uncertainty tranformer using konvensional testing methode.pdf

Embed Size (px)

Citation preview

  • 7/30/2019 uncertainty tranformer using konvensional testing methode.pdf

    1/5

    THE UNCERTAINTY IN POWER TRANSFORMER FAULT DIAGNOSTICS USING

    CONVENTIONAL TESTING METHODS

    Yogendra Dev Vashishtha*, Paul Ascione* and Qi Su**

    * Power and Water Authority

    ** Monash University

    Abstract

    The average age of power transformers in Australia is about 25-35 years. Conventional oil tests,

    dissolved gas analysis (DGA) of oil, dielectric loss angle (DLA or tan) of winding and recoveryvoltage monitoring (RVM) are among many diagnostic techniques available. Power and Water

    Authority (PAWA) of Northern Territory refurbished five 66 / 11 kV, 1030 MVA, 2433 yearsold transformers. From the test results it is observed that a transformer which has very good

    results from these diagnostic tests and even has minimum moisture content in the winding

    (from RVM) may still have very poor mechanical integrity. Winding cellulose paper may be

    aged to such an extent (assessed from degree of polymerisation; DP) that any sudden force ortransient would cause failure. DP test is very difficult to perform regularly to ascertain

    mechanical integrity of winding paper. Furan analysis is another alternative to DP. Most of the

    times Furans are not detected and there is no universal correlation available for DP and Furans.Also, both ageing and moisture content influence Furans. Frequency response analysis (FRA)

    gives information regarding winding movement but it does not give much information about

    mechanical integrity of a winding which is essential for transformer reliability. This paper also

    compares moisture contents in the winding assessed from RVM and estimated from oil PPM(using Norris diagram) and estimated from winding DLA (based on Gussenbauers relationship).

    It appears that moisture content from RVM needs further validation and research to

    separate out ageing and moisture effects.

    1. INTRODUCTIONTransformers represent a high capital investment in a

    transmission substation at the same time as being a

    key element determining the loading capability of thestation within the network. With appropriate

    maintenance, including insulation reconditioning at

    the appropriate time, The technical life of atransformer can be in excess of 60 years. The end of

    life, however, can be strategic or economic.

    Quantitative, risk based approach can be used to aid

    costly investment decisions involving transformer life,

    otherwise made from a subjective viewpoint.

    Diagnostic systems have been listed under three

    categories as portable / periodic, continuous on-lineand specialist support [1]. There are various on-line

    monitors for load, operating conditions, gas-in-oil and

    moisture-in-oil are available these days [5]. Dissolvedgas analysis (DGA) is the main condition monitoring

    technique used at Power and Water Authority(PAWA) in the Northern Territory. Recovery Voltage

    Monitoring (RVM) has been found as a better

    technique to estimate moisture content in the winding

    paper insulation and its ageing. However, RVM does

    not distinguish between moisture content and

    degradation of paper. Some experiments have been

    reported correlating charging current with paperageing. Due to very limited work, these are not very

    conclusive. There is a possibility that charging current

    may also correlate with insulation resistance (IR) as

    we found RVM following polarisation index (PI).

    2. BACKGROUND

    2.1 The major factors involved in transformer

    insulation life are:

    Insulation moisture content

    Extent of oil oxidation

    Extent of cellulose degradationwater, CO,

    CO2 and furans

    Insulation Structure compression

    MOISTURE, OXYGEN and HEAT are the three

    ageing accelerators.

  • 7/30/2019 uncertainty tranformer using konvensional testing methode.pdf

    2/5

    2.2 Transformer Life Assessment Indicators:

    Insulation moisture content in oil provides a simple

    method of estimating residual life. The following

    guide may be useful (based on equilibrium water

    content of paper as a function of water content of

    impregnating transformer oil):

    3 % Maximum acceptable

    4 % Entering at risk zone

    5 %--6 % Considerable risk of failure

    7 % Failure imminent

    For life assessment, emission associated with the

    insulation ageing process is of interest, principally the

    levels of CO, CO2 and furans in the oil. Cellulose

    degradation can be assessed by furan (HPLC) analysisand preferably supported by degree of polymerisation

    (DP) for a more definitive assessment. DP testinvolves the removal of samples of paper from the

    winding insulation. Due to the need for internal access

    and expensive analysis, the test is only recommended

    on suspect transformer on the basis of DGA and other

    tests. DP is correlated to the tensile strength. The

    paper is considered to have no mechanical strength at

    a DP of 150 to 200. New transformers have DP above

    900.

