TYPICAL ROOF CONDITION LAYOUT
1
3
16
Typical Roof Condition Layout...............................
Low Eave Isometric Floating...................................
Low Eave Floating .................................................
High Eave Floating .............................................
High Eave Fixed .................................................
Wall to Roof High Eave Floating.............................
Wall to Roof High Eave Fixed.................................
Panel Slope Transition Floating..............................
Panel End & Closure Isometric...............................
Center Clip Fixed ...................................................
Low Eave Gutter Isometric Floating........................
Low Eave Gutter Floating.......................................
Internal Gutter.........................................................
Internal Gutter At Parapet Wall...............................
Internal Gutter ........................................................
Hip/Ridge Cap Floating...........................................
Hip/Ridge Cap Floating...........................................
Vented Ridge Fixed................................................
Hip To Rake Transition...........................................
Hip To Rake Transition...........................................
Hip - Floating...........................................................
Rake Detail..............................................................
Rake At Stepped Eave....................................................
Rake Installation..............................................................
Wall to Rake Flashing.....................................................
Wall At Sloping To Flat Roof...........................................
Wall To Rake Step Flashing...........................................
Wall To Rake Expansion Joint........................................
Panel Expansion Joint....................................................
Rake At Valley Isometric................................................
Rake At Valley................................................................
Equipment Curb Flashing Plan.......................................
Equipment Curb Flashing Isometric................................
Equipment Curb Flashing - Section B.............................
Equipment Curb Flashing - Section C.............................
Equipment Curb Flashing - Section D.............................
Pipe Penetration.............................................................
Gutter Flashing ..............................................................
Rake And Eave Flashing Condition................................
Rake And Hip Flashing Condition...................................
Downspout......................................................................
Knee Detail.....................................................................
Snow Guard....................................................................
Lighting Protection..........................................................
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
18
29
37
19
35
6
47
FIXED POINTS
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
10
2
17
42
4
5
13
12
22
23
34
36
36
7
15
11
20
BUTYL TUBE SEALANT
RIGID INSULATION (NBM)
ROOF DECK (NBM)
#6 HEX TEK.
(4) PER PANEL MIN.
OR POP RIVETS
DRIP ANGLE
SLR FIXED
OR SLIDING CLIP
EAVE FLASHING
SLR PANEL
40 MIL. ICE AND WATER SHIELD
UNDERLAYMENT (NBM)
BUTYL TUBE SEALANT
LOW EAVE ISOMETRIC-FLOATING
2
*NBM = Not By Morin
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
SLR PANEL
BUTYL TUBE
SEALANT
EAVE TRIM
UNDERLAYMENT
(NBM)
RIGID INSULATION
(NBM)
ROOF DECK
(NBM)
FASTENERS (2) PER
CLIP MIN.
1"X1" DRIP
ANGLE
LOW EAVE-FLOATING
3
Eave design must be able to allow for the total amount of expansion of the panel if the ridge is fixed. A drip trim
should be used to stiffen the flat of the panel and block wind driven rain. This piece also assists in limiting the
amount of bow of the flat under high wind.
Since sealant between roof underlayment and panel may limit expansion or rupture, protection against wind
blown water infiltration is provided by folding the panel under, which allows for thermal expansion.
Detail must be designed to allow for maximum thermal movement. Floating eave requires fixed ridge.
6
"
-
8
"
m
a
x
im
u
m
*NBM = Not By Morin
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
SLR CLIP
1
"
m
in
.
SLR CLIP
RIDGE CAP
FASTENERS (2)
PER CLIP MIN.
RIGID INSULATION
(NBM)
FASTENERS (5)
PER PANEL MIN.
BEARING PLATE
Note:
-Floating high eave requires fixed low eave.
-Gap as required for thermal movement.
-Use J-support for panel with Clip Relief, Pencil Ribs and Striated.
