42
PowerManager II Uninterruptible Power Supply Software User’s Manual For MS-Windows ® 95 MS-Windows ® 98 MS-Windows Me ® MS-Windows NT ® MS-Windows ® 2000 MS-Windows ® 2003 MS-Windows XP ® SCO Unix LINUX

UPS PowermanagerII

Embed Size (px)

Citation preview

Page 1: UPS PowermanagerII

PowerManager II

Uninterruptible Power Supply Software

User’s Manual

For

MS-Windows® 95 MS-Windows® 98 MS-Windows Me®

MS-Windows NT® MS-Windows® 2000 MS-Windows® 2003 MS-Windows XP® SCO Unix LINUX

Page 2: UPS PowermanagerII

Introduction ..................................................................................................................................3 Packing including..............................................................................................................................4 Powermanager II operation manual ..................................................................................................4 System requirements .........................................................................................................................4 PowerManager II for Windows ..............................................................................................5 Featuresa ...........................................................................................................................................5 Software Installation .........................................................................................................................6 Start-up and Quit Powermanager II ..................................................................................................6 Sytem Setting ....................................................................................................................................8 A.Base setting ...................................................................................................................................8 B.Shutdown setting .........................................................................................................................10 C.Crisis process...............................................................................................................................11 D.History data setting of saving......................................................................................................13 Warn program setting......................................................................................................................14 A.Pager BP......................................................................................................................................14 B.Broadcast.....................................................................................................................................18 C.Email ...........................................................................................................................................19 D.SMS.............................................................................................................................................22 E.Sound...........................................................................................................................................25 F.Telephone voice ...........................................................................................................................26 G.Pop-up..........................................................................................................................................29 History Event Log...........................................................................................................................30 History Data ....................................................................................................................................31 Curve format ...................................................................................................................................32 View Chart ......................................................................................................................................33 1.View status chart ..........................................................................................................................33 2.View curve chart ..........................................................................................................................34 3.View list chart ..............................................................................................................................34 UPS rating information ...................................................................................................................35 UPS Control ....................................................................................................................................35 1.Testing..........................................................................................................................................35 2.UPS Turn off/Turn on ..................................................................................................................36 3.Beeper Turn on.............................................................................................................................36 About PowermanagerⅡ..................................................................................................................38 PowerManager II for LINUX .........................................................................................................39 1.Software installation and operation...........................................................................................39 2.software package..........................................................................................................................40 PowerManager II for SCO UNIX ...................................................................................................41 1.Software installation and operation...........................................................................................41 2.software package..........................................................................................................................42

Page 3: UPS PowermanagerII

Introduction

PowermanagerII is a smart UPS monitoring and controlling

software. PowermanagerII displays the status of UPS (e.g. input &

output voltage, line frequency, load, temperature and battery

capacity) in digital and graphic, which can help the users

monitor the quality of power supply. Simultaneously, the

users can remotely monitor UPS via network and manage the

power more effectively. On AC failure or UPS battery low,

PowermanagerII will perform its monitoring function without

people around. PowermanagerII has some new ways to send the

warning messages, auto dialing and by E-mail. In addition,

PowermanagerII has a new Windows NT service function,

which allows the monitoring program to be executed

automatically before login. PowermanagerII is available in many

languages, you can select the one that is most familiar for you

to carry out the software configuration and operation. Today

the Internet is widely used, not only for PC but also for

Server, coming into the times of receiving and sending

information 24 hours a day. The power management without

people has been a necessary function of UPS. PowermanagerII,

with full functions will be the best partner of your smart UPS.

Page 4: UPS PowermanagerII

Packing including   

Powermanager II Installation CD 1pcs DB9F/DB9M cable 1pcs

Note: If you want to use the USB,you must choose the USB Chip or USB Cable.

Powermanager II operation manual    System requirements

   Powermanager II hardware and software requirements as follows:

Computer system RS232 communication port: COM1-COM4

Adopt real RS   -232 communication intelligent

for

MS-Windows® 95

MS-Windows® 98

MS-Windows NT® MS-Windows Me®

MS-Windows® 2000

MS-Windows® 2003

MS-Windows XP®

SCO Unix

LINUX

Page 5: UPS PowermanagerII

PowerManager II for Windows

Featuresa   

Intuitionistic and clarity display pressure 、frequency、load 、batteries of UPS

etc diversified parameter real time fettle communication as data and figure,

help users know the quality of currently electric power accommodate.

