Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

Embed Size (px)

Citation preview

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    1/35

    Estimate Area & Heat Recovery for Flue Gas Heat Recovery for MED BFW Preheat

    air Q=1.08CFM(dT) btuh 1 Estimate only based on simplistic HVAC Air Water-

    water Q=500gpm(dT) btuh 2 Detailed to used actual Cp & Den's

    Water lbs/hr=500gpm 3

    fuel Q=(dH)SCFH(eff) btuh 4

    flue gas (SCF /SCF )=(1+%XA/200)(15.8SG+1.8) FlueGz/ Fuel 5 Calc_F1

    any SCFH/60=SCFM 6

    Q=U(A)LMTD(F) BTUH 7

    Input

    Xair 10.0 % Excess Air from Furnace Design Sheet, Study to verify_basis: Furnace Design Sheet

    Fuel Qual FlueGz SCF/SCF Fuel MW/29 General Statement for Gas Specific Gravity

    0.73 14.0 Flue/Fuel Fuel SG amount of Flue Gas per Quantity of Fuel Used

    Fuel/Furn 3.5 mmscfd Fuel Flow to Furnace from PI 5 year Trend, Design to perform sensitivity analysis see Fuel Analysis sheet

    Fuel 1050.0 BTU/SCF Fuel Heat Content used in calculation to determine Fuel Gas Saving

    dT water 175 F Water Temperature Increase inside Waste Heat Recovery Section *

    H2O/Furn 70.0 gpm BFW Averaged Water Flow per Furnace-assume G80F10 servesG82 F7 & G80F11 serve G82F8_see G26E310A-C

    T FlueGas in 490 F Flue Gas Temperature Average from PI Data Chart see FlueGas T summry

    TH2O in 110 F Water Temperature from Boiler Feed Water prior to Heat Recovery

    Uo 25 BTUH/SF/F Overall Heat Transfer Factor, assume finned tubes

    OUTPUT Qwater=Qfluegas Calculation'

    Flue Gas 2,041,768.8 SCFH Amount of Flue Gas, based on Fuel Flow from PI Fuel Flow & XA% & FuelSG Correlation

    Fuel 145,833.3 scfh Convert PI Fuel Flow to SCFH from MMSCFD

    Q water 6,186,250.0 BTUH Calc Water Heat duty Required by Eq#2

    Flue Gas 34,029.5 SCFM Convert Flue Gas from SCFH to SCFM

    dT FlueGas 154.1 F Flue Gas dT by eqn 1 & Heat Duty of Eq2

    T FlueGas out 335.9 F Flue Gas T out by PI Flue Gas T & dT above

    TH2O out 285.0 F Water T out by Assumed Inlet Water T & dTwater

    LMTD 215.3 F LMTD by Text, (d1-d2)/ln(d1/d2)

    Ax 1,352.1 Feet squared Recovery Exchanger Area by Eq.7 at F=0.85

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    2/35

    Fuel Saved 7,364.6 SCFH

    Fuel Cost 3.5 $/mSCF Calc_F1

    Annual $ $206,208.3 $/year Fuel Saving in $/year

    NPV $ at 7 $1,443,458.33 $

    Pump HP 2.9 HP at 40 psi dP additional dP over what is used already

    Pump elect 18,407.8 KWHR/YR to feed boilers

    $/KWHR 0.035 e Cost unit

    $ elec/yr 644.3 $ electri/yr use BFW Pump to Feed Heat Recovery

    Job Scope

    Add WHR unit to Stack on both Furnace, G80F10&11

    Use Single 4" feed & Return Pipe, insulate Return to G82F10&11

    Add Control Valve at G82 BFW Pumps and BL Isolation Valves

    Relocate Stack TI to top of WHR HX

    Use FBE Pipe as inplant Runs since T does not exceed FBE Limits.

    Used Finned Tubes in Coiled Arrangement approx 32ft L x 5ftOD-400SF extended area

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    3/35

    Boiler feed water average 70 gpm/boiler G26E310A-C sheet Calc_F1

    Summary Apr.28/09 T, F, five yr look back Fuel gpm BFW pH gpm T, F

    MEAN Range L R Hi mmscfd water Steam Inlet W

    stack F1 G26AH 490 385 580 3.5 70 25 110

    stack F2G26AH 515 440 625 3.5 70 25 110

    stack F211G57AH 450 365 545 3.5 70 25 110

    stack F212AM 486 310 255 380

    oil F212 OinAM 48 195 155 235

    oil F212 OoutAM 265 255 380

    Based on Heat Recovered and Fuel Heat Value at 83% Boiler Effiency, study to confirm Boiler Effiency Orsat

    Fuel Ax The Fuel & Ax are input at each dT

    dT H2O m$/yr Ft2 dT H2O Fuel at 3yr CapX guess Fuel at 5yr

    75 88 403 75 265 177 88 442 177 265

    100 118 582 100 353 319 35 589 319 270

    125 147 792 125 442 522 -80 737 522 214

    150 177 1045 150 530 813 -282 884 813 71

    175 206 1352 175 619 1228 -609 1032 1228 -197

    dT H2O PV CRF=3 PV CRF=5

    75 88 265

    100 35 270

    125 -80 214

    150 -282 71

    175 -609 -197

    Calc_F1

    -700

    -600

    -500

    -400

    -300

    -200

    -100

    0100

    200

    300

    400

    50 75 100 125 150 175 200

    PV CRF=3

    PV CRF=5

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    4/35

    Estimate Area & Heat Recovery for Flue Gas Heat Recovery for MED BFW Preheat '- Detailed to used actual Cp & Den's

    air Q=1.08CFM(dT) btuh 1

    H2O Q=500gpm(dT) btuh 2

    H2O lbs/hr=500gpm 3

    fuel Q=(dH)SCFH(eff) btuh 4

    fluegas (SCF /SCF )=(1+%XA/2 Flue/ Fuel 5 '(SCF /SCF )=(1+%XA/200)(15.8SG+1.8)any SCFH/60=SCFM 6