ROOF DECK
(NBM)
SEALANT AROUND
NOTCHED RIBS
"J" SUPPORT AT
PANEL ENDS
HIGH EAVE - FLOATING
CONTINUOUS "Z"
NOTCHED AROUND
PANELS RIBS IN FIELD
HIGH HEAT ICE AND
WATER SHIELD REQ'D
40 MIL MIN. (NBM)
4
SEALANT
*NBM = Not By Morin
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
HIGH EAVE - FIXED
Note:
-Fixed high eave requires floating low eave
-Gap as required for thermal movement
- Use J- support for panel with Clip Relief, Pencil Ribs and Striated
RIDGE CAP
FASTENERS (5)
PER PANEL MIN.
"J" SUPPORT AT
PANEL ENDS
FIXED SLR CLIP
SEALANT AROUND
NOTCHED RIBS
RIGID INSULATION
(NBM)
BEARING PLATE
ROOF DECK
(NBM)
CONTINUOUS "Z"
NOTCHED AROUND
PANELS RIBS IN FIELD
HIGH HEAT ICE AND
WATER SHIELD REQ'D
40 MIL MIN. (NBM)
5
SEALANT
*NBM = Not By Morin
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
FIXED FASTENERS
2 PER PANEL
FASTENERS (2)
PER CLIP MIN.
FASTENERS (2) PER CLIP MIN.
ROOF DECK
(NBM)
SLR FLOATING CLIP
SEALANT (NBM)
HIGH EAVE
FLASHING
MASONRY FASTENER
BUTYL SEALANT
2" MIN.
FASTENERS (5) PER
PANEL MIN.
SEALANT
AROUND RIBS
"Z" CLOSURE
NOTCH AROUND
RIBS IN FIELD
"J" SUPPORT AT
PANEL ENDS
THROUGH WALL FLASHING
WALL TO ROOF HIGH EAVE - FLOATING
6
High eave flashings are similar to ridge conditions. Attention must be given to the design for sealing and panel
movement. Where snow buildup is a concern the design of the trim must take into account the excess loading.
Floating high eave requires fixed low eave. Use J- support for panel with clip relief, pencil ribs and striated.
Floating high eave requires fixed low eave and fixed high eave required floating eave.
URETHANE SEALANT
BETWEEN FLASHING
AND MASONRY
SEALANT
*NBM = Not By Morin
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
FASTENERS (2) PER CLIP MIN.
ROOF DECK
(NBM)
SEALANT (NBM)
HIGH EAVE
FLASHING
MASONRY FASTENER
BUTYL SEALANT
2" MIN.
FASTENERS (5) PER
PANEL MIN.
"J" SUPPORT AT
PANEL ENDS
THROUGH WALL FLASHING
WALL TO ROOF HIGH EAVE - FIXED
7
High eave flashings are similar to ridge conditions. Attention must be given to the design for sealing and panel
movement. Where snow buildup is a concern the design of the trim must take into account the excess loading.
Floating high eave requires fixed low eave. Use J- support for panel with clip relief, pencil ribs and striated.
Floating high eave requires fixed low eave and fixed high eave required floating eave.
URETHANE SEALANT
BETWEEN FLASHING
AND MASONRY
SEALANT
*NBM = Not By Morin
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
SLR FIXED CLIP
SEALANT
AROUND RIBS
"Z" CLOSURE
NOTCH AROUND
RIBS IN FIELD
PANEL SLOPE TRANSITION - FLOATING
Note:
- Floating panels require fixed connections at opposite ends.
- Use J- support for panel with clip relief, pencil ribs and striated.
8
SLR CLIP
BUTYL TUBE SEALANT
FASTENERS
(2) PER CLIP MIN.
METAL DECK (NBM)
RIGID INSULATION (NBM)
SLR CLIP
CONTINUOUS "Z"
CLOSURE NOTCH
AROUND RIBS IN FIELD
SEALANT AROUND RIBS
1
8
"X1" CONTINUOUS
BUTYL TAPE
"J" SUPPORT AT
PANEL ENDS
*NBM = Not By Morin
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
TRANSITION FLASHING
"Z" CLOSURE NOTCHED
AROUND RIBS IN FIELD
SLR PANEL
CONTINUOUS LINE OF
DOUBLE BEADED BUTYL
TAPE SEALANT
"J" SUPPORT AT
PANEL ENDS
PANEL END & CLOSURE ISOMETRIC
9
(5) FASTENERS PER
PANEL MIN.