Supporting Windows NT Service function.

Can select save application files before shutdown system or let computer

enter sleep mode directly (need the computer support this function)

   Transmitting the warning message by e-mail automatically.

   Calling the warning message automatically.

   Monitoring UPS remotely via TCPIP or Internet.

   Detecting the AC fail and the UPS battery low automatically.

   Setting the turning on/off time automatically.

   Displaying the UPS status in drawing, such as the

temperature, voltage, load, line frequency etc.

   Broadcasting the warning message.

Pop-up alarm message on the computer with Windows OS through

Windows NT Messenger service.

Auto send alarm message via GSM SMS.

Auto send alarm message via BP-call.

Auto send alarm voice to via telephone.

Seamless connect to controlplane, realize nobody on duty.

   Setting the countdown time and the interval of each warning.

   Setting UPS diagnostic and self testing time.

   Before removing the system, automatically close and

store the applicable programs.

   Recording and analyzing the UPS status

Supporting Multi-Language.

Page 6: UPS PowermanagerII

Software Installation The SETUP program is required for Powermanager II installation.

After installation, the files will be copied to the “richcomm\ Powermanager II”

directory.

Following the steps below:

1. Turn on UPS and PC.

2. Place the Powermanager II CD to the CD ROM.

Powermanager II will display the installation menu。

3.Select language when install. If you want to change language, uninstall

Powermanager II and reinstall again for new selection.

4.After installation, Powermanager II files will be copied into the directory you

appointed.

Start-up and Quit Powermanager II Start-up Powermanager II After installation, please restart the computer. For Windows 98, check if there is

a ‘PowerManager II’ icon in task bar. For Windows 2000,xp,2003, go to

‘control panel->service’ and check if ‘PMService’ service has started.

If you want to change the function configuration, please run the Powermanager

II in the task bar directly or select " Powermanager II for Windows" from "

Powermanager II " in program group of start menu in Windows.

Powermanager II in gear

Powermanager II un-start up or not on line

Quit Powermanager II

After installation, there is 4 selection as below under" Powermanager II " in

Windows start menu. If you want to ‘Exit’ the Powermanager II from the system,

please select " Quit ".

Page 7: UPS PowermanagerII

Description The main interface window of PowerManager II

(1)Menu bar and Tool bar

(2)UPS status chart

(3)UPS warn parameter display area

Page 8: UPS PowermanagerII

Sytem Setting

A.Base setting Local UPS, Please Chose the Local UPS and Chose the Serial port or USB

port which is connect the UPS.

Page 9: UPS PowermanagerII

Remote UPS, Please chose the Remote UPS and setting the IP address

which is Running the PowerManagerII Program and has accredit.

Page 10: UPS PowermanagerII

B.Shutdown setting

1. Auto Save files: Chose Auto save Files, PowermangerII will auto

save the edited files before the system shutdown.

2. Turn off UPS: Chose Turn off UPS and setting Turn off UPS delay

X Minutes. After the system shutdown, delay X Minutes the UPS

shutdown.

3. Show save files when windows start up: Chose Show save files

when windows start up. PowerManagerII will show the files which

are saved in the last time when the system start up.

4. Execute the program before shutdown Windows: Click the Brows

button to Chose a program which is will Executed before shutdown

Windows.

Page 11: UPS PowermanagerII

C.Crisis process

1) Chose the Shutdown System

1. Active When AC failure Keep on X Mins : When the AC failure the system

will shutdown after X Mins.

2. Active When Battery Volt low keep on X Mins : When the Battery Volt low

the system will shutdown after X Mins.

3. Active When UPS Bypass Keep on X Mins: When the UPS Bypass the

system will shutdown after X Mins.

4. Active When UPS Overheat Keep on X Mins: When the UPS Overheat the

system will shutdown after X Mins.

5. Active When UPS OverLoad Keep on X Mins: When the UPS OverLoad the

system will shutdown after X Mins.

6. Active When UPS Failure Keep on X Mins: When the UPS Failure the

system will shutdown after X Mins.

