VVF Drive- Technical Specification Project: CHD Application of drive: Passenger Ropeway Scope: Design, Supply, testing and commissioning of VVF drive including supply of suitable encoder S. No. Parameter Value GENERAL SITE CONDITIONS: 1. Max. ambient temperature 40° C inside control room 2. Maximum relative humidity 100 %, non-condensing 3. Altitude above mean sea level Less than 1000 meter 4. Environmental condition Tropical humid climate with dusty industrial atmosphere. Maximum ambient temperature and maximum relative humidity will not occur simultaneously INPUT POWER SUPPLY SYSTEM: 1. Supply Voltage 415V, 3Ph, 4 W, + 10% 2. Frequency 50Hz, + 5% 3. Grounding Solidly Ground 4. Fault Level 15kA, 1 sec DRIVE SPECIFICATIONS: 1. Drive Rating 100KW, VVVF Type 2. Drive Type Regenerative, 4 Quadrant 3. Technology PWM based, with IGBT 4. Mode of operation Constant torque 5. Starting Torque 150% or above at 1 Hz 6. Mode of control Vector control using encoder / Tacho generator 7. Acceleration Ramp Linear, and ‘S’ type curve, 0-99 Sec 8. Speed regulation 0.1% or better 9. D/I, D/O, A/I, A/O a. D/I 1.Normal Stop 2.Emergency Stop - I at 6 Sec -ve Ramp 3.Emergency Stop - II at 3 Sec –ve Ramp 4.Start at full load with 16 sec +ve

VVF Drive Induction Motor Specs CHD_02

Embed Size (px)

DESCRIPTION

VSD and Motor Specs

Citation preview

Page 1: VVF Drive Induction Motor Specs CHD_02

VVF Drive- Technical Specification

Project: CHD

Application of drive: Passenger Ropeway

Scope: Design, Supply, testing and commissioning of VVF drive including supply of suitable encoder

S. No. Parameter ValueGENERAL SITE CONDITIONS:

1. Max. ambient temperature 40° C inside control room2. Maximum relative humidity 100 %, non-condensing3. Altitude above mean sea level Less than 1000 meter4. Environmental condition Tropical humid climate with dusty industrial atmosphere.

Maximum ambient temperature and maximum relative humidity will not occur simultaneously

INPUT POWER SUPPLY SYSTEM:1. Supply Voltage 415V, 3Ph, 4 W, +10%2. Frequency 50Hz, +5%3. Grounding Solidly Ground4. Fault Level 15kA, 1 sec

DRIVE SPECIFICATIONS:1. Drive Rating 100KW, VVVF Type2. Drive Type Regenerative, 4 Quadrant3. Technology PWM based, with IGBT4. Mode of operation Constant torque5. Starting Torque 150% or above at 1 Hz6. Mode of control Vector control using encoder / Tacho generator7. Acceleration Ramp Linear, and ‘S’ type curve, 0-99 Sec8. Speed regulation 0.1% or better9. D/I, D/O, A/I, A/O

a. D/I 1. Normal Stop2. Emergency Stop - I at 6 Sec -ve Ramp3. Emergency Stop - II at 3 Sec –ve Ramp4. Start at full load with 16 sec +ve Ramp (Adjustable)5. Auto Start (optional)

b. D/O Potential free 2 no (Programmable)c. A/I 1. Encoder / Tacho input

2. Speed Reference (thru pot or program)3. Current Feedback4. Motor winding Temperature

d. A/O 1. Output Voltage2. Speed3. Current

10. Drive Protections 1. Over speed2. Over Current

Page 2: VVF Drive Induction Motor Specs CHD_02

S. No. Parameter Value3. Single phasing4. Under Voltage5. Feedback Failure6. Over Voltage7. DC link Under and Over Voltage8. Control power supply failure9. Earth Fault (DC Side)10. Inversion fault, di/dt & dv/dt11.DC side short circuit12. Motor stalling protection13. Panel fan overload