SEALANT
Note:
- Use larger J- support for panel with clip relief, pencil ribs and striated.
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
SLR FIXED CLIP
6" X 6" BEARING PLATE
SLR METAL PANEL
CENTER CLIP-FIXED
SLR FIXED CLIP
6" X 6" BEARING PLATE
22 GA. MINIMUM
SLR METAL PANEL
10
2 FASTENERS MINIMUM
The roofing system as a floating system must have some means by which to attach it to the structure & yet not restrict its
floating ability to handle the thermal expansion/ contraction found in the system. Because of the above reasons, Morin’s
SLR panels must be positively attached at one or more purlins along a line perpendicular to the panel’s vertical rib. The
ideal location of what the panel industry calls a “fix point line” is at the center of the panel run. By having the fixed point at
this location, the amount of travel of the panel over the clip is held to a minimum. Where you have very long panel runs, it
may be required to have more then one row of fixed points. When this is necessary, then the rows should be on adjacent
rows of purlins. Refer to fixed point details in this manual for methods of installation and recommended locations.
Acceptable alternate locations for these fixed point are at either the ridge or eave of the roof. Exceptions to all of the
recommended fixed point locations may be needed because of various design restrictions such as large roof penetrations,
restraints at the ends of a panel run, an irregular shaped roof surface or at roof hip and valley locations. Panel lengths over
50' require fixed point at mid-run.
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
RIGID INSULATION (NBM)
ROOF DECK (NBM)
40 MIL ICE AND
WATER SHIELD
UNDERLAYMENT (NBM)
GUTTER STRAP
GUTTER
SUPPLEMENTAL GUTTER
SUPPORT STRAPS AS
REQUIRED 2" WIDE
SLR CLIP
SLR PANEL
LOW EAVE GUTTER ISOMETRIC-FLOATING
11
*NBM = Not By Morin
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
SLR CLIP
SLR PANEL
40 MIL ICE AND
WATER SHIELD
(NBM)
RIGID INSULATION
(NBM)
ROOF DECK
(NBM)
FASTENERS (2)
PER CLIP MIN.
EAVE TRIM
SUPPLEMENTAL
GUTTER STRAP
2" WIDE
GUTTER
GUTTER STRAP
BUTYL TUBE SEALANT
BETWEEN RIBS
AND UNDER PANEL
1"X1" DRIP ANGLE
LOW EAVE WITH GUTTER
12
Consideration during design must be given to capacity, overflow, accessibility for cleaning, and aesthetics.
Attachments must provide structural supports and allow for thermal movement. Protection from ice and snow
must be considered during the detailing of this condition. Edge of gutter should be reinforced in areas of snow or
ice accumulation. The edge of the gutter should be below the roof plane to allow for evacuation of the snow
build-up. The gutter should be independent of the roof panel as not to inhibit the thermal movement of the roof.
Floating eave requires fixed ridge.
*NBM = Not By Morin
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
1
"
m
in
.
FASTENERS (2) PER CLIP MIN.
FLOATING SLR CLIP
BUTYL TUBE SEALANT
BETWEEN RIBS AND
UNDER PANEL
GUTTER FLASHING
METAL DECK (NBM)
RIGID INSULATION (NBM)
GUTTER DRAIN
"Z" CLOSURE NOTCH
AROUND RIBS IN FIELD
SEALANT AROUND
RIBS
"J" SUPPORT AT
PANEL ENDS
INTERNAL GUTTER
13
Where an exposed gutter may distract from the aesthetics of the building, an internal gutter may be required.
The condition and roof design must allow for this condition to be “fixed” against thermal movement.
Considerations must be made in areas of ice or snow to avoid blockage of the gutter or drains. Overflow
scuppers are required at each end of the gutter. This design relies on sealant to form the weather barrier.
Designers should be aware of the hazards and allow for adequate drainage. Morin requires membrane liner for
all internal gutter (NBM). Use J- support for panel with clip relief, pencil ribs and striated.
