VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 James J. Murphy, Jr. Vice Chairman The Connecticut Siting Council Ten Franklin Square New Britain, CT 06051 Re: The United Illuminating Company’s Notice of Exempt Modification Pursuant to R.C.S.A. § 16-50j-58 to Existing Energy Facility Site between Pequonnock Substation in Bridgeport and Sasco Creek Substation in Westport (“Notice of Exempt Modification”) Dear Vice Chairman Murphy: Pursuant to Regulations of Connecticut State Agencies (“R.C.S.A.”) §16-50j-58, The United Illuminating Company (“UI” ) hereby notifies the Connecticut Siting Council (the “Council”) of its intent to make exempt modifications (the “Project”) to its transmission line along the Metro- North Railroad corridor (“Railroad Corridor”) from Pequonnock Substation in Bridgeport to Ash Creek Substation in Fairfield interconnecting with The Connecticut Light and Power Company d//b/a Eversource Energy’s (“Eversource”) Sasco Creek Substation in Westport (“Facility” or “Energy Facility”). The $625 filing fees, along with 2 copies of this Notice of Exempt Modification, are enclosed herewith. Existing Energy Facility The Facility begins at Pequonnock Substation in the City of Bridgeport at 41°10′20" and Λ 73°11′06" and proceeds in a westerly direction approximately 3.75 miles along the Railroad Corridor to Ash Creek Substation at 41°09′23" and Λ 73°14′03" continuing westerly an additional 5.27 miles interconnecting with Eversource’s Sasco Creek Substation at 41°07′27" and Λ 73°18′29": The existing Facility consists of a FOCAS Skylite 12 fiber Optical Ground Wire (OPGW) completed in 1994. This Facility provides communications and lightning protection for UI’s and Eversource’s 115 kV transmission lines and are installed on bonnet extensions on top of the Metro-North catenary system from Pequonnock Substation to Metro-North Catenary # 737 (41°10'20.58"N and Λ 73°11'6.62"W). At this point the Facility is erected on single circuit monopole structures installed within the Railroad Corridor continuing westerly to Eversource’s Sasco Creek Substation. James M. Yeske, Jr., Manager, Electric Capital Line Projects 180 Marsh Hill Road, Orange, CT 06477 Telephone 888.UITENYR, Fax 203.926.4664 www.uinet.com An equal opportunity employer

VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin

VIA FEDEX AND ELECTRONIC MAIL

March 5, 2019

James J. Murphy, Jr. Vice Chairman The Connecticut Siting Council Ten Franklin Square New Britain, CT 06051

Re: The United Illuminating Company’s Notice of Exempt Modification Pursuant to R.C.S.A. § 16-50j-58 to Existing Energy Facility Site between Pequonnock Substation in Bridgeport and Sasco Creek Substation in Westport (“Notice of Exempt Modification”)

Dear Vice Chairman Murphy:

Pursuant to Regulations of Connecticut State Agencies (“R.C.S.A.”) §16-50j-58, The United Illuminating Company (“UI” ) hereby notifies the Connecticut Siting Council (the “Council”) of its intent to make exempt modifications (the “Project”) to its transmission line along the Metro-North Railroad corridor (“Railroad Corridor”) from Pequonnock Substation in Bridgeport to Ash Creek Substation in Fairfield interconnecting with The Connecticut Light and Power Company d//b/a Eversource Energy’s (“Eversource”) Sasco Creek Substation in Westport (“Facility” or “Energy Facility”). The $625 filing fees, along with 2 copies of this Notice of Exempt Modification, are enclosed herewith.

Existing Energy Facility

The Facility begins at Pequonnock Substation in the City of Bridgeport at 41°10′20"𝑁𝑁 and Λ 73°11′06"𝑊𝑊 and proceeds in a westerly direction approximately 3.75 miles along the Railroad Corridor to Ash Creek Substation at 41°09′23"𝑁𝑁 and Λ 73°14′03"𝑊𝑊 continuing westerly an additional 5.27 miles interconnecting with Eversource’s Sasco Creek Substation at 41°07′27"𝑁𝑁 and Λ 73°18′29"𝑊𝑊:

The existing Facility consists of a FOCAS Skylite 12 fiber Optical Ground Wire (OPGW) completed in 1994. This Facility provides communications and lightning protection for UI’s and Eversource’s 115 kV transmission lines and are installed on bonnet extensions on top of the Metro-North catenary system from Pequonnock Substation to Metro-North Catenary # 737 (41°10'20.58"N and Λ 73°11'6.62"W). At this point the Facility is erected on single circuit monopole structures installed within the Railroad Corridor continuing westerly to Eversource’s Sasco Creek Substation.

