Upload
marcos-amorim
View
214
Download
0
Embed Size (px)
Citation preview
8/10/2019 UK TechnBrosch
1/52
Kalzip Systems
Product information and specification
8/10/2019 UK TechnBrosch
2/52
8/10/2019 UK TechnBrosch
3/52
Introduction
1a
Roofs and walls are the main factors
marking the external appearance
of buildings. The fundamental rule
applying to architectural design is:
form follows function.
As far as the realisation of an architec-
tural design is concerned the costs
for building, operating and maintaining
the building are crucial factors for
any decision maker. This is why high
quality building materials requiringonly little maintenance are more
economical in the long run. In addition,
the increasing shortage of resources
is raising awareness of the need for
energy saving construction methods.
The beneficial characteristics of
aluminium as a building material go
a long way towards meeting these
requirements.
Corus Bausysteme is the leading
manufacturer of profiled aluminium
sheets and in the form of Kalzip
offers a mature system for covering
both roofs and walls. This brochure
offers detailed product information
and demonstrates various fields of
application.
Planning specifications and dimensio-
ning tables are also included to provide
a comprehensive guide to the design
of Kalzip roofs and walls for a wide
range of building types. Fashion centre Almere (NL)
Architect: KOW Stedenbouw & Architectuur
Primary school Hille (D)
Architect: Brinkmeier, Kraus, Stanczus, Lbbecke
Offices Wrth Den Bosch (NL)
Architect: De Twee Snoeken
Roofs and walls
Exhibition hall 3, Frankfurt trade fair (D)
Architect: N icholas Grimshaw & Partners
8/10/2019 UK TechnBrosch
4/52
8/10/2019 UK TechnBrosch
5/52
1b
1. Introduction Site
Contents 1bKalzip the economical all-round solution 1cLightweight building envelopes 1d
2. The construction system and its components
2.1 Dimensions of the profiled sheets 2a2.2 Clips and thermal barrier pads 2b2.3 Different finishes and colours 2e2.4 Accessories 2g2.5 Structural components for roof superstructures and safety devices 2i
3. Kalzip range of applications
Kalzip non ventilated roof on trapezoidal steel deck 3aKalzip non venti lated roof on purl in with trapezoidal sheets inner skin 3bKalzip non ventilated roof on timber rafters with visible timber lining 3bKalzip ventilated roof with common rafter insulation 3bKalzip DuoPlus 3cKalzip Duo 3c
Kalzip NatureRoof
3cKalzip AF 3dKalzip AF with Prodach-insulation on trapezoidal steel deck 3dKalzip AF with Prodach-insulation on timber rafters with timber lining 3eKalzip AF with common rafter insulation 3eKalzip AF on FOAMGLAS insulation 3e
4. General data and characteristics
4.1 Roof pitch 4a4.2 Minimum radii for crimp, smooth and on-site curving 4b4.2.3 Natural curving 4d4.3 Tapered shapes 4e4.4 Walkability/fall arrest system 4f4.5 Material/corrosion resistance 4g4.6 Ecological aspects 4h4.7 Approval by surveyor's office/design calculation 4i
4.8 Transport 4i4.9 Sheet thickness 4i
5. Design specifications
5.1 Thermal insulation 5a5.2 - 5.4 Moisture proof, Acoustic performance, fire/lightning protection 5b5.5 Constructional features 5c5.5.1 Rafter roof: Kalzip perpendicular to the trapezoidal steel deck 5c5.5.2 Purlin roof : Kalzip parallel to inner skin 5d5.5.3 Kalzip Duo and Kalzip DuoPlus 5e5.6 Connections 5g5.7 Thermal expansion 5h5.8 Fixed point 5h5.9 Ridge, eaves, gable ends 5h5.10 Skylights/smoke extractors 5i
5.11 Transverse joints 5j5.12 Substructures 5j5.13 Roof projections with cantilevers/clip bars 5j5.14 Instructions for the installation of cantilevers/clip bars 5j5.15 Roof projections without clip bars 5k5.16 Installation rules 5k
6. Dimensioning tables for Kalzip multi-span sheets
6.1 Thermal conductivity coefficents for TK 15 6a6.1.1 Thermal conductivity coefficents for Kalzip DuoPlus 6b6.2 Clip spacings 6c6.2.1 Rafter roof with aluminium clips 6c6.2.2 Rafter roof with compound clips 6d6.2.3 Purlin roof with aluminium clips 6e6.2.4 Purlin roof with compound clips 6f6.2.5 Kalzip ProDach with aluminium clips 6g
6.2.6 Stainless Steel with aluminium clips and compound clips 6h
Index
8/10/2019 UK TechnBrosch
6/52
Introduction
1c
Kalzip the economical all-round solution
Highly flexible and proven
For more than 35 years Kalzip has been
used in the design and construction of
buildings all over the world. Developed
upon the basic principles of the classic
handmade standing seam roof Kalzip
is perfectly suitable for roofs featuring a
very low pitch. Due to the great variety
of different designs and its attractive
appearance, the Kalzip system is the
first choice when it comes to combining
architectural design and function. The
proven modular Kalzip system offers a
great variety of different shapes and
includes all the accessories needed to
construct a beautiful building envelope.
Quality at its best
The standard version of the Kalzip
aluminium sheets is stucco-embossed
and plated on both sides with a specialalloy providing the surface with an
effective additional protection.
Designed to fit any architectural
style of roof or building
Kalzip offers economical solutions for
almost all requirements of advanced
architecture no matter what shape
or size the building may be. Despite
its low structural weight the Kalzip
roof is able to span large widths and
can achieve the most elegant, filigree
constructions. Kalzip profiled sheets
are perfectly suitable for the lining oflarge areas of facades and roofs.
Introducing colour into architectural
design
Kalzip is a highly diverse product and
is also available in a variety of colours.
A colour chart illustrates the range of
standard and special colours available.
Only top quality coatings are used on
a polyester, PVDF and CFTE base.
The colour range includes:
RAL colours
RAL special colours
SoftColor
TitanColor
AntGraffiti
This diverse range of options increases
the freedom of design even further
and guarantees the highest level of
resistance to weathering and corrosion.
Kalzip
colour products are the resultof the very latest surface refinement
techniques.
