Designed with the installer and end user in mind, the FAAST LT serves a wide variety of EN54-20 Class C applications where maintenance is difficult, other smoke detection methods are inappropriate, due to harsh environments, or areas where aesthetics matters.
FAAST LT devices are available as single channel and dual channel devices, offering flexibility for different detection strategies. A range of customisable settings are geared towards maximising device performance and meeting different application needs.
Key Features• Single & Dual channel versions with independent channels including fan, sensor and flow monitoring
• Multiple event logging up to 2240 events
• Ultrasonic airflow sensing
• PipeIQ™LT software provides intuitive system layout and configuration all in one package
• User friendly air flow pendulum graph for verification of pipe network functionality
• Protected electronics from air flow and accidental damage during installation or maintenance
• Easily replaceable and reusable filter without affecting the rest of the device
• Designed for efficient wiring and installation: cable gland holes, easy access to the wiring area and no specialtools required.
• Easy access to parts requiring routine maintenance: filter(s) or sensors(s).
• IP65 enclosure
FAASTTM LT
FAAST LT delivers a flexible solution for
applications where standard detection
methods are prone to failure or false alarm
AspiratingSmokeDetection
Dimensions UserInterfaceDisplay
MECHANICALSPECIFICATION ELECTRICAL
FAAST™ LT FL0111E, FL0112E, FL0122E
Height403 mm (including inlets & outlets)
Smoke Sensor Optical laser point type
Width 356 mm External Supply Voltage 18.5 - 31.5 VDC
Depth 135 mm Remote Reset Time 2 seconds
Cable Access Knock out cable gland holes Power Reset 0.5 seconds
Wire Gauge 0.5 mm2 to 2 mm2
Avg. Operating Current (excluding sounders) 1 Channel Device 2 Channel Device
170mA @ 24 VDC 270mA @ 24 VDC
Maximum Single Pipe Length 100 m
Maximum Total Branched Pipe Length 160 m (per channel)
Maximum Air Inlet Holes 18 holes (per channel)
Coverage Area up to 2000m2
Outside Pipe Diameter 25 mm or 27 mmMax. Avg. Operating Current (excluding sounders) 1 Channel Device 2 Channel Device
360mA @ 24 VDC 570mA @ 24 VDC
Internal Pipe Diameter 15-21 mm
Sensitivity Range (obscuration) 0.07%/m
Relays3 (1 Alarm, 1 Fault, 1 Pre-alarm)
Relay Contact Ratings 2.0 A @ 30 VDC, 0.5 A @ 30 VAC
Sounder Outputs 1 per channelCommunication Loop Supply Voltage Loop Standby Current @ 24V
15-29 VDC (Loop current ≤ 900mA)900 μA max. (poll once every 5s)
Event Log 2244 events ENVIRONMENTAL
Interfaces
Terminal blocks: power supply, relays, sounder outputs, external input; Loop Connection, USB port; Buttons (Test, Reset, Disable)
Operating Temperature -10°C to 55°C
Humidity Range 10 to 93% (non-condensing)
IP Rating IP65
Power supply & relays connections 2mm2 LISTINGSANDAPPROVALS
USBStandard USB cable for Type B USB Connection
CPD
Shipping Weight6.5kg (dual channel) includes packaging
LPCB
Flow monitoring and reportingHigh & low according to EN54-20
EN54-20 (holes per channel)Class A – 3 holes Class B – 6 holes Class C - 18 holesFiltration Replaceable filter
Fan control 10 programmable speeds
367mm
135 mm
56 mm
44 mm
403mm
356 mm
The front panel will be different depending on which of the models is being installed. The following display information is possible:
• Alarm level; Alarm, Pre-Alarm
• Particulate Levels; 1-9
• Fault Status
• Flow Level
• Test, Reset and Disable Buttons
FAASTLTTECHNICALSPECIFICATION
HoneywellTel: +44 (0) 116 246 2000Fax: +44 (0) 116 246 2300Email: [email protected] Waterside RoadHamilton Industrial ParkLeicesterLE5 1TN
November 2014© 2014 Honeywell International Inc.