James M. Yeske, Jr., Manager, Electric Capital Line Projects

180 Marsh Hill Road, Orange, CT 06477 Telephone 888.UITENYR, Fax 203.926.4664 www.uinet.com

An equal opportunity employer

Page 2: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin

Aerial Photos of the Facilities

UI’s Pequonnock Substation - Google Earth 2/23/19

UI’s Ash Creek Substation - Google Earth 2/23/19

Page 3: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin

Eversource’s Sasco Creek Substation - Google Earth 2/23/19

GIS Photo of the Facility

1130/1430 Fiber Route Pequonnock-Ash Creek-Sasco Creek - Google Earth 2/23/19

Page 4: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin

Existing Site and Equipment

Typical Bonnet Mounted OPGW & Splice Can L753 – August 5, 2019 Inspection

Typical Bonnet Mounted OPGW & Splice Can L753 – August 5, 2019 Inspection

Page 5: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin

Typical Pole Mounted OPGW & Splice Can L704N – August 5, 2018 Inspection

Proposed Modifications UI is proposing to replace the existing FOCAS Skylite 12 OPGW (See Attachment B for existing OPGW Cut Sheet) with a new Prysmian 64K78s 48 fiber OPGW (See Attachment C for proposed OPGW Cut Sheet). This replacement is due to fiber communication issues associated with loss of signal, fiber breaks, lack of spare fibers and intermittent signal failure. This OPGW is critical for the reliable operation of UI’s and Eversource’s transmission system. These fibers are used to monitor and control the 1130, 1430, and 91001 Lines primary relaying, UI’s and Eversource’s Jungle MUX, UI’s Corporate Network, UI’s Supervisory Control and Data Acquisition Network, Advanced Metering Infrastructure communications, and Ash Creek Substation’s telecommunications system. As the Project relates solely to improving system maintenance, the modifications will not impact the existing Facility’s structural capability or impact electric and magnetic fields or noise levels.

Page 6: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin

OPGW Inspection – December 8, 2018

Page 7: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin

Compliance with R.C.S.A. § 16-50j-57(b) Pursuant to R.C.S.A. §16-50j-57(b), the Project does not constitute a modification to an existing facility that may have a substantial adverse environmental effect and are exempt from the requirement to obtain a certificate pursuant to Section 16-50k of the Connecticut General Statutes. Specifically, consistent with R.C.S.A. § 16-50j-57(b), the proposed changes to the existing site do not:

(A) Extend the boundaries of the site beyond the existing right-of-way; (B) Increase the height of existing associated equipment; (C) Increase noise levels along the right-of-way by six decibels or more, or to levels that

exceed state and local criteria; (D) Impact electric and magnetic field levels along the right-of-way in a manner that is

inconsistent with the Council’s Best Management practices for Electric and Magnetic Fields;

(E) Cause a significant adverse change or alteration in the physical or environmental characteristics of the right-of-way; or

(F) Impair the structural integrity of the facility, as determined in a certification provided by a professional engineer licensed in Connecticut, where applicable.

The Project would not have a substantial adverse environmental effect or cause a significant adverse change or alteration in the physical or environmental characteristics because:

(A) The Project would be located within the transmission line’s existing right-of-way; the right-of-way area would not be expanded;

(B) The equipment would be no taller than existing equipment within the right-of-way; (C) There would be no change to the existing television or radio interference resulting

from the modifications of the transmission line; (D) Sound-pressure levels at all points along properties lines would continue to meet

state regulations set out in R.C.S.A. §§ 22a-69-1 et seq.; (E) The project work would not affect water resource areas. (F) UI’s review of the Connecticut Department of Energy and Environmental

Protection’s Natural Diversity Data Base did not identify any state-listed endangered, threatened, or special concern species in the vicinity of the Project; and

(G) Electric and Magnetic field levels along the transmission line will not change as a result of the Project.

Page 8: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin

UI intends to initiate the Project on or after the Council’s acknowledgement that the proposed activities are exempt.

Please do not hesitate to contact me at 203-988-9746 should you have any questions regarding this notice.

Very truly yours,

James M. Yeske Jr. Manager – Electric Capital Line Projects The United Illuminating Company

cc: The Honorable Joseph P. Ganim Mayor, City of Bridgeport The Honorable Mike Tetreau, First Selectman, Town of FairfieldThe Honorable Jim Marpe, First Selectman, Town of WestportKathleen M. Shanley, Manager – Transmission Siting, Eversource EnergyChristopher Soderman, Engineering Manager, Eversource EnergyAmy Hicks, The United Illuminating Company, Public Outreach

Enclosures

Attachment A – Design Drawings

Attachment B – Existing FOCUS Skylite OPGW Cut Sheet

Attachment C – Proposed Prysmian OPGW Cut Sheet

Attachment D - Structure Load Comparison

Page 9: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin

Attachment A

Page 10: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin
Page 11: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin
Page 12: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin
Page 13: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin
Page 14: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin
Page 15: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin
Page 16: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin
Page 17: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin
Page 18: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin
Page 19: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin
Page 20: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin
Page 21: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin
Page 22: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin
Page 23: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin
Page 24: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin
Page 25: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin
Page 26: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin
Page 27: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin

Attachment B

Page 28: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin
Page 29: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin
Page 30: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin
Page 31: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin

Attachment C

Page 32: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin

OPGW 64K78s Ref: 7540usa

Rev.05 Issued by: L. Roldán 25-jul-14 page 1 of 3

PRYSMIAN GROUP, All Rights Reserved. Prysmian Group reserves the right to amend this specification without prior notice.

