Upload
zaidbisma
View
215
Download
0
Embed Size (px)
Citation preview
7/30/2019 uncertainty tranformer using konvensional testing methode.pdf
1/5
THE UNCERTAINTY IN POWER TRANSFORMER FAULT DIAGNOSTICS USING
CONVENTIONAL TESTING METHODS
Yogendra Dev Vashishtha*, Paul Ascione* and Qi Su**
* Power and Water Authority
** Monash University
Abstract
The average age of power transformers in Australia is about 25-35 years. Conventional oil tests,
dissolved gas analysis (DGA) of oil, dielectric loss angle (DLA or tan) of winding and recoveryvoltage monitoring (RVM) are among many diagnostic techniques available. Power and Water
Authority (PAWA) of Northern Territory refurbished five 66 / 11 kV, 1030 MVA, 2433 yearsold transformers. From the test results it is observed that a transformer which has very good
results from these diagnostic tests and even has minimum moisture content in the winding
(from RVM) may still have very poor mechanical integrity. Winding cellulose paper may be
aged to such an extent (assessed from degree of polymerisation; DP) that any sudden force ortransient would cause failure. DP test is very difficult to perform regularly to ascertain
mechanical integrity of winding paper. Furan analysis is another alternative to DP. Most of the
times Furans are not detected and there is no universal correlation available for DP and Furans.Also, both ageing and moisture content influence Furans. Frequency response analysis (FRA)
gives information regarding winding movement but it does not give much information about
mechanical integrity of a winding which is essential for transformer reliability. This paper also
compares moisture contents in the winding assessed from RVM and estimated from oil PPM(using Norris diagram) and estimated from winding DLA (based on Gussenbauers relationship).
It appears that moisture content from RVM needs further validation and research to
separate out ageing and moisture effects.
1. INTRODUCTIONTransformers represent a high capital investment in a
transmission substation at the same time as being a
key element determining the loading capability of thestation within the network. With appropriate
maintenance, including insulation reconditioning at
the appropriate time, The technical life of atransformer can be in excess of 60 years. The end of
life, however, can be strategic or economic.
Quantitative, risk based approach can be used to aid
costly investment decisions involving transformer life,
otherwise made from a subjective viewpoint.
Diagnostic systems have been listed under three
categories as portable / periodic, continuous on-lineand specialist support [1]. There are various on-line
monitors for load, operating conditions, gas-in-oil and
moisture-in-oil are available these days [5]. Dissolvedgas analysis (DGA) is the main condition monitoring
technique used at Power and Water Authority(PAWA) in the Northern Territory. Recovery Voltage
Monitoring (RVM) has been found as a better
technique to estimate moisture content in the winding
paper insulation and its ageing. However, RVM does
not distinguish between moisture content and
degradation of paper. Some experiments have been
reported correlating charging current with paperageing. Due to very limited work, these are not very
conclusive. There is a possibility that charging current
may also correlate with insulation resistance (IR) as
we found RVM following polarisation index (PI).
2. BACKGROUND
2.1 The major factors involved in transformer
insulation life are:
Insulation moisture content
Extent of oil oxidation
Extent of cellulose degradationwater, CO,
CO2 and furans
Insulation Structure compression
MOISTURE, OXYGEN and HEAT are the three
ageing accelerators.
7/30/2019 uncertainty tranformer using konvensional testing methode.pdf
2/5
2.2 Transformer Life Assessment Indicators:
Insulation moisture content in oil provides a simple
method of estimating residual life. The following
guide may be useful (based on equilibrium water
content of paper as a function of water content of
impregnating transformer oil):
3 % Maximum acceptable
4 % Entering at risk zone
5 %--6 % Considerable risk of failure
7 % Failure imminent
For life assessment, emission associated with the
insulation ageing process is of interest, principally the
levels of CO, CO2 and furans in the oil. Cellulose
degradation can be assessed by furan (HPLC) analysisand preferably supported by degree of polymerisation
(DP) for a more definitive assessment. DP testinvolves the removal of samples of paper from the
winding insulation. Due to the need for internal access
and expensive analysis, the test is only recommended
on suspect transformer on the basis of DGA and other
tests. DP is correlated to the tensile strength. The
paper is considered to have no mechanical strength at
a DP of 150 to 200. New transformers have DP above
900.