    Q=U(A)LMTD(F) BTUH 7

    Input

    Xair 10.0 % Excess Air from Furnace Design Sheet, Study to verify

    Fuel Qual FlueGz SCF/SCFFuel MW/29 General Statement for Gas Specific Gravity

    0.73 14.0 Flue/Fuel Fuel SG amount of Flue Gas per Quantity of Fuel Used

    Fuel/Furn 3.5 mmscfd Fuel Flow to Furnace from PI 5 year Trend, Design to perform sensitivity analysis

    Fuel 1050.0 BTU/SCF Fuel Heat Content used in calculation to determine Fuel Gas Saving

    dTH2O 254 F Water Temperature Increase inside Waste Heat Recovery Section *

    H2O/Furn 11.0 gpm BFW Averaged Water Flow per Furnace-assume G80F10 servesG82 F7 & G80F11 serve G82F8T Flue in 490 F Flue Gas Temperature Average from PI Data Chart

    TH2O in 110 F Water Temperature from Boiler Feed Water prior to Heat Recovery

    Uo 25 BTUH/SF/F Overall Heat Transfer Factor, assume finned tubes

    OUTPUT Qwater=Qfluegas Calc.' Amount of Flue Gas, based on Fuel Flow from PI Fuel Flow & XA% & FuelSG Correlation

    Flue Gas 2,041,768.8 SCFH

    Fuel 145,833.3 scfh Convert PI Fuel Flow to SCFH from MMSCFD

    Q water 1,410,970.0 BTUH Calc Water Heat duty Required by Eq#2

    Flue Gas 34,029.5 SCFM Convert Flue Gas from SCFH to SCFM

    dT.FlueGz 35.1 F Flue Gas dT by eqn 1 & Heat Duty of Eq2

    T Flue out 336.1 F Flue Gas T out by PI Flue Gas T & dT aboveTH2O out 364.0 F Water T out by Assumed Inlet Water T & dTwater

    LMTD 63.6 F LMTD by Text, (d1-d2)/ln(d1/d2)

    Ax 1,043.8 Feet2

    Recovery Exchanger Area by Eq.7 at F=0.85

    Fuel Saved 7,356.5 SCFH

    Fuel Cost 3.5 $/mSCF

    Annual $ $205,982.3 $/year Fuel Saving in $/year

    NPV $ at $1,441,876.33 $

    Pump HP 0.5 HP at 40 psi dP additional dP over what is used already

    Pump ele2,892.7 KWHR/YR to feed boilers

    $/KWHR 0.035 e Cost unit

    $ elec/yr 101.2 $ electri/yr use BFW Pump to Feed Heat Recovery

    Calc_F1-BOIL

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    5/35

    If steam is produced use above to calc Sensible Heat Calc_F1-BOIL

    Then Carry the value to cal. Latent Heat Requirements

    H liq at T 337 Btu/# Tsat= 364 F use stm table for H

    H vap at T 1204 Btu/# Psat= 160 psia use stm table for H

    dH stm at T 867 Btu/# net Latent Heat Required

    flow H2O 5500 #/hr frm B16 Convert gpm500=#/hrLatent Q 4768500 BTUH (BTU/#)(#/HR)

    dT flue gas 119 F by ratio of above 224

    T flue out 371 F 254

    LMTD 67 F 84

    Ax 3.9 SQ Ft.

    Job Scope

    Add WHR unit to Stack on both Furnace, G80F10&11

    Use Single 4" feed & Return Pipe, insulate Return to G82F10&11

    Add Control Valve at G82 BFW Pumps and BL Isolation Valves

    Relocate Stack TI to top of WHR HX

    Use FBE Pipe as inplant Runs since T does not exceed FBE Limits.

    Used Finned Tubes in Coiled Arrangement approx 32ft L x 5ftOD-400SF extended area

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    6/35

    basis: Vendor Proposal Summary Apr.28/09 mmscfd gpm

    Recv./furn 4.2 MW/Furnace T, F, five yr look back Fuel gpm BFW pH T, F

    Recv in BTUH 14.3 mmbtuh/fur MEAN Range L R Hi water Steam Inlet W

    net dHs 1116 btu/# Stm F1 G26AH 490 385 580 3.5 70 25 110

    H2O mass 12833 #S/hr/furn F2G26AH 515 440 625 3.5 70 25 110

    H2O volume 25.7 gpm/furn F211G57AH 450 365 545 3.5 70 25 110numb Furn 4.0 number F212AM 486 310 255 380

    max H2O 102.7 gpm avail 4.2MW/Furnace F212 OinAM 486 195 155 235

    required H2O 210.0 gpm req'd 70*3boilers F212 OoutAM 486 265 255 380

    Boiler feed water average 70 gpm/boiler G26E310A-C sheet

    Based on Heat Recovered and Fuel Heat Value at 83% Boiler Effiency, study to confirm Boiler Effiency Orsat

    Fuel Ax

    gpm H2O m$/yr Ft2 gpm H2O Fuel at 3yrPOT CapX guess Fuel at 5yr

    4 75 138 4 225 32 193 375 32 343

    6 112 245 6 337 80 257 562 80 4828 150 406 8 449 179 269 748 179 568

    10 187 707 10 562 435 127 937 435 501

    11 206 1048 11 618 817 -199 1030 817 213

    1,048 gpm H2OPV CRF=3 PC CRF=5

    4 193 343

    6 257 482

    Calc_F1-BOIL 8 269 568

    10 127 501

    11 -199 213

    Calc_F1-BOIL

    -300

    -200

    -100

    0

    100

    200

    300

    400

    500

    600

    700

    0 2 4 6 8 10 12

    PV CRF=3

    PC CRF=5

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    7/35

    Estimate Area & Heat Recovery for Flue Gas Heat Recovery for MED BFW Preheat

    Estimate only based on simplistic HVAC Air Water- Detailed to used actual Cp & Den's

    air Q=1.08CFM(dT) btuh 1

    water Q=500gpm(dT) btuh 2 Calc_F2

    Water lbs/hr=500gpm 3

    fuel Q=(dH)SCFH(eff) btuh 4

    flue gas (SCF /SCF )=(1+%XA/200)(15FlueGz/NG 5 '(SCF /SCF )=(1+%XA/200)(15.8SG+1.8)any SCFH/60=SCFM 6