OPTICAL GROUND WIRE

with capacity for 48 optical fibres

Cable structure

Optical core

[1] Optical fibres [2] PBT loose buffer tubes. Ø = 0.098 in

[3] Pultrusioned threaded glass rod [4] Hydrogen absorbent jelly

Aluminium Tube

[5] Ø = 0.433 in

Armour

Layer 1 (S):

[6] 15 ACS 20.3% IACS Ø 0.1071 in

In areas where there is a high contamination or in

the proximity of the sea, Prysmian recommend greasing the cable.

Features and benefits

This cable has been custom designed to best match with

customer requirements from optical, electrical, mechanical, quality and cost point of view, optimising

diameter, weight, breaking load and short circuit capacity.

Cable characteristics

Mechanical and physical Approximate cable diameter: 0.647 in

Approximate cable weight: 0.524 lb/ft

Rated tensile strength: 25000 lbf

Maximum cable design tension: 20000 lbf

Elasticity Modulus*: 16549 kpsi

Section*: 0.223 in2

Linear expansion thermal coefficient: 8.11x10-6 ºF-1

Minimum bending radius:

On pulley blocks (first and last of each reel,

span ≥ 600 m or angles > 15º): 15.75 in

On pulley blocks (others): 11.81 in

On tensioner devices: 25.59 in

After clamping (slack cable): 11.81 in

Operating temperature range: from -40ºF to +176ºF

*for stress-strain calculus

**see "Installation procedures for OPGW fibre optic cable" document reference SIG-07-PE-PA-013

Electrical Short circuit rating from 40ºC: 153.8 kA2s

Short circuit current for 1 s: 12.4 kA

Geometric Mean Radius: 0.233 in

DC Resistance at 20ºC: 0.56 /mil

DC Resistance at 25ºC: 0.57 /mil

DC Resistance at 50ºC: 0.63 /mil

DC Resistance at 75ºC: 0.68 /mil

AC Resistance at 20ºC: 0.57 /mil

AC Resistance at 25ºC: 0.58 /mil

AC Resistance at 50ºC: 0.64 /mil

AC Resistance at 75ºC: 0.70 /mil

60 Hz Inductive Reactance (1 ft): 0.48 /mil

PLSCADD coefficients (American units)

A0 A1 A2 A3 A4

9.46 158319 40992 -172929 85240

-144.65 124843 65318 -142293 57290

[5]

[6]

[1] [2]

[3]

[4]

Page 33: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin

OPGW 64K78s Ref: 7540usa

Rev.05 Issued by: L. Roldán 25-jul-14 page 2 of 3

PRYSMIAN GROUP, All Rights Reserved. Prysmian Group reserves the right to amend this specification without prior notice.

OPTICAL GROUND WIRE

with capacity for 48 optical fibres

Fiber identification

No. 1 2 3 4 5 6

Color Blue Orange Green Brown Slate White

No. 7 8 9 10 11 12

Color Red Black Yellow Violet Pink Aqua

Tube identification

No. 1 2 3 4

Color Blue Orange Green Brown

48 G.652D:

Fiber G.652D: Tubes #1, #2, #3 and #4

24G.655 + 24 G.652D:

Fiber G.655: Tubes #1 and #2

Fiber G.652D: Tubes #3 and #4

Fibre characteristics Fiber manufacturer: FOS (Prysmian Group)

According to ITU-T G.652D or ITU-T G.655

ITU-T G.652D Attenuation coefficients (uncabled)

at 1310 nm 0.35 dB/km

at 1385 nm 0.35 dB/km

at 1550 nm 0.20 dB/km

at 1625 nm 0.23 dB/km

Mode Field Diameter

at1310 nm 9.2 ± 0.4 µm

at1550 nm 10.4 ± 0.5 µm

Geometrical properties

Cladding diameter 125 ± 7 µm

Cladding non-circularity ≤1 %

Core – cladding concentricity error

≤0.6 µm

Coating diameter 245 ± 5 µm

Coating – cladding concentricity error

≤12 µm

Dispersion coefficients

from 1285 to 1330 nm 3.5 ps/(nm·km)

at 1550 nm 18 ps/(nm·km)

