Proven Solution The O'Brien VIPAK Draft Transmitter enclosure, is a field tested and proven solution addressing the common sources of draft transmitter installation error with: Still Air Chamber Atmospheric Equalization Uniform Capsule Temperature Pressure measurement in furnace and boiler combustion is critical for safety, efficiency and environmental control. The pressure is extremely low, often in the range of -1.0 to +2.0” H 2 O and installation problems that would normally be inconsequential can wreak havoc with draft range systems. Using a differential pressure transmitter the reference measurement is vented to atmosphere where air flowing past the open port creates pressure changes and errors in furnace, heater and boiler combustion box pressure. As part of the Safety Instrumented System these measurement errors can create nuisance maintenance and shutdowns affecting the entire unit. VIPAK ® ENCLOSURES for DRAFT RANGE TRANSMITTERS Low pressure draft range DP transmitters for furnace, heater and boiler control are problematic. They are affected by wind and weather changes. Many solutions have been attempted to ‘solve’ the problem but none have been universally successful until now. A large gulf coast refinery was experiencing furnace upsets and shutdowns caused by storms and wind in the unit. They installed two O'Brien Draft Transmitter Enclosures on their most trouble prone units as a trial. After a severe storm hit and the units with the O'Brien Draft Transmitter enclosures ran with no problems they installed another 128 protection enclosures. To date there have been no more upsets or shutdowns caused by wind induced measurement errors. The O'Brien STILL AIR PORT is an integral part of the draft range transmitter solution. PAT. PEND. The O'Brien VIPAK draft range transmitter enclosure atmospherically equalizes the still air chamber for the transmitter and manifold. The pressure inside the enclosure changes at the same rate as the barometric pressure but is unaffected by wind or wind gusts. The enclosure system also ensures that both sides of the instrument measurement capsule are at the same temperature. Since these instruments are often placed near the furnace, heater or boiler one side can be hotter than the other creating an error in measurement.

VIPAK ENCLOSURES for DRAFT RANGE TRANSMITTERS · 2020-03-02 · • Uniform Capsule Temperature Pressure measurement in furnace and boiler combustion is critical for safety, efficiency

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: VIPAK ENCLOSURES for DRAFT RANGE TRANSMITTERS · 2020-03-02 · • Uniform Capsule Temperature Pressure measurement in furnace and boiler combustion is critical for safety, efficiency

ww

w.o

bcorp.com

STA

TIC

AIR

PO

RT

PAT. PEND.

Proven Solution

The O'Brien VIPAK Draft Transmitter enclosure, is a field tested and proven solution addressing the common sources of draft transmitter installation error with:

• Still Air Chamber

• Atmospheric Equalization

• Uniform Capsule Temperature

Pressure measurement in furnace and boiler combustion is critical for safety, efficiency and environmental control. The pressure is extremely low, often in the range of -1.0 to +2.0” H2O and installation problems that would normally be inconsequential can wreak havoc with draft range systems.

Using a differential pressure transmitter the reference measurement is vented to atmosphere where air flowing past the open port creates pressure changes and errors in furnace, heater and boiler combustion box pressure. As part of the Safety Instrumented System these measurement errors can create nuisance maintenance and shutdowns affecting the entire unit.

VIPAK® ENCLOSURES for DRAFT RANGE TRANSMITTERS

Low pressure draft range DP transmitters for furnace, heater and boiler control are problematic. They are affected by wind and

weather changes. Many solutions have been attempted to ‘solve’ the problem but none have been universally successful until now.

A large gulf coast refinery was experiencing furnace upsets and shutdowns caused by storms and wind in the unit. They installed

two O'Brien Draft Transmitter Enclosures on their most trouble prone units as a trial.

After a severe storm hit and the units with the O'Brien Draft Transmitter enclosures ran with no problems they installed another

128 protection enclosures.

To date there have been no more upsets or shutdowns caused by wind induced measurement errors.

The O'Brien STILL AIR PORT is an integral part of the draft range transmitter solution.

PAT. PEND.

The O'Brien VIPAK draft range transmitter enclosure atmospherically equalizes the still air chamber for the transmitter and manifold. The pressure inside the enclosure changes at the same rate as the barometric pressure but is unaffected by wind or wind gusts.

The enclosure system also ensures that both sides of the instrument measurement capsule are at the same temperature. Since these instruments are often placed near the furnace, heater or boiler one side can be hotter than the other creating an error in measurement.

Page 2: VIPAK ENCLOSURES for DRAFT RANGE TRANSMITTERS · 2020-03-02 · • Uniform Capsule Temperature Pressure measurement in furnace and boiler combustion is critical for safety, efficiency

Internal Static Air BaffleSome specifications require a static air baffle mounted directly to the ambient sensing port of the transmitter. O'Brien offers two standard units:

Order: BDT6 Internal manifold mounted static filter, replaces the compression nut and ferrules of a customer supplied 3/8" tube fitting. Equalization 0.07 ft3/hr Rated for 11.4 mph wind speed.

