Voltage Stress in Power Systems -

Embed Size (px)

Citation preview

  • 7/30/2019 Voltage Stress in Power Systems -

    1/29

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 1 -

    Voltage Stress in Power Systems - Classification

    IEC 60071-1

  • 7/30/2019 Voltage Stress in Power Systems -

    2/29

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 2 -

    Classification of real stress

    Classification of real stress

    Voltage Stress in Power Systems

    "Continuous (power-frequency) voltage"

    Power-frequency voltage, considered having constant r.m.s. value, continuously applied to any pair of

    terminals of an insulation configuration

    f= 50 Hz or 60 Hz

    T1 3 600 s

    Any power-frequency voltage lasting for 1 h or more is considered a continuous voltage!

    Standard voltage

    Standard voltage "Standard power-frequency voltage"

    A sinusoidal voltage with frequency of 50 Hz or 60 Hz

    T1 to be specified by the apparatus committees T1 up to 2 years! see next slides

    Conversioninto

    Voltage Stress in Power Systems - Classification

  • 7/30/2019 Voltage Stress in Power Systems -

    3/29

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 3 -

    Example: Cable tests at power-frequency voltage

    Example: Cable tests at power-frequency voltage

    Voltage Stress in Power SystemsVoltage Stress in Power Systems - Classification

    Lifetime characteristic:

  • 7/30/2019 Voltage Stress in Power Systems -

    4/29

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 4 -

    Example: Cable tests at power-frequency voltageExample: Cable tests at power-frequency voltage

    Voltage Stress in Power SystemsVoltage Stress in Power Systems - Classification

    Source: Brugg Cables

    11.4 years

  • 7/30/2019 Voltage Stress in Power Systems -

    5/29

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 5 -

    Voltage Stress in Power Systems

    "Temporary overvoltage"

    Power-frequency overvoltage of relatively long duration. The overvoltage may be damped or

    undamped. In some cases its frequency may be several times smaller or higher than power

    frequency.

    10 Hz < f< 500 Hz

    3 600 s T1 0.02 s

    Highest values by following main reasons:

    phase-to-earth earth faults and load rejection

    phase-to-phase load rejection

    longitudinal phase opposition during synchronization of two grids

    Standard voltageStandard voltage "Standard short-duration power-frequency voltage"

    A sinusoidal voltage with frequency between 48 Hz and 62 Hz

    T1 = 60 s

    Conversioninto

    Classification of real stressClassification of real stress

    Example [THI-01]

    Voltage Stress in Power Systems - Classification

  • 7/30/2019 Voltage Stress in Power Systems -

    6/29

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 6 -

    Voltage Stress in Power Systems

    "Transient overvoltage"

    Short-duration overvoltage of few milliseconds or less, oscillatory or non-oscillatory, usually highly

    damped. May be followed by temporary overvoltages. In this case, both events are considered as

    separate events.

    Standard voltageStandard voltage "Standard switching impulse"

    An impulse voltage of

    Tp = 250 s

    T2 = 2 500 s

    Conversioninto

    Classification of real stressClassification of real stress

    "Slow-front overvoltage"

    Transient overvoltage, usually unidirectional

    5000 s Tp > 20 s

    T2 20 ms

    Main reasons: line faults, switching

    Example [THI-01]

    Voltage Stress in Power Systems - Classification

  • 7/30/2019 Voltage Stress in Power Systems -

    7/29

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 7 -

    Voltage Stress in Power Systems

    "Transient overvoltage"

    Short-duration overvoltage of few milliseconds or less, oscillatory or non-oscillatory, usually highly

    damped. May be followed by temporary overvoltages. In this case, both events are considered as

    separate events.

    Standard voltageStandard voltage "Standard lightning impulse"

    An impulse voltage of

    T1 = 1.2 s

    T2 = 50 s

    Conversioninto

    Classification of real stressClassification of real stress

    "Fast-front overvoltage"

    Transient overvoltage, usually unidirectional

    20 s T1 > 0.1 s

    T2 300 s

    Main reasons: lightning strokes, switching

    Example [THI-01]

    Voltage Stress in Power Systems - Classification

  • 7/30/2019 Voltage Stress in Power Systems -

    8/29

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 8 -

    Voltage Stress in Power Systems

    "Transient overvoltage"

    Short-duration overvoltage of few milliseconds or less, oscillatory or non-oscillatory, usually highly

    damped. May be followed by temporary overvoltages. In this case, both events are considered as

    separate events.