Cable Cut-off

Cable Cut-off <1260 λcc nm

Zero dispersion wavelenght 1302 – 1322 nm

ITU-T G.655 Attenuation coefficients (uncabled)

at 1550 nm 0.23 dB/km

at 1625 nm 0.25 dB/km

Mode Field Diameter

at1550 nm 9.6 ± 0.4 µm

Geometrical properties

Cladding diameter 125 ± 0.7 µm

Cladding non-circularity ≤1 %

Core – cladding concentricity error

≤0.5 µm

Coating diameter 245 ± 5 µm

Coating – cladding concentricity error

≤10 µm

Dispersion coefficients

from 1530 to 1565 nm 2.0÷6.0 ps/(nm·km)

In the range 1565-1625 nm 4.5÷11.2 ps/(nm·km)

Cable Cut-off

Cable Cut-off <1450 λcc nm

Routine tests 100% of optical fibres will be measured by OTDR

technique before leaving factory.

Installation procedure

Prysmian recommends to install the cable described in

this specification following the latest version of our "Installation procedures for OPGW fibre optic cable"

reference SIG-07-PE-PA-013, "Instruction for the installation of the EWMJ joint box" reference SIG-07-PE-

PA-015 and "Instruction for the installation of the EWJ

joint box" reference SIG-07-PE-PA-008.

Page 34: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin

OPGW 64K78s Ref: 7540usa

Rev.05 Issued by: L. Roldán 25-jul-14 page 3 of 3

PRYSMIAN GROUP, All Rights Reserved. Prysmian Group reserves the right to amend this specification without prior notice.

OPTICAL GROUND WIRE

with capacity for 48 optical fibres

Reels Type N Type P

Wheel (A): 66.9 in 82.7 in

Cylinder (B): 35.4 in 35.4 in

Inside (C): 35.4 in 35.4 in

Outside (D): 41.3 in 41.3 in

Axe (H): 4.13 in 4.13 in

Weight:

- empty: 604 lb 877 lb

- full: 7826 lb 13087 lb

Maximum length: 13780 ft 23290 ft

Tolerance length of the produced reel: ±3%

NOTE: Ordered lengths should include a distribution of lengths, i.e., all reels cannot be ordered at the maximum.The reel lengths’ distribution should be as follows:

Reel lengths

0 - 8200 More than 5%

8200 - 14800 More than 30%

14800 - 19700 Less than 55%

> 19700 Less than 10%

Page 35: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin

Attachment D

Page 36: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin

Str No Load Case DescriptionHorizontal Load (lb/ft)

Vertical Load

(lb/ft)

Horizontal Tension (lb)

Str NoLoad Case

DescriptionHorizontal Load (lb/ft)

Vertical Load (lb/ft)

Horizontal Tension (lb)

Pertcent Change

Horizontal Load

Pertcent Change Vertical

Load

Change is Tension

(lb)

