gGE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power
Transformers
Wave Cast Type
SCB Series of Cast Resin
Dry-Type Power Transformers
Technical Manual
Shanghai GE Guangdian CO., LTD
gGE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power
Transformers
Page 2 of 29
Table of Contents 1. Introduction of the Enterprise...................................................................3
2. Features of Products .................................................................................4
3. Core.............................................................................................................5
4. Windings.....................................................................................................6
5. Accessories................................................................................................8
6. On-load Tap Switch ...................................................................................9
7. Technical Specifications .........................................................................10
8. Tests .........................................................................................................12
9. Dry-Type transformer dimensions and terminal drawings...................12
10. Specifications and dimensions for SCB type 10kV three-phase cast resin dry-type distribution transformer with off-circuit tap changing.....13
11. SCZB9 type 10KV dry-type distribution transformer with on-load tap changing.......................................................................................................15
12. Specifications and dimensions for SCB9 type 1KV and lower three-phase cast resin dry-type isolation transformer.......................................17
13. Specifications for SCB9 type 10kV three-phase cast resin dry-type power transformer .......................................................................................18
14. Specifications for SCB9 type 20kV three-phase cast resin dry-type distribution transformer ..............................................................................18
15. Specifications and dimensions for SCB9 types 35kV three-phase cast resin dry-type distribution transformer .............................................19
16. Specifications for SCB9 type 35kV three-phase cast resin dry-type power transformer .......................................................................................20
gGE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power
Transformers
Page 3 of 29
17. Dry type transformer with protection enclosure .................................21
18. Inquiry, Order .........................................................................................27 1. Introduction of the Enterprise
Shanghai GE Guangdian Co., Ltd. has introduced advanced production technology, facilities and testing instruments in designing, manufacturing and selling three-phase cast resin dry-type transformers, which are also exported to the United States and all over the world.
Our products have passed all the quality tests carried out by the National Center of Quality Supervision and Inspection for Transformers, the short-circuit test for SCB type distribution transformers by KEMA lab, and the test of resistance to vibration for transformer with cubicle and connection busbar run by the Main National Lab for Civil Engineering Disaster Prevention of Tongji University.
Shanghai GE Guangdian Co., Ltd. Dry-type Transformer with Outdoors Enclosure IP23
gGE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power
Transformers
Page 4 of 29
Certificate of the ISO 9001 Quality System SCB9-10000/35/10.5 large-scale dry-type power transformer
2. Features of Products
• Safe, fire self-extinguishing, fireproof, low noise level, pollution-free; available at load center.
• Made up of all-copper foil, the H&L voltage windings have high short circuit withstand capabilities, high lightning impulse withstand capability and high reliability.
• The H&L voltage windings are molded with epoxy resin on high vacuum. The partial discharge is lower. Air channels can be installed. Humid-resistant and high heat dissipating ability. It is able to run normally under the relative humidity of 100%. Rated capacity can increase 40% as air-cooling.
• Convenient installation; easy maintenance; low losses and general operation cost.
• Temperature display and controlling system, which resists the interference from electric and magnetic field, is installed on windings to ensure safe operation of transformer. Computer interface can be fixed so that it can be controlled and monitored remotely.
• It can be equipped with protection enclosure and connection busar, which enables it to be used both indoors and outdoors. Indoor built-up structures may be immune to the limitation of the doorframes in the installation location. Connection busbar can be directly connected to the busbar of switchgear, which is really convenient.
gGE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power
Transformers
Page 5 of 29
Dry-type Distribution Transformer with SCB9-3150/10/0.4 Dry-type Protection Enclosure IP30 Distribution Transformer
ZSCB-1500/15.75/0.5 Dry-type field Transformer SCB9-10000/35/10.5 Dry-type Distribution Transformer
3. Core
• Made of high-quality cold-rolled grain-oriented steel sheets
gGE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power
Transformers
Page 6 of 29
• Mitred type adopts 45 degrees cuts; multistage step-by-step stacking• No punching holes on yokes; connecting plate structure • Coated with resin-emulsion paint. The surface of yokes locking
armature has been treated by electrostatic painting to protect them against humidity, rusts and salt fog.
• It has the advantages of lower no-load losses and current as well as lower noise.
