Vlt6000 Hvac

  • View
    90

  • Download
    0

Embed Size (px)

Text of Vlt6000 Hvac

VLT Series Drives ServiceManual

VLT 4006 - 4072 VT, 380-460VVLT 4006 - 4032 VT, 200-240VVLT 4006 - 4072 VT, 550-600V

VLT 5001 - 5062, 380-500VVLT 5001 - 5027, 200-240VVLT 5001 - 5062, 550-600V

VLT 6002 - 6072, 380-460VVLT 6002 - 6032, 200-240VVLT 6002 - 6072, 550-600V

VLT 8006 - 8072 AQUA, 380-460VVLT 8006 - 8032 AQUA, 200-240VVLT 8002 - 8072 AQUA, 550-600V

Document Version 3.0

Table of ContentsIntroduction5ESD Precaution5Warnings6Tools Required6Product Overview7Enclosures7Component Cross-reference8Hardware Configurations9RFI Filter10Servicing10Description of Operation11Logic Section11Logic to Power Interface12Power Section13Intermediate Voltage Limits13Voltage and Current Values14Key Diagram15List of Warnings and Alarms16Warning and Alarm Descriptions17Ground Fault Trips23Overcurrent Trips24Overcurrent Trips: Unequal Phase to Ground Input Voltage24Overvoltage Trips: Regenerative Applications25AMA Faults26Input Phase Loss Trips27Output Phase Loss Trips27Troubleshooting28General Troubleshooting Tips28Troubleshooting Recommendations29Troubleshooting Flow Chart31Symptom/Cause Charts34

Table of Contents (continued)Static Test Procedures36Test Equipment Setup36Input Rectifier Testing37Soft Charge Circuit Testing38Inverter Testing39Dynamic Test Procedures40Output Phase Imbalance Testing40Gate Drive Firing Circuit Testing41Current Sensors Testing43Component Replacement Procedures44Control Card Removal and Replacement44Power Components Disassembly NEMA 1 (IP20)45Power Card Replacement45Power Card Mounting Plate Removal45Replacement of IGBT Modules NEMA 1 (IP20)46Power Components Replacement NEMA 12 (IP54)53Power Card Replacement NEMA 12 (IP54)53Replacement of ICBT Modules NEMA 12 (IP54)54Spare Parts List60Power Card Block Diagram63

4

Introduction

ESD Precaution

Electrostatic Discharge

The purpose of this manual is to provide technical information and instructions that will enable the user to identify f8iuIts and repair Danfoss VLT adjustable frequency drives. The following drive series and power ranges are addressed in this manual:

VLT 4006 - 4072, 380-460VVLT 4006 - 4032, 200- 240VVLT 4006 - 4072, 550-600V

VLT 500J 5062,380 500V VLT 500J- 5027,200-240V VLT 500J -5062,550-600V

VLT 6002 - 6072, 380-460VVLT 6002 - 6032, 200- 240VVLT 6002 6072, SEO 600V

VCT 8006 8O72 , 380460VVLT 8006 8032, 200 240VVLT 8002 8072, 550600V

This manual begins with the product overview and sequence of operations. Next fault messages cre defined along with suggested remedies. A troubleshooting section lists general tips and recommendations. A flow dicgrcm provides troubleshooting followed by symptoWcause charts. Tests and methods used to evaluate the dnves condition are described. Finally, the removal and replacement of the various components is covered.

Many electronic components are sensitive to static electricity. Voltages so low that they cannot be felt, seen or hecrd can reduce the life of, effect performance, or completely destroy sensitive electronic components.

When performing service, proper electrostatic discharge (ESD) procedures and equipment should be used to prevent possible damage from occurring.

Warnings

The Adjustable Frequency Drive (AFD) contains dangerous voltages when connected to the line voltage. Only a competent technician should carry out the service.

WARNING

For Your Safety

Tools Required

6

1) DO NOT touch the electncal pcrts of the drive when the AC line is connected. After the AC line is disconnected wait at least 15 minutes before touching any of the components (30 minutes for 600V units).

2) While repairs or inspection is made, the AC line must be disconnected.

3) The STOP key on the control panel does not disconnect the AC line.

4) During operation and programming of the parameters, the motor may startwithout warning. Activate the STOP key when ch8tnging data.

The following: tools will be sufficient to troubleshoot and repcir all units covered in this manual:

Digital multi- meter Clamp on cmmeter Analog voltmeterFlat head screw drivers Phillips screw driversTorx drivers - T1O, T15, T20, T27PliersTorque wrench Oscilloscope (optional)

Product Overview

Enclosures

Dcnfoss provides several models of drives designed for different applications.Operation and features have been configured for those application requirements.