Innovative material combinations for
exclusive surfaces
In addition to the standard stucco-
embossed option, Kalzip also creates
exclusive architectural designs through
the use of innovative material combi-
nations and surface treatments. Kalzip
sheets in AluPlusPatina, AluPlusZinc,
AluPlusTitan and Stain less Steel
provide the perfect finishing touches,
adding individuality to elegant buildingdesign.
Innovation with international appeal:
Kalzip with zinc plated surface
This innovative product developed by
Corus Bausysteme combines two highly
approved materials: aluminium and zinc.
Zinc is a classic roofing material noted for
its timeless appearance. The intrinsic ad-
vantages of the Kalzip system combined
with the distinctive pre-aged zinc look
make this product an attractive option
for those applications where aesthetic
appearance or visual compatiblity with
surrounding structures is desired.
Kalzip AluPlusZinc offers unique
advantages:
Zinc patina with surface protection
Impressive, authentic visual appeal
Dynamic surface effects with
changing light conditions
Durability thanks to aluminium core
Kalzip AluPlusTitan
This combination of aluminium and titani-
um offers architects yet more interesting
design potential. The symbiosis of these
two materials each in themselves high
quality/high performance metals brings
quite unique advantages. Titanium not
only guarantees long-term resistance to
corrosion but also provides exceptionally
high mecha-nical and thermal stability.
For roofs and facades exposed to
particu-larly harsh conditions, Kalzip
AluPlusTitan will provide reliable andlong-lasting protection.
8/10/2019 UK TechnBrosch
7/52
Introduction
1d
Lightweight building envelopes
Kalzip AluPlusTitan offers the following
benefits:
Durable, exceptionally weather-
resistant combination
Outstanding mechanical and
thermal stability
Exclusive metallic appearance
Kalzip Stainless Steel
Where an architectural design is
characterised by the use of stain-less
steel both for decorative and functio-
nal purposes both on the interior and
the exterior of the structure; the effect
can now be extended to the facade and
roof with use of Kalzip Stainless Steel
profile sheets.
Available in a characteristic metal lic
surface, stainless steel provides a
striking visual effect whilst offeringoutstanding durability.
Kalzip Stainless Steel
product advantages:
Durable, weather-resistant
Striking metallic finish
Hi-tec facade appearance
Proven experience
To date more than 65 million square
metres of Kalzip elements have been
installed all over the world. This level
of expertise and the experience gained
over more than 30 years offers theoptimum guarantee to planners and
design engineers for this reason
Corus Bausysteme is the leading
producer of prefabricated aluminium
standing seam systems in the world.
Material Aluminium
light and strong
corrosion-resistant
durable
good workability
weldable
high compatibility in combination with
different materials
nonflammable
suitable as a part of air termination
network
nontoxic
recyclable
reusable
stable in value
valuable
Kalzip variants in shape
precurved
tapered
concave-convex
convex-curved
tapered-curved
smooth curved
crimped curved
Quick and precisely fitting assembly
Kalzip profiled sheets are joined onsite
by mechanical seaming. The roof is fixed
by means of special flanged-in clips,so that the roof surface is not penetrated
by any fixing elements. The clips transfer
the forces of aerodynamic pressure and
uplift to the supporting structure. The
special design of the clips and also of
the flanging allows unrestricted linear
expansion even across long Kalzip
profiled sheets.
Economical reconstruction
Kalzip profiled sheets allow a quick
and easy refurbishment of deckings,
pitch roofs and even steep roofs.
Due to the low weight of approximately
7 kg of the Kalzip elements, there is
in most cases no need either to remove
the existing roof or to reinforce the
supporting structure. The assembly
of the Kalzip system is a speedy
process and usually there is little or
no disruption to either the occupantsof the building or to its function.
Kalzip features and benefits
long lasting durability
high economy
ideal for efficient thermal insulation and
acoustic performance
compatible with any kind of roof
design and supporting structures
ideal for roof refurbishment bitumen,
foil or corrugated asbestos sheet roofs
requires only minimum maintenance
no painting required
comprehensive range of advancedaccessories
8/10/2019 UK TechnBrosch
8/52
The system and its components
2a
2. The system and its components
The standard version is stucco-embossed
and coated with a protective plating on
both sides. The minimum thickness ofthis plating is 4 per cent of the nominal
sheet thickness.
The nominal thickness is subject to the
tolerances specified by DIN EN 485-4.
As far as the lower tolerances areconcerned, only 50 per cent of the
specified values will be allowed.
The length tolerances are:
with sheet lengths up to 3 m:
+ 10 mm / 5 mmwith sheet lengths of more than 3 m:
+ 20 mm / 5mm.
2.1 Dimensions of the profiled sheets
*) Only in combination with accessible insulation materials or wooden timber lining.
Preferable thicknesses 0.9 to 1.2 mm.
**) recommended for facade cladding
Dimensions mm Thickness mm
1,2
1,0
0,9
0,8
1,2
1,0
0,9
0,8
1,2
1,0
0,9
0,8
1,2
1,0
0,9
0,8
1,2
1,0
0,9
0,8
1,2
1,0
0,9
0,8
1,2
1,0
0,9
0,8
1,2
1,0
0,90,8
Kalzip 50/333
Kalzip 50/429
Kalzip 65/305
Kalzip 65/333
Kalzip 65/400
Kalzip 65/500 **)
Kalzip AF 65/333 *)
Kalzip AF 65/434 *)
1,2
1,0
0,9
0,8
Kalzip AS 65/422 *)
There are many variations in shape
for instance
hyperbolically
curved
elliptically
curved
tapered-convex
curved
tapered
concave
curved
convex
curved
straight
65
65
65
65
65
65
50
50
333
429
305
333
400
500
333
434
65
422
8/10/2019 UK TechnBrosch
9/52
The system and its components
2b
2.2 Clips and thermal barrier pads
Kalzip aluminium clip
Special aluminium clips have to be
used for securing the Kalzip profiled
sheets to the substructure of the roof.
They are locked into the seam and will
be overlapped by the following Kalzip
sheet, so that the fixing elements are
hidden under the roofing.
This ensures that the roofing elements
need not be punctured for fastening
and therefore provide a perfect seal.
The clips allow the sheets to move
lengthwise sliding freely to accommodate
thermal expansion.
