ASPIRATING SMOKE

DETECTION SYSTEMS

Designed with the installer and end user in mind, the FAAST LT serves a wide variety of EN54-20 Class C applications where maintenance is difficult, other smoke detection methods are inappropriate, due to harsh environments, or areas where aesthetics matters.

FAAST LT devices are available as single channel and dual channel devices, offering flexibility for different detection strategies. A range of customisable settings are geared towards maximising device performance and meeting different application needs.

Key Features• Single & Dual channel versions with independent channels including fan, sensor and flow monitoring

• Multiple event logging up to 2240 events

• Ultrasonic airflow sensing

• PipeIQ™LT software provides intuitive system layout and configuration all in one package

• User friendly air flow pendulum graph for verification of pipe network functionality

• Protected electronics from air flow and accidental damage during installation or maintenance

• Easily replaceable and reusable filter without affecting the rest of the device

• Designed for efficient wiring and installation: cable gland holes, easy access to the wiring area and no specialtools required.

• Easy access to parts requiring routine maintenance: filter(s) or sensors(s).

• IP65 enclosure

FAASTTM LT

FAAST LT delivers a flexible solution for

applications where standard detection

methods are prone to failure or false alarm

AspiratingSmokeDetection

Dimensions UserInterfaceDisplay

MECHANICALSPECIFICATION ELECTRICAL

FAAST™ LT FL0111E, FL0112E, FL0122E

Height403 mm (including inlets & outlets)

Smoke Sensor Optical laser point type

Width 356 mm External Supply Voltage 18.5 - 31.5 VDC

Depth 135 mm Remote Reset Time 2 seconds

Cable Access Knock out cable gland holes Power Reset 0.5 seconds

Wire Gauge 0.5 mm2 to 2 mm2

Avg. Operating Current (excluding sounders) 1 Channel Device 2 Channel Device

170mA @ 24 VDC 270mA @ 24 VDC

Maximum Single Pipe Length 100 m

Maximum Total Branched Pipe Length 160 m (per channel)

Maximum Air Inlet Holes 18 holes (per channel)

Coverage Area up to 2000m2

Outside Pipe Diameter 25 mm or 27 mmMax. Avg. Operating Current (excluding sounders) 1 Channel Device 2 Channel Device

360mA @ 24 VDC 570mA @ 24 VDC

Internal Pipe Diameter 15-21 mm

Sensitivity Range (obscuration) 0.07%/m

Relays3 (1 Alarm, 1 Fault, 1 Pre-alarm)

Relay Contact Ratings 2.0 A @ 30 VDC, 0.5 A @ 30 VAC

Sounder Outputs 1 per channelCommunication Loop Supply Voltage Loop Standby Current @ 24V

15-29 VDC (Loop current ≤ 900mA)900 μA max. (poll once every 5s)

Event Log 2244 events ENVIRONMENTAL

Interfaces

Terminal blocks: power supply, relays, sounder outputs, external input; Loop Connection, USB port; Buttons (Test, Reset, Disable)

Operating Temperature -10°C to 55°C

Humidity Range 10 to 93% (non-condensing)

IP Rating IP65

Power supply & relays connections 2mm2 LISTINGSANDAPPROVALS

USBStandard USB cable for Type B USB Connection

CPD

Shipping Weight6.5kg (dual channel) includes packaging

LPCB

Flow monitoring and reportingHigh & low according to EN54-20

EN54-20 (holes per channel)Class A – 3 holes Class B – 6 holes Class C - 18 holesFiltration Replaceable filter

Fan control 10 programmable speeds

367mm

135 mm

56 mm

44 mm

403mm

356 mm

The front panel will be different depending on which of the models is being installed. The following display information is possible:

• Alarm level; Alarm, Pre-Alarm

• Particulate Levels; 1-9

• Fault Status

• Flow Level

• Test, Reset and Disable Buttons

FAASTLTTECHNICALSPECIFICATION

HoneywellTel: +44 (0) 116 246 2000Fax: +44 (0) 116 246 2300Email: [email protected] Waterside RoadHamilton Industrial ParkLeicesterLE5 1TN

November 2014© 2014 Honeywell International Inc.