Order: AMCSAPPSS Internal manifold mounted static filter. Attaches to customer supplied 1/2" NPT threaded connection.Rated for 11.4 mph wind speed.

Electric HeatersFor cold temperature installations or wet sample applications enclosure heaters may be added as well as heat traced or insulated impulse tubing.

For Single EnclosuresOrder: TS3115D2CJS1H 120V 150W CL I, Div 2 Gp ABCD FM/CSA heater protects down to -40°F/°C

For Polling EnclosureOrder: TE3130D2CJS1H 120V 300W CL I, Div 2 Gp ABCD FM/CSA heater protects down to -40°F/°C

Order: IPK1 Instrument power/signal connection kit. Suitable for use in CL I, Div 2 areas.

Heat traced and Insulated Impulse LinesFor electric traced or pre-insulated impulse lines consult local repre-sentative or factory and order S-Line tubing or TRACEPAK bundle with TPKES-4S heat shrink entry seal.

Accessories are ordered separately and easily fitted to the enclosure package.

ACCESSORIES

Page 3: VIPAK ENCLOSURES for DRAFT RANGE TRANSMITTERS · 2020-03-02 · • Uniform Capsule Temperature Pressure measurement in furnace and boiler combustion is critical for safety, efficiency

C Style: For retrofit applications this enclosure positions the transmitter in the same position as before and uses the same 2" mounting pipe only shortened.

Order: C31-19137

A

A

11990000 CCRRYYSSTTAALL IINNDD.. CCOOUURRTT SSTT.. LLOOUUIISS,, MMIISSSSOOUURRII 6633111144PPHH 331144--442233--44444444 WWWWWW..OOBBCCOORRPP..CCOOMM

AA11TT--1199113388

77""--

99..55""

AADDJJUUSSTTAABBLLEE

1199""

1177""

1155"" MMAAXX

1155""

IINNSSIIDDEE EENNCCLLOOSSUURREE

1188..55""

IINNSSIIDDEE EENNCCLLOOSSUURREE

DRAWN BY:

APPROVAL:

MATERIAL:

CHECKED:

DATE:

REV DATE

DRAWING NO.

RECORD

SCALE REV

BY

11990000 CCRRYYSSTTAALL IINNDD.. CCOOUURRTT SSTT.. LLOOUUIISS,, MMIISSSSOOUURRII 6633111144PPHH 331144--442233--44444444 WWWWWW..OOBBCCOORRPP..CCOOMM

CC3311--1199113377

TTHHIIRRDD AANNGGLLEE

PPRROOJJEECCTTIIOONN

UUNNLLEESSSS OOTTHHEERRWWIISSEE NNOOTTEEDD..AALLLL DDIIMMEENNSSIIOONNSS AARREE IINN IINNCCHHEESS

A

A

1111""

1188""

1133""

77""

1111""

A Style: Convenient diagonal opening with rail mounting and universal transmitter mount brackets. It also includes a pass-through grommet for the process connection.

Order: A1T-19138

SINGLE TRANSMITTER ENCLOSURES

Page 4: VIPAK ENCLOSURES for DRAFT RANGE TRANSMITTERS · 2020-03-02 · • Uniform Capsule Temperature Pressure measurement in furnace and boiler combustion is critical for safety, efficiency

© 2016, by AMETEK, Inc. All rights reserved • APP-DRAFTTRANS-NP • 9 SEPT 2016

BELGIUM • BRAZIL • CHINA • RUSSIA • SINGAPORE • SOUTH KOREA • [email protected] • www.obcorp.com

TRIPLE TRANSMITTER ENCLOSURE

Triple Mount Poling EnclosureThree transmitters in a single enclosure. Individual rail mounting with universal transmitter mount brackets. Three pass-through grommets for individual process connections.

Order: A3T3-19139

APPROVAL:

MATERIAL:

CHECKED:

DRAWING NO.SCALE REV

..XX `̀ ..0033

..XXXX `̀ ..0011

..XXXXXX `̀ ..000022

FFRRAACCTTIIOONNSS `̀11//3322

BBRREEAAKK SSHHAARRPP EEDDGGEESS ..0011

AANNGGUULLAARR `̀11//22°°

A

A

2288""

IINNSSIIDDEE EENNCCLLOOSSUURREE

3300""

1155"" MMAAXX

1199""

77""--

99..55""

AADDJJUUSSTTAABBLLEE

1188..55""

IINNSSIIDDEE EENNCCLLOOSSUURREE

PAT. PEND.

The O'Brien draft transmitter enclosure solution is not only field tested but we also tried to upset the pressure balance

with an 80 - 90mph wind load up close and at all angles. There was no fluctuation in the differential pressure.

Custom ConfigurationsIf the standard enclosure configurations do not meet your installation requirements your local representative can help you create a custom configuration including flange mounted units.