    2.3 The following methods of moisturemeasurement are available:

    a) Direct measurement of the water content in

    paper on a layer by layer basis by means of

    Karl Fisher moisture meter (KFMM) using

    four bar probe.

    b) Water content in winding established from

    measurement of tan using Gussenbaeurscharacteristics [4].

    c) Water content in winding established from

    measurement of oil PPM using NorrisDiagram.

    d) Water content in winding established from

    RVM [6].

    2.4 Condition Monitoring Methods:Method Suitable for

    WINDING:

    IR & PI Moisture &

    ContaminationDDF & Capacitance Moisture &

    Contamination

    Winding Ratio Faulted turns

    Winding Resistance Conductor damage

    Impedance & Losses Winding movement

    Applied HV Poor dielectric

    Induced HV & PD Poor dielectric

    PD ( acoustic &electrical)

    Detect and locate PD

    Frequency Response

    Analysis

    (Transfer Function)

    Winding displacement,

    possible loose winding,

    and core faults

    Voltage Recovery Moisture in paper

    And ageing of paper

    Off-Line Test

    Vibration Analysis Slack winding &

    Mechanical faults

    DP & Gel Permeation Insulation degradation

    OIL:

    DGA & Ratio

    analysis

    Detecting incipient

    faults

    Furan Analysis Overheating and

    ageing of paperWater content Dryness

    Resistivity, Acidity,

    IFT

    and DDF

    Ageing of oil

    BUSHINGS:

    Tan Delta (DLA) Moisture &

    contamination

    Tan or dielectric loss angle (DLA) is a measure ofoverall quality of insulation system in terms of

    moisture and contamination.

    2.5 Recovery Voltage Method:

    If the DGA analysis is performed correctly (proper

    sampling, storage and calibration), most of the

    incipient faults in the oil may be detected. The paperinsulation is responsible for containing most of the

    moisture due to ageing and thermal stress. The paper

    insulation may fail under high electrical stress or may

  • 7/30/2019 uncertainty tranformer using konvensional testing methode.pdf

    3/5

    release moisture into the oil insulation. To detect

    ageing or moisture content it is necessary to analyse

    low frequency part of polarisation spectrum of

    dissipation factor. A tan would have been sufficientbut finding a sinusoidal source voltage of 0.001 Hz is

    very difficult [6]. The alternative is the recovery

    voltage measurement.

    It was found that IR & PI do not reflect complete

    information on polarisation process. Cases were

    reported where electrical motors having good PI werefound to have contaminated windings and also motors

    having poor PI had no problems in the winding

    insulation [2]. To resolve this, an one thousand

    seconds charging and discharging test (dc absorption)was developed. Recovery Voltage Method for

    transformer seems to be developed from this test.

    In RVM, winding is charged for known time and then

    shorted to ground for pre-decided time. The recovery

    voltage is then measured and dominant time constant

    is achieved which is essentially a polarisation time

    constant.

    Charging current is given as the sum of displacement

    current, the polarisation current and the conduction

    current. Polarising current is dependent on materialproperty and state of ageing. The polarisation of

    dielectric can be expressed as sum of various slowpolarisation phenomena like ion migration, slow

    relaxation and interfacial polarisation. Care must be

    taken in the interpretation of results of RVM, in

    particular the relative effects of moisture, genuine

    ageing and temperature [3].

    2.6 Condition Monitoring Model [1]

    Insulation DP of Failure Expert

    Ageing Insulation Rate Assessment

    Products Paper DataIn Oil Sample RVM

    INSULATION AGE FAILURE PROBABILITY

    Remaining Reliable Life

    Of Transformer

    Data Base Of

    Test Results

    Statistical Analysis

    RELIABILITY ANALYSIS

  • 7/30/2019 uncertainty tranformer using konvensional testing methode.pdf

    4/5

    3. REFURBISHMENT DATA

    Five 66/11kV, 10-30MVA transformers of 24 --33

    years old transformers were refurbished. Some of the

    important parameters are given in table 1, 2, 3 & 4.