Slitting line for silicon steel sheet Core with Non-stacking Top Yoke (Japanese plant)
Cut-to-length line for silicon steel sheet Mitred type core of the limbs and the yokes (Swiss plant)
4. Windings
• All the low and high voltage windings are made up of copper bands (foils). Voltage between layers is low, while layer capacity is great. Its
gGE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power
Transformers
Page 7 of 29
lighting impulse withstand capacity is high. The reactance of high and low voltage is the same. There’s no helical angle. For ampere turns of the high and low voltage windings are best leveled, the windings are capable of withstanding short circuit. Therefore, they have high operating reliability.
• Molded with epoxy resin at high vacuum, the high and low voltage windings have well electrical and mechanical performance. Partial discharge of them is less than 5pC.
• High and low voltage winding can be equipped with ventilating air passages according to requirements for heat dissipation. The isolating resin on the surface is 2.0~2.5mm thick in average, ensuring the temperature increase and strength of the windings and securing the 30-year service life.
• Because of the quartz powder on the epoxy resin and the glass-fiber net banded inside and outside the windings, they have high heat-dissipating ability, humidity-resistance and flame resistance. There is no need to worry about cracking. They can work normally under the humidity of 100%. Their flame-resistant performance accords with the Britain BS7806F2.
• The interior of the low and high voltage windings are credibly welded automatically and protectively by argon with low resistance.
• The imported equipment of high-precision and automation and high-quality imported isolating materials ensure the stable high quality and the safe operation of the windings.
• F and H stands for the two insulation levels. The temperature-rise limitation and voltage combination can be designed according to the customer’s specific requirements.
H&L voltage epoxy resin windings H.V windings casted with epoxy With heat-dissipating air passages resin for special purpose
gGE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power
Transformers
Page 8 of 29
Low voltage foil winding machine High voltage foil winding machine (Swiss plant) (Swiss plant)
Vacuum casting plant Large-scale 35KV winding casted with epoxy resin (Italian plant)
5. Accessories
Temperature Controller • A set of temperature controller can be set on the transformer to ensure
its normal services life through displaying and controlling the temperature of the transformer windings in work.
• The temperature measure sensors, Pt100 platinum resistant, are flushed into low voltage windings to get the temperature signals and circularly show the temperature of windings of each phase on the control panel after being treated by circuit. The temperature control system is capable of temperature setting, saving the highest temperature after power failure, fan picking-up and stopping automatically/manually, fault alarming, over temperature alarming with sound and light, over temperature tripping function besides the electromagnetic interference proof feature of national standard.
gGE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power
Transformers
Page 9 of 29
• Computer interface and software are available to carry out remote control.
Types and functions of temperature controllers of BWD-3K series Type Function
BWD-3K Regularly inspecting and displaying temperature, sensor fault alarming, and the fan is not controlled.
BWD-3K130 Regularly temperature displaying, over temperature alarming, over temperature trip, sensor fault alarming, picking-up and stopping the fan
BWD-3K130A
Same as those of BWD-3K130, added by the networking function with the aid of computer interface.
Fan • Low noise flow fan can reduce the winding temperature, improve its
ability of running under over-load, expand the service life of the transformer. In forced air-cooling mode, output will be increased by 40%.
• Features: low noise, low power and convenient installation The configuration of fan is shown below: Capacity of transformer (kVA) 160 ~
1000 160 ~1000
160 ~1000
≥6300
Account ×power of fan (W) 4×40 4×60 6×90 6 ×250
Temperature Controller Low sound flow fan
6. On-load Tap Switch
When the voltage of the electric net fluctuates, the transformer’s tapping can be changed over automatically or electrically in on-load operation to ensure that the user get the tap switches which employ the stable voltage.
gGE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power
Transformers
Page 10 of 29
MFK type complex on-load pneumatic tap switch As an uninflammable novel on-load tap switch using air as the isolating
and arc-extinguishing media, it is equipped with ZTK self-controller and may be connected to computer interface to carry out remote control. It is suitable for dry-type power transformers of 6~10kV, 3150kVA and lower.
Features: Reliable quality; convenient installation and maintenance; low priced; patented. KY and CVT series of vacuum on-load tap switches
As a transitional unit-resistance on-load tap switch employing air as the isolating media and using vacuum switch pipe in switching over, it is furnished with ZDT20 (40) or HMK-2Z types of automatic tap changing controller and may be linked to computer interface to carry out remote control. It is suitable for dry-type power transformers of 6~10kV, 2500kVA or lower.