    Q=U(A)LMTD(F) BTUH 7

    Input

    Xair 10.0 % Excess Air from Furnace Design Sheet, Study to verify

    Fuel Qual FlueGz SCF/SCF Fuel MW/29 General Statement for Gas Specific Gravity

    0.73 14.0 Flue/Fuel Fuel SG amount of Flue Gas per Quantity of Fuel Used

    Fuel/Furn 3.5 mmscfd Fuel Flow to Furnace from PI 5 year Trend, Design to perform sensitivity analysis

    Fuel 1050.0 BTU/SCF Fuel Heat Content used in calculation to determine Fuel Gas Saving

    dT water 250 F Water Temperature Increase inside Waste Heat Recovery Section *

    H2O/Furn 70.0 gpm BFW Avg H2O Flow per Furnace-assume G80F10 servesG82 F7 & G80F11 serve G82F8

    Flue in T 515 F Flue Gas Temperature Average from PI Data Chart

    T H2O in 110 F Water Temperature from Boiler Feed Water prior to Heat Recovery

    Uo 25 BTUH/SF/F Overall Heat Transfer Factor, assume finned tubes

    OUTPUT Qwater=Qfluegas Calc.'

    Flue Gas 2,041,768.8 SCFH Flue Gas, basis: Fuel Flow from PI Fuel Flow & XA% & FuelSG Correlation

    Fuel 145,833.3 scfh Convert PI Fuel Flow to SCFH from MMSCFD

    Q water 8,837,500.0 BTUH Calc Water Heat duty Required by Eq#2

    Flue Gas 34,029.5 SCFM Convert Flue Gas from SCFH to SCFM

    dT FlueGas 220.1 F Flue Gas dT by eqn 1 & Heat Duty of Eq2

    Flue out T 294.9 F Flue Gas T out by PI Flue Gas T & dT above

    TH2O out 360.0 F Water T out by Assumed Inlet Water T & dTwater

    LMTD 169.5 F LMTD by Text, (d1-d2)/ln(d1/d2)

    Ax 2,453.3 Feet2

    Recovery Exchanger Area by Eq.7 at F=0.85

    Fuel Saved 10,520.8 SCFH Calc_F2

    Fuel Cost 3.5 $/mSCF

    Annual $ $294,583 $/year Fuel Saving in $/year

    NPV $ at 7 $2,062,083 $

    Pump HP 2.9 HP at 40 psi dP additional dP over what is used already

    Pump elect 18,407.8 KWHR/YR to feed boilers

    $/KWHR 0.035 e Cost unit

    $ elec/yr 644.3 $ electri/yr use BFW Pump to Feed Heat RecoveryJob Scope

    Add WHR unit to Stack on both Furnace, G80F10&11

    Use Single 4" feed & Return Pipe, insulate Return to G82F10&11

    Add Control Valve at G82 BFW Pumps and BL Isolation Valves

    Relocate Stack TI to top of WHR HX

    Use FBE Pipe as inplant Runs since T does not exceed FBE Limits.

    Used Finned Tubes in Coiled Arrangement approx 32ft L x 5ftOD-400SF extended area

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    8/35

    Boiler feed water average 70 gpm/boiler G26E310A-C sheet Calc_F2

    Summary Apr.28/09 T, F, five yr look back Fuel gpm BFW pH gpm T, F

    MEAN Range L R Hi mmscfd water Steam Inlet W

    F1 G26AH 490 385 580 3.5 70 25 110

    F2G26AH 515 440 625 3.5 70 25 110

    F211G57AH 450 365 545 3.5 70 25 110

    F212AM 486 310 255 380F212 OinAM 486 195 155 235

    F212 OoutAM 486 265 255 380

    Based on Heat Recovered and Fuel Heat Value at 83% Boiler Effiency, study to confirm Boiler Effiency Orsat

    Fuel Ax

    dT H2O m$/yr Ft2 dT H2O Fuel at 3y CapX guess Fuel at 5yr

    75 88 373 75 265 156 109 442 156 285.6

    100 118 535 100 353 279 75 589 279 310.4

    125 147 724 125 442 452 -10 737 452 285.0

    150 177 946 150 530 693 -163 884 693 191.0

    175 206 1211 175 619 1030 -411 1031 1030 1.0

    dT1 dT2 dT H2O PV CRF=3 PV CRF=5

    185 155 75 108.8 285.6

    170 100 74.8 310.4

    125 -9.6 285.0

    150 -162.6 191.0

    175 -411.4 1.0

    Calc_F2

    -500.0

    -400.0

    -300.0

    -200.0

    -100.0

    0.0

    100.0

    200.0

    300.0

    400.0

    50 75 100 125 150 175 200

    PV

    CRF=3

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    9/35

    Estimate Area & Heat Recovery for Flue Gas Heat Recovery for MED BFW PreheatCalc_F2-BOIL

    air Q=1.08CFM(dT) btuh 1 'Estimate only based on simplistic HVAC Air Water- Detailed to used actual Cp & Den's

    water Q=500gpm(dT) btuh 2

    Water lbs/hr=500gpm 3

    fuel Q=(dH)SCFH(eff) btuh 4

    flue gas (SCF /SCF )=(1+%XA/200)(15.8FlueGz/ Fuel 5 (SCF /SCF )=(1+%XA/200)(15.8SG+1.8) Calc_F2-BOIL

    any SCFH/60=SCFM 6

    Q=U(A)LMTD(F) BTUH 7

    Input THIS SHEET BASIS IS STEAM GENERATION BY COUNTERCURRENT FLOW

    Xair 10.0 % Excess Air from Furnace Design Sheet, Study to verify

    Fuel Qual FlueGz SCF/SCF Fuel MW/29 General Statement for Gas Specific Gravity

    0.73 14.0 Flue/Fuel Fuel SG amount of Flue Gas per Quantity of Fuel Used

    Fuel/Furn 3.5 mmscfd Fuel Flow to Furnace from PI 5 year Trend, Design to perform sensitivity analysis