    Standard voltageStandard voltage not standardized

    Conversioninto

    Classification of real stressClassification of real stress

    "Very-fast-front overvoltage"

    Transient overvoltage, usually unidirectional

    Tf< 100 ns

    (Tt 3 ms)

    basic oscillation (1st harmonics) 30 kHz < f< 300 kHzsuperimposed oscillations 300 kHz < f< 100 MHz

    Main reasons: switching of disconnectors in GIS

    Example [THI-01]

    Voltage Stress in Power Systems - Classification

  • 7/30/2019 Voltage Stress in Power Systems -

    9/29

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 9 -

    Voltage Stress in Power Systems

    "Combined (temporary, slow-front, fast-front,very-fast-front) overvoltage"

    Consisting of two voltage components simultaneously applied between each of the two phase

    terminals of a phase-to-phase (or longitudinal) insulation and earth. It is classified by the component

    of the higher peak value.

    Standard voltageStandard voltage "Standard combined switching impulse"

    Conversioninto

    Classification of real stressClassification of real stress

    Combined impulse voltage having two components of equal peak value and opposite polarity. The

    positive component is a standard switching impulse and the negative one is a switching impulse

    whose times to peak and half value should not be less than those of the positive impulse. Bothimpulses should reach their peak values at the same instant. The peak value of the combined voltage

    is, therefore, the sum of the peak values of the components.

    Voltage Stress in Power Systems - Classification

  • 7/30/2019 Voltage Stress in Power Systems -

    10/29

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 10 -

    Temporary Overvoltages Earth Faults

    Reasons for temporary overvoltages: earth faults

    load rejection

    resonance phenomena

    In case of earth faults the overvoltage amplitudes depend on

    neutral earthing

    fault location.

    Important parameter: Earth fault factor kImportant parameter: Earth fault factor k

    LE

    b/ 3

    Uk

    U=... in other "words": ULE ... phase-to-earth voltage of sound phase during fault

    Ub ... phase-to-phase voltage at same location before fault

    IEC 60071-1

  • 7/30/2019 Voltage Stress in Power Systems -

    11/29

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 11 -

    Temporary Overvoltages Earth Faults

    The earth fault factor depends on the ratio of the complex impedances Z1 andZ0 of the positive and zero sequence systems (German: "Mitsystem",

    "Nullsystem"). In case of neglecting the resistances (possible in high-voltage

    systems) it depends on the ratio of the reactances X0 and X1:

    ( )2

    0 1 0 1

    0 1

    1 / /3

    2 /

    X X X Xk

    X X

    + +=

    +

    a ratio ofX0/X1 = -2 must be avoided!solidlyearth

    edneutral

    resonant earthedneutral,isolated neutral

    resonant earthedneutral,isolated neutral

    not forpractical use!

    according to [BAL-04]

  • 7/30/2019 Voltage Stress in Power Systems -

    12/29

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 12 -

    Temporary Overvoltages Earth Faults

    Treatment of neutral in Germany (VDEW, 1998):

    according to [BAL-04]

    treatment of neutral 10 kV 20 kV 110 kV 380 kV

    isolated 8.6% < 0.1% 0.0% 0.0%

    resonant earthed 77.8% 92.8% 80.9% 0.7%

    solidly earthed 13.6% 2.2% 19.1% 99.3%

    Earthing reactor (Petersen coil):

    fixed or switchable type

    Earthing reactor (Petersen coil):

    variable core type

    Pictures: VATech

    Caused by several recent blackouts it

    has been considered internationally to

    increasingly operate sub-transmission

    systems (Us

    170 kV) in the resonantearthed mode in order to increase

    reliability of power supply. [Information

    from a Cigr meeting in Frankfurt,

    October 2005]

    Caused by several recent blackouts it

    has been considered internationally to

    increasingly operate sub-transmission

    systems (Us 170 kV) in the resonant

    earthed mode in order to increase

    reliability of power supply. [Information

    from a Cigr meeting in Frankfurt,

    October 2005]

  • 7/30/2019 Voltage Stress in Power Systems -

    13/29

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 13 -

    Temporary Overvoltages Earth Faults

    Active part of a high-voltage reactor with variable core

    Fixed part of the core

    Drive

    Lead screw (the core is actually in 100% position)

    coremove

    ment

  • 7/30/2019 Voltage Stress in Power Systems -

    14/29

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 14 -

    Temporary Overvoltages Earth Faults

    Earth fault in case of isolated neutral system:

    according to [BAL-04]