2.3 The following methods of moisturemeasurement are available:
a) Direct measurement of the water content in
paper on a layer by layer basis by means of
Karl Fisher moisture meter (KFMM) using
four bar probe.
b) Water content in winding established from
measurement of tan using Gussenbaeurscharacteristics [4].
c) Water content in winding established from
measurement of oil PPM using NorrisDiagram.
d) Water content in winding established from
RVM [6].
2.4 Condition Monitoring Methods:Method Suitable for
WINDING:
IR & PI Moisture &
ContaminationDDF & Capacitance Moisture &
Contamination
Winding Ratio Faulted turns
Winding Resistance Conductor damage
Impedance & Losses Winding movement
Applied HV Poor dielectric
Induced HV & PD Poor dielectric
PD ( acoustic &electrical)
Detect and locate PD
Frequency Response
Analysis
(Transfer Function)
Winding displacement,
possible loose winding,
and core faults
Voltage Recovery Moisture in paper
And ageing of paper
Off-Line Test
Vibration Analysis Slack winding &
Mechanical faults
DP & Gel Permeation Insulation degradation
OIL:
DGA & Ratio
analysis
Detecting incipient
faults
Furan Analysis Overheating and
ageing of paperWater content Dryness
Resistivity, Acidity,
IFT
and DDF
Ageing of oil
BUSHINGS:
Tan Delta (DLA) Moisture &
contamination
Tan or dielectric loss angle (DLA) is a measure ofoverall quality of insulation system in terms of
moisture and contamination.
2.5 Recovery Voltage Method:
If the DGA analysis is performed correctly (proper
sampling, storage and calibration), most of the
incipient faults in the oil may be detected. The paperinsulation is responsible for containing most of the
moisture due to ageing and thermal stress. The paper
insulation may fail under high electrical stress or may
7/30/2019 uncertainty tranformer using konvensional testing methode.pdf
3/5
release moisture into the oil insulation. To detect
ageing or moisture content it is necessary to analyse
low frequency part of polarisation spectrum of
dissipation factor. A tan would have been sufficientbut finding a sinusoidal source voltage of 0.001 Hz is
very difficult [6]. The alternative is the recovery
voltage measurement.
It was found that IR & PI do not reflect complete
information on polarisation process. Cases were
reported where electrical motors having good PI werefound to have contaminated windings and also motors
having poor PI had no problems in the winding
insulation [2]. To resolve this, an one thousand
seconds charging and discharging test (dc absorption)was developed. Recovery Voltage Method for
transformer seems to be developed from this test.
In RVM, winding is charged for known time and then
shorted to ground for pre-decided time. The recovery
voltage is then measured and dominant time constant
is achieved which is essentially a polarisation time
constant.
Charging current is given as the sum of displacement
current, the polarisation current and the conduction
current. Polarising current is dependent on materialproperty and state of ageing. The polarisation of
dielectric can be expressed as sum of various slowpolarisation phenomena like ion migration, slow
relaxation and interfacial polarisation. Care must be
taken in the interpretation of results of RVM, in
particular the relative effects of moisture, genuine
ageing and temperature [3].
2.6 Condition Monitoring Model [1]
Insulation DP of Failure Expert
Ageing Insulation Rate Assessment
Products Paper DataIn Oil Sample RVM
INSULATION AGE FAILURE PROBABILITY
Remaining Reliable Life
Of Transformer
Data Base Of
Test Results
Statistical Analysis
RELIABILITY ANALYSIS
7/30/2019 uncertainty tranformer using konvensional testing methode.pdf
4/5
3. REFURBISHMENT DATA
Five 66/11kV, 10-30MVA transformers of 24 --33
years old transformers were refurbished. Some of the
important parameters are given in table 1, 2, 3 & 4.