    Fuel 1050.0 BTU/SCF Fuel Heat Content used in calculation to determine Fuel Gas Saving

    dT water 254 F Water Temperature Increase inside Waste Heat Recovery Section *

    H2O/Furn 12.0 gpm BFW Averaged Water Flow per Furnace-assume G80F10 servesG82 F7 & G80F11 serve G82F8

    T FlueGas in 515 F Flue Gas Temperature Average from PI Data Chart

    TH2O in 110 F Water Temperature from Boiler Feed Water prior to Heat Recovery

    Uo 25 BTUH/SF/F Overall Heat Transfer Factor, assume finned tubes

    OUTPUT Qwater=Qfluegas Calculation'

    Flue Gas 2,041,768.8 SCFH Amount of Flue Gas, based on Fuel Flow from PI Fuel Flow & XA% & FuelSG Correlation

    Fuel 145,833.3 scfh Convert PI Fuel Flow to SCFH from MMSCFD

    Q water 1,539,240.0 BTUH Calc Water Heat duty Required by Eq#2

    Flue Gas 34,029.5 SCFM Convert Flue Gas from SCFH to SCFM

    dT FlueGas 38.3 F Flue Gas dT by eqn 1 & Heat Duty of Eq2

    T FlueGas out 347.1 F Flue Gas T out by PI Flue Gas T & dT above

    TH2O out 364.0 F Water T out by Assumed Inlet Water T & dTwater

    LMTD 89.8 F LMTD by Text, (d1-d2)/ln(d1/d2)

    Ax 807.0 Feet squared Recovery Exchanger Area by Eq.7 at F=0.85

    Fuel Saved 8,025.3 SCFH Based on Heat Recovered and Fuel Heat Value at 83% Boiler Effiency,

    Fuel Cost 3.5 $/mSCF study to confirm Boiler Effiency Orsat

    Annual $ $224,708.0 $/year Fuel Saving in $/year

    NPV $ at 7 $1,572,956.00 $

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    10/35

    Pump HP 0.5 HP at 40 psi dP additional dP over what is used already Calc_F2-BOIL

    Pump elect 3,155.6 KWHR/YR to feed boilers

    $/KWHR 0.035 e Cost unit

    $ elec/yr 110.4 $ electri/yr use BFW Pump to Feed Heat Recovery

    If steam is produced use above to calc Sensible Heat dT1 dT2 At

    Then Carry the value to cal. Latent Heat Requirements 237.1 21.5 810.3

    H.liq @T 337.0 Btu/# Tsat= 364 F use stm table for HH.vap @T 1204.0 Btu/# Psat= 160 psia use stm table for H

    dH stm @T 867.0 Btu/# net Latent Heat Required

    flow H2O 6000.0 #/hr frm B16 Convert gpm500=#/hr

    Latent Q 5202000.0 BTUH (BTU/#)(#/HR)

    dT flue gas 129.5 F by ratio of above 224

    T flue out 385.5 F

    LMTD 86.2 F

    Ax 3.3 SQ Ft.

    91.2

    Recv./furn 4.2 MW/Furnace Job Scope

    Recv in BTUH 14.3 mmbtuh/fur Add WHR unit to Stack on both Furnace, G80F10&11

    net dHs 1116.0 btu/# Stm Use Single 4" feed & Return Pipe, insulate Return to G82F10&11

    H2O mass 12833.3 #S/hr/furn Add Control Valve at G82 BFW Pumps and BL Isolation ValvesH2O volume 25.7 gpm/furn Relocate Stack TI to top of WHR HX

    numb Furn 4.0 number Use FBE Pipe as inplant Runs since T does not exceed FBE Limits.

    max H2O 102.7 gpm avail 4.2MW/Furnace Used Finned Tubes in Coiled Arrangement

    required H2O 210.0 gpm req'd 70*3boilers approx 32ft L x 5ftOD-400SF extended area

    clc rec 6.74 mm btuh

    clc rec 1.98 MW/Furn

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    11/35

    Calc_F2-BOIL Boiler feed water average 70 gpm/boiler G26E310A-C sheet

    Summary Apr.28/09 T, F, five yr look back Fuel gpm BFW pH gpm T, F gpm H2O PV CRF=3 PC CRF=5

    MEAN Range L R Hi mmscfd water Steam Inlet W 4 200 350

    stack F1 G26AH 490 385 580 3.5 70 25 110 6 278 502

    stack F2G26AH 515 440 625 3.5 70 25 110 8 326 626

    stack F211G57AH 450 365 545 3.5 70 25 110 10 314 689

    stack F212AM 48 310 255 380 12 133 583

    oil F212 OinAM195 155 235

    oil F212 OoutA 265 255 380

    Calc_F2-BOIL

    Fuel Ax

    gpm H2O m$/yr Ft2 gpm H2O Fuel at 3yr CapX guess Fuel at 5yr

    4 75 118 4 225 25 200 375 25 350

    6 112 204 6 337 60 278 562 60 502

    8 150 321 8 449 123 326 749 123 626

    10 187 497 10 562 248 314 937 248 689

    12 225 810 12 674 541 133 1124 541 583

    0

    100

    200

    300

    400

    500

    600

    700

    800

    0 2 4 6 8 10 12 14

    PV CRF=3

    PC CRF=5

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    12/35

    Estimate Area & Heat Recovery for Flue Gas Heat Recovery for MED BFW Preheat

    air Q=1.08CFM(dT) btuh 1 'Estimate only based on simplistic HVAC Air Water-

    water Q=500gpm(dT) btuh 2 Detailed to used actual Cp & Den's

    Water lbs/hr=500gpm 3 'Boiler feed water average 70 gpm/boiler G26E310A-C sheet

    fuel Q=(dH)SCFH(eff) btuh 4

    flue gas (SCF /SCF )=(1+%XA/200)(1 FlueGz/ Fuel 5 '(SCF /SCF )=(1+%XA/200)(15.8SG+1.8)

    any SCFH/60=SCFM 6Q=U(A)LMTD(F) BTUH 7 Calc_F2-BOIL50#

    Input THIS SHEET BASIS IS STEAM GENERATION BY COUNTERCURRENT FLOW

    Xair 10.0 % Excess Air from Furnace Design Sheet, Study to verify

    Fuel Qual FlueGz SCF/SCF Fuel MW/29 General Statement for Gas Specific Gravity

    0.73 14.0 Flue/Fuel Fuel SG amount of F lue Gas per Quantity of Fuel Used

    Fuel/Furn 3.5 mmscfd Fuel Flow to Furnace: PI 5 year Trend, Design to make sensitivity analysis