Features: Reliable quality; convenient installation and maintenance; widely used. They are classified into two types: cylindric and cubicle type.
MFK type complex on-load Cubicle vacuum on-load tap Automatic tap changing controller pneumatic tap switch
7. Technical Specifications
• Standards: GB6450, 《Dry-type Power Transformer》 GB/T10228-1997 《 Technical Specification and requirements of Dry-type Power Transformer》
IEC726-82 《Dry-type Power Transformer》 IEEE Std C57.12.01-1998 《General Technical Conditions of Dry-type Distribution and Power Transformer》
• Capacity: 160~10000kVA • Voltage: 35kV and below
gGE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power
Transformers
Page 11 of 29
• Changing method: Off-circuit tap changing ±5% or ±2×2.5%, On-load tap changing ±4×2.5% or ±3×2.5%
• Phase: 3 phases • Frequency: 50Hz or 60Hz • Connection: Dyn11, Yyn0, Yd11, Ynd11 or others • Insulation Level: AC3 for 1kV Ll60AC25 for 6kV Ll75AC35 for 10kV Ll125AC50 for 20kV Ll170AC70 for 35kV
• Cooling: Natural cooling (AN) Natural (AN)/forced air (AF) or others
• Protection degree: IP00, IP20, IP30, IP23 or others • Service conditions: Altitude ≤1000m
Ambient temperature ≤40℃Min. temperature: ≥-5℃ for indoor use ≥-30℃ for outdoor use
• Special service: Special design and service are offered for customer with special applications and operation conditions.
Shockproof Test Report Short-circuit Test Certification provided by American KEMA Company for SCB-2500 type dry-type transformers
gGE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power
Transformers
Page 12 of 29
8. Tests
Routine tests: a. Measurement of winding resistance b. Calibration of voltage ratio and voltage vector relationship c. Measurement of insulation resistance d. Measurement of short circuit impedance and load losses e. Measurement of no-load losses and current f. Separate-source power-frequency voltage withstand test g. Induced over voltage withstand test h. Measurement of partial discharge
Type tests: a. Temperature rising test b. Lightning impulse withstand test
Special tests: a. Sound level test b. Short-circuit test Others: Other special tests could be carried out per requirements of the
customers
Partial Discharge Testing Instrument (Imported from Germany)
9. Dry-Type transformer dimensions and terminal drawings
gGE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power
Transformers
Page 13 of 29
10. Specifications and dimensions for SCB type 10kV three-phase cast resin dry-type distribution transformer with off-circuit tap changing
Type: SCB Connection symbol: Dyn11 or Yyn0 H.V: 10 (11、10.5、6.3、6.0) kV L.V: 0.4kV Tapping range of H.V: ±5% or ±2×2.5%Changing method: Off-circuit tap changing Insulation class: F or H
gGE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power
Transformers
Page 14 of 29
Load Losses (W)
Dimensions (mm) Model numberlevel
Rated Capacity (kVA)
No-load Losses(W)
75℃
120℃
No-load Current(%)
LoadImpedance 120℃(%)
Sound Level LPA(dB)
Weight (kg)
L B H W a b c e
TerminalsB×δ(mm)
160 580 1960
2240 1.1 4 48 980 1170
750 953 660 255 315 390 634 40×3
200 680 2320
2650 1.0 4 48 1110
1155
750 992 660 227 314 385 674 40×4
250 780 2540
2900 1.0 4 48 1300
1190
750 1034 660 232 321 400 704 40×4
315 980 3020
3460 1.0 4 48 1330
1230
750 1036 660 253 325 410 677 50×5
400 1080 3480
3980 1.0 4 48 1500
1260
750 1101 660 273 329 420 746 50×5
500 1300 4260
4870 1.0 4 50 1750
1310
750 1156 660 284 336 435 797 60×6
630 1480 5120
5870 1.0 4 50 2070
1410
750 1211 660 300 355 470 837 80×6
630 1400 5200
5950 1.0 4 50 2010
1460
750 1161 660 284 361 485 787 80×6
800 1620 6070
6950 0.8 6 52 2420