ProductRange
FAASTLTStandAloneAspiratingSystems ORDERCODES
Single channel, single detector FAAST LT aspirating unit complete with relay outputs. Also includes built in filter. FL0111E-EB
Single channel, dual detector FAAST LT aspirating unit complete with relay outputs. Also includes built in filter. FL0112E-EB
Dual channel, dual detector FAAST LT aspirating unit complete with relay outputs. Also includes built in filter. FL0122E-EB
FAASTLTspecificaccessories
Earth Bar F-LT-EB
FAAST LT Replacement internal filter (Pack of 6) FL-IF-6
For a full range of filters, pipework and accessories please refer to your price list.u
The FAAST™ Aspirating smoke detector combines dual source (blue LED and infra-red laser) optical smoke detection with advanced algorithms to detect a wide range of fire types while maintaining enhanced immunity to nuisance particulates. This enables FAAST™ to accurately detect incipient fire conditions as early as 30 minutes before a fire actually starts in Class A and Class B fire detection.
Key Features• Detection as precise as 0.0015%/m obscuration
• Integral Ethernet interface enables remote monitoring and e-mail status updates
• Patented particle separator and field-replaceable filter remove contaminants from the system
• Five alarm levels & two sensitivity modes
• Dual flow detection including both ultrasonic and electronic sensing for pipe and chamber air flow measurement
• Protects up to 2,000 square metres
• Advanced detection algorithms reject common nuisance conditions
• PipeIQ™ software provides intuitive system layout, configuration, and monitoring all in one package
• Fault indictors covering a broad spectrum of events
• Unique air flow pendulum graph verifies pipe network functionality
• Particulate graph displays subtle environmental changes for early problem indications
FAASTTM 8100EFAAST is a ground breaking aspirating solution designed to deliver highly accurate and discreet early warning fire detection.
Aspirating Smoke Detection
Dimensions FAAST™ User Interface Display
MECHANICAL SPECIFICATION ELECTRICAL
FAAST™ 8110EHeight 337 mm External Supply Voltage 18-30 VDC
Width 330 mmRemote Reset Time
External monitor must be pulled low for a minimum of 100 msDepth 127 mm
Cable Access 2.54 cm cable entry holes on top and bottom of unit
Power Reset 1 sec.
Wire Gauge max. min.
2.0 mm 0.5 mm
Avg. Operating Current 500 mA @ 24 VDC
Maximum Single Pipe Length 120m
Alarm650 mA – All relays active, all alarm levels displayed. Voltage @ 24 VDC
Maximum Total Branched Pipe Length 320m
Maximum Air Inlet Holes 36 holes
Network Outside Pipe Diameter 25 mm Maximum Current Draw 650 mA Voltage at 18 VDC
Internal Pipe Diameter 15-21 mm ENVIRONMENTAL
Relays8 changeover contacts, 3 AMP, latching or non-latching
Operating Temperature 0°C to 38°C
Sampled Air Temperature -20°C to 60°C
Event Log 18,000 events stored Humidity Range 10 to 95% (non-condensing)
Sensitivity Range (obscuration)0.0015%/m. obs - 20.5%/m obs
IP Rating IP30
Communication NetworkEthernet monitoring, 6 e-mail address alerts
Coverage Area Up to 2000sq. m
The User Interface consists of 5 Alarm levels Alert, Action 1, Action 2, Fire 1, and Fire 2, 10 Particulate levels, 10 Bi-colour Flow and Fault graph
330 mm 127 mm
337
mm
FAAST 8100E TECHNICAL SPECIFICATION
HoneywellTel: +44 (0) 116 246 2000Fax: +44 (0) 116 246 2300Email: [email protected] Waterside RoadHamilton Industrial ParkLeicesterLE5 1TN
November 2014© 2014 Honeywell International Inc.
For a full range of filters, pipework and accessories please refer to your price list.uide
Product Range
DESCRIPTION ORDER CODES
FAAST high sensitivity laser aspirating unit. Includes built in replaceable filter. 8100E
FAAST specific accessories
FAAST Replacement internal filter F-A3384-000
FAAST XS (Model 7100XE)FAAST™ Fire Alarm Aspiration Sensing Technology
FAAST XS aspirating smoke detectors deliver highly accurate Very Early
Warning Fire Detection for the smaller applications and offer extensive
communication capabilities.
DescriptionThe FAAST XS aspirating smoke detector combines advanced particle
separation with unique dual source optical smoke detection technology
to provide highly sensitive Very Early Warning Fire Detection while
providing enhanced immunity to false alarms. This technology enables
FAAST XS to accurately detect incipient fire conditions up to Class A
(according to EN54-20), in applications ranging from mission critical to
harsh and extreme environments.