GDI_0002 NESC Heavy NA+ 1.37 1.85 5613 GDI_0002 NESC Heavy NA+ 1.36 1.9 8634 1% -3% -3021B768A NESC Heavy NA+ 2.74 3.7 290 B768A NESC Heavy NA+ 2.72 3.8 1893 1% -3% -1603B767N NESC Heavy NA+ 2.74 3.7 56 B767N NESC Heavy NA+ 2.72 3.8 376 1% -3% -320B766N NESC Heavy NA+ 2.74 3.7 7 B766N NESC Heavy NA+ 2.72 3.8 186 1% -3% -179B765CN NESC Heavy NA+ 2.74 3.7 8 B765CN NESC Heavy NA+ 2.72 3.8 1501 1% -3% -1493B765BN NESC Heavy NA+ 2.74 3.7 4 B765BN NESC Heavy NA+ 2.72 3.8 140 1% -3% -136B765AN NESC Heavy NA+ 2.74 3.7 14 B765AN NESC Heavy NA+ 2.72 3.8 295 1% -3% -281B765N NESC Heavy NA+ 2.74 3.7 0 B765N NESC Heavy NA+ 2.72 3.8 423 1% -3% -423B764N NESC Heavy NA+ 2.74 3.7 0 B764N NESC Heavy NA+ 2.72 3.8 732 1% -3% -732B763N NESC Heavy NA+ 2.74 3.7 172 B763N NESC Heavy NA+ 2.72 3.8 401 1% -3% -229B762N NESC Heavy NA+ 2.74 3.7 128 B762N NESC Heavy NA+ 2.72 3.8 1099 1% -3% -971B761N NESC Heavy NA+ 2.74 3.7 385 B761N NESC Heavy NA+ 2.72 3.8 1948 1% -3% -1563B760N NESC Heavy NA+ 2.74 3.7 0 B760N NESC Heavy NA+ 2.72 3.8 59 1% -3% -59B759N NESC Heavy NA+ 2.74 3.7 2 B759N NESC Heavy NA+ 2.72 3.8 39 1% -3% -37B758N NESC Heavy NA+ 2.74 3.7 1 B758N NESC Heavy NA+ 2.72 3.8 169 1% -3% -168B757N NESC Heavy NA+ 2.74 3.7 458 B757N NESC Heavy NA+ 2.72 3.8 3686 1% -3% -3228TP756N NESC Heavy NA+ 2.74 3.7 136 TP756N NESC Heavy NA+ 2.72 3.8 6466 1% -3% -6330TP754N NESC Heavy NA+ 2.74 3.7 245 TP754N NESC Heavy NA+ 2.72 3.8 3557 1% -3% -3312B753N NESC Heavy NA+ 2.74 3.7 241 B753N NESC Heavy NA+ 2.72 3.8 1266 1% -3% -1025B752N NESC Heavy NA+ 2.74 3.7 2 B752N NESC Heavy NA+ 2.72 3.8 222 1% -3% -220B751N NESC Heavy NA+ 2.74 3.7 0 B751N NESC Heavy NA+ 2.72 3.8 727 1% -3% -727B750N NESC Heavy NA+ 2.74 3.7 0 B750N NESC Heavy NA+ 2.72 3.8 40 1% -3% -40B749N NESC Heavy NA+ 2.74 3.7 3 B749N NESC Heavy NA+ 2.72 3.8 162 1% -3% -159B748N NESC Heavy NA+ 2.74 3.7 1 B748N NESC Heavy NA+ 2.72 3.8 269 1% -3% -268B747N NESC Heavy NA+ 2.74 3.7 2 B747N NESC Heavy NA+ 2.72 3.8 56 1% -3% -54B746N NESC Heavy NA+ 2.74 3.7 1 B746N NESC Heavy NA+ 2.72 3.8 354 1% -3% -353B745N NESC Heavy NA+ 2.74 3.7 3 B745N NESC Heavy NA+ 2.72 3.8 1364 1% -3% -1361B744N NESC Heavy NA+ 2.74 3.7 4 B744N NESC Heavy NA+ 2.72 3.8 413 1% -3% -409B743N NESC Heavy NA+ 2.74 3.7 1 B743N NESC Heavy NA+ 2.72 3.8 326 1% -3% -325B742N NESC Heavy NA+ 2.74 3.7 1 B742N NESC Heavy NA+ 2.72 3.8 161 1% -3% -160B741N NESC Heavy NA+ 2.74 3.7 1 B741N NESC Heavy NA+ 2.72 3.8 9 1% -3% -8B740N NESC Heavy NA+ 2.74 3.7 1 B740N NESC Heavy NA+ 2.72 3.8 29 1% -3% -28B739N NESC Heavy NA+ 2.74 3.7 495 B739N NESC Heavy NA+ 2.72 3.8 356 1% -3% 139GDI_0035 NESC Heavy NA+ 2.74 3.7 115 GDI_0035 NESC Heavy NA+ 2.72 3.8 669 1% -3% -554B738N NESC Heavy NA+ 2.74 3.7 292 B738N NESC Heavy NA+ 2.72 3.8 45 1% -3% 247B737N NESC Heavy NA+ 2.74 3.7 235 B737N NESC Heavy NA+ 2.72 3.8 658 1% -3% -423736EN NESC Heavy NA+ 2.74 3.7 444 736EN NESC Heavy NA+ 2.72 3.8 441 1% -3% 3TP735N NESC Heavy NA+ 2.74 3.7 88 TP735N NESC Heavy NA+ 2.72 3.8 1245 1% -3% -1157TP734N NESC Heavy NA+ 2.74 3.7 166 TP734N NESC Heavy NA+ 2.72 3.8 1466 1% -3% -1300733WN NESC Heavy NA+ 2.74 3.7 263 733WN NESC Heavy NA+ 2.72 3.8 1085 1% -3% -822732WN NESC Heavy NA+ 2.74 3.7 140 732WN NESC Heavy NA+ 2.72 3.8 949 1% -3% -809

PRYSMIAN (New OPGW) FOCUS (Existing OPGW)

Page 37: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin

Str No Load Case DescriptionHorizontal Load (lb/ft)

Vertical Load

(lb/ft)

Horizontal Tension (lb)

Str NoLoad Case

DescriptionHorizontal Load (lb/ft)

Vertical Load (lb/ft)

Horizontal Tension (lb)

Pertcent Change

Horizontal Load

Pertcent Change Vertical

Load

Change is Tension

(lb)

PRYSMIAN (New OPGW) FOCUS (Existing OPGW)