1500
920 1246 820 300 369 500 837 80×6
1000 1860 7090
8120 0.8 6 52 2750
1560
920 1296 820 316 381 520 877 100×6
1250 2100 8460
9690 0.6 6 52 3190
1580
920 1436 820 319 384 525 979 100×8
1600 2600 10700
12200 0.6 6 54 3970
1760
920 1511 820 355 415 585 1021
100×10
2000 3500 13100
15000 0.4 6 56 4870
1950
920 1562 820 368 445 650 1050
120×12
2500 4200 15900
18200 0.4 6 56 5860
2040
1170
1712 1070 392 460 680 1170
120×15
3150 4800 20000
23000 0.4 6 58 7000
2070
1170
1900 1070 412 479 715 1382
150×15
9
4000 5500 24000
27000 0.4 6 60 9110
2060
1310
2520 1070 402 469 690 1801
180×20
315 880 3020
3460 1.0 4 48 1330
1230
750 1036 660 253 325 410 677 50×5
400 970 3480
3980 1.0 4 48 1500
1260
750 1101 660 273 329 420 746 50×5
500 1160 4260
4870 1.0 4 50 1750
1310
750 1156 660 284 336 435 797 60×6
630 1340 5120
5870 1.0 4 50 2070
1410
750 1211 660 300 355 470 837 80×6
630 1300 5200
5950 1.0 6 50 2010
1460
750 1161 660 284 361 485 787 80×6
800 1520 6070
6950 0.8 6 52 2420
1500
920 1246 820 300 369 500 837 80×6
1000 1760 7090
8120 0.8 6 52 2750
1560
920 1296 820 316 381 520 877 100×6
1250 2000 8460
9690 0.6 6 52 3190
1580
920 1436 820 319 384 525 979 100×8
1600 2400 10240
11730 0.6 6 54 4060
1760
920 1511 820 355 415 585 1021
100×10
2000 3300 12600
14450 0.4 6 54 4870
1850
920 1668 820 356 425 615 1150
120×12
10
2500 3700 14670
16800 0.4 6 56 5720
1910
1170
1737 1070 385 436 635 1200
120×15
gGE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power
Transformers
Page 15 of 29
Note:1) The holes in the base plate are of 4×Φ22. To facilitate moving, 4 wheels of Φ150 are fixed on it, which result in an increase of approximately 130mm in height (H) and 40kg increase in weight.
2) According to request of users, the products of other different connections or other impedance voltage or other H.V. tapping range can be supplied.
11. SCZB9 type 10KV dry-type distribution transformer with on-load tap changing
● With big tap changing range, it is suitable when the voltage of electric net fluctuates dramatically.
● With automatic on-load tap changing, high-quality stable voltage can be gained.
● Equipped with automatic tap-changing controller, which bears the functions of automatic and electrical operation and remote control.
● Compact structure makes the maintenance easy. Reliable operation can be achieved.
● Tap switches fall into pneumatic and vacuum type, cubicle type and disc type, which makes it suitable for many occasions.
● Of series dry-type distribution transformer with on-load tap changing are the same with those of the series dry-type transformer with off-circuit tap changing, having the same capacity.
● The differences from the SCB series are listed below: 1) Tapping range: ±4x2.5%; 2) The differences in length, width and height are illustrated in the
figure below;3) The weight will increase by 180kg when the cylinder tap switches
are applied. The weight will increase by 460kg when the cubicle tap switches are applied.
● The normal positions, where tap switches are installed on the transformer body, are shown in the figure below. The tap switches and the transformer body are arranged centrosymmetrically.
● The outside dimensions of the enclosure of the dry type transformer with on-load tap changing are different from those of the enclosure of the off-circuit tap changing dry type transformers with the same capacity in terms of the following aspects: where tap switches are fixed on the side, the L increases by 620mm; the B increases by 750mm when cylinder tap switches are located in the front; the B increase by 640mm when cubicle tap switches are arranged in the front.