11. Control Supply (for field control circuit)

24VDC, 200VA, isolated from power circuit, Non-regulated, with filter

12. Drive Efficiency at Full Load 96% or better13. Load Capability of drive 1. At 100% Load – Continuous

2. At 125% Load – 2 Hours3. At 200% Load – 10 Sec

14. Fault Warning Alarm / Trip Feature for selected faults15. Power Conditioning Suitable Filters to maintain THD <5%16. Interlock Provision Expendable PLC interface with 36 D/I and 24 D/O17. HMI 6’’ Colour HMI touch screen with suitable communication

for 30 meter distance18. Auxiliary Loads 1. 3.75 KW – 1 No

2. 2.2 KW – 1 No3. 0.75KW – 2 No4. 0.50 KW – 3 No

19. Analog Meter (96x96mm size) 1. Supply Voltage2. Supply Current3. Output Voltage4. Output Current5. Output Speed6. Power Factor

20. Digital Display 1. Motor Temperature2. Multifunction Meter (for Energy Import /Export)

21. Panel Cubicle 1. IP: 312. Enclosure Sheet Thickness : 2mm3. single front type totally enclosed, dust & vermin proof4. Paint – Inside Off white and outside Grey With 7 Tank

method5. Self-standing, floor mounted6. Operating height – Max 1850mm7. System Earthing – 2 No8. Cable Entry – Bottom9. Gland Plate – 2mm, MS, Electro- galvanized10. Suitable panel lifting hook

Page 3: VVF Drive Induction Motor Specs CHD_02

S. No. Parameter Value11. Panel door opening up to 900

12. Panel space heater with adjustable thermostat22. Push Buttons (22.5mm Dia) 1. Start (Normal) – Green

2. Inch (FWD) – Green3. Inch (Rev) – Green4. Em. Stop (Mushroom Head – Red – Push to lock) – Red5. RESET – Black6. Stop (Normal- Projected Head - Red) – Red

23. Selector Switches 1. Local/ Remote2. Mode: Run – Maint. - OFF - Inch3. Control Supply ON4. Voltage Selector Switch5. Ammeter Selector Switch

24. Indications (LED type, 16mm dia) 1. Mains ON – Amber2. Ropeway Run FWD – Green3. Ropeway Run REV – Green4. Service Brake released – Green5. Em. Brake Released – Green6. Drive Ready – Green7. Upper station ready8. Drive Fault – Red9. Motor Fan O/L – Red10. Panel Fan O/L – Red11. Service Brake O/L – Red12. Em Brake O/L – Red13. G.B. Oil Pump O/L – Red14. Chain Haulage O/L – Red15. Spacer O/L – Red16. Field Safety Fail – Red17. Control power supply Healthy – Green18. Cabin Braking Thruster ON – Green19. Panel over temperature – Red20. Semiconductor Fuse blown – Red21. Wrong Supply Phase sequence - Red22. Spare - Red

Fault and Action List:

S. No. Fault Action Type of Reset1. Drive Faulta. Power Quality Problem Alarm, If continue for 1 Min, then N. Stop Manual Resetb. Motor O/L Emergency Stop Type- I Manual Resetc. Motor Over Temp. Alarm, If continue for 5 Min, then N. Stop Manual Resetd. Panel Fan O/L Alarm, If continue for 5 Min, then N. Stop Manual Resete. Panel over Temp. Alarm, If continue for 5 Min, then N. Stop Manual Reset

Page 4: VVF Drive Induction Motor Specs CHD_02

f. Semiconductor fuse fail Emergency Stop Type – I Manual Resetg. Speed Feedback Fail Auto switch to voltage feedback with Alarm Manual Reset2. Motor Fan O/L Alarm, If continue for 1 Min, then N. Stop Manual Reset3. Service Brake O/L Alarm, If continue for 1 Min, then N. Stop Manual Reset4. Em Brake O/L Alarm, If continue for 1 Min, then N. Stop Manual Reset5. G.B. Oil Pump O/L Alarm, If continue for 1 Min, then N. Stop Manual Reset6. Chain Haulage O/L Alarm Manual Reset7. Spacer O/L Alarm Manual Reset8. Field Safety Faila. Safety Fail type – I Emergency Stop Type - I Manual Resetb. Safety Fail Type – II Emergency Stop type -II Manual Reset

Supply wrong Phase sequence

Alarm and Trip all Auxiliary motors Manual Reset

Note: All fault timing shall be adjustable.

