Upload
truongnhan
View
215
Download
0
Embed Size (px)
Citation preview
CM2-VRX100-2001
ULTRA VortexorSmart Ultrasonic Vortex
FlowmeterModel VRX10A
User's Manual
Copyright, Notices and Trademarks
1998-2012 Azbil Corporation All Rights Reserved.
While this information is presented in good faith and believed to be accurate,Azbil Corporation disclaims the implied warranties of merchantability andfitness for a particular purpose and makes no express warranties except asmay be stated in its written agreement with and for its customer.
In no event is Azbil Corporation liable to anyone for any indirect, special orconsequential damages, The information and specifications in this documentare subject to change without notice.
i
Thank you for purchasing a Smart Ultrasonic Vortex Flowmeter. Using ultra-sonic waves to locate and measure the Karman vortex generated by a bluff bodyplaced in the flow, the Smart Ultrasonic Vortex Flowmeter calculates the flowrate to be output/displayed. Before attempting to use this equipment, thoroughly read and understand the contents of thisguidebook to ensureproper usage.
Introduction
ii
Unpacking, Inspecting, and Storing the Product
Unpacking This equipment is a precision instrument. When unpacking, take care to avoidaccidents or damage. Check the contents of the box against the list below asyou unpack.
• Flowmeter• Standard accessories
Confirming theSpecifications
Specifications are marked on the plate attached to the main unit. For fullspecifications, refer to Appendix A "Markings for Standard Specificationsand Model Numbers for Equipment," and confirm that the specifications arecorrect. Particularly, confirm the following:
• Model Number • Output• Power Supply (POWER) • Explosion-proof or not
If you have any questions regarding these specifications, contact us at theaddress listed at the end of this manual. When contacting us, please keephandy for our reference the model number (MODEL NO.) and the productnumber (PRODUCT NO.).
Contact Information
When storing the equipment as shipped, perform the following:
• Store the equipment indoors at room temperature and normal humidity in alocation that is protected from vibration and shock.
• Maintain the original packing condition of the equipment.
When storing the equipment after use, perform the following:
1. Screw on the main unit cover to moisture-proof the unit.
2. Repack the equipment in accordance with the original packing condition.
3. Store the equipment indoors at room temperature and normal humidity inan area protected from vibration and shock.
Notes for Storage
iii
Safety Notices
Proper installation, operation, and appropriate maintenance are essential toensure safe operation. Carefully read the notes and warnings on safety in-cluded in this guidebook, and familiarize yourself with the contents thor-oughly before attempting installation, operation, or maintenance.
Introduction
Standard Symbols This guidebook uses the following safety symbols:
Notifies the user of the possibility of fatal or seriousinjury if the equipment is not handled properly.
Notifies the user of potential danger that may result inminor injury or property damage if the equipment is nothandled properly.
Warning
Caution
iv
How this Manual is Organized and Used
This user’s manual explains, in the order below, the following topics relatingto the use of this equipment:
Chapter 1Explains the structure of measurement systems used by this equipment,and the name and function of each component.
Chapter 2Describes installation procedures for the equipment. Refer to this chapterwhen connecting this equipment to the piping.
Chapter 3Describes the electrical wiring for this equipment. Refer to this chapterwhen installing electrical wiring after installation of the piping has beencompleted.
Chapter 4Explains procedures for setting the parameters when starting to use thisequipment, and the operation for displaying information on the indicator.Refer to this chapter before attempting to operate this equipment.
Chapter 5This section describes the methods for controlling the Vortexor using theSmart Communicator SFC. Please refer to this section if changing param-eter settings.
Chapter 6Describes troubleshooting procedures for this equipment. Refer to thischapter first in the event of a malfunction.
Layout
vi
vii
Contents
Chapter 1 Measurement System Structure ........................................ 1-1Chapter Outline ..................................................................... 1-1
1.1 Measurement System ........................................................... 1-21.2 Structure and Component Functions .................................... 1-31.2.1 Structure of Main Unit ........................................................... 1-3
Chapter 2 Installation of the Equipment ............................................. 2-1Chapter Outline ..................................................................... 2-1
2.1 Installation Location .............................................................. 2-22.2 Notes on Installing the Piping the Equipment ....................... 2-32.3 Caution Points Concerning Fluids Used ............................... 2-62.4 Connect to Piping .................................................................. 2-72.4.1 Basic Installation ................................................................... 2-72.4.2 Required for Installation ........................................................ 2-102.4.3 Connect to Horizontal Piping ................................................. 2-122.4.4 Connection to Vertical Piping ................................................ 2-142.4.5 Basic Installation Method ...................................................... 2-162.4.6 Materials Required for Installation ......................................... 2-192.5 Changing the Direction of the Converter / Indicator .............. 2-202.5.1 Changing the Direction of the Converter Case ..................... 2-202.5.2 Changing the Direction of the Indicator (Optional) ................ 2-22
Chapter 3 Electrical Wiring .................................................................. 3-1Chapter Outline ..................................................................... 3-1
3.1 Wiring Procedure .................................................................. 3-23.2 Wiring Precautions ................................................................ 3-4
Chapter 4 Operation ............................................................................. 4-1Chapter Outline ..................................................................... 4-1
4.1 To Start Operation Immediately ............................................ 4-24.2 Converter Circuit Functions ................................................... 4-34.3 Setting Parameters ............................................................... 4-54.4 Indicator (Optional) ................................................................ 4-9
Chapter 5 Transmission Using Smart Communicator SFC .............. 5-1Summary of this Section ....................................................... 5-1
5.1 Before Transmitting Using S-SFC ......................................... 5-25.1.1 What is Possible Using the S-SFC........................................ 5-25.1.2 Recharging S-SFC ................................................................ 5-35.1.3 Layered Structure of CONFIG Function ................................ 5-45.2 Checks During Operation ...................................................... 5-55.2.1 Starting Transmission : ID key .............................................. 5-55.2.2 Displaying Instantaneous Flow Rate Measurements ............ 5-75.2.3 Displaying Output Transmitted/Outputting Steady-state Vortex . 5-75.2.4 Displaying Self-diagnosis Results ......................................... 5-7
viii
5.3 Printing Out Data ................................................................... 5-85.3.1 Summary of Print Functions .................................................. 5-85.3.2 Printing Out Internal Data: PRINT Key .................................. 5-95.3.3 Printing Out Response Results Continuously:
ACT PRINT Key ........ 5-115.4 Settings and Alterations ........................................................ 5-125.4.1 Pulse Function ...................................................................... 5-125.4.2 Range Function ..................................................................... 5-145.4.3 Detector Function .................................................................. 5-155.4.4 K-Factor Function .................................................................. 5-165.4.5 Setting Working Units ............................................................ 5-175.4.6 Setting Span .......................................................................... 5-185.4.7 Alarm Output Function .......................................................... 5-195.4.8 Setting Error Processing (Fail-safe) ...................................... 5-205.4.9 Totalizer Function .................................................................. 5-21
Chapter 6 Troubleshooting .................................................................. 6-1Chapter Outline ..................................................................... 6-1
6.1 Measures for Malfunctions .................................................... 6-26.2 Error Messages and Corrective Action ................................. 6-46.3 Sensor Replacement Instructions ......................................... 6-56.4 LCD Replacement Instructions ............................................. 6-96.5 Resale Parts List ................................................................... 6-10
1 - 1
1Chapter 1 Measurement System Structure
Chapter Outline
This chapter introduces the measurement system used by this equipment, andthe organization and structure of the equipment.
1 - 2
1.1 Measurement System
A vortexor inserted into a flow alternately generates a regular vortex("Karman vortex") downstream. When specifying f for the Karman fre-quency, d for the width of the vortexor, and v for flow speed, the followingrelation is observable:
f = St V/d
As St represents a non-dimensional number called Strouhal, and is also a con-stant number, within the range of a certain Reynolds number, according to theshape of the vortexor, measuring frequency f tells us V, and V can tells us thevolume rate of flow.