Page 12: UPS PowermanagerII

7. Active When UPS Disconnect Keep on X Mins: When the UPS Disconnect

the system will shutdown after X Mins.

8.Active When UPS will turn off Keep on X Mins: When the UPS will turn off

the system will shutdown after X Mins.

2) Chose the Hibemation (need Windows2000 or above)

1. Active When AC failure Keep on X Mins: When the AC failure the system

will Hibemation after X Mins.

2. Active When Battery Volt low keep on X Mins : When the Battery Volt low

the system will Hibemation after X Mins.

3. Active When UPS Bypass Keep on X Mins: When the UPS Bypass the

system will Hibemation after X Mins.

4. Active When UPS Overheat Keep on X Mins: When the UPS Overheat the

system will Hibemation after X Mins.

5. Active When UPS OverLoad Keep on X Mins: When the UPS OverLoad the

system will Hibemation after X Mins.

6. Active When UPS Failure Keep on X Mins: When the UPS Failure the

system will Hibemation after X Mins.

7. Active When UPS Disconnect Keep on X Mins: When the UPS Disconnect

the system will shutdown after X Mins.

8.Active When UPS will turn off Keep on X Mins: When the UPS will turn off

the system will Hibemation after X Mins.

Page 13: UPS PowermanagerII

D.History data setting of saving

You can select save history data or not, if you want to save it, must input a

number of interval minutes form 1 to 36000.

Page 14: UPS PowermanagerII

Warn program setting

A.Pager BP

Page 15: UPS PowermanagerII

choose the warning receiver,

Page 16: UPS PowermanagerII

As shown below:

Click the "Add",As shown below:

Page 17: UPS PowermanagerII

Click the "Add",As shown below:

Page 18: UPS PowermanagerII

B.Broadcast

Active NT messenger warning if you want, and set the time of the messenger

be sent.

Page 19: UPS PowermanagerII

C.Email

Active email warning if you want, and input the SNTP’s server and the sender’s

mailbox. Commonly, we need not to active the SNTP Authentication, as bellow

chart:

Page 20: UPS PowermanagerII

choose the warning receiver ,As shown below:

Click the "Add",As shown below:

Page 21: UPS PowermanagerII

Click the "Add",As shown below:

Page 22: UPS PowermanagerII

D.SMS

Active SMS warning if you want, the PowermanagerII provided two ways of

send SMS, you can choose one of them according to your instance. The one is

sending SMS by GSM modem, the mean need to connect a GSM MODEM to the

port, then set the Baud Rate and SMSCenter’s number of your root place. The

other is sending SMS through internet SMS service provider.

Page 23: UPS PowermanagerII

choose the warning receiver, As shown below:

Click the "Add",As shown below:

Page 24: UPS PowermanagerII

Click the "Add",As shown below:

Page 25: UPS PowermanagerII

E. Sound

Active sound warning if you want, every event have a voice different from

other events. If you want to modify it, press modify button to change it.

Page 26: UPS PowermanagerII

F.Telephone voice

Active Telephone voice warning if you want, you must choose the Voice

Modem which is Connect. Every event have a telephone voice different from

other events. If you want to modify it, press modify button to change it.

Page 27: UPS PowermanagerII

choose the warning receiver ,As shown below:

Click the "Add",As shown below:

Page 28: UPS PowermanagerII

Click the "Add",As shown below:

Page 29: UPS PowermanagerII

G.Pop-up

Active Pop-Up Warnings if you want, then when event occurred, the window

will appearing automatism.

Page 30: UPS PowermanagerII

History Event Log

All of events are noted in a while time that you set. You can choose event level

which you want to known.

All events—if you select it, the bellow window will display all events.

General events—if you select it, the bellow window will display the General

events

Warning events—if you select it, the bellow window will display the warning

events.

Severity events—if you select it, the bellow window will display the severity

events.

Page 31: UPS PowermanagerII

History Data

The PowermanagerⅡ provided the memorize function of history data, for

every ip address, system can noted its input voltage、input frequently、output

voltage、output frequently、battery capacity、temperature、battery voltage、

AC indication、battery voltage、by pass indication、UPS fail indication、UPS type、

test status、shutdown indication、beep on LED and UPS connect.