Safety Fail Type-I : Need 6 Sec Stop Normal Stop : 10 Sec Ramp Stop

Safety Fail Type-II : Need 3 Sec Stop Alarm : Warning Indication with beep sound

Emergency Stop Type – I : 6 Sec Ramp Stop

Emergency Stop Type – II : 3 Sec Ramp Stop

General Specification

The above parameters to be followed as minimum. Drive shall be supplied, considering the following

guidelines –

1. Drive shall be used to run an AC Squirrel Cage Induction Motor.

2. Application of this drive is to run a passenger ropeway, where system will start at full load (i.e.

100KW) and run at constant torque mode.

3. Drive shall be equipped with phase sequence monitor and any phase sequence shall be

acceptable to drive.

4. Drive shall be interlocked with other auxiliary loads, like motor air blower, gear box oil pump,

service brake, emergency brake, chain haulage and spacer.

5. Drive shall be run in following modes –

I. Normal full speed with ramp : 2.75 m/s

II. Maintenance Speed (approx 30% of full speed) with ramp : 0.60 m/s

III. Jog forward with ramp : 0.25 m/s

Page 5: VVF Drive Induction Motor Specs CHD_02

IV. Jog Reverse with ramp : 0.25 m/s

6. Positive and Negative ramp for different mode of run shall be adjustable. There shall be

following types of ramp –

I. +Ve 0-16 Sec (for normal and maintenance run)

II. +Ve 0-4 Sec (for Jog)

III. –Ve 0-16 Sec ( for normal stop in case of normal run and maintenance mode)

IV. –Ve 0-10 Sec (for Emergency Stop Type-I)

V. –Ve 0-6 Sec (For emergency Stop Type-II)

Ramp curve shall be selectable either linear or ‘S’ profile.

7. Drive should be capable to deliver minimum 150% torque at 1 Hz output

8. Drive shall keep its own memory with Lithium battery to keep set program. Drive shall be

programmable and the program shall be ready to copy and paste for future use. Drive shall be

able to store at least 16 previous faults in memory on FIFO sequence.

9. Drive shall be equipped with suitable memory card, to keep the program saved in case of

Lithium battery ageing or failure.

10. Drive shall have additional inbuilt following protections –

I. Lightning & surge protection

II. Heat sink temperature protection with Microcontroller monitored thermal sensor

III. IGBTs shall have soft recovery freewheeling diodes to prevent IGBT failure when

subjected to motor discharge spikes.

11. Ropeway running parameters – Supply voltage, Supply Current, Power Factor, Motor Voltage,

Motor current, Speed, output frequency and load kilowatt shall be designed such that these

parameters can be displayed at drive panel and at an auxiliary control cabinet simultaneously.

12. Drive shall be designed as overloading capacity given in drive specifications.

13. Drive shall be capable to run without any speed feedback with 1% speed regulation. However,

vector control shall be applicable using a Tacho / encoder with 0.1% speed regulation.

14. Drive shall be capable to run for 15 minute every hour up to 18% regeneration mode. Generated

power shall be absorbed by the auxiliary load, connected to local grid.

15. Drive shall be supplied with a touch control mimic display (HMI). The display shall be suitable to

communicate with drive and PLC both. For communication, suitable medium of communication

to be selected considering 30 meter distance of mimic from drove panel. Graphics design shall

be such that a user can start and stop ropeway in all mode of operations from mimic panel. In

Page 6: VVF Drive Induction Motor Specs CHD_02

mimic panel, ropeway faults also to be configured including ropeway parameters e.g. ropeway

speed, supply voltage, motor voltage and frequency, load on drive, etc.