ProductRange

FAASTLTStandAloneAspiratingSystems ORDERCODES

Single channel, single detector FAAST LT aspirating unit complete with relay outputs. Also includes built in filter. FL0111E-EB

Single channel, dual detector FAAST LT aspirating unit complete with relay outputs. Also includes built in filter. FL0112E-EB

Dual channel, dual detector FAAST LT aspirating unit complete with relay outputs. Also includes built in filter. FL0122E-EB

FAASTLTspecificaccessories

Earth Bar F-LT-EB

FAAST LT Replacement internal filter (Pack of 6) FL-IF-6

For a full range of filters, pipework and accessories please refer to your price list.u

The FAAST™ Aspirating smoke detector combines dual source (blue LED and infra-red laser) optical smoke detection with advanced algorithms to detect a wide range of fire types while maintaining enhanced immunity to nuisance particulates. This enables FAAST™ to accurately detect incipient fire conditions as early as 30 minutes before a fire actually starts in Class A and Class B fire detection.

Key Features• Detection as precise as 0.0015%/m obscuration

• Integral Ethernet interface enables remote monitoring and e-mail status updates

• Patented particle separator and field-replaceable filter remove contaminants from the system

• Five alarm levels & two sensitivity modes

• Dual flow detection including both ultrasonic and electronic sensing for pipe and chamber air flow measurement

• Protects up to 2,000 square metres

• Advanced detection algorithms reject common nuisance conditions

• PipeIQ™ software provides intuitive system layout, configuration, and monitoring all in one package

• Fault indictors covering a broad spectrum of events

• Unique air flow pendulum graph verifies pipe network functionality

• Particulate graph displays subtle environmental changes for early problem indications

FAASTTM 8100EFAAST is a ground breaking aspirating solution designed to deliver highly accurate and discreet early warning fire detection.

Aspirating Smoke Detection

Dimensions FAAST™ User Interface Display

MECHANICAL SPECIFICATION ELECTRICAL

FAAST™ 8110EHeight 337 mm External Supply Voltage 18-30 VDC

Width 330 mmRemote Reset Time

External monitor must be pulled low for a minimum of 100 msDepth 127 mm

Cable Access 2.54 cm cable entry holes on top and bottom of unit

Power Reset 1 sec.

Wire Gauge max. min.

2.0 mm 0.5 mm

Avg. Operating Current 500 mA @ 24 VDC

Maximum Single Pipe Length 120m

Alarm650 mA – All relays active, all alarm levels displayed. Voltage @ 24 VDC

Maximum Total Branched Pipe Length 320m

Maximum Air Inlet Holes 36 holes

Network Outside Pipe Diameter 25 mm Maximum Current Draw 650 mA Voltage at 18 VDC

Internal Pipe Diameter 15-21 mm ENVIRONMENTAL

Relays8 changeover contacts, 3 AMP, latching or non-latching

Operating Temperature 0°C to 38°C

Sampled Air Temperature -20°C to 60°C

Event Log 18,000 events stored Humidity Range 10 to 95% (non-condensing)

Sensitivity Range (obscuration)0.0015%/m. obs - 20.5%/m obs

IP Rating IP30

Communication NetworkEthernet monitoring, 6 e-mail address alerts

Coverage Area Up to 2000sq. m

The User Interface consists of 5 Alarm levels Alert, Action 1, Action 2, Fire 1, and Fire 2, 10 Particulate levels, 10 Bi-colour Flow and Fault graph

330 mm 127 mm

337

mm

FAAST 8100E TECHNICAL SPECIFICATION

HoneywellTel: +44 (0) 116 246 2000Fax: +44 (0) 116 246 2300Email: [email protected] Waterside RoadHamilton Industrial ParkLeicesterLE5 1TN

November 2014© 2014 Honeywell International Inc.

For a full range of filters, pipework and accessories please refer to your price list.uide

Product Range

DESCRIPTION ORDER CODES

FAAST high sensitivity laser aspirating unit. Includes built in replaceable filter. 8100E

FAAST specific accessories

FAAST Replacement internal filter F-A3384-000

FAAST XS (Model 7100XE)FAAST™ Fire Alarm Aspiration Sensing Technology

FAAST XS aspirating smoke detectors deliver highly accurate Very Early

Warning Fire Detection for the smaller applications and offer extensive

communication capabilities.

DescriptionThe FAAST XS aspirating smoke detector combines advanced particle

separation with unique dual source optical smoke detection technology

to provide highly sensitive Very Early Warning Fire Detection while

providing enhanced immunity to false alarms. This technology enables

FAAST XS to accurately detect incipient fire conditions up to Class A

(according to EN54-20), in applications ranging from mission critical to

harsh and extreme environments.