As shown in Figure 1.1, this flowmeter is equipped with two pairs of ultra-sonic wave sensors, each consisting of a transmitter and a receiver, down-stream from the vortexor. The transmitter constantly sends ultrasonic wavesinto the liquid. These ultrasonic waves pass through the liquid, and reach thereceiver within a specific period of time. When a Karman vortex is generatedin the opposite direction from this transmission as shown in Figure 1.1, trans-mission time to the receiver is increased. On the other hand, when the direc-tion of the Karman vortex flow and the ultrasonic wave are the same, thetransmission time is decreased. The transmission time changes in proportionto the frequency of the vortex. The flow rate can therefore be measured byidentifying changes in the amount of time it takes an ultrasonic wave to reachthe receiver.
As the ultrasonic wave sensors are affixed outside the pipeline of theflowmeter main unit, measurement without touching the measured flow ispossible, and the sensor system is highly sensitive while remaining highlyresistant to the influence of vibration.
Figure 1.1 Measurement Principles
The concept behindthe measurement offlow when using thisequipment
Karman vortex Receiver
Ultrasonic wave
TransmitterHousing
Flow
Bluff body
1 - 3
1
1.2 Structure and Component Functions
1.2.1 Structure of Main Unit
Main components This equipment features a 'one-piece' construction comprising both converterand a detector.The detector can either be configured as a wafer type (flangeclamping type) or a flange type for connecting to the pipes.
External view ofthe equipment
Figure 1.2 External View of the Ultrasonic Vortex Flowmeter
TermminalConverter
Indicator(optional)
Key switchDetector
ReplaceableUltrasonicwave sensor
(Continued on next page)
1 - 4
Chapter 1 Measurement System Structure
The table below describes the function of each component.Name and de-scription ofcomponents(Continued)
Converter • Converts signals from the detector to analog orpulse output signals, then outputs or displayssuch signals
Detector • Uses the ultrasonic wave sensor to detect thefrequency of the Karman vortex according toflow speed, then transmits the data to the con-verterContains a bluff body
Indicator (optional) • Displays the instantaneous flow rate, reset inte-grated flow rate, total integrated flow rate, unit,alarm, and self-diagnostic status
Key Switch • Allows changing of parameter settings for theconverter. When using Vortexor in an explo-sion-proof area, changes to settings during op-eration not possible.
ReplaceableUltrasonicWave Sensor
• Detects a Karman vortex generated in propor-tion to flow speed using four sensors (twopairs) which do not come into contact with theflow. The sensors are protected by an SUS 316cover.
Name Description
2 - 1
Chapter Outline
How to connect this equipment to piping and complete installation proceduresup to operation stage.
Chapter 2 Installation of the Equipment
2 - 2
Chapter 2 Installation
2.1 Installation Location
To facilitate daily maintenance and operation, and to ensure accuracy evenduring extended use, take the following into consideration when selecting aninstallation site.
Caution• Measurement may not be possible in a two-phase flow consisting
of gas and liquid or a flow that contains bubbles. Take care not toget liquids containing air bubbles in flows.
• If bubbles are trapped in the flowmeter, accurate measurementmay not be possible. When installing the flowmeter, take care thatbubbles are not trapped in the flowmeter.
• Do not subject the flow meter directly to water or other fluids. Ifinstalling in locations subject to water, the wiring connectors mustbe sealed thoroughly with glands, and the transducer cover mustbe closed tightly.
1) The flowmeter may be installed at any angle; always confirm, however,that the pipe is completely filled with liquid.Avoid installing the Transducer unit below the water surface, to protectagainst power shortage. Liquid builds up around the flowmeter duringoperation.
2) When installing on vertical pipe, make the piping in such a way thatensures that measured liquid flows from bottom to top when the pipe isfilled with liquid.
3) Avoid any location subject to extreme fluctuations in temperature.4) Although the flowmeter possesses a good aseismatic structure, to maxi-
mize protection of the piping and joints, keep vibration and shocks un-der 9.8 m/s2 by using supports.
5) As the main unit is made of a stainless and aluminum alloy, avoid expo-sure to corrosive environments.
6) As the water-resistant structure of this flowmeter is comparable to theJIS C0920 water-resistant structure (IEC IP66), it is not intended forsubmerged use.
7) Install at a location with sufficient clearance to conduct inspections.8) Install at a location with sufficient clearance to enable installation of
wiring and piping.
Introduction
Installation locationprecautions
2 - 3
2.2 Notes on Installing the Piping the Equipment
To ensure accuracy even during extended use, take the following into consid-eration when installing the piping and equipment.
Table 2.1 Required Length of Straight Pipe
Upstream Piping Straight Pipe Length for the upstream Side Straight Pipe Length for the downstream side
Diameter x to a factor of 23 or greater
Diameter x to a factor of 25 or greater
Diameter x to a factor of 40 or greater
Diameter x to a factor of 15 or greater
Diameter x to a factor of 27 or greater
Diameter x to a factor of 15 or greater
One 90° bend
2 or more bends on the same plane
2 or more bends on a different plane
Ingot pipe
Expansion pipe
Gate valve
Diameter x to a factor of 5 or greater
Table 2.2 Connection Pipe
Diameter Internal Diameter of Flowmeter Connection Pipe
25A to 50A Comparable to schedule 40 Schedule 40 or greater
80A to 100A Comparable to schedule 80 Schedule 80 or greater
4) To ensure flow-rate measurement accuracy, make sure the gaskets be-tween the flowmeter and the connection pipe remain outside the flowroute.
5) In the event that a pressure tap is required, to ensure the flow-rate mea-surement accuracy, install the tap at a distance, as measured from theedge of the downstream side of the flowmeter toward the lower stream,equal to at least twice the outlet diameter the diameter of the flowmeter.In the event that a temperature tap is required, install the tap at a dis-tance from the pressure tap toward the lower stream equal to at leastthree times the outlet diameter the diameter.
6) When making piping, ensure that the flowmeter and connection pipe arecoaxial. Any gaps in the coaxial (gap in the center) will causeunstability and instrument errors. Use the center-aligning metal fittingsand carry this out referring to page 2-11 included with the flowmeter,for installation.
7) Large ripples, such as those caused by a bellows pump, may create vari-ance. Use a damper to minimize such ripples.
8) With lines which have globe valves and in which drift currents or rotat-ing flows may occur, the flow meter should be positioned upstream ofthe valves.
(Continued on the next page)
1) Match the flow direction of the fluid to the direction indicated ( u mark)on the flowmeter.
2) To ensure flow-rate measurement accuracy, install straight pipes of alength described in Table 2.1 on upstream and downstream sides of theflowmeter.
Introduction
Pipework andinstallation precautions
2 - 4
Chapter 2 Installation
9) When installing a heat converter that significantly modifies liquid tem-perature, install it downstream of the flowmeter. In the event that itmust be installed upstream, do so at an appropriate distance from theflowmeter.
10) Cavitation lowers flow-rate measurement accuracy. To prevent cavita-tion, maintain the minimum pressure at the downstream line (located ata distance of 2-7 times the diameter of the flowmeter) at a pressuregreater than or equal to the result of the formula shown below.
Pd = 2.7 Í ∆P + 1.3 Í P0
Pd : Downstream pressure (kPa, absolute pressure)∆P: Pressure loss (kPa)P0 : Vapor pressure of fluid at the temperature during measure-
ment (kPa, absolute pressure)
The following formula calculates pressure loss.∆P = c Í γ
∆P: Pressure loss (kPa)c : Pressure-loss coefficient (according to Figure 2.1)γ : Fluid density (kg/m3)
Caution • Ensure that the internal diameter of the connection pipe is equal to
or greater than that of the flowmeter. • Install gaskets between the flowmeter and the connection pipe and
ensure that they are installed outside the flow route; otherwise, aninstrument error will occur.This will cause errors.
• Pipe vibration should be minimized. The vibration frequency cannotbe matched, and errors may occur.
• To prevent cavitation, allow sufficient back-pressure (pressuredownstream of the flowmeter).
(Continued)
(Continued on the next page)
2 - 5
(Continued) Figure 2.1 Pressure-Loss Coefficient
Pre
ssur
e-lo
ss c
oeffi
cien
t of l
iqui
d (c
)
Flow rate of liquid m3/h
2 - 6
Chapter 2 Installation
2.3 Caution Points Concerning Fluids Used
Please note the caution points described below in order to ensure consistentmeasurements over a long period of time.
Introduction
1) The fluid temperature range is 20 to 160°C for general types, and 20 to120°C for JIS explosion-proof types.
2) The fluid pressures up to a maximum of 5MPa are possible, but themaximum value should match the rating of the flange actually beingused.
