Very Early Warning Smoke Detection

Embed Size (px)

Citation preview

  • 8/3/2019 Very Early Warning Smoke Detection

    1/9

    VVVeeerrryyy EEEaaarrrlllyyy WWWaaarrrnnniiinnnggg SSSmmmoookkkeee DDDeeettteeeccctttiiiooonnn

    Smoke detection technologies are basically classified into EWSD

    (Early warning Smoke Detection) and Very Early Warning Smoke Detection (VEWSD). EWSD

    detectors are of ionization or photoelectric type. Ionization detectors are designed to detect very

    small particles such as the type produced by flammable liquids. Photoelectric detectors detect

    larger particles such as those produced by non- natural materials like PVC.

    An EWSD provides detection of a fire condition prior to the time that

    it becomes threatening to the occupants of the building. Generally this is the time that smoke is

    visible. Let us use the example of paper catching fire within an office. Seconds after the paper

    has ignited, smoke will generate and rise to the ceiling. This visible and hot smoke will

    eventually enter the smoke detection chamber and trigger the alarm to alert the occupants that a

    fire has commenced.

    The EWSD are passive in the sense that the smoke has to find its

    way to the detector. These detectors wait for smoke and rely on the airflow to transport the

    smoke to the detector. Therefore their performance is affected by airflow.

    If a computer terminal within a room had a fault in its electronics

    resulting in a thermal event, it may smoulder for hours before a flame ignites. This smouldering

    stage is the incipient stage to a fire. During this incipient stage the human eye will not see the

    particles but may smell them. EWSD are not sensitive enough to detect smoke at the incipient

    stage of an electrical type fire. Only a VEWSD will detect an incipient fire and thus the term

    VERY EARLY WARNING. This stage of a fire could last for hours or even days.

    Since the rate of smoke generation in a smouldering fire is relatively

    small, and the airflow velocity in the room is quite high, the movement of smoke is dominated by

    the airflow of the mechanical systems. Furthermore the smoke generated during the incipient

    stage is not hot therefore there is very little thermal lift. This often restricts smoke movement

    directly to the ceiling, where spot type detectors are located, causing the smoke to dissipate more

    widely.

    The aspirated smoke detection or VESDA is active , constantly

    sampling the air from multiple points throughout the environment and therefore is not

    totally dependant on thermal energy to transport smoke to enter into the smoke detector.

  • 8/3/2019 Very Early Warning Smoke Detection

    2/9

    AAAssspppiiirrraaattteeeddd DDDeeettteeecccttt iiiooonnn::: Aspirated smoke detection (ASD) systems are quite different from

    conventional spot type smoke detectors. Aspirated systems typically comprise a number of small-

    bore pipes laid out above or below a ceiling in parallel runs, some metres apart. Small holes, also

    some metres apart, are drilled into each pipe to form a matrix of holes (sampling points),

    providing an even distribution across the ceiling. Air or smoke is drawn into the pipework throughthe holes and onward to a very sensitive smoke detector mounted nearby, using the negative

    pressure of an aspirator (air pump).

    HHHooowww mmmuuuccchhh sssmmmoookkkeee ssshhhooouuulllddd wwweee dddeeettteeecccttt??? Obscuration as a unit of measurement has

    become the standard definition of smoke detector sensitivity used in the industry today.

    Obscuration is the effect that smoke has on reducing visibility. Higher concentrations of smoke

    result in higher obscuration levels, lowering visibility.

  • 8/3/2019 Very Early Warning Smoke Detection

    3/9

    Typical Smoke Detection Ratings for smoke detectors:

    Photoelectric : 3.0 % 12 % obscuration per metre

    Beam : 3.0 % 7.0% obscuration per metre

    VESDA : 0.005 % - 20 % obscuration per metre

  • 8/3/2019 Very Early Warning Smoke Detection

    4/9

    Note that the obscuration level at which VESDA detects smokeis lesser (0.005 %) compared to the lower limit of 3.0 % obscuration level for Photoelectric or

    Beam detector.

    DDDeeesssiiigggnnn TTTeeeccchhhnnniiiqqquuueeesss fffooorrr VVVeeerrryyy EEEaaarrrlllyyy WWWaaarrrnnniiinnnggg SSSmmmoookkkeee DDDeeettteeeccctttiiiooonnn:::

    The following have to be considered when designing a VEWSD system

    1. The coverage area per detector or sample point

    2. The sensitivity required per sampling point

    3. The airflow characteristics and the air change rate within the room.

    4. The room size and characteristics raised floor, tall ceilings etc.

    5. The annunciation of emergency response systems.

    6. The activation of mechanical control systems such as air extraction and suppression systems.

  • 8/3/2019 Very Early Warning Smoke Detection

    5/9

    CCCooovvveeerrraaagggeee AAArrreeeaaa ooofff AAASSSDDD::: The maximum coverage area of ASD detector is 2000 sq. meters

    (this is the maximum area coverage permissible within the codes, BS, AS, NFPA). The sample

    point of an ASD detector is treated the same as a spot type detector.

    The area of coverage for a sampling point is effectively around

    100-sq. metre. For ASD applications in high airflow environments, we can decrease the area of

    coverage for the sample point by adding more holes and making the distance between each pipe

    less.

    SSSeeennnsssiiitttiiivvviiitttyyy ooofff AAASSSDDD:::The smoke that reaches the detector is the cumulative smoke, which has

    entered all the sampling points in the network. Take the example of a 200 square metre room

    with 10 sample points on the ceiling. If the detector sensitivity is set to 0.1 % Obscuration / m this

    effectively makes each sample points sensitivity as 0.1 X 10 = 1.0 % Obscuration / m. That is, if

    only one sample point was exposed to smoke it would require 1.0 % Obscuration / m to trigger an

    alarm. This is because we take into account the dilution caused by the other holes.