An installed FAAST XS device can administrate up to 170 m pipe length

in standard coverage type applications and can be monitored in several

different ways, including: Serial or TCP Modbus, Ethernet over a LAN or a

direct connection, or via FAAST XS’s onboard USB.

When connected to a LAN, FAAST XS’s email server can provide

email event notification to appropriate personnel. FAAST XS also

communicates alarm and notifications via relays.

PipeIQ® is FAAST XS’s intuitive design,

configuration, and monitoring software. The

all-in-one program can be used to create a

pipe network tailored to meet site specific

requirements, configure a FAAST XS device,

and monitor an installed device - including live

trending and reading of historic reports.

A complimentary download of PipeIQ is available at

www.faast-detection.com.

F E AT U R E S

• Approved for use in Class A, B and C, according to EN54-20

• Provides Very Early Warning Fire Detection, as precise as 0.00095%/m obscuration

• Three alarm levels and three sensitivity modes provide application flexibility

• User configurable 3-speed fan, allowing for maximum coverage area or minimizing on current consumption

• Ultrasonic flow sensing and chamber airflow monitoring for precise system health information

• Dual source optical detection chamber with enhanced algorithms provide high sensitivity with greater immunity to nuisance conditions

• Patented particle separator removes large, non-fire particulate, ensuring chamber health and extending the life of the field-replaceable filter

• TCP and Serial Modbus for easy integration with building management systems

• Easy configuration via USB interface, no external power needed

• Onboard Ethernet interface enables remote monitoring, configuration, web server and e-mail notifications

• Multilingual LCD user interface allows for detailed device information and interaction such as: Active faults, precise airflow monitoring, reset of airflow baseline, test/reset/isolate and more

• Configurable air flow fault thresholds and verification period

• Convenient wiring compartment

• Status-at-a-glance provides immediate alarm, fault and airflow status

Agency Listings (pending). Pending

Aspirating Smoke Detection

FAAST XS (Model 7100XE) Product Specifications

PHYSICAL SPECIFICATION

HEIGHT 279 mm

WIDTH 229 mm

DEPTH 159 mm

WEIGHT 4 Kg

CABLE ACCESS 2.54 cm cable entry holes on top and back of the unit

WIRE GAUGE Minimum 0.5 mm - 2.0 mm maximum

TOTAL PIPE LENGTH 170 m (all designs must be verified within PipeIQ software)

TOTAL HOLE NUMBERS Class A: 16 holes / Class B: 20 holes / Class C: 20 holes (all designs must be verified within PipeIQ software)

OUTSIDE PIPE DIAMETER 25 mm

INTERNAL PIPE DIAMETER 15-21 mm

RELAYS 5 changeover , programmable latching or non-latchingAlert, Fire (2), Fault, Isolated

OPERATING SPECIFICATION

OPERATING TEMPERATURE 0°C to 38°C; Factory Tested to 55°C

SAMPLED AIR TEMPERATURE -20°C to 60°C

HUMIDITY 10 to 95% (non-condensing)

SENSITIVITY RANGE 0.00095% Obs/m to 20.5% Obs/m

IP RATING IP30

COVERAGE AREA Up to 2,000 m2 (please consider regional standards and guidelines)

AIR MOVEMENT 0-1,219m/min

DIAGNOSTIC SPECIFICATION

EVENT LOG 18,000 events stored

TREND DATA LOG configurable sampling period 1 minute to 1 day

SERVICE LOG 300 customer user entries

NETWORKING SPECIFICATION

COMMUNICATION NETWORK Ethernet monitoring, 6 email address alerts, TCP and Serial Modbus

NETWORK SERVICES DHCP, SMTP, HTTP, MODBUS/TCP, AutoIP, NetBIOS-NS, Serial MODBUS

ETHERNET 10/100 Mbps, MDI-X

MODBUS TCP or Serial RS-485

EMAIL 6 recipients, selectable notifications

WEBSERVER Read Configuration, Live View, Logs

ELECTRICAL SPECIFICATION

EXTERNAL SUPPLY VOLTAGE 18-30 VDC

REMOTE RESET TIME External monitor must be pulled low for a minimum of 100 ms

POWER RESET 1 sec.