An installed FAAST XS device can administrate up to 170 m pipe length
in standard coverage type applications and can be monitored in several
different ways, including: Serial or TCP Modbus, Ethernet over a LAN or a
direct connection, or via FAAST XS’s onboard USB.
When connected to a LAN, FAAST XS’s email server can provide
email event notification to appropriate personnel. FAAST XS also
communicates alarm and notifications via relays.
PipeIQ® is FAAST XS’s intuitive design,
configuration, and monitoring software. The
all-in-one program can be used to create a
pipe network tailored to meet site specific
requirements, configure a FAAST XS device,
and monitor an installed device - including live
trending and reading of historic reports.
A complimentary download of PipeIQ is available at
www.faast-detection.com.
F E AT U R E S
• Approved for use in Class A, B and C, according to EN54-20
• Provides Very Early Warning Fire Detection, as precise as 0.00095%/m obscuration
• Three alarm levels and three sensitivity modes provide application flexibility
• User configurable 3-speed fan, allowing for maximum coverage area or minimizing on current consumption
• Ultrasonic flow sensing and chamber airflow monitoring for precise system health information
• Dual source optical detection chamber with enhanced algorithms provide high sensitivity with greater immunity to nuisance conditions
• Patented particle separator removes large, non-fire particulate, ensuring chamber health and extending the life of the field-replaceable filter
• TCP and Serial Modbus for easy integration with building management systems
• Easy configuration via USB interface, no external power needed
• Onboard Ethernet interface enables remote monitoring, configuration, web server and e-mail notifications
• Multilingual LCD user interface allows for detailed device information and interaction such as: Active faults, precise airflow monitoring, reset of airflow baseline, test/reset/isolate and more
• Configurable air flow fault thresholds and verification period
• Convenient wiring compartment
• Status-at-a-glance provides immediate alarm, fault and airflow status
Agency Listings (pending). Pending
Aspirating Smoke Detection
FAAST XS (Model 7100XE) Product Specifications
PHYSICAL SPECIFICATION
HEIGHT 279 mm
WIDTH 229 mm
DEPTH 159 mm
WEIGHT 4 Kg
CABLE ACCESS 2.54 cm cable entry holes on top and back of the unit
WIRE GAUGE Minimum 0.5 mm - 2.0 mm maximum
TOTAL PIPE LENGTH 170 m (all designs must be verified within PipeIQ software)
TOTAL HOLE NUMBERS Class A: 16 holes / Class B: 20 holes / Class C: 20 holes (all designs must be verified within PipeIQ software)
OUTSIDE PIPE DIAMETER 25 mm
INTERNAL PIPE DIAMETER 15-21 mm
RELAYS 5 changeover , programmable latching or non-latchingAlert, Fire (2), Fault, Isolated
OPERATING SPECIFICATION
OPERATING TEMPERATURE 0°C to 38°C; Factory Tested to 55°C
SAMPLED AIR TEMPERATURE -20°C to 60°C
HUMIDITY 10 to 95% (non-condensing)
SENSITIVITY RANGE 0.00095% Obs/m to 20.5% Obs/m
IP RATING IP30
COVERAGE AREA Up to 2,000 m2 (please consider regional standards and guidelines)
AIR MOVEMENT 0-1,219m/min
DIAGNOSTIC SPECIFICATION
EVENT LOG 18,000 events stored
TREND DATA LOG configurable sampling period 1 minute to 1 day
SERVICE LOG 300 customer user entries
NETWORKING SPECIFICATION
COMMUNICATION NETWORK Ethernet monitoring, 6 email address alerts, TCP and Serial Modbus
NETWORK SERVICES DHCP, SMTP, HTTP, MODBUS/TCP, AutoIP, NetBIOS-NS, Serial MODBUS
ETHERNET 10/100 Mbps, MDI-X
MODBUS TCP or Serial RS-485
EMAIL 6 recipients, selectable notifications
WEBSERVER Read Configuration, Live View, Logs
ELECTRICAL SPECIFICATION
EXTERNAL SUPPLY VOLTAGE 18-30 VDC
REMOTE RESET TIME External monitor must be pulled low for a minimum of 100 ms
POWER RESET 1 sec.