    Taking the same example, If smoke enters three holes then the

    effective sensitivity required to trigger an alarm is 0.1 x 10 divided by three = 0.33 % Obscuration

    / m per sampling point. Clearly, cumulative sampling allows much lower levels of smoke, and

    thus enable very early detection. If the same room was designed with EWSD and each detector

    was rated at 5 Obscuration /m, the alarm would only trigger once the smoke density has reached

    this point throughout the room or at one detector.

    UUUsssaaagggeee ooofff VVVEEEWWWSSSDDD iiinnn cccaaassseee ooofff CCCooommmpppuuuttteeerrr RRRoooooommm aaannnddd AAAiiirrr CCCooonnndddiiitttiiiooonnniiinnnggg (((CCCRRRAAACCC)))

    SSSyyysssttteeemmmsss: In the diagram given below, The sampling pipes on the ceiling and within the floor

    void are used for detection where the CRAC is out of service. The pipe used to detect smoke

    across the return air path is used for detection where CRAC is operational. The enabling and

    disabling of the sampling pipes helps to achieve this.

    VEWSD techniques are preferred in areas where Air Handling Units

    (AHUs) and other DX systems are installed because the air changes which happen in theserooms will dilute the smoke, thus making smoke detection difficult for EWSD.

  • 8/3/2019 Very Early Warning Smoke Detection

    6/9

    UUUsssaaagggeee ooofff VVVEEESSSDDDAAA iiinnn EEExxxppplllooosssiiiooonnn ppprrrooonnneee EEEnnnvvviiirrrooonnnmmmeeennntttsss::: VESDA is installed in

    hazardous areas like petrochemical plants and also warehouses storing solvents and alcohol.

    These are areas where explosive mixtures of gases or vapours can accumulate. These gases if

    ignited would cause an explosion.

    Equipment installed in hazardous areas must be CE marked and have

    appropriate Ex ratings. Flameproof enclosures (Exd) will hold ignition sources within them in such

    a way that any ignition of the hazard inside the enclosure will not be transmitted to the

    atmosphere outside the enclosure. The VESDA model VESDA smoke detector type VLX - 100

    has been specially designed for use in areas where there is a high possibility of explosion.

    The VLX 100 consists of a VLC (Vesda Laser Compact) detector enclosed

    in a flameproof enclosure made of cast aluminium. The VLX-100 smoke detector draws air

    from the monitored area through a piping network. The sampled air passes through a flame

    arrestor before reaching the detector. Similarly the exhaust air from the detector passes through

    the flame arrester before discharging to a designated area. The VLX 100 model can be used in

    Zone 1(refer glossary) areas

  • 8/3/2019 Very Early Warning Smoke Detection

    7/9

    TTThhheee dddiiiaaagggrrraaammm bbbeeelllooowww iiisss ttthhhaaattt ooofff VVVLLLXXX 111000000:::

    TTThhheee dddiiiaaagggrrraaammm bbbeeelllooowww iiisss aaa ttteeemmmppplllaaattteee ooofff ttthhheee FFFlllaaammmeee AAArrrrrreeesssttteeerrr:::

  • 8/3/2019 Very Early Warning Smoke Detection

    8/9

    VVVaaarrriiiooouuusss PPPooossssssiiibbbllleee wwwaaayyysss ooofff aaarrrrrraaannngggiiinnnggg VVVLLLXXX---111000000 nnneeeaaarrr HHHaaazzzaaarrrdddooouuusss RRReeegggiiiooonnnsss:::

    Scheme C & D where the Detector is mounted in an enclosure and the exhaust is

    released into the hazardous area is recommended.

  • 8/3/2019 Very Early Warning Smoke Detection

    9/9

    GGGlllooossssssaaarrryyy:::

    Hazardous area: An area in which flammable substance in the form of gas, vapour or dust when

    mixed with air, is present in such proportions that it can explode when in contact with an ignition

    source.

    Explosion Proof Apparatus: This apparatus is enclosed in a case that is capable of

    withstanding an explosion of a specified gas or vapour that may occur within it .It also prevents

    ignition of a specified gas or vapour that may occur within it. It also prevents ignition of a

    specified gas or vapour surrounding the enclosure by sparks, flashes, or explosion of the gas or

    vapour within and that operates at an external temperature that a surrounding flammable

    atmosphere will not be ignited.

    Flame Proof: The enclosure of the equipment will withstand an internal explosion, and prevent

    passage of flame to the surrounding atmosphere.

    ExD: Abbreviation for Eex d method for flameproof protection. This includes the use of

    explosion-proof enclosure and flame arresters. This protection level is deemed suitable for

    electrical equipment in Class I, Zone 1 or Zone 2 environments.

    Class I: Locations where flammable gases or vapours are or may be present in the air in

    quantities sufficient to produce ignitable mixtures.

    Class II: Locations, which are hazardous due to the presence of combustible or electrically

    conductive dusts in sufficient quantities for a fire or explosion hazard to exist.

    Class III: Locations, which are hazardous due to the presence of easily ignitable fibres of flyings.

    However, the material is not suspended in the air in quantities sufficient to produce ignitable

    mixtures.

    Zone 1: Where ignitable concentrations of flammable gases, vapours or liquids can exist some of

    the time under normal operating conditions. (IEC adds: Typically between 10 to 100 hours per

    year)