3) Fluid constituents adhering to the vortex generator may cause errors.Particular caution should be taken when using easily-precipitated fluidsor fluids containing impurities.
Fluid propertiesprecautions
The following fluids cannot be measured.1) Fluids that corrode SUS316L2) Steam, gases3) Fluids with viscosities exceeding 20 µ m2/s (20mm2/s)
Precautions forfluids that cannotbe used
2 - 7
Caution • This instrument has a heavy construction. Use caution when han-
dling or moving the Vortexor in order to prevent injuries.
This device can be used with either wafer or flange-type connections. Referto installation procedures to ensure proper installation of the equipment.
Introduction
Sample installationof a wafer detector
Figure 2-2 shows basic installation procedure of the wafer detector.Figure 2-2 Installation Example
Connection pipe
Bolts
Nuts
Gasket
Center-aligning metal fitting
(included)
(Continued on the next page)
2.4 Connect to Piping
2.4.1 Basic Installation
Chapter 2 Installation
2 - 8
• Table 2-3 shows the allowable torque for each caliber. To preventleakage from the piping, which can cause injuries, tighten the cen-ter-aligning metal fittings to the specified torque.
CautionTorque(Continued)
Table 2-3 Torque
Nominal Diameter of Detector Torque
25A 20 to 30N•m(200 to 300kgf•cm)
40A 50A 80A 30 to 50N•m(300 to 500kgf•cm)
100A 50 to 70N•m(500 to 700kgf•cm)
Configuration offlange at connectionpipe
As shown in Figure 2-3, use a flange that has considerable gasket-contactsurface area.Figure 2-3 Flange Configuration
ô Proper Configuration(Insufficientgasket-contactsurface areamay lead toleakage.)
Í Improper Configuration
Welded part
Notes: Before installing the detector, flush to clean inside the pipe and re-move any foreign matter from the flow route. Such substances causeirregular outputs. Match the direction indicated on the flowmeter to the flow direction. Measurements will not be possible.
(Continued on the next page)
Welded part
Flange
Pipe
2 - 9
• Match the internal diameter of the connection pipe and the detector,and ensure that the gasket does not shift out of proper alignment,and penetrate the boundary of the piping.
• Before installation, confirm that the pipe is not installed at an angleand is properly aligned. Failure to do so may cause leakage, andresult in injury.
Flange configuration(Continued) Warning
Figure 2-4 Example of Improper Installation (1)
Pipe at an angle Misaligned Misaligned
Note: • Do not force the Vortexor into a too-narrow space between pipe
flanges, as the equipment may be damaged.
Figure 2-5 Example of Improper Installation (2)
Caution
Note: • Tighten each bolt uniformly to the prescribed torque. If leakage does
not stop after the bolts have been tightened, confirm that the centerof piping is aligned, and cinch the bolts gradually. Ensure tighteningtorque is within the specified values; otherwise, the equipment maybe damaged.
Chapter 2 Installation
2 - 10
2.4.2 Required for Installation
Flange
The following are required for installation: • Metal center-aligning fittings • Through-bolts and nuts • Gaskets
Introduction
Center-aligningfittings
Metal center-aligning fittings prevent misalignment between the connectionpipes and the detector.
Pass the bolts through the center-aligning metal fittings. The detector must bepositioned on or directly between the metal fittings.
The installation position of the metal fittings varies depending on the angle atwhich the detector is installed.
See Figure 2-6 and 2-7 for installation position.
Figure 2-6 Horizontal Installation (Attach two metal fittings -- one each to left and right flanges.)
Figure 2-7 Vertical Installation(Attach four metal fittings to the lower flange only.)
Position of center-aligning metal fitting
Position of center-aligning metal fitting
Flange
(Continued on the next page)
2 - 11
Notes: • If the internal diameter of the gasket is too small, flow speed distribu-
tion may be unbalanced and negatively impact accuracy.
• If the internal diameter of the gasket is too large, leakage may occur.If the measured flow includes solid substances, solids may accumu-late between the gasket and flange, reducing accuracy.
Table 2-4 Recommended Internal Diameter of Full-Face Gasket(Unit mm)
Gasket(Continued)
SizeDiameter of detector 25A 40A 50A 80A 100A
Internal Diameter 30 44 55 76 98±1 ± 1 ± 1 ± 1 ±1
Chapter 2 Installation
2 - 12
2.4.3 Connect to Horizontal Piping
• Improper installation may cause leakage of the measured flow,damage the flanges, and result in injury.
Caution
Required forinstallation
Prepare the following: • Through-bolts and nuts • Metal center-aligning fittings • Gaskets
Install according to the following procedure.Procedure
1
(Continued on the next page)
Step Description Figure
Pass the bolts through the holes(shown in black in the Figure)at the flange. At this time, passtwo center-aligning metal fit-tings through each bolt.
Flange
2 • Match the direction of theflow to the direction indi-cated on the Vortexor.
• Position the gasket and thedetector between the flanges.
• Place the detector on themetal center-aligning fit-tings.
Flow direction
Gasket
2 - 13
Step Description Figure
3
Procedure(Continued)
• Confirm that the center of thecomponents are aligned.
• Confirm that the gasket doesnot protrude into the flowroute.
• After confirming the above,pass the remaining boltsthrough the holes at theflanges, and tighten uni-formly all bolts to the torqueshown on page 2-7.
Chapter 2 Installation
2 - 14
2.4.4 Connection to Vertical Piping
• Improper installation may cause leakage from the measured flowstream, damage the flanges, and result in injury.
Caution
Required forinstallation
Prepare the following: • Through-bolts and nuts • Center-aligning metal fittings • Gaskets
Procedure Perform installation according to the following procedure:
1
Top
(Continued on the next page)
Flange
Step Description Figure
Pass the bolts through the twotop holes, shown in black in thefigure, of the flange, andtighten them partly with thenuts. At this time, pass thebolts one the center-aligningmetal fittings through eachbolt.
2
Terminal-boxside
Center-aligningmetal fitting
• Match the direction of theflow to the direction indi-cated on the Vortexor.
• Insert both the gasket and thedetector between the flanges.
Flow direction
Gasket
2 - 15
3
Step Description FigureProcedure(Continued)
Pass the bolts though the tworemaining flange holes shownin black in the figure at Step 1and 2, through the center-align-ing metal fittings, and partiallytighten.
4 • Confirm that the center of thecomponents are aligned.
• Confirm that the gasket doesnot protrude into the flowroute.
• After confirming the above,pass the remaining boltsthrough the holes at theflanges, and tighten all boltsequally to the torque shownon page 2-7.
Chapter 2 Installation
2 - 16
Figure 2-8 shows the basic installation method.
Figure 2-8: Installation example
2.4.5 Basic Installation Method
Installation examplefor flange type
Nut
Through-bolt
Pipe
Gasket (optional, or provided by user)
(Continued on next page)
• Flange-type detector is heavy. Dropping on feet will result in injuryor broken bones. Sufficient care must be taken.
Caution
• Table 2-5 shows the tightening torques for each bore diameter.Tighten to the prescribed torques to prevent fluid leakage from thepipe. Risk of injury.
Caution
2 - 17
25mm JIS10K 21 to 31 (214 to 316)
JIS20K 21 to 32 (214 to 326)
JPI/ANSI150 11 to 17 (112 to 173)
JPI/ANSI300 22 to 34 (224 to 347)
40mm JIS10K 22 to 32 (224 to 326)
JIS20K 22 to 34 (224 to 347)
JPI/ANSI150 13 to 18 (132 to 184)
JPI/ANSI300 36 to 57 (367 to 581)
50mm JIS10K 24 to 34 (245 to 347)
JIS20K 19 to 31 (194 to 316)
JPI/ANSI150 23 to 32 (235 to 326)
JPI/ANSI300 20 to 32 (204 to 326)
80mm JIS10K 20 to 31 (204 to 316)
JIS20K 37 to 61 (377 to 622)
JPI/ANSI150 26 to 35 (265 to 357)
JPI/ANSI300 37 to 57 (377 to 581)
100mm JIS10K 22 to 33 (224 to 337)
JIS20K 41 to 66 (418 to 673)
JPI/ANSI150 21 to 31 (214 to 316)
JPI/ANSI300 43 to 66 (439 to 673)
Table 2-5: Tightening torquesTightening torques
Bore diameter, flange rating Units:N·m (kgf·cm)
Chapter 2 Installation
2 - 18
A large flange should be used to maximize the contact area with the gasket asshown in figure 2-9.