  • 7/30/2019 Voltage Stress in Power Systems -

    15/29

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 15 -

    Temporary Overvoltages Earth Faults

    Earth fault in case of isolated neutral system:

    faultaccording to [BAL-04]

  • 7/30/2019 Voltage Stress in Power Systems -

    16/29

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 16 -

    Temporary Overvoltages Earth Faults

    Earth fault in case of isolated neutral system:

    fault clearing

    k= 2 due to capacitances of zero sequence system, charged to a direct voltage

    according to [BAL-04]

  • 7/30/2019 Voltage Stress in Power Systems -

    17/29

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 17 -

    Temporary Overvoltages Earth Faults

    Intermitting earth fault in case of isolated neutral system:new fault after initial fault clearing

    voltage offaulty phaseaccording to [BAL-04]

  • 7/30/2019 Voltage Stress in Power Systems -

    18/29

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 18 -

    Temporary Overvoltages Earth Faults

    Intermitting earth fault in case of isolated neutral system:new fault after initial fault clearing

    voltage ofsound phaseaccording to [BAL-04]

  • 7/30/2019 Voltage Stress in Power Systems -

    19/29

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 19 -

    Temporary Overvoltages Earth Faults

    Intermitting earth fault in case of isolated neutral system:

    voltage of the zero sequence systemaccording to [BAL-04]

  • 7/30/2019 Voltage Stress in Power Systems -

    20/29

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 20 -

    Temporary Overvoltages Earth Faults

    3 ... 2k

    1.4k

    1.4 1.8k<

  • 7/30/2019 Voltage Stress in Power Systems -

    21/29

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 21 -

    Temporary Overvoltages Load Rejection (Example 1)

    Example according to [ETG-93]

    Increase in generator

    voltage of 120%

    voltage increase on high-

    voltage side of generator

    transformer:from 380 kV 460 kV

    for 1.4 s duration!

    Increase in generator

    voltage of 120%

    voltage increase on high-

    voltage side of generator

    transformer:from 380 kV 460 kV

    for 1.4 s duration!

    Increase in frequency

    leads to repeated phase

    oppositions at the open

    circuit breaker for several

    minutes, see next slide

    Increase in frequency

    leads to repeated phase

    oppositions at the open

    circuit breaker for several

    minutes, see next slide

  • 7/30/2019 Voltage Stress in Power Systems -

    22/29

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 22 -

    Temporary Overvoltages Load Rejection (Example 1)

    Example according to [ETG-93]

    Phase opposition between open circuit breaker terminals stress of longitudinal insulationPhase opposition between open circuit breaker terminals stress of longitudinal insulation

  • 7/30/2019 Voltage Stress in Power Systems -

    23/29

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 23 -

    Temporary Overvoltages Load Rejection (Example 2)

    Example according to [DOR-81]

    1: Excitation by rotating rectifiers

    2: Constant excitation (manual regulation)

    Voltage increase by factor of 1.35;

    decrease to factor of 1.2 after 2 s.

    Voltage increase by factor of 1.35;

    decrease to factor of 1.2 after 2 s.

  • 7/30/2019 Voltage Stress in Power Systems -

    24/29

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 24 -

    Temporary Overvoltages Load Rejection (Example 3)

    TOV at the end of a long transmission lineTOV at the end of a long transmission line

    caused by capacitive currents

    can be controlled by parallel compensation

    e

    1cos

    aU

    U

    =

    Ue ... voltage at end of lineUa ... voltage at line entrance

    1

    1

    av

    =1 ... phase angle of the positive system

    1

    1 1

    1v

    L C

    =

    v1 ... phase velocity of the positive system

    [DOR-81]

    Not an issue for "normal"

    length transmission lines

    Not an issue for "normal"

    length transmission lines

  • 7/30/2019 Voltage Stress in Power Systems -

    25/29

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 25 -

    Temporary Overvoltages Load Rejection (Summary)

    Voltage increase factors due to load rejection:

    moderately extended systems: < 1.2 p.u. for up to several minutes

    widely extended systems: 1.5 p.u. for some seconds

    close to turbo generator: 1.3 p.u.

    close to salient pole (German: "Schenkelpol") generator: 1.5 p.u.