16. Drive panel shall contain –

I. 5A, Switch & socket – 1 Set in each cubicle

II. Thermostat controlled Space Heater – 1 Set in each cubicle

III. Panel illumination with door operated switch – 2 Set in each cubicle (for both front and

back side)

17. Provision shall be made to feed Control supply from two sources with an internal changeover

switch.

18. Panel wiring shall be done with FRLS type flexible wire. Wire size shall not be less than 1.5Sqmm.

All wires shall be single core multi-strand/ flexible copper, PVC insulated HFLS/ ZHFR grade as

per IS: 694 and shall be 660 V / 1100 V with 99.97% pure electrolytic grade bright annealed

stranded bare copper conductors. Special parameters of HFLS/ZHFR PVC insulation like critical

oxygen index, temperature index, smoke density and flammability test shall conform to relevant

IEC and ASTM Standards.

All wires shall be colour coded as follows:

Phase Colour of wire

R Red

Y Yellow

B Blue

N Black

Earth Green (insulated)

Control Grey

19. Component selection shall be done as per ‘Type-2’ coordination.

20. Power Cable termination provision shall be made for incoming and outgoing cables.

21. All live parts shall be covered with transparent cover to avoid any unintentional touch

22. Drive panel shall be equipped with ventilation fan, to maintain drive performance at full load,

considering a room temperature as 300C.

23. Control power supply for drive reference shall be regulated.

24. All power electronics components of drive shall be suitably selected to withstand inverse

voltage.

Page 7: VVF Drive Induction Motor Specs CHD_02

Other Requirements –

1. Panel Supply, testing and commissioning shall be in scope of vendor

2. All internal components, wires, cables, etc shall be in scope of vendor.

3. Panel components shall be as per approved make, as per attached list.

4. 3 sets of Drive software and drawing shall be supplied along with panel. Drive applicable

software shall be of latest version. Update of the software shall be made available online or off

line free of charge till the drive useful life.

5. Panel testing shall be witnessed by company representative

6. Applicable commissioning spares shall be supplied along with drive.

7. Vendor shall furnish a list of recommended routine spares.

8. Drive and panel shall be guaranteed for a period of 1 year from drive commissioning.

9. All software work shall be in vendor scope. Parameters configuration, including graphics design

in mimic display also shall be in vendor scope.

Page 8: VVF Drive Induction Motor Specs CHD_02

Make of Components

S. No. Component Make1. Inductor BCH, Indcoil, AB Power, Ambik Harmonics, Arihant Elecrical2. Control Transformer AE, Unitech, EPI, Advance Power Control, BCH3. Power Capacitor L&T, BCH, Schneider, Epcos, Shreem, Datar4. MCCB Schneider, L&T, Siemens, ABB, Moeller5. MCB Schneider, L&T, Siemens, ABB, Havells, MDS, Indoasian6. MPCB Schneider, L&T, ABB, Siemens, SE, Moeller7. ELCB Schneider, L&T, Havells, MDS, ABB, Indoasian8. Switch / SFU L&T, Schneider, Havells, Anchor, GE9. HRC Fuse L&T, Siemens, Havells, Bussman, ABB, GE10. Semiconductor Fuse Bussman, ABB, Siemens, GE, La-Ferraz