*NBM = Not By Morin
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
SLR FIXED CLIP
1" m
in.
SLR CLIP
METAL DECK
(NBM)
FASTENERS
(2) PER CLIP MIN.
40 MIL ICE AND
WATER SHIELD
(NBM)
PARAPET CAP
CONTINUOUS
CLEAT
Note:
-Over flow scupper recommended at ends of gutter.
-Morin recommends use of membrane liner for all internal gutter (NBM).
GUTTER
FLASHING (NBM)
INTERNAL GUTTER AT PARAPET WALL
14
BUTYL TUBE SEALANT
BETWEEN RIBS
AND UNDER PANEL
*NBM = Not By Morin
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
1"
min
.
SLR CLIP
FASTENERS (2)
PER CLIP MIN.
METAL DECK (NBM)
RIGID INSULATION (NBM)
Note:
-Over flow scupper recommended at ends of gutter.
-Morin recommends use of membrane liner for all internal gutter (NBM).
GUTTER DRAIN (NBM)
OVERFLOW SCUPPER
AT ENDWALLS
GUTTER SUPPORT (NBM)
INTERNAL GUTTER
15
BUTYL TUBE SEALANT
BETWEEN RIBS
AND UNDER PANEL
*NBM = Not By Morin
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
1
"
m
in
.
1
"
m
in
.
SLR CLIP
RIDGE CAP
BEARING PLATE
FASTENERS
(2) PER CLIP MIN.
RIGID INSULATION
(NBM)
ROOF DECK (NBM)
FASTENERS
(5) PER PANEL MIN.
"Z" CLOSURE SET ON
DOUBLE BEAD BUTYL
SEALANT
SEALANT
AROUND RIBS
"J" SUPPORT AT
PANEL ENDS
HIP/RIDGE CAP - FLOATING
16
If ridge condition is required to “float”, slip joints at each side must be made to accommodate the
required expansion. Clip fasteners must be long enough to fasten into low cells of decking. Use
J- support for panel with clip relief, pencil ribs and striated.
*NBM = Not By Morin
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
4"
HIP/RIDGE CAP-FIXED
FASTENERS
(5) PER PANEL MIN.
(FIXED POINT)
SEALANT
AROUND RIBS
RIDGE CAP
RIGID INSULATION
(NBM)
ROOF DECK (NBM)
FASTENERS
(2) PER CLIP MIN.
BEARING PLATE
4"
17
SUPPORT FLASHING
20 GA. MINIMUM
"Z" CLOSURE SET ON
DOUBLE BEAD BUTYL
SEALANT
BUTYL SEALANT
Note:
- Clip fasteners must be long enough to fasten into low cells of decking.
- Use J- support for panel with clip relief, pencil ribs and striated.
*NBM = Not By Morin
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
SLR CLIP
VENTED RIDGE - FIXED
RIGID INSULATION
(NBM)
ROOF DECK (NBM)
BEARING
PLATE
RIDGE CAP
SLR
FIXED CLIP
V-600TE CORE-A-VENT
Note:
- Clip fasteners must be long enough to fasten into low cells of decking.
- Use J- support for panel with clip relief, pencil ribs and striated.
4"
SEALANT
AROUND RIBS
FASTENERS
(2) PER CLIP MIN.
FASTENERS
(5) PER PANEL MIN.
18
"Z" CLOSURE SET ON
DOUBLE BEAD BUTYL
SEALANT
FASTENER WITH NEOPRENE
WASHER AT 12" O.C
*NBM = Not By Morin
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
GABLE SUPPORT
RIGID INSULATION (NBM)
METAL DECK (NBM)
SLR CLIP
OPTIONS:
1) Field cut starter panel so that rake panels on both ends of roof are of same width requires field bending of cut panel
to fit under formed 18 gauge support (as shown below).
2) Start roof with full panel, insert female leg under formed 18 gauge support.
3) Use J- support for panel with clip relief, pencil ribs and striated.
#12 X
7
8
", HWH, W/W,
(DO NOT PENETRATE PANEL)
"Z" CLOSURE NOTCH
AROUND RIBS IN FIELD
SEALANT AROUND
RIBS
FASTENERS (2) PER CLIP MIN.