    Fuel 1050.0 BTU/SCF Fuel Heat Content used in calculation to determine Fuel Gas Saving

    dT water 149.3 F Water Temperature Increase inside Waste Heat Recovery Section *

    H2O/Furn 18.0 gpm BFW Avg. H2O Flow/Furnace-assume G80F10->G82 F7 & G80F11->G82F8

    T FlueGas in 515 F Flue Gas Temperature Average from PI Data ChartTH2O in 110 F Water Temperature from Boiler Feed Water prior to Heat Recovery

    Uo 25 BTUH/SF/F Overal l Heat Transfer Factor, assume finned tubes

    OUTPUT Qwater=Qfluegas Calculation

    Flue Gas 2,041,768.8 SCFH Flue Gas, basis: Fuel Flow from PI Fuel Flow & XA% & FuelSG Correlation

    Fuel 145,833.3 scfh Convert PI Fuel Flow to SCFH from MMSCFD

    Q water 1,357,137.0 BTUH Calc Water Heat duty Required by Eq#2

    Flue Gas 34,029.5 SCFM Convert Flue Gas from SCFH to SCFM

    dT FlueGas 33.8 F Flue Gas dT by eqn 1 & Heat Duty of Eq2

    T FlueGas out 270.7 F Flue Gas T out by PI Flue Gas T & dT above

    TH2O out 259.3 F Water T out by Assumed Inlet Water T & dTwater

    LMTD 91.1 F LMTD by Text, (d1-d2)/ln(d1/d2)

    Ax 701.0 FeetSquared Recovery Exchanger Area by Eq.7 at F=0.85

    Fuel Saved 11,676.4 SCFH Based on Heat Recovered and Fuel Heat Value

    Fuel Cost 3.5 $/mSCF at 83% Boiler Effiency, study to confirm Boiler Effiency Orsat

    Annual $ $326,937.9 $/year Fuel Saving in $/year

    NPV $ at 7 $2,288,565.30 $

    Pump HP 0.7 HP at 40 psi dP additional dP over what is used already

    Pump elect 4,733.4 KWHR/YR to feed boilers

    $/KWHR 0.035 e Cost unit$ elec/yr 165.7 $ electri/yr use BFW Pump to Feed Heat Recovery

    Calc_F2-BOIL50#

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    13/35

    If steam is produced use above to calc Sensible Heat Calc_F2-BOIL50#

    Then Carry the value to cal. Latent Heat Requirements At

    H liq at T 703.8

    H vap at T

    dH stm at T

    flow H2O dT1 dT2

    Latent Q 160.7 45.2dT flue gas 228 Btu/# Tsat= 259 F use stm table for H

    T flue out 1167 Btu/# Psat= 35 psia use stm table for H

    LMTD 939 Btu/# net Latent Heat Required

    Ax 9000 #/hr frm B16 Convert gpm500=#/hr

    8451000 BTUH (BTU/#)(#/HR)

    210 F by ratio of above 224

    Recv./furn 305 F

    Recv in BTUH 150 F

    net dHs 2.8 SQ Ft.

    H2O mass Calc_F2-BOIL50#

    H2O volume 177

    numb Furn 4.2 MW/Furnace

    max H2O 14.3 mmbtuh/fur

    required H2O 1116 btu/# Stm

    12833 #S/hr/furn

    25.7 gpm/furn

    4.0 number

    102.7 gpm avail 4.2MW/Furnace

    210.0 gpm req'd 70*3boilers

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    14/35

    Summary Apr.28/09 T, F, five yr look bac Fuel gpm BFW pH gpm T, F

    MEAN Range L R Hi mmscfd water Steam Inlet W

    stack F1 G26AH 490 385 580 3.5 70 25 110

    stack F2G26AH 515 440 625 3.5 70 25 110

    stack F211G57AH 450 365 545 3.5 70 25 110

    stack F212AM 486 310 255 380

    oil F212 OinAM 486 195 155 235oil F212 OoutAM 486 265 255 380

    Calc_F2-BOIL50#

    Fuel Ax gpm H2O CapX guess

    gpm H2O m$/yr Ft2 Fuel at 3yrPOT Fuel at 5yr

    10 182 181 10 545 49 495 908 49 859

    12 218 250 12 654 82 572 1090 82 1008

    15 273 406 15 819 179 640 1365 179 1186

    18 327 703 18 981 431 550 1635 431 1204

    21 381 1678 21 1144 1735 -591 1907 1735 172

    gpm H2O PV CRF=3PC CRF=5

    10 495 859

    12 572 1008

    15 640 1186

    18 550 1204

    21 -591 172

    Calc_F2-BOIL50#

    Job Scope

    Add WHR unit to Stack on both Furnace, G80F10&11

    Use Single 4" feed & Return Pipe, insulate Return to G82F10&11

    Add Control Valve at G82 BFW Pumps and BL Isolation ValvesRelocate Stack TI to top of WHR HX

    Use FBE Pipe as inplant Runs since T does not exceed FBE Limits.