OPERATING CURRENT Fan High - 200mA, 4.8W; Fan Med - 151mA, 3.7W;Fan Low - 120mA, 2.1W

ALARM CURRENT Fan High - 230mA, 5.6W; Fan Med - 172mA, 4.2W;Fan Low - 142mA, 3.5W

RELAY CONTACT RATINGS 3.0 A @ 30 VDC, 0.5 A @ 125 VAC

INTERFACE SPECIFICATION

PIPEIQ USB or Ethernet

MODBUS Ethernet or RS-485

ORDERING INFORMATION

PART NO 7100XE

DESCRIPTION FAAST XS HIGH SENSITIVITY LASER

ACCESSORIES † Various accessories are available upon request

† Additional accessory information, including part numbers,can be accessed at systemsensor.com/faast

229 mm

279 mm

159 mm

FAAST XS User Interface Display

The User Interface consists of 3 Alarm levels -

Alert, Fire 1, and Fire 2, 10 Particulate levels, 10

Airflow indicators, 4 Fault indicators, LCD.

All technical data is correct at the time of publication and is subject to changes without notice. All trademarks acknowledged.Installation information: In order to ensure full functionality, refer to the installation instructions as supplied.

DS9400XE-16 | 2 | 03/17© 2017 Honeywell International Inc.

Honeywell 140 Waterside Road

Hamilton Industrial Park

Leicester

LE5 1TN

Tel: +44 (0) 116 246 2000

Fax: +44 (0) 116 246 2300

Email: [email protected]

Automatic Purging Unit: F-BO-AFE70-2FAAST™ Fire Alarm Aspiration Sensing Technology

OverviewThe FAAST Automatic Purging Unit provides a fully integrated

and compact solution with user-selectable preventative or event

triggered purging programs. An intelligent and installation-

friendly design ensures AFE70-2 is a cost effective and reliable

means of preventing pipe network contaminant blockages.

DescriptionASD systems continuously monitor the air in a

protected environment, potentially subjecting

the system to contamination over time. In order

to prevent the build up of pipe or aspiration hole

contaminates, regular ASD system purging with

compressed air is essential.

In contrast to conventional purging

systems,Honeywell’s compact and user-friendly

AFE70-2 unit features a single built- in Solenoid

valve, which initiates the release of air into the

ASD system. This valve also increases reliability

by protecting the unit from any compressed air

damage and can be accessed through a control

board that is integrated into the housing.

Installation time is greatly reduced, thanks to a

compact and fully integrated design, removing

the need for mechanical and electrical control

devices. Further cost savings can be leveraged

by a reduced need for cabling and pipe work to

commission the system.

With user-definable purging processes and

customisable program features, AFE70-2

delivers continuous and uninterrupted air flow

and is also optimised to assist with benchmark

preventative maintenance regimes, through

automatic purging processes that can be set

up at specific times. These purging processes

are independent of any fault-initiated purging

procedures performed by the system.

Designed with the engineer in mind, the system

offers excellent flexibility; external devices -

such as a push- button or a central timer – can

be connected to an input to allow initiation of

additional manual or automatic activations of

the purging process.

F E AT U R E S

• A fully integrated and compact system, designed for larger pipe networks

• Designed for use in Honeywell Aspiration Smoke Detection ( ASD) systems

• Patented design without air resistance (as defined by EN 54-20)

• 6 user selectable preventive or event-triggered purging programs - Short or long purging cycle options

• Internal clock or external clock timer can be connected

• Several systems can be coupled in Master-Slave mode

• Manual control via external push-button

• Automatic initiation if a fault message is received from the ASD system (activating through FACP only)

• Easy commissioning without software tools

• Multicolored LED indicates the system condition

Honeywell 140 Waterside Road

Hamilton Industrial Park

Leicester

LE5 1TN

Tel: +44 (0) 116 246 2000

Fax: +44 (0) 116 246 2300

Email: [email protected]

All technical data is correct at the time of publication and is subject to changes without notice. All trademarks acknowledged.Installation information: In order to ensure full functionality, refer to the installation instructions as supplied.

DSF-PSU-2405 | 07/17© 2017 Honeywell International Inc.

F-BO-AFE70-2 Architect/Engineer Specifications

PURGING UNIT

HEIGHT 68 mm

WIDTH 204 mm

DEPTH 160 mm

HOUSING COVER COLOUR Grey white, RAL 9002

WEIGHT 3.2kg (approx.)