DOUBLE BEADED SEALANT
"J" SUPPORT AT
PANEL ENDS
FOAM BLOCK
W/ BUTYL TAPE SEALANT
HIP/ RAKE CAP
19
HIP TO RAKE
*NBM = Not By Morin
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
SLR METAL
PANEL
RIGID INSULATION (NBM)
METAL DECK (NBM)
SLR CLIP
OPTIONS:
1) Field cut starter panel so that rake panels on both ends of roof are of same width requires field bending of cut panel
to fit under formed 18 gauge support (as shown below).
2) Start roof with full panel, insert female leg under formed 18 gauge support.
3) Use J- support for panel with clip relief, pencil ribs and striated.
"Z" CLOSURE NOTCH
AROUND RIBS IN FIELD
SEALANT AROUND
RIBS
FASTENERS (2) PER CLIP MIN.
DOUBLE BEADED SEALANT
"J" SUPPORT AT
PANEL ENDS
HIP/ RAKE CAP
20
HIP TO RAKE
*NBM = Not By Morin
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
SLOPE
HIP/RIDGE CAP
METAL HIP/RIDGE CLOSURE SUPPLIED
10' LONG BEVEL CUT TO FIT SLOPE
DOUBLE BEADED
SEALANT
21
HIP/RIDGE ISOMETRIC
METAL CLOSURE NOTCHED AT THE
ENDS TO ACCEPT PANELS
PANEL WIDTH
*NBM = Not By Morin
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
#12 X
7
8
", HWH, W/W,
(DO NOT PENETRATE
PANEL)
FOAM BLOCK
W/ BUTYL TAPE SEALANT
RAKE TRIM
RIGID INSULATION (NBM)
ROOF DECK (NBM)
SLR PANEL
GABLE SUPPORT
BEARING PLATE
SLR PANEL CLIP
22
RAKE DETAIL
The roof and structure must be allowed to move independently of each other. Thermal movement cannot be
restricted. The gable clip is designed to allow this movement while holding down the roof panel. It will also hold
the roof panel off the structure the same distance as both hold down clips. Since the gable clip is stationary, the
gable trim piece can be attached to it for positive anchoring. The design of the gable flashing can be modified to
suit the individual project as long as the basic concept is maintained. Spacing for gable clip is 2’0” o.c. maximum.
For longer purlin spacing a gable clip trim is available in 10’0” sections.
Options:
1) Field cut starter panel so that rake panels on both ends of roof are of same width. requires field bending of cut
panel to fit under formed gable support .
2) Start roof with full panel, insert female leg under formed gable support.
3) Clip fasteners must be long enough to fasten into low cells of decking
FASTENER WITH
NEOPRENE WASHER
*NBM = Not By Morin
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
RIGID INSULATION (NBM)
ROOF DECK (NBM)
BEARING PLATE
SLR PANEL CLIP
RAKE FLASHING
BUTYL SEALANT
Note:
Clip fasteners must be long enough to fasten into low cells of decking.
SLR PANEL
RAKE DETAIL (OPTIONAL)
23
*NBM = Not By Morin
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
FASTENER WITH
NEOPRENE WASHER
COMPLETE ASSEMBLY
STEP: 1
FASTEN RAKE CLEAT
STEP: 2
RAKE FLASHING
STEP: 3
2 ROWS OF CONTINUOUS
BUTYL SEALANT
STEP: 4
FIELD CUT PANEL
STEP: 5
FIELD NOTCH AND BEND
TO CREATE OPEN HEM
24
STEPPED EAVE RAKE ISOMETRIC INSTALLATION
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
RAKE FLASHING
FOAM BLOCK
W/ BUTYL SEALANT
FASTENERS (2) PER CLIP MIN.
