links be located within the wiring harness. All such components shall be located in an easy to access wiring junction box or the main circuit breaker area. All wire shall meet white book, baseline advanced design transit coach specification and Society of Automotive Engineers recommended practices. It shall be stranded copper wire core with cross linked polyethylene insulation complying with SAE specification J1128. Each wire shall be hot stamp function coded every three inches starting one inch from the end and continuing throughout the entire harness. In addition to function coding, each wire shall be number, color, and gauge coded.

Wire harnesses shall be wrapped with a high abrasion and chemical resistant thermoplastic polyester elastomer coated polyester yarn for braiding constructions of electrical wiring systems. The braid yarn shall have a minimum tensile strength of 15 lbs before breaking and have a maximum of 20% elongation before breaking. Temperature properties for the yarn shall range from a minimum 280°F (138°C) service temperature to

Page 39 of 55

Page 40:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

a maximum -112°F (-80°C) brittleness temperature with a cold flex tolerance of at least -49°F (-45°C).

Harnesses shall be modular in design; a main harness system subdivided into several smaller sub-harnesses. The harness subsections shall be connected using Deutsch branded, heavy duty, environmentally sealed, connectors with silicone seals and a rear insertion/removal contact system. For isolation of electrical “zones” the harness subsections shall consist of a main harness, a pump harness with a separate pump gauge panel harness, a left body harness with a separate left compartment harness, a right body harness with a separate right compartment harness, and a rear body harness with two separate rear compartment harnesses.

The main harness and three body harnesses shall interconnect at a central, easy to reach location and their connectors shall not be obstructed by other harnesses or fuel/air lines. In addition, the main and body harness connectors shall be color coded for ease of identification with their respective colors noted on the accompanying electrical diagrams.

Where connectors are not provided by the electrical component manufacturer, all 12 volt lights and other electrical components (excluding rocker and toggle switches) shall connect to the harnesses using Deutsch brand connectors; butt connectors are considered unacceptable.

All Deutsch connectors shall meet the following criteria: All connectors shall have a minimum IP67 rating. Temperature range from -67°F (-55°C) to 257°F (125°C) continuous at

rated current. Only solid contacts will be used. Stamped and formed contacts are

unacceptable. All contacts shall be soldered unless a crimping tool or machine is used

that gives an even and precise pressure for the terminal being used. All contacts shall be pull-tested to insure their integrity.

V-MUX ELECTRICAL MANAGEMENT SYSTEM

The apparatus be equipped with a V-MUX Multiplex System, no substitutes accepted. The Manufacture of the Multiplex system shall provide at a minimum three cities of reference that have at least 10 trucks operational for over a one year period. The Multiplex system hardware that is being put into the apparatus of this bid shall be field proven for a minimum of two years. Any multiplex system that has less then 200 systems in vehicles with less then two years field time on the identical hardware that shall be put into the apparatus shall be excluded from this bid process. Any Multiplex system with a warranty higher then 1% over the past 2 years shall be excluded. There are several key benefits to multiplexing, one is to reduce the number of connections in a vehicles electrical system, because of this it is important to limit the amount of modules that control certain functions of the vehicle, therefore wherever it is stated that an “add-on” module will not be acceptable, there shall be No Exceptions.

Outputs:The outputs shall perform all the following items without added modules to perform any of the tasks.

Page 40 of 55

Page 41:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

1. Load Shedding: The System shall have the capability to Load Shed with 8 levels any output. This means you can specify which outputs (barring NFPA restrictions) you would like Load Shed. Level 1 12.9v, Level 2 12.5V, Level 3 - 12.1V, Level 4 - 11.7V, Level 5 11.3V, Level 6 10.9V, Level 7 10.5, Level 8 10.1. Unlike conventional load shedding devices you can assign a level to any or all outputs. No add-on modules shall be acceptable; the module with the outputs must perform this function. 2. Load Sequencing: The System shall be able to sequence from 0 8 levels any output. With 0 being no delay and 1 being a 1 second delay, 2 being a 2 second delay and so on. Sequencing reduces the amount of voltage spikes and drops on your vehicle, and can help limit damage to your charging system. No add-on modules shall be acceptable; the module with the outputs must perform this function.

3. Output Device: The System shall have solid-state output devices. Each solid-state output shall be a MOS-FET (Metal Oxide Semiconductor - Field Effect Transistors); MOS-FETs are solid-state devices with no moving parts to wear out. A typical relay when loaded to spec has a life of 100,000 cycles. The life of a FET is more than 100 times that of a relay. No add-on modules shall be acceptable; the module with the outputs must perform this function.