731WN NESC Heavy NA+ 2.74 3.7 125 731WN NESC Heavy NA+ 2.72 3.8 56 1% -3% 69730EN NESC Heavy NA+ 2.74 3.7 236 730EN NESC Heavy NA+ 2.72 3.8 165 1% -3% 71729WN NESC Heavy NA+ 2.74 3.7 108 729WN NESC Heavy NA+ 2.72 3.8 108 1% -3% 0728WN NESC Heavy NA+ 2.74 3.7 7 728WN NESC Heavy NA+ 2.72 3.8 298 1% -3% -291727WN NESC Heavy NA+ 2.74 3.7 2 727WN NESC Heavy NA+ 2.72 3.8 577 1% -3% -575726WN NESC Heavy NA+ 2.74 3.7 0 726WN NESC Heavy NA+ 2.72 3.8 53 1% -3% -53725WN NESC Heavy NA+ 2.74 3.7 1 725WN NESC Heavy NA+ 2.72 3.8 267 1% -3% -266724WN NESC Heavy NA+ 2.74 3.7 22 724WN NESC Heavy NA+ 2.72 3.8 187 1% -3% -165723WN NESC Heavy NA+ 2.74 3.7 25 723WN NESC Heavy NA+ 2.72 3.8 254 1% -3% -229722WN NESC Heavy NA+ 2.74 3.7 58 722WN NESC Heavy NA+ 2.72 3.8 250 1% -3% -192721EN NESC Heavy NA+ 2.74 3.7 93 721EN NESC Heavy NA+ 2.72 3.8 30 1% -3% 63720EN NESC Heavy NA+ 2.74 3.7 83 720EN NESC Heavy NA+ 2.72 3.8 233 1% -3% -150719WN NESC Heavy NA+ 2.74 3.7 95 719WN NESC Heavy NA+ 2.72 3.8 394 1% -3% -299718WN NESC Heavy NA+ 2.74 3.7 4 718WN NESC Heavy NA+ 2.72 3.8 598 1% -3% -594717WN NESC Heavy NA+ 2.74 3.7 2 717WN NESC Heavy NA+ 2.72 3.8 117 1% -3% -115716WN NESC Heavy NA+ 2.74 3.7 1 716WN NESC Heavy NA+ 2.72 3.8 170 1% -3% -169715WN NESC Heavy NA+ 2.74 3.7 3 715WN NESC Heavy NA+ 2.72 3.8 946 1% -3% -943714WN NESC Heavy NA+ 2.74 3.7 31 714WN NESC Heavy NA+ 2.72 3.8 1851 1% -3% -1820713WN NESC Heavy NA+ 2.74 3.7 12 713WN NESC Heavy NA+ 2.72 3.8 91 1% -3% -79712WN NESC Heavy NA+ 2.74 3.7 30 712WN NESC Heavy NA+ 2.72 3.8 16 1% -3% 14711WN NESC Heavy NA+ 2.74 3.7 86 711WN NESC Heavy NA+ 2.72 3.8 43 1% -3% 43710EN NESC Heavy NA+ 2.74 3.7 38 710EN NESC Heavy NA+ 2.72 3.8 88 1% -3% -50709EN NESC Heavy NA+ 2.74 3.7 107 709EN NESC Heavy NA+ 2.72 3.8 58 1% -3% 49708WN NESC Heavy NA+ 2.74 3.7 51 708WN NESC Heavy NA+ 2.72 3.8 144 1% -3% -93TP707WN NESC Heavy NA+ 2.74 3.7 717 TP707WN NESC Heavy NA+ 2.72 3.8 119 1% -3% 598TP706EN NESC Heavy NA+ 2.74 3.7 690 TP706EN NESC Heavy NA+ 2.72 3.8 156 1% -3% 534705EN NESC Heavy NA+ 2.74 3.7 19 705EN NESC Heavy NA+ 2.72 3.8 198 1% -3% -179704WN NESC Heavy NA+ 2.74 3.7 37 704WN NESC Heavy NA+ 2.72 3.8 624 1% -3% -587703WN NESC Heavy NA+ 2.74 3.7 5 703WN NESC Heavy NA+ 2.72 3.8 18 1% -3% -13702WN NESC Heavy NA+ 2.74 3.7 3 702WN NESC Heavy NA+ 2.72 3.8 36 1% -3% -33701WN NESC Heavy NA+ 2.74 3.7 0 701WN NESC Heavy NA+ 2.72 3.8 144 1% -3% -144700WN NESC Heavy NA+ 2.74 3.7 0 700WN NESC Heavy NA+ 2.72 3.8 1 1% -3% -1699WN NESC Heavy NA+ 2.74 3.7 0 699WN NESC Heavy NA+ 2.72 3.8 207 1% -3% -207698WN NESC Heavy NA+ 2.74 3.7 3 698WN NESC Heavy NA+ 2.72 3.8 12 1% -3% -9697WN NESC Heavy NA+ 2.74 3.7 6 697WN NESC Heavy NA+ 2.72 3.8 213 1% -3% -207696WN NESC Heavy NA+ 2.74 3.7 1 696WN NESC Heavy NA+ 2.72 3.8 264 1% -3% -263695WN NESC Heavy NA+ 2.74 3.7 4 695WN NESC Heavy NA+ 2.72 3.8 3 1% -3% 1694WN NESC Heavy NA+ 2.74 3.7 0 694WN NESC Heavy NA+ 2.72 3.8 14 1% -3% -14693WN NESC Heavy NA+ 2.74 3.7 0 693WN NESC Heavy NA+ 2.72 3.8 144 1% -3% -144692WN NESC Heavy NA+ 2.74 3.7 2 692WN NESC Heavy NA+ 2.72 3.8 82 1% -3% -80691WN NESC Heavy NA+ 2.74 3.7 1 691WN NESC Heavy NA+ 2.72 3.8 76 1% -3% -75