gGE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power
Transformers
Page 16 of 29
Cylindric On-load Switch on the Side Cubicle On-load Switch on Front Side
Cylindric On-load Switch on Front Side OSCZB9-2500/10 series of dry type self-coupling transformer with on-load tap changing
gGE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power
Transformers
Page 17 of 29
SCB9 type of transformer with SCB9 type of transformer with cylindriccylindric on-load switches on the side on-load switches on front side
12. Specifications and dimensions for SCB9 type 1KV and lower three-phase cast resin dry-type isolation transformer
Type: SCBG Connection symbol: Dyn、Yd、YNd、Yyn Primary voltage (V): 575、480、400、380 Secondary voltage (V): 400、220、210、208、120、100Tapping range: ±5%Insulation level: AC3/AC3 Insulation class: F or H
Dimensions (mm) Ratedcapacity(KVA)
No-load Losses (w)
Load losses 120(w)
No-load Current (%)
Short-circuit impedance (%)
Sound level
(dB)
Weight (kg)
L B H W
Remarks
160 650 2500 845 1080 916 200 750 2970
481140 1040 993
250 850 3240
1.4
1320 1230 1059
315 1000 3700
49
1405 1230 1119
400 1100 4200 1590 1230 1183
500 1300 5000
1.0
4
50
1750 1290
750
1220
660 Selected terminals shall be correspondent to rated current (see the figure below). If the external windings current is not more than 500A, bolt terminals can be adopted.
Note: Caster wheel and shielding as well as products of other voltage ratio or three-winding transformers are available on request.
HV Terminal LV Terminal
gGE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power
Transformers
Page 18 of 29
13. Specifications for SCB9 type 10kV three-phase cast resin dry-type power transformer
Combination of various rated voltages
Load Losses (W)
Rated capacity (kVA) H.V
(kV) H.Vtapping range
LV(kV)
Connection Symbol
No-load Losses (W)
75℃ 120℃ 145℃
No-loadcurrent
Short-circuit impedance(%)
SoundLevelLPA(dB)
630 1600 5850 6700 7170 0.9 56 800 1800 6810 7800 8350 0.9 561000 2200 8030 9200 9850 0.9 561250 2500 9600 11000 11770 0.8 561600 3000 11700 13400 14340 0.8 582000 4000 13970 16000 17100 0.7 582500 4800 16500 18900 20200 0.7
6
603150
6;6.3;6.6;10;10.5;11
5700 19200 22000 23500 0.6 624000 6800 23100 26500 28400 0.6 625000 8000 27400 31400 33600 0.5 626300
10;10.5;11
±5% ; ±2×2.5%
3;3.15;6;6.3
Yd11
9500 32400 37200 39800 0.5
7
62
14. Specifications for SCB9 type 20kV three-phase cast resin dry-type distribution transformer
Combination of various rated voltages
Load Losses (W)
Rated capacity (kVA)
H.V(kV)
H.Vtapping range
LV(kV)
Connection Symbol
No-loadLosses (W)
75℃ 120℃ 145℃
No-loadCurrent (%)
Short-circuit Impedance (%)
SoundLevel LPA(dB)
160 18; ±5% ; 0.4 Yyn0; 680 2180 2500 2670 1.4 6 50
gGE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power
Transformers
Page 19 of 29
200 780 2570 2950 3150 1.2 50 250 900 2820 3240 3470 1.2 50 315 1140 3490 4000 4280 1.0 50 400 1300 4270 4900 5240 1.0 52 500 1550 5230 6000 6420 1.0 52 630 1760 6200 7100 7600 0.7 52 800 2070 7330 8400 9000 0.7 54 1000 2340 8550 9800 10500 0.7 54 1250 2740 10300 11800 12600 0,6 54 1600 3170 12400 14300 15300 0.6 54 2000 3900 15000 17200 18400 0.5 56 2500
20;22
±2×2.5%
Dyn11
4700 17900 20500 22000 0.5 56
15. Specifications and dimensions for SCB9 types 35kV three-phase cast resin dry-type distribution transformer
Type: SCB9 Connection symbol: Dyn11 or Yyn0 H.V: 35 (38.5) kV L.V: 0.4kV Tapping range of H.V: ±5% or ±2×2.5%Changing method: Off-circuit tap changing Insulation class: F
Load Losses (W) Dimensions (mm) Rated Capacity(kVA)
No-loadLosses(W)
75℃ 120℃
No-loadcurrent(%)
Loadimpedance120℃(%)
Sound level LPA(dB)
Weight(kg)
L B H W a b c e
Busbar terminals B×δ(mm)
800 2430 8400 9630 0.9 58 3500
1880
920 1740
820
320 455
625
1070
80×60
1000 2700 9660 11070
0.9 58 4100
1940
920 1890
820
327 464
645
1210
100×6
1250 3150 11700 13400
0.8 60 4640
1970
920 1980
820
330 470
655
1290
100×8
1600 3600 14100 16200
0.8 60 4970
2030
1170 2140