    Used Finned Tubes in Coiled Arrangement approx 32ft L x 5ftOD-400SF extended area

    Calc_F2-BOIL50#

    -1000

    -500

    0

    500

    1000

    1500

    10 15 20 25

    PV

    CRF=3

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    15/35

    Estimate Area & Heat Recovery for Flue Gas Heat Recovery for MED BFW Preheat

    air Q=1.08CFM(dT) btuh 1 Estimate only based on simplistic HVAC Air Water- Detailed to used actual Cp & Den's

    water Q=500gpm(dT) btuh 2

    Water lbs/hr=500gpm 3 Calc_F211

    fuel Q=(dH)SCFH(eff) btuh 4

    flue gas (SCF /SCF )=(1+%XA/200)(15.8SG+1.8) FlueGz/ Fuel 5 '(SCF /SCF )=(1+%XA/200)(15.8SG+1.8)

    any SCFH/60=SCFM 6

    Q=U(A)LMTD(F) BTUH 7

    Input

    Xair 10.0 % Excess Air from Furnace Design Sheet, Study to verifyFuel Qual FlueGz SCF/SCF Fuel MW/29 General Statement for Gas Specific Gravity

    0.73 14.0 Flue/Fuel Fuel SG amount of Flue Gas per Quantity of Fuel Used

    Fuel/Furn 3.5 mmscfd Fuel Flow to Furnace from PI 5 year Trend, Design to perform sensitivity analysis

    Fuel 1050.0 BTU/SCF Fuel Heat Content used in calculation to determine Fuel Gas Saving

    dT water 75 F Water Temperature Increase inside Waste Heat Recovery Section *

    H2O/Furn 70.0 gpm BFW Averaged Water Flow per Furnace-assume G80F10 servesG82 F7 & G80F11 serve G82F8

    T FlueGas in 450 F Flue Gas Temperature Average from PI Data Chart

    TH2O in 110 F Water Temperature from Boiler Feed Water prior to Heat Recovery

    Uo 25 BTUH/SF/F Overall Heat Transfer Factor, assume finned tubes

    OUTPUT Qwater=Qfluegas Calculation'

    Flue Gas 2,041,768.8 SCFH FlueGas, basis: Fuel by PI Fuel & XA% & FuelSG Corr.

    Fuel 145,833.3 scfh Convert PI Fuel Flow to SCFH from MMSCFD

    Q water 2,651,250.0 BTUH Calc Water Heat duty Required by Eq#2Flue Gas 34,029.5 SCFM Convert Flue Gas from SCFH to SCFM

    dT FlueGas 66.0 F Flue Gas dT by eqn 1 & Heat Duty of Eq2

    T FlueGas out 384.0 F Flue Gas T out by PI Flue Gas T & dT above

    TH2O out 185.0 F Water T out by Assumed Inlet Water T & dTwater

    LMTD 269.5 F LMTD by Text, (d1-d2)/ln(d1/d2)

    Ax 463.0 Feet squared Recovery Exchanger Area by Eq.7 at F=0.85

    Calc_F211

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    16/35

    Fuel Saved 3,156.3 SCFH Calc_F211

    Fuel Cost 3.5 $/mSCF

    Annual $ $88,375.0 $/year Fuel Saving in $/year

    NPV $ at 7 $618,625.00 $

    Pump HP 2.9 HP at 40 psi dP additional dP over what is used already

    Pump elect 18,407.8 KWHR/YR to feed boilers

    $/KWHR 0.035 e Cost unit

    $ elec/yr 644.3 $ electri/yr use BFW Pump to Feed Heat Recovery

    If steam is produced use above to calc Sensible Heat

    Then Carry the value to cal. Latent Heat Requirements

    H liq at T 337 Btu/# Tsat= 364 F use stm table for H

    H vap at T 1204 Btu/# Psat= 160 psia use stm table for H

    dH stm at T 867 Btu/# net Latent Heat Required

    flow H2O 35000 #/hr frm B16 Convert gpm500=#/hr

    Latent Q 30345000 BTUH (BTU/#)(#/HR)

    dT flue gas 755.7007138 F by ratio of above 224

    T flue out -371.7

    Job Scope Calc_F211

    Add WHR unit to Stack on both Furnace, G80F10&11

    Use Single 4" feed & Return Pipe, insulate Return to G82F10&11

    Add Control Valve at G82 BFW Pumps and BL Isolation Valves

    Relocate Stack TI to top of WHR HX

    Use FBE Pipe as inplant Runs since T does not exceed FBE Limits.

    Used Finned Tubes in Coiled Arrangement approx 32ft L x 5ftOD-400SF extended area

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    17/35

    Calc_F211 Boiler feed water average 70 gpm/boiler G26E310A-C sheet

    Summary Apr.28/09 T, F, five yr look back Fuel gpm BFW pH gpm T, F

    MEAN Range L R Hi mmscfd water Steam Inlet W dT H2O PV CRF=3 PC CRF=5

    F1 G26AH 490 385 580 3.5 70 25 110 75 44 221

    F2G26AH 515 440 625 3.5 70 25 110 100 255 490

    F211G57AH 450 365 545 3.5 70 25 110 125 -239 56

    F212AM 486 310 255 380 150 -560 -206

    F212 OinAM 486 195 155 235 175 -1088 -676

    F212 OoutAM 486 265 255 380Based on Heat Recovered and Fuel Heat Value at 83% Boiler Effiency, study to confirm Boiler Effiency Orsat

    Fuel Ax CapX guess

    dT H2O m$/yr Ft2 dT H2O Fuel at 3yrPOT Fuel at 5yr

    75 88 463 75 265 221 44 442 221 221

    100 118 280 100 353 99 255 589 99 490

    125 147 935 125 442 681 -239 737 681 56

    150 177 1255 150 530 1090 -560 884 1090 -206

    175 206 1661 175 619 1707 -1088 1031 1707 -676

    -1200

    -1000

    -800

    -600

    -400

    -2000

    200

    400

    600

    50 75 100 125 150 175 200PV CRF=3

    PC CRF=5

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    18/35

    Estimate Area & Heat Recovery for Flue Gas Heat Recovery for MED BFW Preheat

    air Q=1.08CFM(dT) btuh 1 'Estimate only based on simplistic HVAC Air Water- Detailed to used actual Cp & Den's

    water Q=500gpm(dT) btuh 2

    Water lbs/hr=500gpm 3 Calc_F211_BOIL

    fuel Q=(dH)SCFH(eff) btuh 4

    flue gas (SCF /SCF )=(1+%XA/200)(15.8SG+1.8) FlueGz/ Fuel 5 Boiler feed water average 70 gpm/boiler G26E310A-C sheet

    any SCFH/60=SCFM 6

    Q=U(A)LMTD(F) BTUH 7

    Input

    Xair 10.0 % Excess Air from Furnace Design Sheet, Study to verifyFuel Qual FlueGz SCF/SCF Fuel MW/29 General Statement for Gas Specific Gravity