The clip head has a special shape
which has been designed to ease this
longitudinal expansion of the profiled
sheets enabling the use of very long
sheets.
Movement generally occurs from the
fixed point towards the eaves.
The movement of the sheets must not
be restricted by rigid joints with other
constructional elements.
The clips have to be directly fixedto the steel, aluminium or wooden
substructure by means of approved
fasteners.
When fixing the profiled sheets to concrete
substructures; steel, aluminium or wooden
spacers, firmly anchored in the concrete
must be used for mounting the profiled
Kalzip sheets.
When installing Kalzip sheets on roofs
with a very low pitch special care has
to be taken to see that the clips are
positioned at the correct height both at
the eaves and at the ridge of the roof in
order to avoid an inverse pitch.
At the ridge the head of the clip should
be positioned slightly higher and at the
eaves preferably slightly lower.
Kalzip zipping machineKalzip aluminium clip
8/10/2019 UK TechnBrosch
10/52
8/10/2019 UK TechnBrosch
11/52
2d
The system and its components
Kalzip DuoPlus rotatable clips and
Kalzip DuoPlus rail, perforated
The DuoPlus rail along with the DuoPlus
clip create a total solution for secure
and convenient installation of the
mounting elements for Kalzip profile
sheets.
After install ing the insulant, the rails are
aligned according to the calculation and
mounted with the fixing elements of
SFS intec SD2-S16-6.0 x L in the
steel trapezoidal profile subshell.
Subsequently, the DuoPlus clips are
manually screwed in.
Although these remain adjustable, the
DuoPlus rail still offers a secure hold;
therefore DuoPlus can be adapted to
the individual circumstances depending
on the profile dimension and/or toleran-
ce. Therefore a customised and conve-
nient installation is guaranteed every
time.
Kalzip E 140/160
compound clips
According to the European heating
requirements, which has been an inte-
gral part of building regulations in
several countries, it is now obligatory
to take account of thermal bridges
when planning building projects.
The new Kalzip compound clip, which
is used to connect Kalzip aluminium
standing seam to the substructure ofthe roof, fulfils this requirement in an
exemplary manner, prevents thermal
bridges (see diagrams) and succeeds
in creating a system which is virtually
cold-bridge free therefore optimizing
the performance & efficiency of the
roof. All characteristics and functions
relating to the load carrying capacity
and attachment to structure or decking
are fulfilled and are documented in the
approval granted by the state con-
struction supervisors. The clip has a
PA structure which is reinforced witha steel core.
Kalzip E 140/160
compound clips
Kalzip DuoPlus rotatable clip
Kalzip DuoPlus rotatable clips in
Kalzip DuoPlus rail, perforated
Dimensions: 120 x 6000 length
Kalzip 50/ Kalzip 65/
clip type clip height (H) w3 w3
E 140 201 155 140
E 160 221 175 160
dimensions in mm
Kalzip 50/ Kalzip 65/
clip type clip height (H) w4 w4
D 60 116 75 60D 80 136 95 80
D 100 156 115 100
D 120 176 135 120
D 140 196 155 140
dimensions in mm
H = height of cl ip
w3 = distance between Kalzip bottom
and bottom edge of clip foot type E
w4 = distance between Kalzip bottom
and bottom edge of DuoPlus rail
8/10/2019 UK TechnBrosch
12/52
8/10/2019 UK TechnBrosch
13/52
The system and its components
2f
Alumin ium strips with single-sided
coating are also given a coat of pro-
tective varnish on the reverse side.
In order to achieve a weather resistant
and colourfast coating, only high
quality stove enamels have been
used on a polyester, PVDF or CFTE
base.
The coil-coating process is monitored
in accordance with the standards of
the ECCA (European Coil-Coating
Association).
These standards relate to the following
important criteria: colour tone, degree
of lustre, thickness of finish) coating,
hardness of finish, bonding and consi-
stency of finish.
Long-duration tests are also carried
out, for example, acid salt spray tests,
QUV B tests, tests carried out in a
saturated atmosphere in the presence
of SO2 and outdoor exposure tests
conducted in a hostile environment.
Kalzip SoftColor
This coating has a soft textured
appearance, which reduces reflection
and provides the architectural design
with a distinctive appearance. Softcolor
contains a special polyester laquer
that is added during a separate pre-
treatment process.
Kalzip TitanColor
TitanColor features a special, unbrus-
hed aluminium base with a tough,
UV-resistant, single-layer polyurethane/
polyamide coating, which effectivelygives the appearance of high quality
titanium.
KalzipAntiGraffiti
The multi-layer AntiGraffiti system is
designed to remove graffiti using speci-
ally approved cleaning agents and the
associated cleaning technology. When
correctly used, the system will remove
all traces of graffiti. The colour structure
is not affected.
The AntiGraffiti coating provides a
combined colour structure of PVDF
and CTFE, and has similar properties
to Teflon.
Surface finishes and colours
In addition to the diverse range of
shape variants, Kalzip also offers a
wide range of colour and surface
finishes which provides optimum design
freedom and safety. Only high-quality
coatings on a PVDF or polyester base
are used for Kalzip sheets and these
coatings meet the extreme demands
of modern building technology.
The coloured coating is applied in the
quality-monitored coil coating procedurein accordance with the strict standards
of the ECCA (European Coil Coating
Association). A wide range of RAL
colours is also available as standard
for the fittings.
Coil-Coating
Liquid lacquer is rolled onto the
aluminium layer in a coil coating
process. These colour coated coils
are then used to roll-form the Kalzip
profiles. Coil coating is the most
economical, environmentally friendly
and safest way of fabricating largequantities of coated semi-finished
products of uniform quality.
The coating materials used for coil coa-
ted Kalzip profiled sheets offer outs-
tanding resistance to weathering and
also to the effects of high levels of air
pollution.
These excellent performance characte-
ristics ensure a long decorative life for
coil coated profiles. Profiled sheets in
standard colours shown in our colour
chart are kept in stock. Special colours
in small quantities have to be individu-
ally coated piece by piece either by
powder coating or by wet coating.
Protective foil
On request the whole surface or just
the flanges will be protected against
damage by a self-adhesive foil.
Metallic enamels
In the case of metallic enamel coating,
variations in colour may occur between
different production batches. For this
reason it is advisable to take care when
planning facades or visible roofs to
make sure that the profiled sheets areroll formed from the same batch of
material.
