Upload
donald-lane
View
264
Download
2
Tags:
Embed Size (px)
Citation preview
UNIT 2
FREQUENCY CONTROL AND AUTOMATIC GENERATION CONTROL
IMPORTANCE OF FREQUENCY CONTROL
If frequency changes there won’t be get required receiving end voltage.
When two systems working at diff. frequency are tied together to make same frequency by frequency converting station.
Change in real power affect mainly the system frequency, while reactive power is less sensitive to changes in frequency and is mainly dependent on changes in voltage magnitude.
The load frequency control (LFC) loop controls the real power and frequency and the automatic voltage regulator (AVR) loop regulates the reactive power and voltage magnitude.
AUTOMATIC GENERATION CONTROL
PURPOSE OF AGC
To maintain power balance in the system.
Make sure that operating limits are not exceeded:- Generators limit Tie-lines limit
Make sure that system frequency is constant (not change by load).
OVERVIEW OF AGC
Load is always changing.
To maintain power balance, generators need to produce more or less to keep up with the load.
When Gen < Load (Gen > Load), generator speed and frequency will drop (rise).
=> We use this generator speed and frequency as control signals!
3 COMPONENTS OF AGC
Primary control Immediate (automatic) action to sudden change of load.For example, reaction to frequency change.
Secondary controlTo bring tie-line flows to scheduled.Corrective actions are done by operators.
Economic dispatchMake sure that the units are scheduled in the most
economical way. This is function of primary and secondary control of AGC.
If the load on the system is increased, the turbine speed drops before the governor can adjust the input of the steam to the new load.
The speed of the rotor can be maintained constant by adding an integrator. The integral unit monitors the average error over a period of time and will overcome the offset.
Thus, as the system load changes continuously, the generation is adjusted automatically to restore the frequency to its nominal value. This scheme is known as automatic generation control (AGC).
CONCEPT OF AUTOMATIC GENERATION CONTROL
As shown in the block diagram, the valve opening changes either by changing the reference setting or by the change in speed (or frequency). This is called primary regulation.
The reference setting can also be changed remotely by power system load frequency control. This is called secondary regulation.
Only some generating units in a power system may be used for secondary regulation
STATIC SPEED-POWER CURVE
• From,
• Primary control: Immediate change corresponding to sudden change of load (frequency)
• Secondary control: Change in setting control power to maintain operating frequency.
• The higher R (regulation), the better.
R
PP CM
1
Slope = -R
1MP 2MP1CP 2CP
MP
= =
1
2
0
AGC FOR SINGLE AREA
• System Modeling• Single Generator• Multi Generators, special case: two
generators
LFC FOR SINGLE AREA
AGC FOR MULTI AREAS
During transient period, sudden change of load causes each area generation to react according to its frequency-power characteristics.This is “called primary control”.
This change also effects steady state frequency and tie-line flows between areas.
We need toRestore system frequency, Restore tie-line capacities to the scheduled value, and,Make the areas absorb their own load.
This is called “secondary control”.
AGC FOR MULTIPLE AREA SYSTEM
AGC FOR 2-GENERATOR: BLOCK DIAGRAM
sGM 2
2
1
R
+-
sGP222MP
2LP
2CP212 PP
+
-
- 2s
-
sGM1
1
1
R
+-
sGP11
1MP1LP
1CP
121 PP
+
-
-
1s
+
-112T
Load ↑
Frequency 2 ↓
Different phase angle ↑Transfer power 12 ↑
Frequency 1 ↓
Governor 2 sense speed ↓, try to ↑ mechanical power
Governor 1 sense speed ↓, try to ↑ mechanical power
Steady state: New (lower) system Frequency
AGC FOR 2-GENERATOR: STATIC SPEED-POWER CURVE
Load increases. Frequency drops. Steady state is reached
when frequency of both generators is the same.
1MP 2MP
MP
1
2
0
+ = Change in total load
1MP 2MP
STEADY STATE FREQUENCY CALCULATION:2 GENERATORS
• From• Consider the frequency at steady state,
• But, , ,and• Then,
iLiiiiLiiiiiMi PPDPPDMP ~~
linetieLM PPDP 1111
~
linetieLM PPDP 2222
~
21 1
1
1
RPM
22
1
RPM
2121
21
11~~RR
DD
PP LL
Area Control Error (ACE)
Control setting power of each area needs to be adjusted corresponding to the change of scheduled tie-line capacity and change of system frequency.
ACE measures this balance, and is given by,
for two area case. Where = Frequency bias setting of area i (>0) and
1121 BPACE
2212 BPACE
iB
iLii RDB
1
TIE-LINE MODEL ( )
From power flow equation,
Approximate at normal operating condition, we have
Then, for small change,
Where is called stiffness or synchronizing power coefficient
iP
n
kkiikkii BVVP
1
sin
n
kkiiki BP
1
n
kkiik
n
kkiiki TBP
11
ikT
19
ACE: TIE-LINE BIAS CONTROL
Use ACE to adjust setting control power, , of each area.
Goal:To drive ACE in all area to zero.To send appropriate signal to setting control
power, Use integrator controller so that ACE goes to
zero at steady state.
CiP
20
AGC FOR 2-AREA WITH TIE-LINE BIAS CONTROL : STATIC SPEED-POWER CURVE
Load in area 2 increases. Frequency of both area
drops. ACE makes Control power
of area 2 increases. Steady state is reached when
frequency is back at the operating point and generator in area 2 take its own load.
1MP 2MP
MP
1
2
0
+ = Change in load 2
1MP 2MP
2’
1MP 2MP