    Voltage increase factors due to load rejection:

    moderately extended systems: < 1.2 p.u. for up to several minutes

    widely extended systems: 1.5 p.u. for some seconds

    close to turbo generator: 1.3 p.u.

    close to salient pole (German: "Schenkelpol") generator: 1.5 p.u.

    Temporary overvoltages caused by load rejection depend on the rejected load

    the system layout after disconnection

    the characteristics of the sources (short-circuit power, generator type and regulation)

    Extremes:

    Low values of temporary overvoltages in systems with relatively short lines and highvalues of the short-circuit power at the terminal stations.

    High values of temporary overvoltages in systems with long lines and low values of short-circuit power at the generating side (= typical situation of extra-high voltage systems intheir initial stage).

  • 7/30/2019 Voltage Stress in Power Systems -

    26/29

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 26 -

    Temporary Overvoltages Resonance Phenomena

    Temporary overvoltages caused by resonance phenomena generally arise when circuitswith large capacitive elements, such as

    lines

    cables

    series compensated linesand inductive elements having non-linear magnetizing characteristics, such as

    transformers

    shunt reactors

    are energized, or as result of load rejections.

    Can easily be avoided by de-tuning the system from the resonance frequency!Can easily be avoided by de-tuning the system from the resonance frequency!

  • 7/30/2019 Voltage Stress in Power Systems -

    27/29

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 27 -

    Temporary Overvoltages Resonance Phenomena (Example 1)

    Energizing a transformer in a grid tuned to resonance at 3rd harmonics (150 Hz)Energizing a transformer in a grid tuned to resonance at 3rd harmonics (150 Hz)

    Grid tuned to 150 Hz TOV of 1.9 p.u. Grid tuned to (150 Hz 7%) TOV of 1.2 p.u.

    [DOR-81]

  • 7/30/2019 Voltage Stress in Power Systems -

    28/29

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 28 -

    Temporary Overvoltages Resonance Phenomena (Example 2)

    Load rejection with transformer in a grid tuned to resonance at 5th harmonics (250 Hz)Load rejection with transformer in a grid tuned to resonance at 5th harmonics (250 Hz) [DOR-81]

    length of line: a

    Length of line: 174 km fr= 250 Hz5th harmonics 33% TOV = 1.7 p.u.

    Length of line: 116 km fr= 300 Hz5th harmonics 10% TOV = 1. p.u.

  • 7/30/2019 Voltage Stress in Power Systems -

    29/29

    Fachgebiet

    HochspannungstechnikOvervoltage Protection and Insulation Coordination / Chapter 2 - 29 -

    Temporary Overvoltages and Surge Arresters

    Surge arresters cannot limit TOV!Exception: resonance effects may be suppressed or even avoided by MO arresters.

    Care has then to be taken not to thermally overload the arresters!

    Surge arresters cannot limit TOV!Exception: resonance effects may be suppressed or even avoided by MO arresters.

    Care has then to be taken not to thermally overload the arresters!

    0,8

    0,85

    0,9

    0,95

    1

    1,05

    1,1

    1,15

    1,2

    1,25

    1,3

    0,1 1 10 100 1000

    t / s

    ktov=

    U/Ur

    Time duration of (over-)voltage

    Possible voltages without arresters

    Voltages limited by arresters

    Withstand voltage of equipment

    Lightning overvoltages

    (Microseconds)

    Switching overvoltages

    (Milliseconds)

    Temporary overvoltages

    (Seconds)

    Highest voltage of equipment

    (Continuously)

    Magnitudeo

    f(over-)voltage

    /p.u.

    1

    2

    3

    4

    0

    5

    Time duration of (over-)voltage

    Possible voltages without arresters

    Voltages limited by arresters

    Withstand voltage of equipment

    Lightning overvoltages

    (Microseconds)

    Switching overvoltages

    (Milliseconds)

    Temporary overvoltages

    (Seconds)

    Highest voltage of equipment

    (Continuously)

    Magnitudeo

    f(over-)voltage

    /p.u.

    1

    2

    3

    4

    0

    5

    region of impressed voltage current develops according to

    U-I-characteristics

    region of impressed voltage current develops according toU-I-characteristics

    region of impressed current

    voltage develops according toU-I-characteristics

    region of impressed current

    voltage develops according toU-I-characteristics