4. Flashing Outputs: The System shall be able to flash any output in either A or B phase, and logic is used to shut down needed outputs in park, or any one of several combined interlocks. The flash rate can be selected at either 80, or 160 FPM. This means any light can be specified with a multiplex truck with no need to add flashers. Flashing outputs can also be used to warn of problems or other unique idea you may come up with. No add-on modules shall be acceptable; the module with the outputs must perform this function. 5. PWM: The modules shall have the ability to PWM at some outputs so that a Headlight PWM module is not needed. No add-on modules shall be acceptable; the module with the outputs must perform this function.

6. Diagnostics: An output shall be able to detect either a short or open circuit.

Inputs:1. The inputs shall have the ability to switch by a ground or battery signal.

2. The inputs shall be filtered for noise suppression via hardware and software so that RF or dirty power will not trick an input into changing its status. System Network:

The Multiplex system contain a Peer-to-Peer network. A Master Slave Type network is not suitable for the Fire/Rescue industry. A Peer-to-Peer network means that all the modules are equal on the network; a Master is not needed to tell other nodes when to talk.

System Reliability:

Page 41 of 55

Page 42:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

The Multiplex system shall be able to perform in extreme temperature conditions, from -40° to +85° C (-40° to +185° F.) The system shall be sealed against the environment, moisture, humidity, salt or fluids such as diesel fuel, motor oil or brake fluid. The enclosures shall be rugged to withstand being mounted in various locations or compartments around the vehicle. The modules shall be protected from over voltage and reverse polarity.

12 VOLT SYSTEM SCHEMATIC

A complete electrical schematic for the apparatus shall be provided. This schematic shall be specifically prepared for this individual unit rather than a generic schematic designed to accommodate all apparatus.

12 VOLT SYSTEMS TEST

After completion of the unit, the 12 volt electrical system shall undergo a battery of tests as listed in the latest addition of NFPA Pamphlet 1901. These tests shall include, but not be limited to; a reserve capacity test, alternator performance test at idle, alternator performance test at full load, and a low voltage alarm test. Certification of the results shall be supplied with the apparatus at the time of delivery.

LED MIDSHIP TURN SIGNAL

There shall be one (1) Truck-Lite Model 21 LED midship auxiliary / turn signal lights, installed in the wheel well area, on each side of the body, for a total of two (2).

GROUND LIGHTING

Grote White LED lights shall be installed beneath the apparatus in areas where personnel may be expected to climb on and off of the apparatus. The lights shall illuminate the ground within 30" of the apparatus to provide visibility of any obstructions or hazards. These areas shall include, but not be limited to, side running boards and the rear step area.

GROTE LED HOSE BED LOADING LIGHTS

There shall be two (2) Grote LED lights installed in the top of the bulkhead at the front of the hose bed. This light shall provide illumination of the hose bed area. The lights shall be turned on with in conjunction with the park-brake being set.

BACK-UP ALARM

The backup alarm shall be an Ecco 510 Dba type. The sound level shall be 87 decibels.

HAZARD WARNING CIRCUIT

The open compartment door circuitry shall be tied into the open passenger door warning light circuitry of the chassis to warn the driver of an unsafe condition. Also connected to this circuit shall be any other compartment door, device or other item which may pose a hazard or cause damage should the apparatus be moved. The hazard warning circuit shall only become energize when the chassis parking brake is released.

Page 42 of 55

Page 43:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

A warning sign shall be placed near the warning light that reads "Do Not Move Apparatus When Light Is On."

ON-SCENE NIGHT STIK ACCESS LED COMPARTMENT LIGHTING

The side and rear compartments that are equipped with a roll-up style door shall be furnished with one (1) On-Scene Night Stik Access Super LED compartment light mounted on the front corner of the compartment.

The lights shall be rated 400 lumens per 18" light. The light shall be moisture and vibration resistant. The light shall be enclosed in tough 5/8" tube. Multi-clip attachment shall allows for installation into any roll up, or standard door configuration.

An automatic door switch shall activate the compartment lights.

LED CLEARANCE LIGHTS

Grote Model 65282 red LED clearance lights shall be installed on the rear of the body as necessary to be in full compliance with applicable ICC and DOT codes and regulations.