OPERATING CURRENT Fan High - 200mA, 4.8W; Fan Med - 151mA, 3.7W;Fan Low - 120mA, 2.1W
ALARM CURRENT Fan High - 230mA, 5.6W; Fan Med - 172mA, 4.2W;Fan Low - 142mA, 3.5W
RELAY CONTACT RATINGS 3.0 A @ 30 VDC, 0.5 A @ 125 VAC
INTERFACE SPECIFICATION
PIPEIQ USB or Ethernet
MODBUS Ethernet or RS-485
ORDERING INFORMATION
PART NO 7100XE
DESCRIPTION FAAST XS HIGH SENSITIVITY LASER
ACCESSORIES † Various accessories are available upon request
† Additional accessory information, including part numbers,can be accessed at systemsensor.com/faast
229 mm
279 mm
159 mm
FAAST XS User Interface Display
The User Interface consists of 3 Alarm levels -
Alert, Fire 1, and Fire 2, 10 Particulate levels, 10
Airflow indicators, 4 Fault indicators, LCD.
All technical data is correct at the time of publication and is subject to changes without notice. All trademarks acknowledged.Installation information: In order to ensure full functionality, refer to the installation instructions as supplied.
DS9400XE-16 | 2 | 03/17© 2017 Honeywell International Inc.
Honeywell 140 Waterside Road
Hamilton Industrial Park
Leicester
LE5 1TN
Tel: +44 (0) 116 246 2000
Fax: +44 (0) 116 246 2300
Email: [email protected]
Automatic Purging Unit: F-BO-AFE70-2FAAST™ Fire Alarm Aspiration Sensing Technology
OverviewThe FAAST Automatic Purging Unit provides a fully integrated
and compact solution with user-selectable preventative or event
triggered purging programs. An intelligent and installation-
friendly design ensures AFE70-2 is a cost effective and reliable
means of preventing pipe network contaminant blockages.
DescriptionASD systems continuously monitor the air in a
protected environment, potentially subjecting
the system to contamination over time. In order
to prevent the build up of pipe or aspiration hole
contaminates, regular ASD system purging with
compressed air is essential.
In contrast to conventional purging
systems,Honeywell’s compact and user-friendly
AFE70-2 unit features a single built- in Solenoid
valve, which initiates the release of air into the
ASD system. This valve also increases reliability
by protecting the unit from any compressed air
damage and can be accessed through a control
board that is integrated into the housing.
Installation time is greatly reduced, thanks to a
compact and fully integrated design, removing
the need for mechanical and electrical control
devices. Further cost savings can be leveraged
by a reduced need for cabling and pipe work to
commission the system.
With user-definable purging processes and
customisable program features, AFE70-2
delivers continuous and uninterrupted air flow
and is also optimised to assist with benchmark
preventative maintenance regimes, through
automatic purging processes that can be set
up at specific times. These purging processes
are independent of any fault-initiated purging
procedures performed by the system.
Designed with the engineer in mind, the system
offers excellent flexibility; external devices -
such as a push- button or a central timer – can
be connected to an input to allow initiation of
additional manual or automatic activations of
the purging process.
F E AT U R E S
• A fully integrated and compact system, designed for larger pipe networks
• Designed for use in Honeywell Aspiration Smoke Detection ( ASD) systems
• Patented design without air resistance (as defined by EN 54-20)
• 6 user selectable preventive or event-triggered purging programs - Short or long purging cycle options
• Internal clock or external clock timer can be connected
• Several systems can be coupled in Master-Slave mode
• Manual control via external push-button
• Automatic initiation if a fault message is received from the ASD system (activating through FACP only)
• Easy commissioning without software tools
• Multicolored LED indicates the system condition
Honeywell 140 Waterside Road
Hamilton Industrial Park
Leicester
LE5 1TN
Tel: +44 (0) 116 246 2000
Fax: +44 (0) 116 246 2300
Email: [email protected]
All technical data is correct at the time of publication and is subject to changes without notice. All trademarks acknowledged.Installation information: In order to ensure full functionality, refer to the installation instructions as supplied.
DSF-PSU-2405 | 07/17© 2017 Honeywell International Inc.
F-BO-AFE70-2 Architect/Engineer Specifications
PURGING UNIT
HEIGHT 68 mm
WIDTH 204 mm
DEPTH 160 mm
HOUSING COVER COLOUR Grey white, RAL 9002
WEIGHT 3.2kg (approx.)