Figure 2-9: Flange profile
Flange profile
(Fluid leakage mayoccur due to lowcontact area withgasket.)
Good example Poor example
Flange
Weld
Pipe
Note:• Always flush the pipe to remove any debris from inside before install-
ing the detector. Failure to do this will cause the output to drift. Inserta short length of pipe in place of the detector when flushing.
• Match the flow direction mark on the detector with the fluid flow di-rection. Failure to do this will prevent measurements.
• Do not force objects between the flange faces. This will result indamage to the device.
• Match the internal diameters of the pipes and detector to ensure thatthe gaskets do not protrude inside the pipes.
Caution
Note:• When tightening bolts, tighten each bolt evenly. If fluid leakage does
not stop after tightening, gradually tighten the bolts further. Takecare to not to tighten the bolts over the prescribed torques. This willresult in damage to the device.
2 - 19
Joint sheet or PTFE is recommended for the gasket material.
The gasket internal diameters should be as shown in table 2-6.
Note:• If the gasket internal diameters are too small, the flow rate distribu-
tion will be disrupted, affecting accuracy.
Table 2-6: Recommended gasket internal diameters
2.4.6 Materials Required for Installation
Introduction The following materials are required for installing the Vortexor.• Gaskets
Gaskets
Detector opening diameter (mm) Internal diameter (mm)
25 30±1
40 44±1
50 55±1
80 76±1
100 98±1
Chapter 2 Installation
2 - 20
2.5 Changing the Direction of the Converter / Indicator
When installation location of the flowmeter necessitates changing the direc-tion of the converter and/or indicator, perform the following procedures.
The flowmeter must be connected to piping or placed on a stable work table.
2.5.1 Changing the Direction of the Converter Case
To turn the converter case through 180˚ in relation to the flow direction, per-form the following procedure:
1) If power is being supplied to the flowmeter, turn off the power.2) Remove the four bolts (5-inch) at the bottom of the converter.3) Lift the converter 2 to3 mm, and turn it through 180˚.
The ultrasonic-wave sensor cable (thin electric wire) resides betweenthe flowmeter main unit and the converter case, and connects them.When rotating the converter, be careful not to sever the cable. Do notrepeatedly turn the converter 180˚ in the same direction. Turn the casein the opposite direction every rotation to prevent the internal cablefrom being twisted and possibly severed.
4) After setting the direction of the converter, place the converter on theflowmeter main unit, and completely tighten the four bolts (5-inch) atthe bottom of the converter completely.Since the JIS pressure-resistance explosion-proof model of the flowme-ter has a pressure-resistant, explosion-proof structure, completelytighten the bolts.
• Since the flowmeter has a pressure-resistant explosion-proof struc-ture, completely tighten the four bolts (5-inch) at the bottom of theconverter after changing the direction of the converter, to maintainthe explosion-proof structure.
• If the explosion-proof structure is not maintained due to insufficienttightening of the bolts, a fire or explosion may occur when the flow-meter is used in hazardous operating conditions.
Warning
• When changing the converter direction, be careful not to sever theultrasonic wave sensor cable running between the flowmeter mainunit. Turn the converter in the opposite direction every rotation toprevent the internal cable from being twisted and possibly severed.
(Continued on the next page)
Caution
2 - 21
(Continued) Figure 2.10 Changing the Direction of the Converter
180˚
4 bolts (M5)
Chapter 2 Installation
2 - 22
2.5.2 Changing the Direction of the Indicator (Optional)
To turn the direction of the indicator 90˚ as shown in Figure 2.11, perform thefollowing procedure.
1) If power is being supplied to the flowmeter, turn off the power.2) Remove the converter lid after loosening the set screws (with which it is
affixed), as shown in Figure 2.12.After loosening the set screws, turn the converter lid to remove it. Notethat there is an O-ring in the connection area.
3) Remove the LCD.Remove the two screws affixing the LCD, and remove the LCD to-gether with the outer-facade panels.
4) Change the direction of the indicator.After changing the direction of the indicator, insert the connector at thebottom of the board into the LCD receptacle.
5) Fix the LCD into place.Affix the LCD with the two screws (removed in Step (3) above).
6) Attach the converter lid to the converter main unit. Remember to cor-rectly position O-ring.
7) After completely tightening the converter lid, tighten the set screws forthe turn stopper.
• Since the flowmeter has a pressure-resistant explosion-proof struc-ture, completely tighten the converter lid after changing the directionof the indicator, to maintain the explosion-proof structure.
• If the explosion-proof structure is not maintained due to a failure totighten the converter lid, a fire or explosion may occur when theflowmeter is used in dangerous operating conditions.
Warning
• Do not forget to insert the O-ring between the converter main unitand the lid when tightening the converter lid.
• Without the O-ring, water-resistance may be negatively affected,and the converter circuit may be damaged due by liquid intrusion.
Caution
(Continued on the next page)
2 - 23
2
Figure 2.11 Direction of the Indicator
Figure 2.12 Changing the Direction of the Indicator
O-ring
Set screw
Stud (2 locations)
Screws (2 locations)
Outer-facade plate
LCD board
Connector
Converter lid
(Continued)
Chapter 2 Installation
2 - 24
MEMO
3
3 - 1
Chapter Outline
This chapter explains the electrical wiring for the power and output of theVortexor.
Chapter 3 Electrical Wiring
Chapter 3 Electrical Wiring
1) Follow Figure 3.1a to wire external cables for the flowmeter, powersupply, and external equipment.
Figure 3.1a Connection Diagram
Note 1: To make use of the communication function via the smartcommunicator, 250 or greater load resistance, includingcable resistance, is required.
Note 2: Supply power to the flowmeter
Note 3: When grounding the cable shield, use one-point grounding atthe flowmeter side or at upstream equipment.
3.1 Wiring Procedure
Introduction This section describes the method for wiring the flow meter.Please read this when wiring the power supply and outputs.
Wiring instructions
Figure 3.1b Wiring diagram (When using pulse/alarm outputs only)
Analog Receiver
Power source(Note 2)
Smart communicator
Analog output
250 (Note 1)Counter etc.(Opencorrector input)
Pulse/Alarm output(Open collector output)Pulse/Alarm output(Open collector output)Pulse/Alarm output(Open collector output)
Note 3
3 - 2
3
3 - 3
2) Analog outputThe analog transmission loop of this flowmeter is created by establish-ing load resistance between the + line and - line of the analog outputline. (The analog output line is also used as a power supply line for theflowmeter.)
3) Pulse output / Alarm outputThe pulse output/alarm output of this flowmeter is an open collectoroutput. Connect a power source, using the current limit resistance, be-tween the pulse/alarm output line and COM line to be used. Ensure thevalue of current limit resistance does not exceed the capacity of thepulse output.
4) Remove the terminal cover at the amp case and the dust-proof plug atthe wiring connection before attempting to install the wiring.
5) To assure water-resistance, conduit tubes and ducts should be used forexternal wiring.
Chapter 3 Electrical Wiring
3 - 4
3.2 Wiring Precautions
• The specified pressure-resistant seal fittings must be used at thecable inlets when using in hazardous atmospheres.
• Failure to use the specified pressure-resistant seal fittings, or use ofunspecified fittings will not guarantee the explosion-proof construc-tion, and there will be a danger of explosion in some cases.
Warning
1) The cables used should be as follows.Recommended cable: CVV-S or CEV-S
Flow meter output Cores
None, or analog output only 2-core shielded
None, or analog output only 2-core shielded x2
+
pulse output or alarm output
Pulse or alarm output only 3-core shielded
* Ensure that the total of the circuit resistance and load resistancematches the value in figure 2.2.
* It is recommended that cables are used with cross-sectional areas of atleast 1.25mm2.
* It is recommended that CEV-S cable with a cross-sectional area of atleast 2mm2 is used if the transmission distance exceeds 500m.
2) In order to prevent noise intruding, the cables should be kept away fromnoise sources such as large-capacity motors, transformers and powerplants, or from high-voltage and high-current sources.
3) If using explosion-proof specifications, the pressure-resistant seal fit-tings included (or as optional specifications) must be used.