TAIL LIGHTS

There shall be a 4" Grote Supernova® LED tail light assembly installed on each side of the rear of the apparatus. Each assembly shall include one (1) red LED stop/tail light, one (1) amber LED turn light and one (1) clear LED backup light.

Each light shall be housed in a rubber grommet.

PROTECTIVE COVERS AND ENCLOUSRES FOR ELECTRICAL TERMINALS

All ungrounded electrical terminal shall have a protective cover or be in an enclosure.

UPPER ZONE A VISUAL WARNING

There shall be one (1) Whelen Engineering model JE2NFPA, 56" long light bar installed on the chassis cab roof. The lightbar shall be equipped with four (4) forward facing flashing Red LED's, two (2) forward facing flashing White LED's, Two (2) corner front facing Red LED's, and two (2) corner rear facing Red LED's.

The lightbar shall be equipped with clear lenses. All clear LED's in the lightbar shall be deactivated in the Blocking Right of Way mode.

UPPER ZONE C VISUAL WARNING

There shall be one (1) Whelen Engineering models RB6PRP/RB6PRP rotating beacon installed high at the rear of the apparatus. The rotators shall have red lenses.

LOWER ZONE VISUAL WARNING

There shall be Whelen LIN3 super LED lights installed in the lower warning zones.

Page 43 of 55

Page 44:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

The LIN3 is a sub-compact, full-featured LED light head with wide-angle light spread. The light head is designed for heavy duty vibration, moisture and corrosion resistance.

The LEDs have a five (5) year warranty.

LOWER ZONE A VISUAL WARNING

There shall be two (2) Whelen LIN LED lights installed on the front chassis grill of the apparatus. The lights shall have red lenses and chrome trim bezels.

LOWER ZONE B VISUAL WARNING

There shall be a three (3) Whelen LIN3 LED light installed on the right side of the body. The lights {will/shall} have red lenses. The one (1) light on the chassis shall have a chrome trim bezel and the two (2) lights on the body shall have black grommet mounts.

LOWER ZONE C VISUAL WARNING

There shall be a two (2) Whelen LIN3 LED light installed on the rear of the body. The lights {will/shall} have red lenses and shall have black grommet mounts.

LOWER ZONE D VISUAL WARNING

There be a three (3) Whelen LIN3 LED light installed on the left side of the body. The lights {will/shall} have red lenses. The one (1) light on the chassis shall have a chrome trim bezel and the two (2) lights on the body shall have black grommet mounts.

ELECTRONIC SIREN

There shall be one (1) Code 3 model 3930, 100 watt, Scorpion electronic siren installed in the cab. Full features of the siren shall include Wail, Yelp, hyperyelp, Air Horn, and PA system.

SIREN SPEAKER

There shall be one (1) Federal Dyna-Max aluminum 100 watt speaker(s) recessed in the front bumper. The model number MS100 speaker shall be mounted utilizing an MSFMT mounting bracket and hardware.

OEM PAINTED CHASSIS RIMS

The chassis rims shall be as painted from the chassis manufacturer.

CHEVRON REFLECTIVE STRIPING, RED/FLUORESCENT YELLOW

The chevron striping shall consist of 3M part numbers 1172 EC, red and 3983, fluorescent yellow-green.

Page 44 of 55

Page 45:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

PAINT COMPARTMENT INTERIORS

The interior of the body compartments be painted off white with Amerlock®/400, a self-priming epoxy.

Amerlock’s low solvent level meets VOC requirements, reduces the chances for film pin holing and solvent entrapment at the substrate-coating interface. The superior wetting action permits excellent adhesion, thoroughly soaking in and tightly bonding to the underlying metal.

Amerlock®/400 provides an excellent resistance to high humidity and moisture.

BODY PAINT PREPARATION

After the body and components have been fabricated and assembled they shall then be disassembled prior to painting so when the apparatus is completed there shall be finish paint beneath the removable components. The body shall be totally removed from the chassis during the painting process to insure the entire unit is covered. The apparatus body and components shall be metal finished as follows to provide a superior substrate for painting.

All aluminum sections of the body shall undergo a thorough cleaning process starting with a phosphoric acid solution to begin the etching process followed by a complete rinse. The next step shall consist of a chemical conversion coating applied to seal the metal substrate and become part of the aluminum surface for greater film adhesion.

After the cleaning process the body and it's components shall be primed with an High Solids primer and the seams shall be caulked.