    0.73 14.0 Flue/Fuel Fuel SG amount of Flue Gas per Quantity of Fuel Used

    Fuel/Furn 3.5 mmscfd Fuel Flow to Furnace from PI 5 year Trend, Design to perform sensitivity analysis

    Fuel 1050.0 BTU/SCF Fuel Heat Content used in calculation to determine Fuel Gas Saving

    dT water 254 F Water Temperature Increase inside Waste Heat Recovery Section *

    H2O/Furn 7.0 gpm BFW Averaged Water Flow per Furnace-assume G80F10 servesG82 F7 & G80F11 serve G82F8

    T FlueGas in 450 F Flue Gas Temperature Average from PI Data Chart

    TH2O in 110 F Water Temperature from Boiler Feed Water prior to Heat Recovery

    Uo 25 BTUH/SF/F Overall Heat Transfer Factor, assume finned tubes

    OUTPUT Qwater=Qfluegas Calculation'

    Flue Gas 2,041,768.8 SCFH Flue Gas, based on Fuel Flow from PI Fuel Flow & XA% & FuelSG Correlation

    Fuel 145,833.3 scfh Convert PI Fuel Flow to SCFH from MMSCFD

    Q water 897,890.0 BTUH Calc Water Heat duty Required by Eq#2Flue Gas 34,029.5 SCFM Convert Flue Gas from SCFH to SCFM

    dT FlueGas 22.4 F Flue Gas dT by eqn 1 & Heat Duty of Eq2

    T FlueGas out 352.1 F Flue Gas T out by PI Flue Gas T & dT above

    TH2O out 364.0 F Water T out by Assumed Inlet Water T & dTwater

    LMTD 73.7 F LMTD by Text, (d1-d2)/ln(d1/d2)

    Ax 573.6 Feet squared Recovery Exchanger Area by Eq.7 at F=0.85

    Calc_F211_BOIL

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    19/35

    Fuel Saved 4,681.4 SCFH

    Fuel Cost 3.5 $/mSCF

    Annual $ $131,079.7 $/year Fuel Saving in $/year

    NPV $ at 7 $917,557.67 $ Calc_F211_BOIL

    Pump HP 0.3 HP at 40 psi dP additional dP over what is used already

    Pump elect 1,840.8 KWHR/YR to feed boilers

    $/KWHR 0.035 e Cost unit

    $ elec/yr 64.4 $ electri/yr use BFW Pump to Feed Heat Recovery

    If steam is produced use above to calc Sensible Heat dT1 dT2

    Then Carry the value to cal. Latent Heat Requirements 242.1 10.4

    H liq at T 337.0 Btu/# Tsat= 364 F use stm table for H

    H vap at T 1204.0 Btu/# Psat= 160 psia use stm table for H

    dH stm at T 867.0 Btu/# net Latent Heat Required

    flow H2O 3500.0 #/hr frm B16 Convert gpm500=#/hr

    Latent Q 3034500.0 BTUH (BTU/#)(#/HR)

    dT flue gas 75.6 F by ratio of above 224

    T flue out 374.4 F Calc_F211_BOIL

    LMTD 48.2 F

    Ax 3.4 SQ Ft. Job Scope

    53.2 Add WHR unit to Stack on both Furnace, G80F10&11

    Recv./furn 4.2 MW/Furnace Use Single 4" feed & Return Pipe, insulate Return to G82F10&11

    Recv in BTUH 14.3 mmbtuh/fur Add Control Valve at G82 BFW Pumps and BL Isolation Valves

    net dHs 1116.0 btu/# Stm Relocate Stack TI to top of WHR HX

    H2O mass 12833.3 #S/hr/furn Use FBE Pipe as inplant Runs since T does not exceed FBE Limits.

    H2O volume 25.7 gpm/furn Used Finned Tubes in Coiled Arrangement approx 32ft L x 5ftOD-400SF extended area

    numb Furn 4.0 number

    max H2O 102.7 gpm avail 4.2MW/Furnace

    required H2O 210.0 gpm req'd 70*3boilers

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    20/35

    Summary Apr.28/09 T, F, five yr look back Fuel gpm BFW pH gpm T, F dT H2O PV CRF=3 PV CRF=5

    MEAN Range L R Hi mmscfd water Steam Inlet W 2 100 175

    F1 G26AH 490 385 580 3.5 70 25 110 3 140 253

    F2G26AH 515 440 625 3.5 70 25 110 4 170 319

    F211G57A 450 365 545 3.5 70 25 110 6 171 396

    F212AM 4 310 255 380 7 79 341

    F212 OinA 195 155 235

    F212 Oout 265 255 380

    Based on Heat Recovered and Fuel Heat Value at 83% Boiler Effiency, study to confirm Boiler Effiency Orsat