PATENT NUMBER AT 514912

ENVIRONMENT

OPERATING TEMPERATURE +5°C to +50°C

IP RATING IP20D

RELATIVE HUMIDITY Max. 95% at 40°C

COMPRESSED AIR CONNECTION

MAX. PERMISSIBLE OVERPRESSURE

0.7MPa (7.0bar)

RECOMMENDED MINIMUM PRESSURE

0.2MPa (2.0bar)

FLOW RATE SOLENOID VALVE 0.2MPa: typ. 1,300 l/min

0.4MPa: typ. 2,300 l/min

0.6MPa: typ. 3,200 l/min

0.7MPa: typ. 3,700 l/min

ORDERING INFORMATION

DESCRIPTION PART NUMBER

Purging Unit / AFE70-2 F-BO-AFE70-2

Non-return valve for pipework RSV-R25

ELECTRICAL SPECIFICATION

SUPPLY VOLTAGE 21.6 – 30 VDC

CURRENT CONSUMPTION @ 24V

8mA (normal condition)

300mA (solenoid valve energised)

System Configuration

RSV-R25 non return valvePipe Network

A S P I R AT I N G S M O K E D E T E C T I O N S Y S T E M S

EN54-4 APPROVED POWER

SUPPLY UNITS

Power supply Units fully certified to EN54-4 provide a stable and fully regulated, true 24V output

for fire alarm system applications under all power conditions. The unique regulation techniques

ensure that even when running on standby batteries, a stable 24V supply is available to all parts

of the system ensuring that all 24V powered devices connected are supplied with optimum

power. The powerful onboard micro-controller ensures that all battery types are conditioned with

optimum, temperature compensated charging algorithms to maximise battery life and maintain

batteries in top condition. The EN54-4 compliant power supplies can be fitted with an optional

dual fused output monitoring module to ensure compliance with European standards when

supplying fire control panels with an external power supply.

DIMENSIONS (mm)

355 117

500

ORDER CODES

EN54 2.5A Power Supply

able to charge up to 12Ah

batteries (500 x 355 x 117mm) ASD-PSU25

EN54 5.25 Amp Power

Supply able to charge up

to 12Ah batteries (with Dual

Output Board) 4I0AC 05214-24-EN

l 2.5A and 5.25A versions

l Enclosure mounted with battery space

l 110V or 230V input, Regulated true 24V output

l Intelligent battery charging and temperature compensation

l Houses up to 12Ah batteries

l Status indicators for monitored faults

l Fully enclosed and robust construction

A S P I R AT I N G S M O K E D E T E C T I O N S Y S T E M S

EN54-4 APPROVED POWER

SUPPLY UNITS

TECHNICAL SPECIFICATION

Construction 1.2mm mild sheet steel

Finish Epoxy powder coated

Colour – lid & box BS 00 A 05 grey – fine texture

Mains input supply voltage 230V AC 50/60Hz or 11 0V AC 50/60Hz (link selectable)

Mains supply fuse 250V, 3A, SB, 5mm x 20mm

Load output voltage 19-30V DC +/- 1%

Maximum load current – 05214-24-EN models

5.25 Amps continuous with maximum battery charge output of 1.25A

Maximum load current – ASD-PSU25

2.5 Amps continuous with maximum battery charge output of 1.0A

Maximum ripple 200 milliamps

Load fuse 5 Amp, self resetting Polyfuse

Maximum current draw from batteries

5 Amps

Battery charge output voltage 27.4V DC nominal at 20ºC

Battery charge current 2 stage, constant voltage 1.25 Amps maximum

Deep discharge prevention Battery disconnects at 1 9V

Compatible batteriesYuasa – NP7-1 2, NP1 2-12, NP1 7-12, NP24-1 2 Powersonic – PS-1270, PS-12120, PS-12170, PS12260

Operating temperature -5ºC to +45ºC

Common fault output Normally energised volt free changeover relay – 30V DC 1 Amp

Battery disconnected output Open collector 50 milliamps

Battery low output Open collector 50 milliamps

Charger fault output Open collector 50 milliamps

Earth fault output Open collector 50 milliamps

Mains failed output Open collector 50 milliamps

Fault output connector 14 way DIL header 0.1" spacing

Mains connector 3 way terminal, 7.62mm spacing, 2.5mm maximum cable size

Load connector 2 way terminal, 7.62mm spacing, 2.5mm maximum cable size

Battery connector 2 way terminal, 7.62mm spacing, 2.5mm maximum cable size

Front panel Power On indicator Green LED

Front panel Fault indicator Yellow LED

Power outputDual 24V supply terminals with EN54-4 clause 6.4 interface (When fitted with optional dual fused output monitoring module)