Anti-condensation and
anti-drum coatings
If required the profile sheets can also
be fitted with an anti-condensation or
anti-drum coating.
Continuous
coil coating
Roll forming
8/10/2019 UK TechnBrosch
14/52
Rib fillerseals the edge of the eaves
Drip angle (Al)
stiffens the bottom sheet and
makes the water drip into the gutter
indispensable for static reasons!
Compressible adhesive tape
prevents flow-back of rain
water
Kalzip vapour barrier
avoids air flow and
diffusion
The system and its components
2g
2.4 Accessories
gable bar verge Eaves
Transition sheet (Al)
for rising walls and gable ends
8/10/2019 UK TechnBrosch
15/52
The system and its components
2h
Drip angle Ridge
Reinforcing profile for
verge flashing (Al)
stiffens the flange
Gable end hook (Al)
secures gable end against storm
Ridge profile (Al)
protects the form filler against UV radiati-
on and reduces wind pressure
Form filler
ends flush with the ridge
Spacer section (Al)
compensates height differences
to the end plate
Gable end profile (Al)
provides fastening device for
joining sheets
8/10/2019 UK TechnBrosch
16/52
The system and its components
2i
2.5 Components for roof superstructuresand safety appliances
Photovoltaics Step
8/10/2019 UK TechnBrosch
17/52
The system and its components
2j
Seam clips Snow guard
8/10/2019 UK TechnBrosch
18/52
Kalzip range of applications
3a
3. Kalzip range of applications
Non-ventilated Kalzip roof
on a trapezoidal steel deck
Rw = ~ 35 dB (A)*
* varies depending on thickness and material qualities
Appl icat ion specific system build-upKalzip sheets can be used both for
ventilated and non ventilated roofs as
well as for any roof shape or down to
a minimum pitch of 1.5.
Furthermore it may be combined with
any kind of support or substructure.
The system depends on the special
requirements of the individual application.
The likely effects of snow, wind,
humidity and weathering are fully
taken into account. Kalzip can easily
be configured to provide the highestlevels of thermal insulation.
The thickness of the insulation can be
perfectly adapted to the individua lre-
quirements of the building.
In addition, the system offers advanceddetailed solutions for effective interior or
exterior draining of the roof which means
a high degree of reliabilty throughout the
long serviceable life of the roof.
Insulated roof systems are the norm
The main applications for Kalzip roof
systems are insulated roof structures
supported by trapezoidal steel, timber
linings, purlins or concrete elements.
Because of the generally very long pro-
filed sheets and the low pitch of most
of the roofs a non ventilated roof is
recommended.
Chemically neutral, fibrous insulating
materials as specified by e.g. the
German DIN 18 165 are recommended
as suitable thermal insulation.
The insulation is laid into position andis then compressed to its required
final thickness when are installed the
profiled Kalzip sheets on top. There
should be no cavity between the
Kalzip sheets and the insulation.
A vapour barrier must be incorporated.
Properly installed it provides the
required air tightness.
Ventilated roofs are also an option.
The sound reduction values of the
standard roof are subsequentlydescribed. Further improvements
can be achieved by including
additional layers.
Non-ventilated Kalzip roof on a
trapezoidal steel deck
This very economical roof system is
used both for industrial and residential
buildings. In order to make sure that
there are no air cavities under the
Kalzip roof skin, compressible thermal
insulation is used. Incorporated within
the roof system the insulation material
is compressed by approx. 20 mm. The
loading on the top skin is not transferred
to the inner skin as an evenly distributed
load but rather at set points via the
secret fixing clips. The design roof load
must be increased by 15 per cent when
dimensioning the trapezoidal steel
sheets. The clips must be staggered
on the inner sheet to make sure that
the load is evenly distributed across allcorrugations of the inner sheet.
8/10/2019 UK TechnBrosch
19/52
Kalzip range of applications
3b
Non-ventilated Kalzip
roof on purlinswith trapezoidal inner sheet
If the roof is supported on purlins, the
inner sheet has to be oriented parallel
to the top layer. If the module of the
inner sheet does not correspond with
the Kalzip elements a top hat section
must be installed to support the clips.
If the Kalzip sheets can span the exi-
sting spacing of the purlins, the top
hat sections will be positioned on top
of the purlins. By this way the inner
sheet carries only the weight of the
insulation. For larger purlin spans
additional top hat sections are required.In this instance, part of the load needs
to be transferred by the inner sheet.
Non-ventilated Kalzip roof on timber
rafters with visible timber lining
In residential buildings the roof system
is frequently built-up using wooden
rafters with visible timber lining. This
is advantageous, because:
1. there is a clear separation between
the trades of carpenters, roofers etc.
2. a continuous flat vapour barrier
can be installed.
The clips can only be fixed directly to a
timber lining that has a minimum thick-
ness of 30 mm. If the lining is too thin
an additional wooden purlin connected
to the rafters must be mounted on top
of the lining.
Ventilated Kalzip roof with thermal
insulation of the rafter levelWith roofs featuring a structure as shown
on the left it is quite often impossible to
design the roof as a non-ventilated version
because the distances are too great bet-
ween the vapour barrier and the roof skin.
Therefore such a roof must be designed
as a ventilated roof. Consequently perfect
functioning of the vapour barrier is a pre-
requisite condition. Sufficient ventilation
is essential for efficient dispersal of any
condensation that might occur. If there
are any risks of wind driven snow it may
be necessary to install a foil barrier to
prevent snow from coming into contactwith the insulating material.
Non-ventilated Kalzip roof on timber rafters
with visible timber lining
Rw = ~ 38 dB (A)*
Ventilated Ka lzip
roof with thermalinsulation of the rafter level
Rw = ~ 35 dB (A)*
* varies depending on thickness and material qualities
Non-ventilated Kalzip roof
on purlins with trapezoidal inner sheet
Rw = ~ 35 dB (A)*
8/10/2019 UK TechnBrosch
20/52
Kalzip range of applications
3c
Kalzip DuoPlus
The Kalzip DuoPlus system combines
the advantages of rigid insulation with
the constructional possibilities offered by
the conventional Kalzip roofing system.
