Water Loss and Acoustic LeakTechnologies – Then and Now
Name: James FisherManager Non Revenue Water Services(770) [email protected]
2
Journals of the AWWA Conventions – Proceedings and Papers1887 to 1936 – Leakage – Then and Now
3
1887 1901
4
NEW YORK – 1900’s
FIRE HYDRANT FLOW TO KEEP COOL
5
CYPRUS WATER MAINS HAND LAYED WATER MAINS
6
NEW YORK - 1901
7
8
IN the 1900’s LEAKAGE IS LABELED “WASTE”
9
1907 – BURSTING WATER MAINS
10
Water Loss has Always and Always Will Be With Us
From the Journal of the AWWA – Vol. 24, No.11 November 1932
11
Leak Listening Methods
12
NITROUS OXIDE INJECTION – LEAK DETECTION
13
Geophones
14
Listening for Leak Sounds
15
Listening for Leak Sounds
16
Then and Now• Unamplified Listeners
▸ Have no batteries▸ Cheaper▸ Easier to Repair and Maintain
• Amplified Listeners▸ Can hear quieter leaks and
further away leaks▸ Can isolate external noise▸ Filters can remove unwanted
noise
17
Wavelength & Frequency
Short wavelength means lots of waves; high frequency, high sound
Long wavelength means fewer waves; low frequency, low sound
18
Typical Frequency Ranges
Human male voice
Human female voice
Music – middle C note
Music – middle A note
Typical 6” cast iron pipe
Typical ¾” copper pipe leak
Typical 6” PVC pipe
125 – 2000 Hz
250 – 5000 Hz
256 Hz
440 Hz
200 – 800 Hz
400 – 2000 Hz
5 – 30 Hz
19
How Far Can I HearGeneral Distance Sounds Travel for 2 GPM
Leak at 60 PSIPipe Size & Material Distance _• 6 inch Cast Iron Pipe - 600 to 1,000 feet• 12 inch Cast Iron Pipe - 400 to 800 feet• 24 inch Cast Iron Pipe - 200 to 400 feet• 6 inch AC Pipe - 400 to 800 feet• 12 inch AC Pipe - 300 to 500 feet• 24 inch AC Pipe - 100 to 300 feet• 6 inch PVC Pipe - 200 to 300 feet• 12 inch PVC Pipe - 100 to 200 feet• 24 inch PVC Pipe - 50 to 100 feet
20
Rate the Loudness
21
Ground Microphone Instruments
22
PITOMETER DISTRICTS
WASTE METER AREAS
DISTRICT METERED AREAS
SUB-DIVISION
STEP TESTING
23
PHOTO PITOMETER RECORDER
Measuring Water Flow to Identify WATER WASTE
1903
24
Pitometer District 1924 – District Metered Areas (DMA)
25
Pictured is a DMA from 1924
The theory and process has not changed, but the instrumentation to measure flow and pressure has advanced.
DMA’s Are Not New
26
Mobile WASTE METER – 1974 UK
27
Mobile WASTE METER Chart
28
DMA Development
District Metered Area (DMA) – 1990’sA DMA is just a smaller geographic area within the distribution system that can be temporarily isolated by closing valves.
An instrument capable of measuring flow into and out of the area is temporarily inserted into the main for 24-48 hours.
InsertionMeter
29
DMA/District Measurements are Indicators of Leakage Potential (Real Losses)
Lower night time flow rate is an indicator of minimal leakage
Unavoidable Leaks
Undiscovered Leaks
Meter Error
30
LEAK CORRELATORS
31
Correlators I Have Used
32
Leak Correlators – My First One
33
Correlation Theory• Leaks make noise• Time of flight technology• Correlation function:
▸ Leak bracketed with 2 Sensors▸ Leak noise takes longer to arrive at Sensor 1 than Sensor 2▸ Correlator measures time difference to identify exact leak location
34
Know Pipe Construction
• The use of non-metallic flexible pipe can lead to incorrect distance measurements that result in an incorrect location of a leak correlation
• A 22 degree bend in a pipe segment not shown on a map may cause incorrect length measurement
35
Frequencies – Pipe Material
36
Mixed Pipe Materials
37
Plastic Mains – PVC HDPE• Leak detection on plastic and large diameter mains does take longer to complete.
• Multiple leak shots normally have to be taken at different filter settings to dial in the best setting.
• Out of Bracket or In-bracket velocity calibrations have to be conducted to identify the correct velocity input
• The frequencies where leaks on plastic pipe and large diameter concrete pipes are identified are extremely low and in a narrow band.
• It takes time, much more time than leak detection on metallic mains, consequently the amount that can be completed in a day is much less and the cost is higher
38
Leak Noise LoggersThese Instruments Provide an Indication of leak noise and confidence• Provides for sounding investigations before leak correlation• Can be Permanently Installed or Moved around the system• Data interrogation can be accomplished with: Drive‐by Radio, SMS Text Message Communication or, Connected
to an AMR system
39
Network of interconnected nodes monitors a service area
Mi.Hubdata collector unit
System comprised of a series of nodes and radio infrastructure:
Mueller Data Center
Mi.Net RF
Mi.Host customer interface
Cellular Network
Fire Hydrants as Permanent Leak Detectors
40
Processor & Comm.
Hardware
Power Source
Hydrophone
Antenna
Node 1 Node 2 Node 3
MonitoredTransmission Main ½ mi. ½ mi.
Permanent Transmission Main Monitoring
41
Current AWWA M36 Manual Water Audits and Loss Control 4th Ed.
42
AWWA-IWA Water Balance
43
44
THREE TYPES of LEAKAGE
45
Previous Definition of Unavoidable Leakage
46
Unavoidable Leaks – Best Case - UARLInfrastructure Component Background
(Undetectable) LossesReported Breaks Unreported Breaks
Mains 8.5 gal/mi/hr. 0.20 breaks/mi/yr.@ 50 gpm for3 days duration
1 breaks/mi/yr@ 25 gpm for50 days duration
Service linesMain tap to curb stop(Company responsibility)
0.33 gal/service line/hr. 2.25/1,000 service lines/yr.@ 7 gpm for 8 days duration
0.75/1,000 service lines/yr.@ 7 gpm for 100 days duration
Service LinesCurb Stop to meter(For 50 ft. avg. length)
0.13 gal/service line/hr. 1.5/1,000 service lines/yr.@ 7 gpm for 9 days duration
0.50/1,000 service lines/yr.@ 7 gpm for 101 days duration
Infrastructure Component
Background (Undetectable) Losses
Reported Breaks
Unreported Breaks
UARL Total
Units
Mains 2.87 1.75 0.77 5.41 Gallons/mile of mains/day/psi of pressure
Service linesMain tap to curb stop(Company responsibility)
0.112 0.007 0.030 0.15 Gallons/mile of mains/day/psi of pressure
Service LinesCurb Stop to meter
4.78 0.57 2.12 7.5 Gallons/mile of mains/day/psi of pressure
47
Leak Run Times Not all leaks surface and many can run for many months or years before identification if an aggressive leak program is not active. For this reason we modified the run times to create several scenarios firstbeing that all leaks had ran for 30 days then all leaks ran for 60 days.
Water Loss Value.
� Current Estimated Run Time 105.780 MG $ 24,383� All at 30 Days 309.010 MG $ 71,230� All at 60 Days 618.019 MG $142,460
The current AWWA free software does not have cells that let you account for this but if these leaks are discovered during the audit period the volume and values should be taken into consideration in a water audit.
48
THANK YOU