4 - 1
4
Chapter 4 Operation
Chapter Outline
This chapter explains the procedures for setting parameters prior to operatingthe equipment, and the operation of the indicator.
Chapter 4 Operation
4 - 2
Step Details
1 Switch on the power. If an LCD is fitted, check the LCD dis-play.
2 Press the " u " and "ENT switches simultaneously for at least 3seconds. "FUNC1" is displayed.
3 Press the "ENT" key to check the instantaneous flow rate units.Use the " p " and " q " switches to make changes if necessary.
4 Press the "ENT" key to check the PASS display. Then press" p " or " q " to display "FUNC3".
5 Press the "ENT" key to check the maximum flow rate value.Use the "p " and " q " switches to make changes if necessary.
Use the "u " key to change to the next digit.
6 Press the "ENT" key to check the PASS display.
7 Press the "ENT" key for at least 3 seconds to return to measure-ment mode and enable start of measurements.
4.1 To start Operation Immediately
Introduction This section describes the simple operations to start operation immediatelyafter installation.
Steps for startingoperation imme-diately
Please perform the following steps.
4 - 3
4
4.2 Converter Circuit Functions
Figure 4.1 shows the structure of the converter circuit board for the UltrasonicVortex Flowmeter.
Figure 4.1 Block Schematic View of Converter Circuit
1) DRV BoardThe DRV board includes the transmission and receiving circuits for theultrasonic wave sensor, as well as the signal processing circuit for re-ceived vortex signals.
Since it is necessary to change the internal constant for each diameter,the jumper pins (JP4-6) should be set as shown in Table 4.1, for eachdiameter. (These are set at our factory at the time of shipping.)
Table 4.1 Settings of Jumper Pin Corresponding to Each Diameter
Diameter Jumper No.
JP4 JP5 JP625A 1-2 short 2-3 short 2-3 short
40,50,80A 2-3 short 1-2 short 1-2 short100A 2-3 short Open Open
2) CPU BoardThe CPU board contains both the CPU, which controls flow-rate calcu-lation and communication, and memory.
3) IF BoardThe IF board contains power circuits, and analog and pulse output cir-cuits.
4) LCD BoardThe LCD board consists of an LC, which displays the measured flowrate (or an alarm number) and the drive circuits of the LC.
This section gives a simple description of the transducer circuit layout.Introduction
Circuit layout
D-class earthconnection(contact resistance100Ω max.)
(Continued on the next page)
Communicationcircuit
Driver
Mode
switchLCD board(optional)
BRI board
Noise
filter
IF board
Pulse output
Analog output
Power circuit
Ultrasonicwave sensor
CPU board
Memory
Microcomputer
DRV board
Receivingamp
Phasecomparator
Transmittingcircuit
LCD
Chapter 4 Operation
4 - 4
5) BRI BoardThe BRI board consists of a terminal base for external cable connec-tions, and noise filter circuits.
(Continued)
4 - 5
4
4.3 Setting Parameters
It is possible to set the following parameters using the four key switches onthe LCD board. Communication via the smart communicator also enablesparameters setting. (See the guidebook on the smart communicator for how toset parameters using the smart communicator.)
Figure 4.2 Indicator
Key switch
1. Switch to User Setting ModeThe flow meter is in measurement mode when in normal use. To changethis mode to a User Setting Mode in which the user is able to set parameters,press both " " and "ENT" at the key switch at the same time for at leastthree seconds. "FUNC 1", as shown in Figure 4.3, will blink on the LCD.
Figure 4.3 Display After Switching to User Setting Mode
LCD Blinking
(Continued on the next page)
Introduction This section describes the method for inputting the transducer parameters.
Parameter settingprocedure
Chapter 4 Operation
4 - 6
2. Selecting ParametersAfter switching to the User Setting Mode, select the FUNC number for thedesired parameter using "" p " or " q " at the key switch.See Table 4.2 for FUNC numbers for each parameter.
Table 4.2 FUNC Numbers and Parameters
(Continued)
FUNC Number Parameter Default Value Valid Value
FUNC1 Unit for instantaneous-flow rate m3/ h L, m3, /s, min, h, day
FUNC2 Unit for integrated-flow rate L, m3 L, m3
FUNC3 Maximum instantaneous-flow rate 14m3/ h Up to the maximum flow rate for each size
FUNC4 Output frequency denominator 1 L 0.1L,10L,100L,1m3 (depending on diameter)
FUNC5 Dumping (0-90 % response) 1 second 1 to 199 seconds
FUNC6 Upper limit for flow rate alarm 100% 1 to 100%
FUNC7 Lower limit for flow rate alarm 0% 0 to 99%
FUNC8 No. of times used for EEPROM Not changeable (Display only)
FUNC9 Contact output Alarm Alarm
Flow rate alarm, Pulse
3. Changes to SettingsAfter selecting the FUNC number for the parameter to be changed, performthe following operation, to change any settings.1) Press "ENT" key switch while the selected FUNC number is blinking.
The LCD will display a stored set value.
2) The changeable positions of the displayed set value should blink.
For FUNC 1 and 2, pressing the key switch " p " or " q " changes the setunit.
For FUNC 3, 5, 6 and 7, press the key switch " p " or " q " to change theblinking value.
(" p " increases the value, and " q " decreases the value.)
To change the blinking position (changeable digit), use the key switch" u ".
For FUNC 4, pressing " p " or " q " displays each valid value in order.
For FUNC 8, the LCD displays the number of times data has been writ-ten in the EEPROM. (Display only; value is not changeable.)
For FUNC 9, pressing the key switch " p " or " q " displays the settingsfor contact output in order. (The LCD displays "AL" for "Alarm", "F"for "Flow rate alarm", and "P" for "Pulse output" as contact output.)
(Continued on the next page)
4 - 7
4
(Continued) 3) After settings have been changed, press the key switch "ENT." If thenew setting is valid, the LCD displays "PASS," the setting value is writ-ten into internal memory, and the FUNC number will blink again. If thenew setting is invalid, the LCD will display "ERR," and will return to itsstatus in Step (2). The LCD will then display a stored set value, and thechangeable position will begin blinking, and wait for new input.
4. Leaving User Setting Mode (Finishing Setting Changes)Press the key switch "ENT" and hold three seconds or more while FUNCnumber is blinking. This returns to measurement mode and performs flowrate measurements.
5. Parameter setting rangeSet the parameters within the ranges shown below.
(Continued on the next page)
FUNC No. Parameter Opening dia. Setting range
FUNC3 Max. instantaneous 25A 1.4 to 14m3/h
flow rate 40A 3.6 to 36m3/h
50A 6.0 to 60m3/h
80A 11.5 to 115m3/h
100A 20.0 to 200m3/h
FUNC4 Output pulse units 25A 0.1L, 1L, 10L, 100L
40A 0.1L, 1L, 10L, 100L
50A 1L, 10L, 100L, 1m3
80A 1L, 10L, 100L, 1m3
100A 1L, 10L, 100L, 1m3
Chapter 4 Operation
4 - 8
NG
OK
The sequence for setting the parameters is shown in figure 4.4.
Figure 4.4 Parameter setting method
Parameter settingsequence
Measurementmode
Press " u " and "ENT" switches togetherfor at least 3 secs.
User setting mode"FUNC1" flashes.
Press "ENT" switch for at least 3secs.
Select parameters (FUNC No.) using"p " or "q " switches.
User setting modeSelected FUNC No. flashes.
Press "ENT" switch.
User setting modeSetting value displayed.
Locations that can bechanged flash.
User setting mode"ERR" displayed.
Change settings using "p ", "q " or" u " switches. Then press "ENT".
User setting mode"PASS" displayed.
4 - 9
4
4.4 Indicator (Optional)
This flowmeter is capable of displaying (via LCD) total integrated flow rate,instantaneous flow rate, reset integrated flow rate, and alarm number (in theevent that an error occurs).Figure 4.5 shows the contents of the display at the indicator.
Figure 4.5 Liquid Crystal Display
1. Flow-rate DisplayThe display during flow-rate measurement changes depending on the"MODE" number. Table 4.3 shows the contents of the display.