All bright metal fittings, if unavailable in stainless steel or polished aluminum, shall be heavily chrome plated. Iron fittings shall be copper underplated prior to chrome plating.

PAINT PROCESS

The paint process shall follow the strict standards as set forth by PPG Fleet Finish Guidelines.

The body shall go through a two-stage paint process: Primer Coat and Base Coat (Color). In the first stage of the paint process the body shall be coated with PPG F3980 Low VOC / High Solids primer to achieve a total thickness of 2-4 mills. In the second stage of the paint process the body shall be painted with PPG Delfleet™ High Solids Polyurethane Base Coat. A minimum of two to three coats of paint shall be applied to achieve hiding.

As part of the curing process the painted body shall go through a Force Dry / Bake Cycle process. The painted components shall be baked at 185 degrees for 3 hours to achieve a complete coating cure on the finished product.

APPARATUS BODY COLOR

The apparatus shall be painted with PPG High Solids Polyurethane Base Coat.

Page 45 of 55

Page 46:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

The apparatus shall be painted ( RED ) PPG# FDG - 71096-ALT.

TOUCH UP PAINT

One (1) four ounce bottle of acrylic enamel touch-up paint shall be supplied.

CORROSION PREVENTION

One (1) 3.75 ounce shall be provided to use whenever additional items are mounted to the apparatus.

ECK protects aluminum and stainless steel against electrolytic reaction, isolates dissimilar metals and gives bedding protection for hardware and fasteners. ECK contains anti-seizing lubricant for threads. ECK is dielectric and perfect for use with electrical connectors.

NFPA COMPLIANT REFLECTIVE STRIPING

Reflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition. It shall consist of a straight, 4" wide stripe along thethe chassis beginning behind the front wheels and running along the sides, staying below the tops of the wheel well areas. The reflective striping shall be white in color.

CHEVRON REFLECTIVE STRIPING, REAR OF UNIT

In addition to the custom striping pattern supplied on the apparatus, there shall be additional reflective striping applied to the entire rear of the unit. The reflective striping shall cover at least 50% of the rear facing vertical surface, per NFPA 1901 newest edition.

The striping shall consist of alternating red and fluorescent yellow-green reflective stripes. Each stripe shall be a minimum of 6" in width and shall be applied to the apparatus at 45° angle.

The striping shall be on the painted aluminum surface of the rear, from the rear deck to the top of T1, on both sides of T1.

CAB DOOR REFLECTIVE STRIPING

A minimum of 96 sq. in. of reflective striping shall be applied to the interior of each cab door.

MUD FLAPS

Two (2) mud flaps shall be installed on the apparatus at the rear. The mud flaps shall be a minimum of 3/8" thick to prevent "sailing".

WHEEL CHOCKS, (1) PAIR, IN ANY COMPARTMENT

Page 46 of 55

Page 47:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

There shall be one (1) pair of Worden HRX model 211003 wheel chocks provided. The chocks shall be stored loose in a compartment for quick and easy access. The wheel chocks shall be constructed of heavy extruded rubber and shall be resistant to abrasive materials, heat, cold, oils, and fuels. The chocks shall meet DOT and NFPA 1901 standards with paired usage.

ADDITIONAL HARDWARE

There shall be one (1) bag(s) of stainless steel nuts, bolts, and washers supplied with the apparatus for mounting of equipment.

One (1) 10' folding attic ladder(s), Duo Safety 585AOne (1) 14' roof ladder(s), Duo Safety 775AOne (1) 24' Two section extension ladder(s), Duo Safety 900A

NFPA RECOMMENDED TOP SPEEDS

GVWR OVER 26,000 LBS. (11,800 KG): The maximum top speed shall not exceed either 68 MPH (105 km/hr) or the tire manufacturer's maximum fire service speed rating, whichever is lower.

GVWR OVER 50,000 LBS. (22,680 KG): The maximum top speed shall not exceed either 60 MPH (85 km/hr) or the tire manufacturer's maximum fire service speed rating, whichever is lower.

FOAM & WATER TANK CAPACITY EXCEEDS 1,250 GALLONS (4,732 L): The maximum top speed shall not exceed either 60 MPH (85 km/hr) or the tire manufacturer's maximum fire service speed rating, whichever is lower.

VISUAL TIRE PRESSURE INDICATOR

Each tire shall be equipped with a visual indicator to monitor tire pressure. The tire pressure indicator will display the following:

Green – tire is properly inflatedHalf green/half red – tire is approximately 10% under inflatedRed – tire is 20% or more under inflated

Each tire pressure indicator has a one (1) year warranty.