PATENT NUMBER AT 514912
ENVIRONMENT
OPERATING TEMPERATURE +5°C to +50°C
IP RATING IP20D
RELATIVE HUMIDITY Max. 95% at 40°C
COMPRESSED AIR CONNECTION
MAX. PERMISSIBLE OVERPRESSURE
0.7MPa (7.0bar)
RECOMMENDED MINIMUM PRESSURE
0.2MPa (2.0bar)
FLOW RATE SOLENOID VALVE 0.2MPa: typ. 1,300 l/min
0.4MPa: typ. 2,300 l/min
0.6MPa: typ. 3,200 l/min
0.7MPa: typ. 3,700 l/min
ORDERING INFORMATION
DESCRIPTION PART NUMBER
Purging Unit / AFE70-2 F-BO-AFE70-2
Non-return valve for pipework RSV-R25
ELECTRICAL SPECIFICATION
SUPPLY VOLTAGE 21.6 – 30 VDC
CURRENT CONSUMPTION @ 24V
8mA (normal condition)
300mA (solenoid valve energised)
System Configuration
RSV-R25 non return valvePipe Network
A S P I R AT I N G S M O K E D E T E C T I O N S Y S T E M S
EN54-4 APPROVED POWER
SUPPLY UNITS
Power supply Units fully certified to EN54-4 provide a stable and fully regulated, true 24V output
for fire alarm system applications under all power conditions. The unique regulation techniques
ensure that even when running on standby batteries, a stable 24V supply is available to all parts
of the system ensuring that all 24V powered devices connected are supplied with optimum
power. The powerful onboard micro-controller ensures that all battery types are conditioned with
optimum, temperature compensated charging algorithms to maximise battery life and maintain
batteries in top condition. The EN54-4 compliant power supplies can be fitted with an optional
dual fused output monitoring module to ensure compliance with European standards when
supplying fire control panels with an external power supply.
DIMENSIONS (mm)
355 117
500
ORDER CODES
EN54 2.5A Power Supply
able to charge up to 12Ah
batteries (500 x 355 x 117mm) ASD-PSU25
EN54 5.25 Amp Power
Supply able to charge up
to 12Ah batteries (with Dual
Output Board) 4I0AC 05214-24-EN
l 2.5A and 5.25A versions
l Enclosure mounted with battery space
l 110V or 230V input, Regulated true 24V output
l Intelligent battery charging and temperature compensation
l Houses up to 12Ah batteries
l Status indicators for monitored faults
l Fully enclosed and robust construction
A S P I R AT I N G S M O K E D E T E C T I O N S Y S T E M S
EN54-4 APPROVED POWER
SUPPLY UNITS
TECHNICAL SPECIFICATION
Construction 1.2mm mild sheet steel
Finish Epoxy powder coated
Colour – lid & box BS 00 A 05 grey – fine texture
Mains input supply voltage 230V AC 50/60Hz or 11 0V AC 50/60Hz (link selectable)
Mains supply fuse 250V, 3A, SB, 5mm x 20mm
Load output voltage 19-30V DC +/- 1%
Maximum load current – 05214-24-EN models
5.25 Amps continuous with maximum battery charge output of 1.25A
Maximum load current – ASD-PSU25
2.5 Amps continuous with maximum battery charge output of 1.0A
Maximum ripple 200 milliamps
Load fuse 5 Amp, self resetting Polyfuse
Maximum current draw from batteries
5 Amps
Battery charge output voltage 27.4V DC nominal at 20ºC
Battery charge current 2 stage, constant voltage 1.25 Amps maximum
Deep discharge prevention Battery disconnects at 1 9V
Compatible batteriesYuasa – NP7-1 2, NP1 2-12, NP1 7-12, NP24-1 2 Powersonic – PS-1270, PS-12120, PS-12170, PS12260
Operating temperature -5ºC to +45ºC
Common fault output Normally energised volt free changeover relay – 30V DC 1 Amp
Battery disconnected output Open collector 50 milliamps
Battery low output Open collector 50 milliamps
Charger fault output Open collector 50 milliamps
Earth fault output Open collector 50 milliamps
Mains failed output Open collector 50 milliamps
Fault output connector 14 way DIL header 0.1" spacing
Mains connector 3 way terminal, 7.62mm spacing, 2.5mm maximum cable size
Load connector 2 way terminal, 7.62mm spacing, 2.5mm maximum cable size
Battery connector 2 way terminal, 7.62mm spacing, 2.5mm maximum cable size
Front panel Power On indicator Green LED
Front panel Fault indicator Yellow LED
Power outputDual 24V supply terminals with EN54-4 clause 6.4 interface (When fitted with optional dual fused output monitoring module)