Table 4.3 Contents of Display for Flow-rate Measurement
MODE Number Contents of Display
MODE1 Total integrated flow rate
MODE2 Instantaneous flow rate
MODE3 Reset integrated flow rate (can be reset)
MODE4 % flow rate
Turning on the flowmeter power engages the flow-rate measurement dis-play.To switch the contents of the display (MODE change), use the magnet (in-cluded) or the smart communicator. (See the guidebook on the smart com-municator for instructions on changes to settings via the smart communica-tor.)To change the mode using a magnet, perform the following procedure.
1) Moving the magnet close to the word "Azbil" at the bottom of the indi-cator switches the "MODE" number and changes the display.
2) Switching the "MODE" number is performed in the following order:"MODE1" (total integrated flow rate) → "MODE2" (instantaneous flowrate) → "MODE3" (reset integrated flow rate)→ "MODE1".
(Continued on the next page)
Introduction This section describes the details of LCD.
Details ofdisplay
Chapter 4 Operation
4 - 10
(Continued) 3) To reset (zero) the cumulative value (displayed value) in MODE3 (resetcumulative flow rate), hold a magnet close to the "Azbil" beneath thedisplay unit for at least 3 seconds. The cumulative value will be dis-played as "0". If the magnet is removed within 3 seconds, the cumula-tive value will not be reset, and the display changes to "MODE4" (%flow rate).
Figure 4.6 shows the sequence for the display selections.
Figure 4.6 Display selection
(Continued on the next page)
『MODE1』
トータル積算流量値
『Yamatake』にマグネット
を近づける。
『Yamatake』にマグネット
を近づける。
『MODE2』
瞬時流量値
『Yamatake』にマグネット
を近づける。
『MODE3』
瞬時流量値
自動
『MODE2』
リセット積算流量値
積算値リセット
『Yamatake』にマグネット
を3秒以内近づける。
『Yamatake』にマグネット
を3秒以内近づける。
『MODE4』
%流量値
Hold magnet close to"Azbil".
"MODE1"Total cumulative flow rate
"MODE4"% flow rate
Hold magnet close to"Azbil".
"MODE2"Instantaneous flow rate
Hold magnet close to"Azbil".
Hold magnet close to "Azbil"for less than 3 secs.
Hold magnet close to "Azbil"for less than 3 secs.
"MODE3"Instantaneous flow rate
Aut
o
"MODE2"Reset cumulative flow rateCumulative value reset
4 - 11
4
If an error occurs in the flowmeter, "ALARM" blinks, and the alarm num-ber is displayed, to indicate the error status. Table 4.4 shows the meaningsof the alarm numbers.
Table 4.4 Alarm Number and Error Status
ALARM No. Error Status Flow-rate Measurement Status
ALARM1 Sensor-drive-circuit error Measurement terminated
ALARM2 Single receiving sensor error Measurement continued
ALARM3 Single receiving sensor error Measurement continued
ALARM4 Double receiving sensor error Measurement terminated
ALARM5 – –
ALARM6 EEPROM error Measurement continued
ALARM7 RAM error Measurement stops
ALARM8 ROM error Measurement stops
ALARM9 Cumulative value protection error Measurement continues
If an alarm is displayed, immediately take measures to recover Vortexor fromerror status.(Or perform required maintenance.)
• If an alarm is displayed, immediately perform maintenance to re-cover Vortexor from error status.
• Contining to use the equipment when it is in error status may causeinaccurate measurements to be recorded.
Caution
Alarm display
Chapter 4 Operation
4 - 12
MEMO
5 - 1
Chapter 5 Transmission using Smart
Communicator SFC
Summary of this Section
This section describes the operating procedures for when the Vortexor is con-nected to a Smart Communicator SFC.SFC software version 7.6 and upwards can be used.
Chapter 5 Transmission Using Smart Communicator SFC
5 - 2
5.1.1 What is Possible Using the S-SFC
5.1 Before Transmitting Using S-SFC
The S-SFC can be used to communicate with the Vortexor enabling data to beread from the device, and settings to be altered. The functions of the S-SFCare described here split into purpose.Note:Please check that the S-SFC is at least version 7.6. Some functions cannot beused for lower versions.
Introduction
The following functions are used while the Vortexor is operating.• Starting transmission/Enter tag No.: ID/
Digital transmission key ........................................................... Page 5-5• Displaying instantaneous flow rate measurement:
INPUT/Input value key ............................................................. Page 5-7• Displaying output transmitted: OUTPUT/Output key .............. Page 5-7• Displaying results of self-diagnosis: STAT/Diagnosis key ...... Page 5-7
Checks duringoperation
The S-SFC has the following print functions if a printer is fitted.• Printing out internal data: PRINT/Print data key ..................... Page 5-8• Printing out continuous response results:
ACT PRINT/Continuous print key ........................................... Page 5-10
Printing out data
The following functions are used to set or alter data inside the Vortexor.• Setting pulse output parameters: PULSE/Pulse ........................ Page 5-11• Setting display/low flow cutoff: RANGE/Range ..................... Page 5-14• Setting detector parameters: DETECTOR/Detector ................. Page 5-15• Setting compensation factor: K-FACTOR/
Compensation factor ................................................................. Page 5-16• Setting working units: UNIT/Units key .................................... Page 5-17• Setting span: URV key ............................................................. Page 5-18• Changing/setting damping constant : DAMP/Damping key .... Page 5-18• Selecting/setting pulse/alarm output:
ALARM/Alarm function .......................................................... Page 5-19• Setting error processing (fail-safe): FAILSAFE/Fail-safe........ Page 5-20• Checking converted value/Setting dummy pulse output:
TOTALIZER/Counter capacity ................................................ Page 5-21
Settings andalterations
5 - 3
5.1.2 Recharging S-SFC
If a ":" mark appears at the 8th digit at the top of the S-SFC screen as shownbelow, stop using the S-SFC immediately, and recharge. Continuing to usebeyond this will over-discharge the S-SFC batteries, preventing recharging.
Note:
:
Please refer to the S-SFC operating instruction manual (CM1-SFC100-2001)for details of recharging the S-SFC.
Procedure
Chapter 5 Transmission Using Smart Communicator SFC
5 - 4
The CONFIG function has a layered structure. When using the CONFIGfunction, please check the position of the individual sub-functions on the at-tached layer structure diagram first.Likewise, the S-SFC screen only displays 2 lines, so the layer diagram belowshould be referred to when it is not known which layer is being displayed.
5.1.3 Layered Structure of CONFIG Function
Layer structurediagram
English display
5 - 5
5.2.1 Starting Transmission: ID Key
5.2 Checks During Operation
When starting transmission with the Vortexor using the S-SFC with ananalog output system, the uppermost controller must always beswitched to manual control. This is to prevent the analog output varia-tions from the Vortexor caused by transmission from directly affectingthe uppermost controller on starting up the S-SFC.
Warning
Start up the S-SFC using the following procedure.Procedure
Step Procedure
1 Check that the Vortexor is started up. If not, start up the devicereferring to "Starting up the SMT3000" on page 5-2.
2 Check that the transmission cables are correctly connected to theVortexor and S-SFC.
3 Switch on the S-SFC power.Result:• The S-SFC runs a diagnostic check, and displays the following
screen.
• This display asks for appropriate measures to prevent outputvariations from the Vortexor caused by transmission between itand the S-SFC from affecting the controller directly above.Take appropriate measures to switch the controller to manualbefore pressing the "ID" key. Particular care is necessary foranalog output systems.
4 For an analog output system, press the "ID" key here.
(Continued on next page)
SELF CHECK...
LOOP IN MANUAL?
PRESS ID
VRX TAG No.
MAG SR XXXXXXXX
TAG No.
WORKING...
Chapter 5 Transmission Using Smart Communicator SFC
5 - 6
(Continued)Step Procedure
5 The Tag No. can now be input.Up to 8 characters can be input using the "ALPHA" keys and nu-merical keys.
6 Press the "CLR" (clear) key. The following screen appears.Result:The S-SFC runs a diagnostic check, and the screen appears asshown below.
VRX XXXXXXXX
READY...
5 - 7
5.2.2 Displaying Instantaneous Flow Rate Measurements
Press "SHIFT" + "OUTPUT" keys.
Procedure This screen is displayed. If thisscreen is not displayed, press the"CLR" key.
VRX XXXXXXXX
READY...