RIGID INSULATION (NBM)
METAL DECK (NBM)
METAL WALL
RAKE FLASHING
FLASHING
#12 X
7
8
", HWH, W/W,
(DO NOT PENETRATE PANEL)
SLR METAL PANEL
SLR CLIP
GABLE SUPPORT
6"X6"
BEARING PLATE
25
WALL TO RAKE FLASHING
Since the width of the standing seam
roof can vary due to compression or
spreading during the installation, the
module can be altered to minimize
the endwall trim width. In cases of
fixed panel width or module, the
designer should center the roof
panels if possible, to reduce the
width of the trim pieces.
The endwall flash should be sloped
to allow drainage of water to avoid
leaks at joints in the trim. Reinforcing
of the trim may be required at large
widths to support the joints.
URETHANE SEALANT
BETWEEN FLASHING
AND MASONRY
12
1
4
" MIN.
*NBM = Not By Morin
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
RIGID INSULATION (NBM)
METAL DECK (NBM)
FASTENERS (2)
PER CLIP MIN.
SLR CLIP
BUTYL TUBE SEALANT BETWEEN
RIBS AND UNDER PANEL
TRANSITION FLASHING
SLR CLIP
6" X 6" BEARING PLATE
3
8
" SUPPORT (NBM)
ALIGN FACE OF TRIM WITH
CONTINUOUS RAKE CLIP AND
STEP RAKE FLASHING
RAKE AT SLOPING TO FLAT ROOF (FLOATING)
26
*NBM = Not By Morin
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
THROUGH-WALL FLASHING
STEP RAKE FLASHING
MASONRY BLOCK (NBM)
SLR METAL PANEL
SLR METAL
PANEL CLIP
GABLE SUPPORT
FASTENERS (2) PER CLIP MIN.
RIGID INSULATION (NBM)
METAL DECK (NBM)
#12 X
7
8
", HWH, W/W,
(DO NOT PENETRATE THRU THE PANEL)
SLR METAL PANEL
FOAM BLOCK
W/ BUTYL SEALANT
27
WALL TO RAKE STEP FLASHING
6" X 6" BEARING PLATE
MASONRY FASTENER
URETHANE SEALANT
BETWEEN FLASHING AND MASONRY
12
1
2
" MIN.
*NBM = Not By Morin
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
METAL DECK (NBM)
#12 X
7
8
", HWH, W/W,
(DO NOT PENETRATE PANEL)
RIGID INSULATION (NBM)
COMPRESSIBLE INSULATION
(NBM)
1" 1" 1"
FOAM BLOCK
W/ BUTYL SEALANT
GABLE SUPPORT
THROUGH-WALL
FLASHING
RAKE FLASHING
28
WALL TO RAKE EXPANSION JOINT
6"X6" BEARING PLATE
URETHANE SEALANT
BETWEEN FLASHING
AND MASONRY
OPTIONS:
1) Field cut starter panel so that rake panels on both ends of roof are of same width requires field bending of
cut panel to fit under continuous rake clip (as shown below).
2) start roof with full panel, insert female leg under continuous rake clip.
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
*NBM = Not By Morin
METAL DECK (NBM)
RIGID INSULATION (NBM)
1" 1" 1"
#12 X
7
8
", HWH, W/W,
(DO NOT PENETRATE PANEL)
FOAM BLOCK
W/ BUTYL SEALANT
SLR METAL PANEL
CONTINUOUS GABLE SUPPORT
BUTYL TUBE SEALANT ON
TOP OF GABLE SUPPORT
29
PANEL EXPANSION JOINT
Some building designs require an expansion joint to accommodate movement of the structure. The detail must
be designed to allow movement in the anticipated directions. Several proprietary products are available which
can be integrated into this basic design.
Options:
1) Field cut starter panel so that rake panels on both ends of roof are of same width. Requires field bending of
cut panel to fit under gable support (as shown below).
2) Start roof with full panel, insert female leg under gable support.
*NBM = Not By Morin
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
VALLEY FLASHING
EAVE CLEAT
1
8
"X1" CONTINUOUS
TAPE SEALANT
20 GA. SUB-PLATE
SLR METAL PANEL
30
RAKE @ VALLEY (FLOATING)
#10 X 1" TEK. WAFER
HEAD FASTENERS
AT 6" O.C.