VLT SOOO SeriesVLT SOOO Process is a general purpose, high performance drive designed for industrial applications. These drives ccn be used for constant torque or variable torque loads. They ccn be operated in open or closed loop, and speed or torque control modes. They are available in power sizes from 1 - 50 HP (200- 240V), 1 SOO H (380 500\/), and 1 250 HP (ISO 600V.

The VLT SOOO Flux is similar to the VLT SOOO Process, out it utilizes Flux Vector technology for applications requiring more precise speed regulation or faster response. The same power and voltage ranges are available cs the VL SOOO Process drive.

VLT 4000 VT SeriesThe VLT 4000 VT is designed for industnal pumping applications. They are available in power sizes of 5 - 60 HP (200- 240V), 5 - 600 HP (380-460VJ , and 5 - 300 HP (550-600V.

VLT 6000 SeriesThe VLT 6000 Series is a VT only drive for use in HVAC equipment. Available power sizes are 1 .5 - 60 HP (200- 240V) 1 .5 - 600 HP (380-460W , and 1.5 - 300 HP (550-600V).

VLT 8000 Aqua SeriesThe VLT 8000 Aqua Series serves the water and wastewater treatment market. Pnmanly designed for pumping applications, it is available in power ranges from 5- 6O HP (2O0- 240V), 5 - 600 HP (380-460, nd 5 - 300 HP (550-600 .

All models are avaiIaDIe with Compact Protected Chassis and NEMA 1 enclosures. They are also available in NEMA 12 enclosures, except in the 550-600V range. In addition, the VLT SOOO series is available in 1 - 10 HP 380- 500V or 1 - 5 HP 200- 240V in a Bookstyle" enclosure to enable optimum use of space when mounting the drives in a panel.hese units are narrow (3.54 to 5. 12 in.) and are able to be mounted side by side with no spacing required between units for cooling. This enables several units to be mounted in c relatively small crea within a panel

7

Component Cross-referenceMany of the VL models use the same power components as their counterpartsin the other VLT senes. A crossreference chart showing the various models and

ModelModelModelModelMin Volt5001200500260022005003600320050046004200500560052005006600680064006200500860088008400820050116011801 140112005016601680164016200502260228022402220050276027802740272005032603280324032200504260428042404220050526052805240522005062606280624062200their counterparts is shown below. 200V - 240V

380V - SOOV

ModelModelModelModelMin Volt

5001380

50026002380

50036003380

50046004380

50056005380

5006600680064006380

5008600880084008380

50116011801 14011380

5016601680164016380

5022602280224022380

5027602780274027380

5032603280324032380

5042604280424042380

5052605280524052380

5062606280624062380

5075607280724072380

5100610081004100380

5125612581254125380

5150615081504150380

5200617582004200380

5250622582504250380

5300627583004300380

5350635083504350380

5450640084504450380

SSOO650085004500380

SSSO655086004600380

Component Cross-reference (continued)

Hardware Configurations

SSOV - 600V

ModelModelModelModelMin Volt 500260028002ISO

500360038003ISO

500460048004ISO

500560058005ISO

5006600680064006ISO

5008600880084008ISO

5011601180114011ISO

5016601680164016ISO

5022602280224022ISO

5027602780274027ISO

5032603280324032ISO

5042604280424042ISO

5052605280524052ISO

5062606280624062ISO

5075607280724072ISO

5100610081004100ISO

5125612581254125ISO

5150615081504150ISO

5200617582004200ISO

5250622582504250ISO

627583004300ISO

The VLT 4000, 6000 and 8000 AQLIA units are avaiI8IDIe in the standard version only The VLT SOOO has three hardware configurations available for all sizes of drives: Standard (ST), Standard with Brake (SB), and Extended with Brake (EB). The SB and EB units contain all logic and hardware necessary to connect an ex1ernal resistor to provide dynamic braking.

The EB configuration offers connection terminals for load sharing capabilities between multiple VLT SOOO units plus input terminals for a remote 24 VDC power supply to maintain control logic during removal of the AC input power. Options are available for synchronizing and positioning.

RFI Filters

Servicing

In the VLT SOOO Series, RFI filtering is standard on all 1 - 10 HP, 380- 500V and 1- 5 H , 200-240V configurations and is available as a built-in option on all largermodels.

Because of the design of the lower power drives (5 HP and below, 200V, and 10 HP and below, 380-600V) it is not practical to perform repairs on these units in the field. The typical service transection in this case would be to exchange the entire unit.

Servicing for the larger models can De performed by replacing defective modules. It is recommended, due to the physical design, that the unit be removed from the installation or panel and placed on a suitable workbench prior to disassembly of the unit.

Description of Operation

Logic Section

The control ccrd contains most of the logic section. A microprocessor on the control card supervises 8IIl functions of the unit's oper8ltion. In add