Table format

Page 32: UPS PowermanagerII

Curve format

Page 33: UPS PowermanagerII

View Chart

The PowermanagerⅡ provided three view chart: 1.view status chart. 2.view

curve chart. 3.view list chart.

The three means expression the UPS’s work status, included its input voltage、

input frequency、output voltage 、load and temperature ect.

1. View status chart

Page 34: UPS PowermanagerII

2. View curve chart

3. View list chart

Page 35: UPS PowermanagerII

UPS rating information

The page can display the UPS’s rating information as bellow chart:

UPS Control

1. Testing

1) UPS Self-Test for 10 Seconds

2) UPS Self-Test Until Battery Low

3) UPS Self-Test for N Mins

4) Cancel UPS Self-Test

Page 36: UPS PowermanagerII

2. UPS Turn off/Turn on

1) Turn off UPS delay n Minutes

2) Turn off UPS delay n Minutes and reboot UPS after n Minutes

3) Cancel ups command of turn off

3. Beeper Turn on

Scheme Task

PowerManagerII can set the scheduled time for UPS turn on /off and

self-test. Therefore, the system could be operated without the

management from system supervisor. You can set what and

how to execute the scheme task . The setting category and

operating frequency are as below.

Actions

1)Turn off UPS delay n minutes

2)Turn off UPS delay n minutes and reboot UPS after n minutes

2)UPS Self-Test Until Battery Low

3)UPS Self-Test for 10 Secs

4)UPS Self-Test n mins

Page 37: UPS PowermanagerII

Execute Cycle

1)Once

2)Every Day

3)EveryWeek

4)EveryMonth

Page 38: UPS PowermanagerII

About PowermanagerⅡ

Click the icon of PowerManager with the right key of mouse, then click the “about” menu which in the pop-up menu, the about PowerManager window.

Page 39: UPS PowermanagerII

PowerManager II for LINUX

1.Software installation and operation i) soft installation

copy the package ups_manager to you favorite directory , example :/root/tmp

Use the tar command to extract files from the diskette or software package:

tar -xzvf ups_manager.tar.gz

Change the working directory to /tmp.

cd /root/tmp

Execute the installation program:

./install.linux.sh

The installation program will not execute in some shell scripts. If this happens,

change to another shell script and try again.

the installation program will automatically copy files to the default location

"/etc/RichComm/ups_manager/" and modify the system startup file to contain

the ups_manager for UNIX daemon process.

ii) start program

The installation program will automatically start the main program .

you can start it use following command:

./ups_manager start

iii) stop program

you can start it use following command:

./ups_manager stop

iv) config program

you can start it use following command:

./ups_manager config

Page 40: UPS PowermanagerII

2.software package

./ups_monitor

./ups_status

./ups_config

./shutdown.sh

./ups_manager

./ups_manager start

./ups_manager stop

./ups_manager config

./ups_manager status

./ups_manager restart

./TimeCfg.conf

./install.linux.sh

./Readme

./SendMSG.sh

./startup.add

Page 41: UPS PowermanagerII

PowerManager II for SCO UNIX

1.Software installation and operation

i) soft installation

copy the package ups_manager to you favorite directory , example :/root/tmp

Use the tar command to extract files from the diskette or software package:

tar -xvf ups_manager.tar

Change the working directory to /tmp.

cd /root/tmp

Execute the installation program:

./install.sco.sh

The installation program will not execute in some shell scripts. If this happens,

change to another shell script and try again.

the installation program will automatically copy files to the default location

"/etc/RichComm/ups_manager/" and modify the system startup file to contain

the ups_manager for UNIX daemon process.

ii) start program

The installation program will automatically start the main program .

you can start it use following command:

./ups_manager start

iii) stop program

you can start it use following command:

./ups_manager stop

iv) config program

you can start it use following command:

./ups_manager config

Page 42: UPS PowermanagerII

2.software package .

/ups_monitor

./ups_status

./ups_config

./shutdown.sh

./ups_manager

./ups_manager start

./ups_manager stop

./ups_manager config

./ups_manager status

./ups_manager restart

./TimeCfg.conf

./install.sco.sh

./Readme

./SendMSG.sh