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
4" OF SEALANT IN
STIFFENING RIBS
SLR CLIP
BUTYL TUBE SEALANT
BETWEEN RIBS
AND UNDER PANEL
RIGID INSULATION (NBM)
METAL DECK (NBM)
VALLEY
FLASHING
FASTENERS (2)
PER CLIP MIN.
S
A
M
E
H
T
.
A
S
P
A
N
E
L
L
A
R
G
E
R
A
T
L
O
W
S
L
O
P
E
20 GA. SUB-PLATE
FASTENERS 6" O.C
SLR METAL
PANEL
31
RAKE AT VALLEY FLOATING
6
"
M
I
N
.
Valley flashing must allow for sufficient area to carry anticipated runoff without overflow or backup under the roof
edge. The raised center assists in diversion of water and allows for thermal movement. Floating valley requires
fixed hip/ ridge.
1
8
" X 1" CONTINUOUS
DOUBLE BEAD
BUTYL TAPE SEALANT
*NBM = Not By Morin
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
12" M
IN
BA
CK
P
AN
B B
C
D
C
D
32
CU
RB
LE
NG
TH
6"
EQUIPMENT CURB FLASHING PLAN VIEW
5"
AP
RO
N
Large openings for equipment or hatchways require a curb with means of diverting the water around the
opening. Set and secure roof curb on support framing. At least two parallel curb walls must be on support
framing. In high load areas engineer needs to check for proper support. Loads shall not be supported by
cantilever sections exceeding 1’0” in length. Cut roof panels to fit snugly around curb walls and to within 1” of the
water diverter. Apply a wide band of tape caulk to the top side of curb flanges. Install and seal closures in ends
of panels. Plug and caulk all rib ends. Press roof panels into place. Fasten roof panels through curb flanges to
support steel using suitable fasteners for the roof system. A spacing of approximately 3” should
be used. Inspect installation and fasteners. Apply an exterior sealant to seal seams around all sides of curb to
insure a weathertight seal. In all cases the curb assembly is capped by a collar or skirt that extends down over
the curb. Curb to be fixed to panel only. Allowance must be made at equipment curb and trim to allow for thermal
movement.
*NBM = Not By Morin
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
SIDE FLASHING
BACK PAN
CURB PENETRATION
33
EQUIPMENT CURB FLASHING
BACK PAN
APRON
SIDE FLASHING
1" TABS
CU
RB
HE
IG
HT
1
2
"
M
I
N
.
1
1
2
"
V
A
R
I
E
S
CU
RB
HE
IG
HT
C
U
R
B
L
E
N
G
T
H
CU
RB
HE
IG
HT
5
"
2"
1
2
"
M
I
N
.
1" TABS
5
"
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
CURB CAP (NBM)
FASTENERS (2) PER CLIP MIN.
METAL DECK (NBM)
RIGID INSULATION (NBM)
6" minimum
TRANSITION FLASHING
34
EQUIPMENT CURB - SECTION B
*NBM = Not By Morin
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
18 GA GALVANIZED
CAP (NBM)
FASTENERS (2) PER CLIP MIN.
METAL DECK (NBM)
RIGID INSULATION (NBM)
BUTYL TUBE
SEALANT
SLR CLIP
6"-10" M
A
X
IM
U
M
DOUBLE BEAD CONTINUOUS
1
8
" x1" BUTYL TAPE SEALANT
18 GA GALVANIZED
CAP (NBM)
35
EQUIPMENT CURB - SECTION C
CURB CAP (NBM)
BUTYL TAPE
SEALANT
BACK PAN
*NBM = Not By Morin
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
CURB CAP (NBM)
FASTENERS (2) PER CLIP MIN.
METAL DECK (NBM)
RIGID INSULATION (NBM)
18 GA GALVANIZED
CAP (NBM)
APRON
SLR CLIP
1" MIN.
SEALANT
AROUND RIBS
"Z" CLOSURE
NOTCH AROUND RIBS IN FIELD
DOUBLE BEAD
1
8
"X1"
BUTYL TAPE SEALANT
"J" SUPPORT AT
PANEL ENDS
36
EQUIPMENT CURB - SECTION D
*NBM = Not By Morin
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
#14 X
7
8
", TEK 3, HWH, W/W,
PAINTED 2" O.C.