The special design is almost cold-bridge
free and has excellent sound absorption
properties. An aluminium rail is placed
on the 100 mm thick rigid thermal insu-
lation and is fixed onto the substructure
through the insulation. Special clips are
inserted in the rail and are adjusted to
suit the respective conditions. Connection
of the individual clips to the rail is not
necessary. The patented and type-testedsystem consists of rigid thermal insu-
lation, DuoPlus rail, DuoPlus clip and
connecting elements to secure the
DuoPlus rail, the compressible heat in-
sulation and the Kalzip profiles sheets.
Kalzip Duo
If there are no specific sound insulation
requirements then the Kalzip Duo
system can be used, whereby a full
layer of rigid thermal insulation is not
necessary. The base for the Kalzip
DuoPlus is simply provided by rigid
insulation strips with a width of 24 cm
and a thickness of 10 cm. The resulting
spaces are filled with soft heat insula-
tion or low-priced rigid insulating
material.
In the case of Kalzip DuoPlus, rigid
thermal insulation only needs to be
used in those areas specified by the
statistical requirements. The rigid
thermal insulation is replaced by a
layer of soft insulation in all areas
where no reduction in snow loads
is required.
Kalzip NatureRoof
All roof designs described above can be
transformed into a Kalzip NatureRoof
providing that the design requirements
are taken into consideration and Kalzip
65/333 is being used.
Kalzip NatureRoof comprises an efficient
draining mat to control the integral water
management and a special substratesupporting a vegetation layer for exten-
sive landscaping with sedum plants (see
special brochure Kalzip NatureRoof).
Kalzip NatureRoof
Kalzip Duo
Rw = ~ 41 dB (A)*
Kalzip DuoPlus
Rw = ~ 43 dB (A)*
8/10/2019 UK TechnBrosch
21/52
3d
Kalzip range of applications
Kalzip AF
Kalzip
AFprofiled aluminium sheets
are especially designed for installation
above rigid support layers. Under
the trade mark Prodach insulating
system Rockwool offers an accessible,
compression-proof, water repellent
mineral wool insulating board featuring
a special fixing system. Kalzip AF
is available in sheet lengths up to
50 m (longer lengths are available
on request).
The level ribless profile provides a
smooth and attractive appearance.
The AF system offers outstandingthermal as well as acoustic properties.
Kalzip AF profiled aluminium sheets
are not only used in combination withthe Prodach-insulation system but
may also be used with FOAMGLAS
insulation and timber lining.
The twin layer Prorock insulating
board: the ideal base for Kalzip AF
non combustible
very efficient thermal insulation
and acoustic properties
dimensionally stable
vibration dampening
open for diffusion
high accessibility during
installation and maintenance safe absorption of pressure
and suction loads
AssemblyThe corrosion-proof and weather resi-
stant Kalzip AF aluminium external
skin is fixed with clips in the usual way.
However, and this is the distinctive
feature of the Prodach insulation
system, rather than being fixed directly
to the substructure the skin is fixed
instead to special U-rails embedded in
the insulation material.
The stainless steel system fasteners
connecting the U-rails to the substruc-
ture of the roof penetrate the insulation
material only locally. This almost entirelyeliminates the effect of cold/heat and
sound bridging.
Kalzip AF with Prodach-insulation
on trapezoidal steel deck
Rw = ~ 42 dB (A)*
Kalzip AF with Prodach-insulation
on trapezoidal steel deck
In order to meet increased demands
for sound reduction and to reduce
cold/heat bridges it is advisable to
install the Prodach Insulation System.
Fixing rails are embedded in the top-
side of the insulation material and
fixed to the trapezoidal steel deck.
* varies depending on thickness and material qualities
8/10/2019 UK TechnBrosch
22/52
Kalzip AF
on FOAMGLAS
insulationKalzip AF can also be installed on the
proven FOAMGLAS insulation. There
are different ways of building up the
roof structure.
The method with claw plates shown in
the drawing on the left does not require
any mechanical connection between the
Kalzip sheets and the supporting layer
thus making it completely free of thermal
bridges.
Kalzip AF with the insulation layer
at rafter level
This structure is comparable to tradi-
tional standing seam systems. It is
frequently used in order to minimise
the overall height of the roof structure.
If there is an air gap under the timber
lining adequate ventilation is essential.
With this in mind, we recommend filling
the total height of the rafters with insu-
lating material for efficient performance.
A vapour barrier beneath the thermal
insulation is also of critical importance.
Kalzip range of applications
3e
Kalzip AF with Prodach-insulation
on timber rafters with formwork
Rw = ~ 45 dB (A)*
Kalzip AF with the insulation
layer at rafter level
Kalzip AF
on FOAMGLAS insulation
Kalzip
AFwith Prodach-insulationon timber rafters with formwork
With this type of roof a 30 mm timber
lining, which remains visible, serves as
a supporting element. This structure
has proved to be ideal for residential
buildings and other buildings of similar
use. The potential extends from public
buildings to multi-purpose halls and
sports-arenas. The rails are invisibly
fixed to the rafters. There are no visible
joints or fasteners.
* varies depending on thickness and material qualities
8/10/2019 UK TechnBrosch
23/52
General data and characteristics
4a
4. General data and characteristics
Minimum roof pitch
without horizontal joints 1.5
respectively 2.6 per cent
- running from the eaves in one length
- all joints are welded
- factory welded soakers welded into
the roofing skin
sheets with horizontal
joints 2.9 (5%)
- with sealed horizontal joints
- soakers sealed into the roof skin
- Factory welded soakers sealed intothe roof skin
Roof pitch in degrees ... in per cent
45 100%
83,9%
70,0%
57,8%
46,6%
36,4%
26,8%
17,5%
10,5%5,2%
40
35
30
25
20
15
10
63
1,5 2,6%
4.1 Roof pitch
The Kalzip system consisting of self
supporting aluminium elements was
specially developed for roofs with
pitches down to 1.5 degrees or 2.6 per
cent together with long sheet lengths.
Owing to the attractive appearance of
the modular system, architects often
use this system for visible steep roofs
and increasingly for wall claddings.
Continous falling gradient required
All parts of the roof must have a conti-
nous downward gradient towards thedraining system.