↓
5.2.3 Displaying Output Transmitted/Outputting Steady-state Vortex
Press "OUTPUT" key.Displays instantaneous value output from 0 to 199%.Setting values in the range 0 to 100% and pressing the "ENTER" key switchesto constant current output mode. To quit constant current mode, press the"CLR" key.
Procedure This screen is displayed. If thisscreen is not displayed, press the"CLR" key.
VRX XXXXXXXX
READY...
↓
5.2.4 Displaying Self-diagnosis Results
Press "STAT" key.The self-diagnosis determines the error messages and corrective action de-scribed in the "Maintenance and troubleshooting" section. The following isdisplayed if there are no problems with the self-diagnosis results.
Procedure This screen is displayed. If thisscreen is not displayed, press the"CLR" key.
VRX XXXXXXXX
READY...
↓
VRX XXXXXXXX
STATUS CHECK OK
Chapter 5 Transmission Using Smart Communicator SFC
5 - 8
5.3.1 Summary of Print Functions
5.3 Printing Out Data
In order to perform flow rate measurements correctly, it is important to checkthe internal settings and responses from the Vortexor when starting operationand while running. It is therefore useful to communicate with an S-SFC fittedwith a printer, and print out the data. S-SFCs fitted with printers have twotypes of print functions, as defined below.
Introduction
Configuration print (data print):The S-SFC printer can be used to print out internal data from the Vortexor,such as tag number, damping time constant, and low flow cutoff. This printfunction is called "Configuration print" or "Data print".
Action print (data print):There is also a function for printing out continuously the response results fromthe Vortexor to the S-SFC key operations. This print function is called "Ac-tion print" or "Continuous print".
Definitions
The printer fitted to the S-SFC as an option is a 24 character/line thermalprinter. On switching on the S-SFC power, the printer automatically movesout and back before stopping. The printer paper is fed out slightly (approxi-mately 5mm) here.
Printer
To feed the printer paper, press "SHIFT" + "8"."PRINTER FEED" is displayed on the screen, and the printer paper is fed outby one line. Pressing "8" while this is still displayed feeds out by another oneline.To cancel the feed function, press the "CLR" key to clear the "PRINTERFEED" display.
Printer paper feed
When the printer paper has run out, replace the roll in the roll holder compart-ment. See the S-SFC operating instruction manual (CM1-SFC100-2001) fordetailed instructions.
Replacing printerpaper
5 - 9
5.3.2 Printing Out internal Data: PRINT Key
In order to perform damping time constant and flow rate measurements cor-rectly, it is important to check the internal settings and responses from theVortexor when starting operation and while running. It is therefore useful tocommunicate with an S-SFC fitted with a printer, and print out the data. S-SFCs fitted with printers have two types of print functions, as defined below.
When used
The following procedure is used for configuration printing.Procedure
Step Procedure
1 Start transmission between the Vortexor and S-SFC.See "Starting transmission" on page 5-5 for details of the proce-dure.
2 Check that the S-SFC is in the READY state.
VRX XXXXXXXX
READY...
If not in the READY state, press the "CLR" key.
3 Press the "SHIFT" key.
SHIFT-
4 Press the "PRINT" key.
Result:Configuration printing starts.
WORKING...
5 Once printing has finished, press the "CLR" key.
Chapter 5 Transmission Using Smart Communicator SFC
5 - 10
Sample print-out
5 - 11
5.3.3 Printing Out Response Results Continuously: ACT PRINT Key
Action printing (continuous printing) is used to retain data by continuouslyprinting out response results from the Vortexor for the key controls from theS-SFC.
When used
The following procedure is used for action printing.Procedure
Step Procedure
1 Start transmissions between Vortexor and S-SFC.See "Starting transmission" on page 5-5 for details of the procedure.
2 Check that the S-SFC is in the READY state.
If not in the READY state, press the "CLR" key.
VRX XXXXXXXX
READY...
3 Press the "SHIFT" key.
SHIFT-
4 Press the "0" key.
VRX XXXXXXXX
ACTION PRINT ?
5 Press the "ENTER" key.
6 To stop action printing, press the "SHIFT" key.
SHIFT-
7 Press the "0" key.
VRX XXXXXXXX
ACTION PRINT ?
8 Press the "CLR" key.
Chapter 5 Transmission Using Smart Communicator SFC
5 - 12
5.4.1 Pulse Function
5.4 Settings and Alterations
This enables the pulse output parameters to be set. Settings should be madewhen using pulse output and when displaying cumulative display.
Introduction
English display
5 - 13
Chapter 5 Transmission Using Smart Communicator SFC
5 - 14
5.4.2 Range Function
This enables the display type and low flow cutoff to be set. Please read thissection for selecting display types, and for setting low flow cutoff.
Introduction
English display
5 - 15
5.4.3 Detector Function
This enables detector data to be set or changed.Introduction
English display
Chapter 5 Transmission Using Smart Communicator SFC
5 -16
5.4.4 K-Factor Function
This enables the compensation factor to be set to determine the detector prop-erties. This factor effects the detector properties, and so sufficient care mustbe taken when altering.
Introduction
English display
5 - 17
5.4.5 Setting Working Units
English display
Chapter 5 Transmission Using Smart Communicator SFC
5 - 18
5.4.6 Setting Span
The range lower limit for the Vortexor is normally 0, so the span can be set bydefining the upper limit.
Introduction
Procedure VRX XXXXXXXX
READY...
↓
This screen is displayed. Ifthis screen is not dis-played, press the "CLR"key.
Press the "URV" key.The span can be set within the ranges shown in the table below.
Diameter Setting range
25A 1.4 to 14m3/h
40A 3.6 to 36m3/h
50A 6.0 to 60m3/h
80A 11.5 to 115m3/h
100A 20 to 200m3/h
The units system can be changed here by pressing the "UNIT" key.
5.4.7 Setting Damping Time Constant
The damping time constant reduces the drift of output and display, resulting instable output.
Introduction
Procedure VRX XXXXXXXX
READY...
This screen is displayed. Ifthis screen is not dis-played, press the "CLR"key.↓
Press the "DAMP" key.
Press the " p " or " q " keys to set the damping time constant from the valuesbelow.Available values:1.0s, 2.0s, 3.0s, 4.0s, 5.0s, 10.0s, 50.0s, 100.0s, 199.0s
↓
5 - 19
5.4.7 Alarm Output Function
This enables the alarm output function to be set. The output can be selectedfrom one of three modes.
Introduction
English display
Chapter 5 Transmission Using Smart Communicator SFC
5 - 20
5.4.8 Setting Error Processing (Fail-safe)
This enables the output mode to be set for when an error occurs with theVortexor.
Introduction
English display
5 - 21
5.4.9 Totalizer Function
This enables the totalizer counter to be set.Introduction
English display
Chapter 5 Transmission Using Smart Communicator SFC
5- 22
5.4.9-(1) Read total
This displays the total flow rate.
English display
5 - 23
5.4.9-(2) READ R.CNTR display
This displays the reset counter value.
English display
Chapter 5 Transmission Using Smart Communicator SFC
5 - 24
5.4.9-(3) SETR R.CNTR display
This changes the reset counter value.
English display
5 - 25
5.4.9-(4) RESET R.CNTR display
This resets the reset counter to zero.
English display
Chapter 5 Transmission Using Smart Communicator SFC
5 - 26
5.4.9-(5) SET VOLUME UNIT
This sets the cumulative flow rate units.
English display
5 - 27
5.4.9-(6) PULSE OUTPUT display
This sets the dummy pulse output frequency.The pulse output frequency is the number of pulses output per second. Thisshould be set depending on the counter used.
English display
Chapter 5 Transmission Using Smart Communicator SFC
5 - 28
MEMO
6 - 1
Chapter 6 Troubleshooting
Chapter Outline
This chapter explains troubleshooting procedures for dealing with malfunc-tions.The following points are described here.
• Corrective action for malfunctions• Sensor replacement method• LCD replacement method• Resale parts list
6 - 2
Chapter 6 Troubleshooting
6.1 Measures for Malfunctions
This equipment is adjusted for the surest usage upon shipment; however, if amalfunction occurs at startup or while operating the equipment, check thefollowing.If unsure of what needs to be done, contact our customer service network.
Incident Checkpoint Countermeasures
· Is the wiring connected
properly?
· Is the power-supply voltage
within the specified range?
· Is the load resistance cor-
rect?