Page 38: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin

Str No Load Case DescriptionHorizontal Load (lb/ft)

Vertical Load

(lb/ft)

Horizontal Tension (lb)

Str NoLoad Case

DescriptionHorizontal Load (lb/ft)

Vertical Load (lb/ft)

Horizontal Tension (lb)

Pertcent Change

Horizontal Load

Pertcent Change Vertical

Load

Change is Tension

(lb)

PRYSMIAN (New OPGW) FOCUS (Existing OPGW)

690WN NESC Heavy NA+ 2.74 3.7 1 690WN NESC Heavy NA+ 2.72 3.8 118 1% -3% -117689WN NESC Heavy NA+ 2.74 3.7 27 689WN NESC Heavy NA+ 2.72 3.8 67 1% -3% -40688EN NESC Heavy NA+ 2.74 3.7 12 688EN NESC Heavy NA+ 2.72 3.8 196 1% -3% -184687WN NESC Heavy NA+ 2.74 3.7 94 687WN NESC Heavy NA+ 2.72 3.8 169 1% -3% -75686WN NESC Heavy NA+ 2.74 3.7 6 686WN NESC Heavy NA+ 2.72 3.8 9 1% -3% -3685WN NESC Heavy NA+ 2.74 3.7 6 685WN NESC Heavy NA+ 2.72 3.8 384 1% -3% -378684WN NESC Heavy NA+ 2.74 3.7 2 684WN NESC Heavy NA+ 2.72 3.8 453 1% -3% -451683WN NESC Heavy NA+ 2.74 3.7 65 683WN NESC Heavy NA+ 2.72 3.8 884 1% -3% -819682WN NESC Heavy NA+ 2.74 3.7 2 682WN NESC Heavy NA+ 2.72 3.8 57 1% -3% -55681WN NESC Heavy NA+ 2.74 3.7 3 681WN NESC Heavy NA+ 2.72 3.8 26 1% -3% -23GDI_0094 NESC Heavy NA+ 2.74 3.7 4 GDI_0094 NESC Heavy NA+ 2.72 3.8 112 1% -3% -108679WN NESC Heavy NA+ 2.74 3.7 129 679WN NESC Heavy NA+ 2.72 3.8 60 1% -3% 69678EN NESC Heavy NA+ 2.74 3.7 240 678EN NESC Heavy NA+ 2.72 3.8 156 1% -3% 84677WN NESC Heavy NA+ 2.74 3.7 112 677WN NESC Heavy NA+ 2.72 3.8 121 1% -3% -9676WN NESC Heavy NA+ 2.74 3.7 1 676WN NESC Heavy NA+ 2.72 3.8 45 1% -3% -44675WN NESC Heavy NA+ 2.74 3.7 1 675WN NESC Heavy NA+ 2.72 3.8 124 1% -3% -123674WN NESC Heavy NA+ 2.74 3.7 1 674WN NESC Heavy NA+ 2.72 3.8 52 1% -3% -51673WN NESC Heavy NA+ 2.74 3.7 1 673WN NESC Heavy NA+ 2.72 3.8 5 1% -3% -4672WN NESC Heavy NA+ 2.74 3.7 2 672WN NESC Heavy NA+ 2.72 3.8 56 1% -3% -54671WN NESC Heavy NA+ 2.74 3.7 14 671WN NESC Heavy NA+ 2.72 3.8 328 1% -3% -314670WN NESC Heavy NA+ 2.74 3.7 1 670WN NESC Heavy NA+ 2.72 3.8 219 1% -3% -218669WN NESC Heavy NA+ 2.74 3.7 164 669WN NESC Heavy NA+ 2.72 3.8 146 1% -3% 18668EN NESC Heavy NA+ 2.74 3.7 210 668EN NESC Heavy NA+ 2.72 3.8 400 1% -3% -190667WN NESC Heavy NA+ 2.74 3.7 211 667WN NESC Heavy NA+ 2.72 3.8 152 1% -3% 59TP667WN NESC Heavy NA+ 2.74 3.7 22 TP667WN NESC Heavy NA+ 2.72 3.8 121 1% -3% -99TP665EN NESC Heavy NA+ 2.74 3.7 55 TP665EN NESC Heavy NA+ 2.72 3.8 266 1% -3% -211665WN NESC Heavy NA+ 2.74 3.7 91 665WN NESC Heavy NA+ 2.72 3.8 506 1% -3% -415664WN NESC Heavy NA+ 2.74 3.7 1 664WN NESC Heavy NA+ 2.72 3.8 58 1% -3% -57663WN NESC Heavy NA+ 2.74 3.7 1 663WN NESC Heavy NA+ 2.72 3.8 129 1% -3% -128662WN NESC Heavy NA+ 2.74 3.7 6 662WN NESC Heavy NA+ 2.72 3.8 168 1% -3% -162661WN NESC Heavy NA+ 2.74 3.7 95 661WN NESC Heavy NA+ 2.72 3.8 199 1% -3% -104660EN NESC Heavy NA+ 2.74 3.7 91 660EN NESC Heavy NA+ 2.72 3.8 275 1% -3% -184659EN NESC Heavy NA+ 2.74 3.7 63 659EN NESC Heavy NA+ 2.72 3.8 105 1% -3% -42658WN NESC Heavy NA+ 2.74 3.7 42 658WN NESC Heavy NA+ 2.72 3.8 275 1% -3% -233657WN NESC Heavy NA+ 2.74 3.7 4 657WN NESC Heavy NA+ 2.72 3.8 199 1% -3% -195656WN NESC Heavy NA+ 2.74 3.7 85 656WN NESC Heavy NA+ 2.72 3.8 311 1% -3% -226655EN NESC Heavy NA+ 2.74 3.7 275 655EN NESC Heavy NA+ 2.72 3.8 594 1% -3% -319GDI_0121 NESC Heavy NA+ 2.74 3.7 3 GDI_0121 NESC Heavy NA+ 2.72 3.8 15 1% -3% -12GDI_0122 NESC Heavy NA+ 2.74 3.7 4 GDI_0122 NESC Heavy NA+ 2.72 3.8 217 1% -3% -213654WN NESC Heavy NA+ 2.74 3.7 390 654WN NESC Heavy NA+ 2.72 3.8 551 1% -3% -161653WN NESC Heavy NA+ 2.74 3.7 13 653WN NESC Heavy NA+ 2.72 3.8 174 1% -3% -161