1070
340 495
675
1482
100×10
2000 4230 16600 19100
0.7
6
62 5940
2120
1170 2280
1070
370 510
705
1532
120×12
gGE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power
Transformers
Page 20 of 29
2500 4950 20000 22900
0.7 62 7210
2240
1310 2240
1070
350 525
745
1452
120×15
3150 6200 22500 25800
0.6 64 8850
2310
1310 2412
1070
434 528
770
1602
150×15
16. Specifications for SCB9 type 35kV three-phase cast resin dry-type power transformer
Combination of various rated voltage
Load Losses (W)
Rated Capacity(kVA) H.V
(kV) H.V tappingrange
LV(kV)
Connectionsymbol
No-load Losses(W)
75℃ 120℃
145℃
No-load current(%)
Short-circuitimpedance(%)
Short levelLPA(dB)
800 2500 9640 9900 10600
0.9 58
1000 2970 10050
11520
12300
0.9 58
1250 3480 11700
13500
14500
0.8 60
1600 4100 14100
16200
17400
0.8
6
60
2000 4720 16600
19100
20500
0.7 61
2500 5400 20000
22900
24500
0.7
7
61
3150
35;38.5
±5%;±2×2.5%
3.15;6;6.3;10;10.5;11
Yyn0; Yd 11
6750 22500
25800
27600
0.6 8 62
gGE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power
Transformers
Page 21 of 29
4000 7830 27000
31000
33200
0.6 62
5000 9360 32000
36800
39400
0.5 63
6300 11000
37000
43000
46000
0.5 63
8000 12600
41000
47700
51000
0.5 65
10000
Yd11; Ynd11
14400
51000
58500
62600
0.5
9
65
17. Dry type transformer with protection enclosure
Products for domestic market: Enclosure protection level of the transformers targeted at the domestic market shall be of standard GB4208-93 (eqvIEC529: 1989), while that of the to-be-exported products shall be in accordance with the American standard NEMA.
Indoor-installed: IP20, which can prevent human body from approaching the enclosed dangerous components and provide protection against entrance of objects with diameter bigger than 12mm.
IP30, which cannot only prevent human body from approaching the enclosed dangerous components, but also provide protection against entrance of objects with diameter bigger than 2.5mm.
Outdoor-installed: IP23, which can not only provide functions as IP20, but also prevent entrance of water drops at a vertical angle of less than 60°.
Products to be exported: NEMA1 enclosure can prevent human body from approaching the enclosed dangerous component and provide protection against entrance of alien objects with diameter bigger than 12.7mm. NEMA3R (ventilation type) can not only provide functions as IP30, but also prevent entrance of water drops at a vertical angle of less than 75°.
The enclosures of above-mentioned types are all made out of sheet steel finished with resin static paint, which enables it to stand salt fog for 200 hours. They can also be made of stainless steel sheets or aluminum alloy sheet.
Structural features:
gGE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power
Transformers
Page 22 of 29
Enclosures for indoor-installed transformers are constructed with bolts and rivets, unlimited by the doorframes on the installation site. Transformers can be moved outside or inside from the front side in case of maintenance. They can be transported and erected in whole. Those for outdoor-installed transformers are constructed with bolts and rivets, or by welding. They provide protection against rain, snow, hail and ice formation. They can be transported and erected in whole.
Temperature controller and electrical control cabinet are installed in the door panel of the enclosure. There are lighting devices inside. Tap changing controller is fixed in the door panel of the enclosure for the transformer with on-load tap changing controller.
We provide enclosures of various protection classes and the corresponding tin-coated copper line banks of several wiring methods. They can stand the test of the ground acceleration ag: caused by earthquake, whose horizontal component is 0.6g and vertical component is 0.3g. The dimensions of some commonly used enclosures of dry-type distribution transformers and their forms of incoming and outgoing are listed below for reference.