    Table 1

    PI % Moisture

    (from RVM)

    % Mechanical

    Strength (from

    DP)

    1.09 2.52 3555

    1.79 2.10 3555

    1.80 1.74 3555

    2.34 1.56 3555

    2.40 1.42 2535

    Table 2

    % Moisture

    estimated from

    Oil PPM

    (Norris

    Diagram)

    % Moisture

    estimated from

    winding DLA

    (Cigre)

    % Moisture

    estimated from

    RVM

    2 2 1.74

    4 3 1.53

    2.5 2 2.52

    3.2 2.8 1.42

    1.5 < 0.5 2.10

    Table 3

    % Moisture

    (from RVM) DP

    % Mechanical

    Strength (from

    DP)

    2.09 250350 3555

    1.53 250350 3555

    1.21 200250 2535

    2.38 250350 3555

    2.18 250350 3555

    Norris diagram gives estimated percentage of moisture

    in paper based upon moisture content in oil (PPM) and

    oil temperature.

    Cigre paper has established a method to estimate

    moisture in paper based upon winding tan (DLA)and temperature.

    Table 4

    2-Furfural

    (PPM) DP

    % Mechanical

    Strength (from

    DP)

    1.10 200250 2535

    0.49 250350 35550.39 200250 2535

    0.54 250350 3555

    2-Furfurylalcohol, 2-Acetylfuran, 5-Methyl-2-Furfuraland 5-Hydroxymethyl-2-Furfural were not detectedin all four cases.

    4. DISCUSSION AND RESULTS It is observed from table 1 that RVM tends to

    follow PI in this case. However, a conclusion

    can not be drawn based on this limited

    number of observations. Essentially RVM

    does have DC absorption phenomenon and

    may / may not follow IR / PI.

    It is also observed that DP values (orpercentage retention of mechanical strength)

    do not correlate with any of the electrical

    parameters. DP reflects ageing and remaining

    mechanical strength of paper but it is not a

    diagnostic test as such.

    From table 3, it is evident that moisture

    percentage in the winding does not correlate

    to DP or mechanical strength retention.

    From table 2, it is evident that percentage ofmoisture estimated from Norris diagram(based upon oil PPM and temperature) and

    percentage moisture estimated from Cigre

    publication (based upon winding DLA) tend

    to agree to some extent. However, these do

    not correlate with moisture percentage

    estimated from RVM. This is due to the fact

    that RVM is a total reflection of ageing of

    cellulose paper and moisture content in the

    winding. There are no established methods

    to separate these components.

    It appears from table 4 that Furan analysis

    may, in some cases, give indication about

    paper ageing. However, most of the times,

    Furans are not detected and there is no

    universal correlation available for DP andFurans. Also, both ageing and moisture

    content influence Furans.

  • 7/30/2019 uncertainty tranformer using konvensional testing methode.pdf

    5/5

    5. CONCLUSION

    Mechanical integrity of paper is very important to

    ensure reliability of transformers. However at this

    stage this is not conclusively reflected in any of the

    electrical diagnostic tests available. There is a need for

    further research to validate RVM results and establish

    more effective method of estimating moisture contentin the cellulose paper winding.

    6.0 REFERENCES:

    1. D.ALLAN, Condition Monitoring & Life

    Assessment Of Aged Transmission / Sub-

    Transmission Plant, Lecture notes of the short

    course program on Insulation Condition

    Monitoring And Reliability Centred Maintenance

    Of Electrical Plant. February 1997, MonashUniversity.

    2. CAJETAN PINTO, An Improved Method of

    detecting Contamination of H.V. Stator Winding

    in the Field", Proceedings of the 20th Electrical

    Electronic Insulation Conference Boston, 1991,

    pp. 55-59.

    3. R.E.JAMES, Assessment Of Electrical

    Insulation, Proceedings of the 1998 ResidentialSchool in Electrical Power Engineering,

    Tasmania.

    4. I.GUSSENBAUER, Examination of Humidity

    Distribution in Transformer Models by Means of

    Dielectric Measurements, Cigre paper 15-02,

    International Conference on Large High Voltage

    Electric System, 1980.

    5. THOMAS LEIBFRIED, On-line Monitors Keep

    Transformers in Service, IEEE Computer

    Application in Power, July 1998, pp 36-42.

    6. SYED MOFIZUL ISLAM, Power Transformer

    Condition Monitoring Pacific Power

    International and University of NewcastleDevelopments, Lecture notes of the short course

    program on Insulation Condition Monitoring And

    Reliability Centred Maintenance Of Electrical

    Plant. February 1997, Monash University.