· Is the piping filled with liq-
uid?
· Is the flow rate within mea-
surable range?
· Is sensor fault alarm given?
· Is the piping filled with liq-
uid?
· Does the liquid inside the
pipe churn due to consider-
able ripple pressure e.g., due
to pumping?
· Is the flowmeter installed on
the T-pipe? (Effect of ripple
pressure caused by T-pipe.)
· Are there any external noise
sources e.g., motor line or
electromagnetic wave gen-
erator?
· Connect wiring correctly.
· Adjust the power-supply so
that it is within the specified
range.
· Adjust the load resistance so
that it is within the specified
range.
· Modify piping or operating
conditions so that the piping
fills with liquid.
· Change the operating condi-
tions.
· If so, replace sensor.
· Modify piping or operating
conditions so that the piping
fills with liquid.
· Control the conditions in-
side the pipe to eliminate
waves.
(Install a valve upstream of
the flowmeter.)
· Install a valve closer to the
junction of the flowmeter.
· Isolate the flowmeter from
noise sources.
· Perform sufficient ground-
ing.
· Use a shield line.
No output
(No output in the presence
of a flow.)
Data is output even in ab-
sence of flow.
(Continued on the next page)
This section describes the action to be taken if the flow meter malfunctions.Introduction
Instructions
6 - 3
Incident Checkpoint Countermeasures
· Is the power-supply voltage
within the specified range?
· Is the load resistance cor-
rect?
· Are there any external noise
sources e.g., motor line,
electromagnetic wave gen-
erator?
· Is there an element that is
disturbing the flow (e.g., a
valve that is upstream and
the closest to the flowme-
ter)?
· Is cavitation occurring?
· Are there bubbles in the liq-
uid?
· Is an object caught in the
vortexor?
· Is sensor fault alarm given?
· Adjust the power-supply so
that it is within the specified
range.
· Adjust the load resistance so
that it is within the specified
range.
· Isolate the flowmeter from
noise sources.
· Use a shield line.
· Change the installation site
of the flowmeter. (Confirm
that the specified length of
straight pipe is sufficient.)
· Confirm there is sufficient
line pressure to prevent
cavitation.
· Prevent the occurrence of
bubbles.
· Remove the object.
· If so, replace sensor.
Significant difference
(Continued)
6 - 4
Chapter 6 Troubleshooting
6.2 Error Messages and Corrective Action
This section describes the error messages given by the SFC self-diagnosticfunction, and includes methods for corrective action.
Introduction
Error messages Details of status displays are described below.
R-1 SENSOR FAULTThe reception level of the receiving ultrasound sensor 1 (upper left and lowerright sensors viewed from upstream side of flow meter) has dropped. Checkthat the flow meter interior is full of water. If full of water, a sensor or receivercircuit fault is likely. If full of water and an alarm is given, the sensors must bereplaced.
R-2 SENSOR FAULTThe reception level of the receivingultrasound sensor 2 (upper right andlower left sensors viewed from up-stream side of flow meter) hasdropped. Check that the flow meterinterior is full of water. If full ofwater, a sensor or receiver circuitfault is likely, and the sensors mustbe replaced.
BAD CONFIG DATAThere is an error in the span or pulseoutput unit settings. Reconfigure atthe CONFIG (special function)menu.
EEPROM FAULTThe EEPROM is faulty. Reset the flow meter. (Hold a magnet close for atleast 3 seconds while pressing " p " and ENT buttons.)
S SENSOR FAULTThe sensor transmission circuit is faulty. The sensor must be replaced.
R12 SENSOR FAULTThe reception levels of both receiving sensors 1 and 2 have dropped. Checkthat the flow meter interior is full of water. If full of water, a sensor or receivercircuit fault is likely, and the sensors must be replaced.
FIXED PULSE MODETest pulse is currently being output.
IN OUTPUT MODEAnalog 4-20mA is currently being test output.
Transmitter 1 Transmitter 2
Flow direction
Receiver 1Receiver 2
6 - 5
6.3 Sensor Replacement Instructions
This section describes the procedure for replacing sensors when sensor faultsoccur.
Introduction
Caution• The sensor capillary lengths vary depending on the opening diam-
eter. The correct replacement part must be used to match the rel-evant diameter.
Replacementprecautions Warning
• Before replacing sensors, check that the detector unit is not hot orcold. There is a danger of injury or burns.
Caution• The output signal disappears while sensors are being replaced.
Precautions must be taken such as operating manually to preventeffects on the control loop.
6 - 6
Chapter 6 Troubleshooting
1. Switch off the power.2. Unscrew the set screw.3. Remove the transducer case cover while rotating.
Note that there is an O-ring in the joint section.4. Unscrew the retaining screws (M3x4) on amplifier unit, and pull out the
amplifier unit.The retaining screws are designed not to fall out, so do not pull out withexcessive force.
5. Detach the cable and power cable connectors attached to the amplifierunit.The sensor cable is fine wire, so take care not pull out with excessiveforce.
Figure 6.1
Replacementprocedure
Sensor cable connector
Transducercase cover
Set screw
O-ring
Amplifier unit
Amplifier unit retaining screws (M3) x4
Power cable connector Transducer case
(Continued on next page)
6 - 7
Replacementprocedure (continued)
6. Remove the bolts (M5x4) from the bottom of the transducer case.
7. Remove the bolts (M4x2, 4 locations) securing the sensor unit holderfrom the housing.
8. Remove the bolts (M8x2) securing the sensor unit to the housing.
9. Remove the sensor unit from the housing.
10. Wash the replacement sensor unit and housing holder attachment surfacewith organic solvent.Take care not to scratch the holder underside and attachment surface, orleave debris adhering when washing.
11. Fit the seal to the replacement sensor unit holder.
12. Thinly apply silicone adhesive to the underside of the holder.Take care that air bubbles are not introduced here.
13. Thread the tube between the housing ribs, and attach the sensor unit to thehousing.If the tube does not align with the groove and the holder rises above at-tachment surface, arrange the tube first before continuing. (The replace-ment sensor unit tube is made to match the housing profile. If the profiledoes not match, however, it should be repaired.)After attaching, seal the holder underside to the attachment face by push-ing the holder firmly against the attachment face to eliminate air bubblesfrom between the holder underside and attachment face.
14. Tighten the flat spring and retaining plate with the bolts (M4x2).(Tightening torque: 12 - 18kgf.cm)
15. Refit the transducer case, amplifier unit, and transducer case cover in thereverse order in which they were removed.Take care not to forget to fit O-rings, connect connectors, or tighten re-taining screws, etc.
(Continued on next page)
6 - 8
Chapter 6 Troubleshooting
Figure 6.2
(Housing ribs)
Seal
(Holder underside)
Seal attachment diagram
4 locations
Bolt (M4) x2Washer
Retaining plateFlat spring
Seal
(Holder attachment face)
Housing
Washer
Bolt (M5) x4
(Tube)(Holder)
Seal
Trans-ducer case
O-ring
Sensor unit
Bolt (M8) x2
Washer
6 - 9
6.4 LCD Replacement Instructions
This section describes the procedure for replacing the LCD when it becomeslife-expired after 5 years have elapsed.
Introduction
1. Switch off the power.
2. Unscrew the set screw.
3. Remove the transducer case cover while rotating.Note that there is an O-ring in the joint section.
4. Remove the LCD mounting panel mounting screws (M3x2).
5. Remove the LCD mounting panel together with the face panel.(The LCD mounting panel is integral with the face panel.)
6. Fit a new LCD panel, and secure with the screws.
7. Attach the transducer case cover and tighten the set screw in the reverseorder in which they were removed. (Do not forget to insert the O-ring.)
8. Switch on the power.
Figure 6.3
Replacementprocedure
Face panel
Transducercase cover
Set screw
O-ring
LCD panel mountingscrew (M3) x2
LCD panelConnector
Transducer case
6 - 10
Chapter 6 Troubleshooting
6.5 Resale Parts List
This section includes exploded views of the ultrasonic vortex flow meter re-sale parts. Please mention the part numbers when ordering parts.
Introduction
Document Number : CM2-VRX100-2001Document Name : ULTRA Vortexor
Smart Ultrasonic VortexFlowmeter User's Manual
Date : 1st Edition: July 19982nd Editoin: Sep. 2012
Issued / Edited by : Azbil Corporation