1.Dimension drawing illustrating normal form of incoming and outgoing of high and low voltage for SCB9 type 10kV transformer
Dimensions (mm) Type Uk
L B H W a b c D e f g
Weight (kg)
Remarks
SCB9-160/10
255 315 390 1073 774 175 1310
SCB9-200/10
227 314 385 1112 814 160 1440
SCB9-250/10
1400
232 321 400 1154 844 180
100
1630
SCB9、10-315/10
253 325 410 1136 817 180 140 1690
SCB9、10-400/10
273 329 420 1201 886 185 1860
SCB9、10-500/10
1600
284 336 435 1266 937 190
130
2110
SCB9、10-630/10
4%
300 355 470 1311 977 195 2490
SCB9、10-630/10
6%
1800
1200 2200 660
284 361 485 1261 927 205
140
2430
H.V and LV outgoing terminals are the same with those of thetransformer
gGE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power
Transformers
Page 23 of 29
SCB9、10-800/10
300 369 500 1346 977 210 2520
SCB9、10-1000/10
316 381 520 4386 1017 210 3310
SCB9、10-1250/10
2000
319 384 525 1526 1119 215
160
3750
SCB9-1600/10
4590
SCB10-1600/10
355 415 585 1601 1161 245 170
4680
SCB9-2000/10
368 445 650 1642 1190 265 5490
SCB10-2000/10
2200
1400 820
356 425 615 1748 1150 250 5490
SCB9-2500/10
392 460 680 1792 1310 280 6660
SCB10-2500/10
2400 1600 1070
385 436 635 1817 1200 260
180
6520
2. Drawing of LV enclosed upper-outgoing busbar for SCB type 10kV transformer
Type Uk Dimensions (mm) Weight Busbar
gGE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power
Transformers
Page 24 of 29
L B H W a b c D e f g (kg) terminals N×B×δ
SCB9-160/10
315 390 774 1320 1×50×4
SCB9-200/10
314 385 814 1450 1×50×4
SCB9-250/10
1400
321 400 844 1640 1×50×4
SCB9、10-315/10
325 410 817 1700 1×50×6
SCB9、10-400/10
329 420 886
130
1870 1×50×6
SCB9、10-500/10
1600
336 435 937 2130 1×100×6
SCB9、10-630/10
4%
355 470 977 2510 1×100×6
SCB9、10-630/10
1200 660
361 485 927 2450 1×100×6
SCB9、10-800/10
1800
369 500 977 2550 1×100×6
SCB9、10-1000/10
400
381 520
120
1017
180
460
3340 1×100×8
SCB9、10-1250/10
2000
384 525 1119 3810 2×100×6
SCB9-1600/10
4650
SCB10-1600/10
415 585 1161
4750
2×100×8
SCB9-2000/10
445 650 1190 5570
SCB10-2000/10
2200
1400 820
425 615 1150 5570
SCB9-2500/10
460 680 1310 6740
SCB10-2500/10
6%
2400 1600
2200
1070
500
436 635
180
1200
200
660
6600
2×120×10
3. Drawing illustrating standard horizontal arrangement for SCB type 10kV transformer
gGE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power
Transformers
Page 25 of 29
Dimensions (mm) Type Uk
L B H W a B c d e f
Weight (kg)
Busbar terminals N×B×δ
SCB9-160/10
315 390 774 1320 1×50×4
SCB9-200/10
314 385 814 1450 1×50×4
SCB9-250/10
1800 100
321 400 844 1640 1×50×4
SCB9、10-315/10
325 410 817 1860 1×60×4
SCB9、10-400/10
4%
2000
1200 2200 660
140
329 420
100
886
2050
2030 1×60×6
gGE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power
Transformers
Page 26 of 29
SCB9、10-500/10
336 435 937 2280 1×60×6
SCB9、10-630/10
355 470 977 2730 1×80×6
SCB9、10-630/10
361 485 927 2670 1×80×6
SCB9、10-800/10
120
369 500 977 3080 1×100×8
SCB9、10-1000/10
381 520 1017
3430 1×100×10
SCB9、10-1250/10
2200
384 525 1119
3890 2×100×6
SCB9-1600/10
4730
SCB10-1600/10
2400
1400
415 585 1161
4820
2×100×8
SCB9-2000/10
1190
5870
SCB10-2000/10
820
445 650
1150
5870
2×100×10
SCB9-2500/10
1310
6860
SCB10-2500/10
6%
2600 1600
1070
100
460 680
150
1200
6720
3×100×8
4. Drawing illustrating standard vertical arrangement for SCB type 10kV transformer
Dimensions (mm) Type Uk
L B H W a B c d e f
Weight (kg)
Busbar terminals N×B×δ
SCB9-160/10
315
390
774 1440 1×50×4