    Fuel Ax

    gpm H2O m$/yr Ft2 gpm H2O Fuel at 3yr CapX guess Fuel at 5yr

    2 38 78 2 113 13 100 188 13 175

    3 56 128 3 169 28 140 281 28 253

    4 75 191 4 224 54 170 373 54 319

    6 112 387 6 337 166 171 562 166 396

    7 131 577 7 393 314 79 655 314 341

    sf total 577

    Calc_F211_BOIL

    0

    50

    100

    150

    200

    250

    300

    350

    400

    450

    0 1 2 3 4 5 6 7 8

    PV CRF=3

    PV CRF=5

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    21/35

    based on this, average water flow is 70 gpm

    3units at 35,000#H2O/hr and 35,000/500= 70 gpm G26E310A-C

    based on chart avg BFW T is 110F

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    22/35

    SFUT_56FI1530.PV Split flow to F1, F2, F211

    G26E310A-C SFUT_56FI1531.PV

    SFUT_56FI1532.PV

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    23/35

    SFWC_53FI1437.pv Fuel F212

    SFDS_85FI1100.PV Q-F212-3 Fuel

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    24/35

    Q-F212-3 Fuel

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    25/35

    avg=3.5mmscfd G26F1Fuel

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    26/35

    G26F1Fuel

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    27/35

    310F avg Stack T F212_486AM-

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    28/35

    F1Stack SFDS_75TI247A.PV F2Stack SFDS_75TI247E.PV F1F2 Stack T_G26AH-

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    29/35

    460 F211_G57AH.

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    30/35

    267F out T 188F inlet 212HotOil T in 212HotOil T in

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    31/35

    Summary Apr.28/09 T, F, five yr look back mmscfd mmscfd gpm BFW pH gpm

    MEAN Range L R Hi fuel flow avg fuel water Steam Oprn sumry

    F1 G26AH stack o 490 385 580 3.5 3.5 70 25

    F2G26AH stack o 515 440 625 3.5 3.5 70 25

    F211G57AH stack o 450 365 545 3.3 3.5 70 25

    F212G57AH stack o 310 255 380 2.7 NA na

    F212 Oil nAM 486 195 155 235

    F212 Oil oAM 486 265 255 380 Oprn sumry

    Average Water Flow Per Boiler 70 gpm average fuel flow per furnace 3.5 mmscfd

    Steam Pressure 175 psig Steam & Water Phy Prop From eSteam Table

    Steam Pressure 160 psia H Sat Stm 160psia 1195.1 btu/lb

    Avg Fd Water T 110 F T sat Stm 160psia 363.6 F

    H Sat H2O 160psia 336.1 btu/lb

    MW Flue Gas 30 #/Mol H Sat H2O 110F 78.0 btu/lb

    Cp Flue Gas 0.25 BTU/#/F Cp water 1.018 btu/lb/F

    Flue Gas Heat F 1.18 BTU/HR/SCFM/dF dH vap 160psia 859.0 btu/lb

    Total dH H2O furn 1117.1 btu/lb

    Sen dH H2O furn 258.1 btu/lb

    Den BFW 61.9 #/CF

    Oprn sumry SG BFW 1.0 v/v

    BFW Heat Factor 505.0 BTU/Hr/gpm/dF

    dT water 253.6

    Oprn sumry

    Fuel Gas to Flue Gas Homologues of Parrifinic HC Gas & Stoc. Combustion

    C+O2=CO2 H2+0.5O2=H2O

    SG gas #C's H2 oC oH Sum O2 N2 Sum Sum air CmbGas FlueGz

    0.55 C1 1 2 1 0.5 2.0 7.5 9.5 3 11.2

    1.03 C2 2 3 1 0.5 3.5 13.2 16.7 5 19.3

    1.52 C3 3 4 1 0.5 5.0 18.8 23.8 7 27.4

    2.00 C4 4 5 1 0.5 6.5 24.5 31.0 9 35.5

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    32/35

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    33/35

    G26-F211 and F212 Spec sheets

    Furnace Spec Sheets

    G26F1 &F2 spec sheet

    G26FurnSpecs-DSN

    D779316001T01.tiff

    D780951001T01.tiff

    D780951002T01.tiff

    D780951003T01.tiff

    D780951004T01.tiff

    D780951005T01.tiff

    D780951006T01.tiff

    Adobe Acrobat

    Document

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    34/35

    Saf Fuel Gas Comp Saf Fuel Gas Comp twister SG1 new

    BI-224 P/L gas P/L gas P/L gas P/L gas

    DBSP.pg9 Lab Sample Saf-S saf-w Saf-S saf-w avg S avg W

    WetGas B Ap20/08

    N2 0.70 3.19 0.71 0.73 0.71 0.73 0.71 0.73

    CO2 1.20 1.23 1.40 1.43 1.40 1.43 1.40 1.43

    H2S 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00C1 72.39 65.64 67.42 69.57 67.44 69.40 67.43 69.49

    C2 16.90 15.15 16.08 16.09 16.08 16.11 16.08 16.10

    C3 7.40 10.77 10.14 9.11 10.14 9.20 10.14 9.15 9.65

    iC4 0.20 0.94 0.93 0.72 0.93 0.73 0.93 0.72 0.83

    nC4 0.80 2.25 2.47 1.80 2.47 1.84 2.47 1.82 2.15

    iC5 0.20 0.23 0.38 0.24 0.38 0.24 0.38 0.24 0.31

    nC5 0.20 0.21 0.38 0.26 0.36 0.27 0.37 0.26 0.32

    n6 0.00 0.01 0.08 0.04 0.08 0.04 0.08 0.04 0.06

    C7+ 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

    nC8 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

    nC9 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

    nC10 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

    O2 0.00 0.38 0.00 0.00 0.00 0.00 0.00 0.00 13.31

    H2 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

    He 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

    H2O 0.01 0.00 0.01 0.01 0.01 0.01 0.01 0.01

    sum 100.00 100.00 100.00 100.00 100.00 100.00 100.00 100.00

    SG 0.74 0.81

    mw 21.58 23.39

    cp/cv 1.25

    NHV 1148

    Tc* R 407.61

    Pc* psia 669.3 Saf Fuel Gas Comp

    Mx&Norm

    sweet

  • 8/3/2019 Waste Heat Boiler Evaluation for Gas Fired Heater Furnace

    35/35

    %Cond HC condy defined as C3+

    Apr20 anal 13.655

    BI224 dbsp 8.8

    1.55 ratio of Conden HC

    bpd condy 466 above ratio times 300bpd/10.5mmscfd feed

    1020 condy at 23MMSCFD with heavy summer feed

    657 condy at 23MMSCFD with light winter feed

    Saf Fuel Gas Comp

    Recovery Range EstimateBasis: Quote From Twister for Tanajib using BI-224 composition & recovery =300bpd/10.5mmscfd

    Consider the summer pipeline gas to be richer as temps are higher, winter has lower dew point

    Winter Case considered as BI-224, summer as Apr.20 analysis

    case summer winter Saf Fuel Gas Comp

    gas mmscfd 23 23

    condy recv. 657 1056