SWITCH PANEL

There shall be one (1) switch panel provided between the front bucket seats in the cab. The panel shall be large enough to accommodate twelve (12) separate switches.

FLOOR MOUNTED CONSOLE

There shall be a floor mounted console provided between the officer and drivers seats. The console shall be used for mounting of siren controls and department supplied radio equipment. The console shall be covered in black Line-X.

VEHICLE DATA RECORDER (VDR)

Page 47 of 55

Page 48:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

There shall be a Vehicle Data Recorder (VDR) installed in the chassis cab to collect essential information in order to assist in the training and safety efforts of the department. It shall be capable of recording 100 engine-hours worth of minute by minute information.

The VDR shall be password protected by the user in order to prevent data tampering by unapproved personnel. The collected data shall be easily extracted by a standard, mini USB cable. The data collected shall include the following:

Vehicle speed (mph)Acceleration (mph/sec)Deceleration (mph/sec)Engine speed (RPM)Engine throttle position (% of full throttle)Anti-lock braking system (on/off)Seat occupied status (Occupied: yes/no by position) Seat belt status (Buckled: yes/no by position)Master optical warning device switch (on/off)Time (24 hour clock)Date (year/month/day)

SEAT BELT INDICATOR

There shall be an indicator module located within view for the driver or officer to easily see which seats are occupied and to insure that seat belts are being utilized.

A green signal indicates the seat is occupied and the seat belt is properly fastened. A red signal indicates that the seat is occupied; however, the seat belt is not fastened. When the seat is vacant the signal will not be illuminated.

Heat Exchangers - Chassis Manufacturer Supplied

ENGINE COMPARTMENT WORK LIGHT

One (1) 12 volt work light shall be installed in the chassis engine compartment.

BATTERY JUMPER STUDS

There shall be a pair of battery jumper studs provided on the drivers side of the apparatus. The studs shall allow the vehicle to be jump started in an emergency due to battery failure.

GROUND LIGHTING -GROTE LED

There shall be two (2) Grote model 61E41-3 LED lights installed beneath the chassis in areas where personnel may be expected to climb on and off of the apparatus. The lights shall illuminate the ground within 30" of the apparatus to provide visibility of any obstructions or hazards.

FIRE EXTINGUISHER There shall be a 2.5 lb. BC DOT approved fire extinguisher shipped loose in the cab of the apparatus.

Page 48 of 55

Page 49:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

ROAD SAFETY KIT There shall be one (1) road safety kit provided with the apparatus. The kit shall consist of three (3) DOT approved reflective triangles.

MANUFACTURING LABELS

A permanent plate shall be mounted in the driver's compartment specifying the quantity and type of the following fluids that may be used in the apparatus for normal maintenance. Where a fluid is not applicable to the unit, the plate shall be marked N/A to inform the service technician who may not be familiar with the apparatus.

Engine oil Engine coolant Transmission fluid Pump transmission fluid Pump primer fluid Drive axle fluid Air conditioning refrigerant Power steering fluid Cab tilt mechanism fluid Transfer case fluid Equipment rack fluid Air compressor system lubricant Generator system lubricant Front tires air pressure Rear tires air pressure

A permanent plate shall be affixed in the driver's area that states the maximum number of personnel allowed to ride on the apparatus at any time.

A sign shall be affixed in the chassis cab, in plain sight of the driver that states the overall travel height, overall length, and gross GVWR of the apparatus.

On any gated inlet on the apparatus, a permanent label shall be provided that states:

"WARNING: Death or serious injury might occur if proper operating procedures are not followed. The pump operator as well as individuals connecting supply or discharges hoses to the apparatus must be familiar with water hydraulics hazards and component limitations."

All other appropriate labels to ensure safe operation of the apparatus shall be permanently affixed in conspicuous locations.

MODIFY CHASSIS WHEELBASE

The chassis wheelbase will be modified to conform to the engineered requirement for this apparatus.

Page 49 of 55

Page 50:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

Page 50 of 55

Page 51:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

Page 51 of 55

Page 52:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

Page 52 of 55

Page 53:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

Page 53 of 55

Page 54:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

Page 54 of 55

Page 55:  · Web viewReflective striping shall be applied to the exterior of the apparatus in a manner consistent with the National Fire Protection Association Pamphlet 1901, latest edition

Enclosed Top Mount #4083

Page 55 of 55