SCB9-200/10
4%
1800
1200
2200
660 255
314
385
100
814
1512.5
1570 1×50×4
gGE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power
Transformers
Page 27 of 29
SCB9-250/10
321
400
844 1640 1×50×4
SCB9、10-315/10
325
410
817 1860 1×60×4
SCB9、10-400/10
329
420
886 2030 1×60×6
SCB9、10-500/10
2000
336
435
937 2280 1×60×6
SCB9、10-630/10
355
470
977 2730 1×80×6
SCB9、10-630/10
361
485
927 2670 1×80×6
SCB9、10-800/10
369
500
120
977 3080 1×100×8
SCB9、10-1000/10
381
520
1017
3430 1×100×10
SCB9、10-1250/10
2200
384
525
1119
3890 2×100×6
SCB9-1600/10
4730
SCB10-1600/10
2400
1400
415
585
1161
4820
2×100×8
SCB9-2000/10
1190
5870
SCB10-2000/10
820
445
650
1150
5870
2×100×10
SCB9-2500/10
1310
6860
SCB10-2500/10
6%
2600
1600
1070
460
680
140
1200
6720
3×100×8
18. Inquiry, Order
gGE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power
Transformers
Page 28 of 29
You are kindly requested to inform us of the following items for inquiries and orders:
Items Content Type Rated capacity Number of phases □single phase □three phase or Others Frequency □50 □60 or Others HV rated voltage □6□6.3 □6.6 □10 □10.5 □11 □35□38.5 or Others HV tapping range □±5□±2×2.5%□±3×2.5%□±4×2.5% or OthersLV rated voltage □0.4□0.69 □6.3 □10 □10.5 □11Changing method □with off-circuit tap changing □with on-load tap changing Connection symbol □Dyn11 □Yn0 □Y d11 □Ynd11 or Others Short-circuit impedance □4 □6 □8 or Others Insulation level □F □H or Others Cooling method □Air natural(AN) □(AN)/Air-forced(AF) or Others Protection degree □IP00 □IP20 □IP30 □IP23 or Others Enclosure material □Steel sheet(with static paint) □Al Alloy Sheet
□Stainless Steel Sheet or Others Temperature thermometer and temperature control box
□Temperature thermometer □Temperature controller □Temperature controller with computer interface □None
Fan □Yes □No
Forms of LV outgoing □Conventional □Enclosed busbar upper outgoing □Standard horizontally-lined busbar side outgoing □Standard vertically-lined busbar side outgoing or Others
Altitude □1000 and lower or OthersMax. temp. □40 or Others Min. temp. □-5(indoors) □-30(outdoors) or Others
Service Conditions
Indoor/outdoor □indoor □Outdoor or OthersPacking Quantities ordered (unit) Time of delivery Delivery taking
gGE Consumer & Industrial SCB Series of Cast Resin Dry-Type Power
Transformers
Page 29 of 29
Transportation Delivery point Miscellaneous
The transformers are numbering according to JB/T3837-1996 Numbering of Transformer Category. Dry-type transformer model number: SCB9-1000/10 H.V. voltage levels (kV) Rated capacity (kVA) Performance calss code name The winding is made of copper foil Moulded with epoxy resin
Three-phase
Notes: a. “Z” is prefixed to the model number of the transformer with
rectification. b. There is an “O” in front of the S in the model number of the self-
coupling transformer. c. There is an “S” behind to the S for three-phase transformers. d. There is a “Z” behind the C for transformers with on-load tap
changing. e. There is an “L” before the B for transformers with windings
made of copper foil. f. There is a “G” behind the B for isolated transformers. g. According to GB/T10288-1997, the performance class of Group Ⅰ is signified with “8”. Those whose no-load and load losses are 10% lower than the “8” type are signified with “9”. Those whose no-load losses are 20% lower than the “8”type while load losses 15% lower are signified with “10”.