BEFORE INSTALLING THE DEKTITE,
PLACE CONTINUOUS BEAD OF
SEALANT AROUND PIPE AT HEIGHT
OF BOOT TOP
STAINLESS STEEL
PIPE CLAMP
APPLY SEALANT BETWEEN BOTTOM
OF DEKTITE AND TOP OF PANEL
37
PIPE PENETRATION DETAIL
Notes:
1) Attach dektite to panel only to allow thermal movement.
2) Center pipe penetration within panel width if possible.
3) Keep base of dektite away from panel edges (minimum 2").
4) Provide 1" clearance between edge of pipe and panel hole.
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
6"
1
8
" GAP
GUTTER SPLICE PLATE
GUTTER LAP DETAIL
4"
2" 1"1"
1" LAP
GUTTER EXPANSION DETAIL
38
GUTTER FLASHING CONDITIONS
3
4
" 1
1
2
"
END CAP
END CAP
END CAP
4
"
GUTTER EXPANSION DETAIL
3
4
"
EXPANSION
COVER
SET IN SEALANT
Note: Use expansion joint every 25'
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
4"
RAKE LAP DETAIL
6
"
L
A
P
4"
EAVE LAP DETAIL
EAVE INSIDE SPLICE PLATE
4
"
N
O
T
C
H
NOTCH IN BOTTOM LEG
39
RAKE AND EAVE FLASHING CONDITION
Note: Shingle laps in direction
of water flow.
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
6"
4
"
N
O
T
C
H
NOTCH IN BOTTOM LEG
SPLICE PLATE
6"
RIDGE CAP - LAP DETAIL
6"
HIP CAP - LAP DETAIL
6
"
L
A
P
W
A
T
E
R
F
L
O
W
BUTYL SEALANT
BUTYL SEALANT
6" NOTCH IN
THE BOTTOM LEG
TYP. LAP DETAIL
40
RIDGE AND HIP FLASHING CONDITION
6
"
L
A
P
FASTEN PANEL CLOSURE
TO PANEL CLOSURE TO
FIX IN PLACE
Note: Field Notch Hems As Required.
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
DOWN SPOUT OUTLET
CENTER HEM
TYPICAL 4" X 3" ELBOW
DIMENSIONS WITH 6"
RETURN
41
DOWNSPOUT
4"
3"
4"
3"
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
KNEE CAP
PART A
MALE SIDE
OF THE PANEL
BUTYL TUBE SEALANT
6
"
NOTES:
- Adjacent clip must be fixed condition caulk all edges around splice plate.
- All dimensions are nominal.
- Fabricate trim to fit inside and outside of panel seam as req'd.
STEP 1
STEP 2
STEP 3
COMPLETED SET
BUTYL SEALANT
(SEE BELOW)
PART B
42
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
KNEE DEATAIL
F.S
F.S
SIDE VIEW
ASSEMBLY
SNOW GUARD
2" STRIP OF MATCHED
GAUGE & COLOR STRIP
SLR METAL PANEL
1
2
"
M
I
N
CROSS MEMBER CONTINUOUS
43
SNOW GUARD
S
L
O
P
E
Note:
1) Mount S-5 clamp directly to top of panel rib with set screw.
2) Install 2" color strip from panel flatstock into snow guard.
3) Connect clip to snow guard, one per panel, centered.
4) Connect assembly to s-5-z clamps.
MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501MORINCORP.COM * BRISTOL, CT * FONTANA, CA * DELAND, FL * T: 800-640-9501
S-5 CLAMP
SLR PANEL CLIP
LIGHTNING ROD AIR TERMINAL
CONDUCTOR CABLE
S-5-U CLAMP
ALUMINUM TOP MOUNT
SIDE VIEW
SECTION CUT VIEW
CONDUCTOR CABLE
ALUMINUM TOP MOUNT
CLAMP
SLR PANEL
44
LIGHTNING PROTECTION
Note:
-Coat cables and clamp with bituminous.
-Coating as necessary to prevent galvanic reaction.