Table 1
PI % Moisture
(from RVM)
% Mechanical
Strength (from
DP)
1.09 2.52 3555
1.79 2.10 3555
1.80 1.74 3555
2.34 1.56 3555
2.40 1.42 2535
Table 2
% Moisture
estimated from
Oil PPM
(Norris
Diagram)
% Moisture
estimated from
winding DLA
(Cigre)
% Moisture
estimated from
RVM
2 2 1.74
4 3 1.53
2.5 2 2.52
3.2 2.8 1.42
1.5 < 0.5 2.10
Table 3
% Moisture
(from RVM) DP
% Mechanical
Strength (from
DP)
2.09 250350 3555
1.53 250350 3555
1.21 200250 2535
2.38 250350 3555
2.18 250350 3555
Norris diagram gives estimated percentage of moisture
in paper based upon moisture content in oil (PPM) and
oil temperature.
Cigre paper has established a method to estimate
moisture in paper based upon winding tan (DLA)and temperature.
Table 4
2-Furfural
(PPM) DP
% Mechanical
Strength (from
DP)
1.10 200250 2535
0.49 250350 35550.39 200250 2535
0.54 250350 3555
2-Furfurylalcohol, 2-Acetylfuran, 5-Methyl-2-Furfuraland 5-Hydroxymethyl-2-Furfural were not detectedin all four cases.
4. DISCUSSION AND RESULTS It is observed from table 1 that RVM tends to
follow PI in this case. However, a conclusion
can not be drawn based on this limited
number of observations. Essentially RVM
does have DC absorption phenomenon and
may / may not follow IR / PI.
It is also observed that DP values (orpercentage retention of mechanical strength)
do not correlate with any of the electrical
parameters. DP reflects ageing and remaining
mechanical strength of paper but it is not a
diagnostic test as such.
From table 3, it is evident that moisture
percentage in the winding does not correlate
to DP or mechanical strength retention.
From table 2, it is evident that percentage ofmoisture estimated from Norris diagram(based upon oil PPM and temperature) and
percentage moisture estimated from Cigre
publication (based upon winding DLA) tend
to agree to some extent. However, these do
not correlate with moisture percentage
estimated from RVM. This is due to the fact
that RVM is a total reflection of ageing of
cellulose paper and moisture content in the
winding. There are no established methods
to separate these components.
It appears from table 4 that Furan analysis
may, in some cases, give indication about
paper ageing. However, most of the times,
Furans are not detected and there is no
universal correlation available for DP andFurans. Also, both ageing and moisture
content influence Furans.
7/30/2019 uncertainty tranformer using konvensional testing methode.pdf
5/5
5. CONCLUSION
Mechanical integrity of paper is very important to
ensure reliability of transformers. However at this
stage this is not conclusively reflected in any of the
electrical diagnostic tests available. There is a need for
further research to validate RVM results and establish
more effective method of estimating moisture contentin the cellulose paper winding.
6.0 REFERENCES:
1. D.ALLAN, Condition Monitoring & Life
Assessment Of Aged Transmission / Sub-
Transmission Plant, Lecture notes of the short
course program on Insulation Condition
Monitoring And Reliability Centred Maintenance
Of Electrical Plant. February 1997, MonashUniversity.
2. CAJETAN PINTO, An Improved Method of
detecting Contamination of H.V. Stator Winding
in the Field", Proceedings of the 20th Electrical
Electronic Insulation Conference Boston, 1991,
pp. 55-59.
3. R.E.JAMES, Assessment Of Electrical
Insulation, Proceedings of the 1998 ResidentialSchool in Electrical Power Engineering,
Tasmania.
4. I.GUSSENBAUER, Examination of Humidity
Distribution in Transformer Models by Means of
Dielectric Measurements, Cigre paper 15-02,
International Conference on Large High Voltage
Electric System, 1980.
5. THOMAS LEIBFRIED, On-line Monitors Keep
Transformers in Service, IEEE Computer
Application in Power, July 1998, pp 36-42.
6. SYED MOFIZUL ISLAM, Power Transformer
Condition Monitoring Pacific Power
International and University of NewcastleDevelopments, Lecture notes of the short course
program on Insulation Condition Monitoring And
Reliability Centred Maintenance Of Electrical
Plant. February 1997, Monash University.