11. IGBT Eupec, West code, Infineon, Semikron, Toshiba, Misubishi, Fuji, ABB

12. Control Relay OEN, L&T, Schneider, Siemens, Rockwell Automation13. Power Contactor L&T, Schneider, Moeller, GE, ABB14. Bi-Metallic Relay Schneider, L&T, Siemens, BCH,15. Electronic O/L Relays Siemens, L&T, Rockwell Automation, Moeller, Schneider16. Timer Siemens, L&T, BCH, Schneider, Selectron17. Limit Switch Schneider, Jai Balaji, BCH, Siemens, L&T18. Indication Lamp (LED) Technik, BCH, Siemens, L&T, Schneider19. Selector Switch ABB, GE, L&T, Teknik, Kaycee, Siemens20. Push Buttons GE, BCH, L&T, Siemens, Schneider, Technik21. Analog Meter L&T, AE, Meco, Conzerve22. Digital / MF Meter L&T, Conzerve, Areva, Schneider, Meco23. Terminal Elmex, Phonix, Connect well, Wago24. Flexible Wire Finolex, Polycab, L&T, KEI, Havells25. Panel Light (LED) L&T, BCH, Technik, Siemens, Philips, Osram, CG26. Panel Cabinet BCH, Rittal, Transrect, Advance Power Control, EPCC27. Tacho generator Hubner, Baumer, Jayshree, Radio-Energie28. Encoder Hubner, IFM, Leonard, Pepperl+Fuchs29. CT ABB, Jayshree, Pragati, Kappa, Intravidut, AE30. Plug-in Relay Omron, OEN, Eaton, Rockwell Automation, Schneider, BCH31. PLC GE-Fanuc, Siemens, Rockwell Automation, L&T, Schneider

32. Annunciator / Mimic Panels

Minilec, Procon, Yashmun, Pyrotech (Udaipur), Oerlikon, GE, BCH, Red Lion, Palas

33. Proximity Switches Rockwell Automation, Schneider, Siemens, IFM

Page 9: VVF Drive Induction Motor Specs CHD_02

AC Squirrel Cage Induction Motor- Technical Specification

Project: CHD

Application of Motor: Passenger Ropeway

Scope: Design, Supply, and Testing of Squirrel Cage Induction Motor

S. No. Parameter ValueGENERAL SITE CONDITIONS:1. Max. ambient temperature 45° C2. Maximum relative humidity 100 %, non-condensing3. Altitude above mean sea level Less than 1000 meter4. Environmental condition Tropical humid climate with dusty industrial atmosphere.

Maximum ambient temperature and maximum relative humidity will not occur simultaneously

INPUT POWER SUPPLY SYSTEM:1. Supply Voltage 415V, 3Ph, 4 W, +10%2. Frequency 50Hz, +5%3. Grounding Solidly Ground4. Fault Level 15kA, 1 secMOTOR SPECIFICATIONS:1. Rating 110KW*2. Voltage 415V3. Enclosure Type TEFC4. Mounting Type B35. Frame size 315S**6. No of Pole 47. Insulation Class F, temperature rise shall be limited to the limits

applicable to Class ‘B’ insulation8. Duty S19. Cooling System IC4A1A6 (using motor shaft independent cooling system)10. Tacho / Encoder Mounting Required at NDE side11. IP Class IP 5412. Terminal Box IP 55, Suitable to rotate for 3600 in 900 steps13. Motor winding temperature sensor RTD-100, 3 no at 1200 apart14. Winding Type VPI, Copper15. Motor Efficiency # to be filled by manufacturer (Eff 1)16. Motor overloading # to be filled by manufacturer17. Motor Starter VVVF Drive18. Shaft Extension As per frame size19. Motor Test # to be filled by manufacturer20. Vibration Limit As per IS 1207521. Noise Limit As per IS 1206522. Rotation Direction CW from NDE side

Page 10: VVF Drive Induction Motor Specs CHD_02

*, ** : Motor Rating / Motor Frame Size / Motor Efficiency / Motor output

Motor Rating Motor Frame Size Motor Efficiency Motor Effective Output

90 KW 280M 95% (Eff 1) 85.5KW

90 KW 280M 93.9% (Eff 2) 84.5KW

110KW 315S 95.2% (Eff 1) 104.7KW

110KW 315S 94.4% (Eff 2) 103.8KW