Anomalies
The specification limiting the minimum
roof slope is not applicable along the
ridge area where roof elements run
without joints from eaves to eaves
over the ridge. Wherever the roof is
penetrated, for instance by light domes
etc., the requirement for minimum roof
pitch may also be by-passed under the
following conditions:
Completely welded soakers are used
Soakers or any other elements pene-trating the roof are tightly welded into
the external skin in order to achieve a
leakproof connection
The local rules and regulations must
be strictly observed for any welding
carried out on aluminium elements
and profiled sheets on the roof.
8/10/2019 UK TechnBrosch
24/52
Minimum length of straight end piecesRi min l1 min l2
[mm] [mm] [mm]
up to 1000 150 150
1000-2000 75 350
over 2000 0 0
4.2 Minimum radii for crimp-,smooth- and on site curving
Exacting design calls for creative
and detailed solutions. Today curved
corners or arched roofs can be easily
achieved by advanced industrial
prefabrication. They provide modern
industrial architecture with a high level
of functional and aesthetic quality
combined with future oriented
perspectives. The minimum radii for
smooth curving of Kalzip elements
are specified on the following page.
4.2.1 Kalzip Convex
Factory crimp-curved
Cover width (BB) nominal width:
50/333 Ri = 450 mm
50/429 Ri = 450 mm
65/305 Ri = 400 mm
65/333 Ri = 400 mm
65/400 Ri = 400 mm
AF 65/333 Ri = 450 mm
AF 65/434 Ri = 450 mm
AS 65/422 Ri = 450 mm
Installation width (DB):
Installation width is the actual width
of the assembled sheets. If the clips
are pre-installed the installation width
must be increased. (Installation width
= cover width (BB) + 3 mm) respectively
BB + 3 mm for pre-installed clips.
Profiled sheets lengths:
Straight lengths 500 mm min.
to 10.000 mm* max. Depending on
radius and transportation limitations
* greater lengths on request
Surface finish:
stucco-embossed
AluPlusPatina
Colour coated with protective foil
AluPlusZinc with protective foil
AluPlusTitan
Stainless Steel
Please take note when ordering:
Please specify the required dimen-
sions in accordance to the sketch.
Transportation:
Max. loading height 2.40 m.
For any queries, please contactour logistics department.
General data and characteristics
4b
8/10/2019 UK TechnBrosch
25/52
General data and characteristics
4c
4.2.2 Kalzip
smooth curved in factory, aluminium
General information
Kalzip AF:
Smooth-curved Kalzip AF profile sheets
can show signs of increased buckling
in the base plate. As it is impossible
for technical production to prevent
this buckling, it will not be accepted
as grounds for complaint. When the
optical characteristics of a building are
of increased importance, then smooth-
curved Kalzip AS profile sheets should
be used instead.
Standard:
Constant radius with a short (approx.
400 mm) straight segment at the
beginning and the end of the profile
sheet. Any radii below the standard
minimum as well as multiple radii and/or
straight elements in one Kalzip sheet
must be agreed with our technical
department in Koblenz. It is unavoidable
that intermediate radii occur in the
transition area of different radii as well
as between curved and straight sectors.
Clips must not be located in these areas.
Limit:
Tolerance limits. Only after consultation
with our technical department in
Koblenz. Special measures are necessary
in order to reach the tolerance limits.
Finish:
stucco-embossed
AluPlusPatina
coated material with protection foil
AluPlusZinc with protection foil
Anti-condensation coating on request AluPlusTitan
Stainless Steel
Installation width:
For pre-installed clips:
cover width + 3 mm
successive installation of clips:
cover width + 0 to + 3 mm
Length of profiled sheet:
Minimum length 1.5 m. Shorter lengths
on request. The final overall length
depends on the individual radii and
possibility of transport. Minimum length
of segment per radius = 500 mm.
Transportation:
Maximum loading height 2.4 m. It
might be necessary to coordinate
details of transportation with our
logistics department.
Validity:
With the publication of this issue any
previously published data becomes
invalid. Any deviations from the limiting
values quoted above depend on the
constant further development and can
be only granted after consultation with
our technical department.
Convex Minimum curving radii in m
Sheet thickness 0,8 mm 0,8 mm 0,9 mm 0,9 mm 1,0 mm 1,0 mm 1,2 mm 1,2 mm
Kalzip Standard Limit Standard Limit Standard Limit Standard Limit
65 / ... 8 6 7 5 3 1,5 2,5 2
50 / ... 10 8 7 5 2 1,3 2 1,3
AF 65 / ... 12 10 10 8 6 3,5 5 3
AS 65 / ... 30 25 20 16 14 10 10 8
Concave
Sheet thickness 0,8 mm 0,8 mm 0,9 mm 0,9 mm 1,0 mm 1,0 mm 1,2 mm 1,2 mm
Kalzip Standard Limit Standard Limit Standard Limit Standard Limit
65 / ... 18 16 16 14 12 10 16 1450 / ... 16 12 12 10 9 7 8 6
AF 65 / ... 17 15 16 14 12 10 10 7
AS 65 / ... 30 25 20 16 18 14 14 10
Curved and tapered: For Kalzip 65/260-480. Please check with our technical department in Koblenz/Germany.
Kalzip smooth curved in factory, stainless steel Minimum curving radii in m
Kalzip 65/400, Sheet thickness 0,6 mm
Convex Concave Tapered convex Tapered concave
1.4301 6 10 10 10
1.4401 6 10 10 10
8/10/2019 UK TechnBrosch
26/52
4.2.3 Kalzip
supplied in straight form, curved to radius during installation
The values given are not standard values. They do not serve as a replacement for project specific consultations.
Kalzip AF Profile cannot be naturally curved. Special forms with beading are available on request.
General information
Naturally curved:
The profile sheets are supplied in
straight form and are curved by hand to
the respective radii during installation.
Cover width:
Depending on the radius, the nominal
width (construction width) must be increa-
sed to the cover width (installed width).
Support spacing:
When the supporting spacings are too large
the supports will appear as polygon lines.
Accessibi lity :
Due to the risk of buckling, access to
the sheets must not be gained without
load spreading equipment.
Finish:
stucco-embossed
AluPlusPatina
coated material with protection foil AluPlusZinc with protection foil
Anti-condensation coating on request
without protection foil on request
AluPlusTitan
Stainless Steel
Appearance:
The minimum radii outlined above reflect
current experiences. As it is necessary to
curve the profile sheets to the respective
radius, buckling cannot be ruled out.