Page 39: VIA FEDEX AND ELECTRONIC MAIL - Connecticut€¦ · VIA FEDEX AND ELECTRONIC MAIL March 5, 2019 . James J. Murphy, Jr. Vice Chairman . The Connecticut Siting Council . Ten Franklin

Str No Load Case DescriptionHorizontal Load (lb/ft)

Vertical Load

(lb/ft)

Horizontal Tension (lb)

Str NoLoad Case

DescriptionHorizontal Load (lb/ft)

Vertical Load (lb/ft)

Horizontal Tension (lb)

Pertcent Change

Horizontal Load

Pertcent Change Vertical

Load

Change is Tension

(lb)

PRYSMIAN (New OPGW) FOCUS (Existing OPGW)

652WN NESC Heavy NA+ 2.74 3.7 0 652WN NESC Heavy NA+ 2.72 3.8 23 1% -3% -23651WN NESC Heavy NA+ 2.74 3.7 1 651WN NESC Heavy NA+ 2.72 3.8 96 1% -3% -95650WN NESC Heavy NA+ 2.74 3.7 0 650WN NESC Heavy NA+ 2.72 3.8 83 1% -3% -83649WN NESC Heavy NA+ 2.74 3.7 274 649WN NESC Heavy NA+ 2.72 3.8 437 1% -3% -163GDI_0129 NESC Heavy NA+ 2.74 3.7 45 GDI_0129 NESC Heavy NA+ 2.72 3.8 187 1% -3% -142648WN NESC Heavy NA+ 2.74 3.7 319 648WN NESC Heavy NA+ 2.72 3.8 861 1% -3% -542647WN NESC Heavy NA+ 2.74 3.7 0 647WN NESC Heavy NA+ 2.72 3.8 32 1% -3% -32GDI_0710 NESC Heavy NA+ 2.74 3.7 1 GDI_0710 NESC Heavy NA+ 2.72 3.8 21 1% -3% -20GDI_0106 NESC Heavy NA+ 1.37 1.85 6288 GDI_0106 NESC Heavy NA+ 1.36 1.9 6505 1% -3% -217