Installation tip:
It is advisable to provide a support on
the ridge over which the profile sheets
can be curved. Installation should takeplace from the direction of the non-
covered side.
Validity:
All prior issues become inval id wi th
the publication of this document. Any
deviations from the limiting values
outlined above can only be approved
following consultation with our technical
department within the context of conti-
nuous product development.
General data and characteristics
4d
Convex Minimum curving radii in m
Kalzip Sheet thickness Radii max. Supporting space Increase in
Sheet thickness (mm) (m) (m) construction width (mm)*
65/305 0,8 36 1,5 +3
65/333 0,9 40 1,6 +3
65/400 1,0 48 1,8 +3
1,2 55 2,0 +3
50/333 0,8 37 1,5 +2
50/429 0,9 37 1,5 +2
1,0 40 1,5 +2
1,2 43 1,8 +2AS 65/422 0,8 50 1,5 +2
0,9 55 1,5 +2
1,0 60 1,5 +2
1,2 70 1,8 +2
Concave
Kalzip Sheet thickness Radii max. Supporting space Increase in
Sheet thickness (mm) (m) (m) construction width (mm)*
65/305 0,8 40 1,5 +3
65/333 0,9 45 1,6 +3
65/400 1,0 50 1,8 +3
1,2 60 2,0 +3
50/333 0,8 38 1,5 +2
50/429 0,9 40 1,6 +2
1,0 42 1,8 +2
1,2 45 2,0 +2
AS 65/422 0,8 50 1,5 +2
0,9 55 1,6 +2
1,0 60 1,8 +2
1,2 70 2,0 +2
* Not when sliding clips are used
8/10/2019 UK TechnBrosch
27/52
General data and characteristics
4e
max.
min.
For construction widths exceeding500 mm only with additional supportand clips spaced at 1.0 m max.
Self-supporting upto a constructionwidth of 500 mm
Sheet layout example with joints
Joint executed as a welded seam
or step joint
4.3 Tapered shapes
Tapered Kalzip profile sheets have
become increasingly significant for
roofing applications as they can
be formed into a diverse range of
shapes. A roof can offer more than
just protection: i t can give the building
architectural perfection. For a perfect
construction some fundamental
aspects have to be observed. The
cover widths are between 230 and
740 mm.
Tapered Kalzip sheets have to be installed
on the roof by following the precise instruc-
tions laid down in the relevant installation
plan. It is advisable to check the actual
dimensions of the substructure against the
dimensions on the installation plan before
the production is started. Larger toleran-
ces of the building may call for a newpartition of the areas to be covered. The
tables on the following page apply to a
cover width of up to 500 mm. With larger
widths the accessibility is limited.
The bottom sheet must be supported
by an insulation material of sufficient
compressive strength. Load distributing
walkways must be provided. To achieve
the required stiffness of the bottom
sheet at the eaves end of the sheet,
the incorporation of an eaves angle is
essential. The sheets are delieverd with
a standard extra length of 50 mm on
both ends and have to be cut to the
required actual length on site.
Finish:
stucco-embossed
AluPlusPatina
coated material
with protection foil
AluPlusZinc
with protection foil
AluPlusTitan Stainless Steel
The full surface is always covered with
foil. Anti-condensation coating only
available subsequently in the spraying
process. Aquasine coating is not possible.
Kalzip 65/ and 50/ Kalzip AF
Minimum construction width 230 mm 170 mm
Maximum width 740 mm1 740 mm1
Minimum length 1500 mm 1500 mm
Maximum length Dependent on transport Dependent on transport
Plate thicknesses 0,80 1,20 mm 0,80 1,20 mmCurved and tapered Possible for construction widths of 230 620 mm.
Only following approval from the technical
department in Koblenz.1 Applies only to stucco-embossed and colour-coated Ka lzip profile sheets.
Other material combinations are available on request.
8/10/2019 UK TechnBrosch
28/52
4.4 Accessibility/fall arrest systems
For maintenance and cleaning Kalzip
sheets are accessible both during and
after installation without any load
distributing measures. As far as the
installation is concerned this will only
be valid if the profiled sheets are zipped
on at least one side. The following table
specifies the critical spans up to which
the profiled sheets are accessible with-
out any additional measures.
It is advisable to install walkways leading
to any units requiring regular mainten-ance or operational elements such as
daylight units, chimneys or heating
plants. When exceeding the critical
span, load distributing elements such
as wooden planks of a minium cross
section of 4 x 24 cm and a maximum
length of 3 m have to be installed
length or crosswise over the Kalzip
sheets.
In situations where no rigid thermal
insulation has been installed along the
ridge and eaves areas, the sheets in
these parts of the roof should not directly
be walked on. The reason being that
this might lead to deformation of the
flat area of the Kalzip sheet resulting in
a possible accumulation of rain water.
The last free sheets along the gable
end, single unzipped sheets and of
course translucent panels should not
be walked on.
During the installation of the roof any
areas which are frequently walked on or
used for the transport of materials should
be protected by temporary walkways,
which should be secured with seam clips
to prevent them from sliding down.
The Kalzip fall arrest system is a reliable
solution to secure walkways on the
finished roof. It consists of a stainless
steel rope which is fastened to perma-
nently fixed Kalzip roof anchors and
coupled to the safety harness by meansof a guide link. Project related planning
is carried out by Corus Bausysteme.
General data and characteristics
4f
Access following installation1
Seamed Kalzip profile sheets with supporting spacings up to the following dimensions are accessible without the use of load
spreading equipment.
Sheet thickness 65/305 65/333 65/400 50/333 50/429 AF 65/333* AF 65/434* AS 65/422*
t/mm lgr/m lgr/m lgr/m lgr/m lgr/m lgr/m lgr/m lgr/m
0,8 2,90 2,90 3,00 2,50 2,50 2,90 3,50 3,50
0,9 3,35 3,35 3,40 2,65 2,60 3,20 3,55 3,55
1,0 3,80 3,80 3,80 2,80 2,70 3,50 3,60 3,60
1,2 3,80 3,80 3,80 3,00 2,90 3,50 3,60 3,60
1
Applies only to stucco-embossed and colour-coated Ka lzip
profile sheets.Other material combinations are available on request.
2 On grounds of final visual appearance, this information is only applicable when rigid thermal insulation is used.
8/10/2019 UK TechnBrosch
29/52
General data and characteristics
4g
4.5 Material/corrosion resistance
An essential advantage of Kalzip
sheets is the lightness of the aluminium
material. Seawater proof alloys are used
as basic materials.
Protection by natural oxidation
Due to the natural formation of a protective
coat of oxide, Kalzip profiled aluminium
sheets are reliably protected against
corrosion when exposed to normal
weathering by maritime, continental
and industrial atmospheres. With plated
material this effect is even greater, asthe plating acts as a sacrificial anode
protecting the core material against
corrosion for many years. If, however,
the roof is exposed to a highly aggressive
atmosphere occurring in the immediate
vicinity of the building, for instance,
industrial premises such as copper
plants emitting high levels of aggressive
chemicals; appropriate resin coatings
with a minimum thickness of 25 will
provide lasting protection.
Contact corrosion
In contact with other unprotected metals
and under the influence of humidity,
aluminium produces an electrochemical
contact element, which may lead to
corrosion. The annexed table is the result
of extensive tests and investigations
carried out in Sweden and proves that
the Kalzip alloy can be combined with
most of the common materials used for
building purposes without the risk of
corrosion.
Protective measures to avoid contactcorrosion are
colour coating
neutralizing the steel surfaces for
instance by hot-dip galvanizing
interrupting the metallic conductive
contact by applying a primer or by
incorporating a suitable separation
layer
Installation in combination with
different materials
Steel:
Direct contact between the profiledaluminium sheets and unprotected steel
parts of the substructure must be avoided
due to the likely risk of contact corrosion.
There are a number of different protective
measures such as plastic foils, interme-
diate layers coated with bituminous,
zinc chromate or chlorinated rubber
paint or the galvanizing of the contact
areas of steel parts.
Timber:Timber parts in contact with Kalzip
should be dry. For the protection of timber
rafters and other wooden construction
elements in direct contact with aluminium
structures only compatible (f.i. oil
based) wood preservatives must be
used. They must not belong to the
group of naphtalenic chlorines and
must not contain any copper, mercury
salts or fluorine compounds.
Concrete and mortar:
Any direct contact with concrete and
mortar must be avoided.
Compatibility with other materials
Atmospheres
Combination of materials rural town/industrial maritime
zinc safe safe safe
stainless steel safe safe safe*
lead safe safe critical
hot-dip galvanized steel safe safe safe
unprotected steel critical critical critical
copper critical critical critical
* Only applies to stainless steel self-tapping screws and blind rivets, if a formation of an electrolyte
can be excluded.
8/10/2019 UK TechnBrosch
30/52
4.6 Ecological aspects
It is a fact, that aluminium, just like any
other material cannot be produced with-
out the use of energy and emissions
resulting from the production process.
However, the industry has achieved
considerable progress in the field of
advanced production technologies
and the considerable investment in
environmental protection is now having
a notable effect. Today the energy
required for the electrolytic production
of aluminium amounts only 60 per cent
of the energy required 40 years ago.
Special advantage:
high strenghts/low weight
Due to the fairly high strength of Kalzip
profiled sheets they can fulfill important
structural demands such as enclosing
and sealing a building off, protecting it
from the weather thereby retaining its
value with relatively low material expen-
diture. This saving of resources meets
one of the most important ecological
demands in a truly exemplary way.
100 per cent recyclable after a long
environmentally friendly service life
Throughout the long service life there
is nearly no erosion of the aluminium
surface at all. At the end of use, the
structural elements can be recycled.
Aluminium is especially suitable for
this procedure, because it is available
in large and relatively homogenous
quantities. Only 5 per cent of the ener-
gy initially used for the production of
alumimium is required for remelting.
And, in additon, this low energy recyclingprocess can be repeated again and
again without impairing the intrinsic
qualities of the material. Aluminium
structures have a constantly increasing
proportion of recycled aluminium.
Today virtually all the scrap aluminium
resulting from construction industry is
recycled.
General data and characteristics
4h
8/10/2019 UK TechnBrosch
31/52
General data and characteristics
4i
4.7 Official approvals/
design calculation
The use of Kalzip roof elements is sub-
ject to the offic ial building regulations.
Correspondingly the stabilty and fitness
for use must be proved in each and
every individual case. The basis for
any design calculation is always the
No. Z-14.1-181 issued by the Institute
for Building Technology. Kalzip is
officially approved by many European
Building authorities.
For further details please contact ourexport department. The appendix of the
licensing agreement contains tables
concerning standard details, value cha-
racteristic figures for the proof of the
stability and fitness for use.
For frequently recurring applications you
will find load-span-tables, from which the
maximum spans under practical wind-
and snow loads can be extracted. So
the proof required by law can be easily
provided at any time.
4.8 Transport
When designing unusual special roof
shapes (for instance, long profiled
sheets with small curving radii) thefeasablity of transportation has to be
checked with our logistics department.
For sheets of extreme length it is essen-
tial to allow for the time required to gain
permits from the local road authorities.
4.9 Sheet thicknesses
According to the licensing agreement
issued by the building authorities the
minimum thickness for Kalzip profiled
sheets is t = 0.7 mm. Although these
sheets are accessible both during as
well as after their installation for main-
tenance and cleaning without the need
of load distributing measures, it is
however not advisable to use sheets
of this thickness because of the risk of
denting resulting from people walking
on the sheets during installation. Foraesthetic reasons it is advisable to
choose a minimum sheet thickness
of 1 mm on any visible areas.
8/10/2019 UK TechnBrosch
32/52
5. Design specifications
Determination of the U-value of a roof build-up
The thickness of the installed thermal insulation is predetermined.
The diagram above indicates actual thermal conductivity of the roof
structure depending on the number of clips used.
Example based on the use of 15 mm thick thermal barrier pads (red):
Thermal insulation compressed to a final thickness of 120 mm results in a
calculated thermal coefficient (k-value) of 0.315 W/m2K.
Number of clips installed per m 2 1.5 nos/m2.
According to the d iagram the actual k-value is 0,342 W/m2K.
Example based on the use of Kalzip E140 plastic compound (green):
In the case of the Type E clip, the number of clips/m 2 is not important.
The reading is always taken on the 0-axis (0 clips/m 2). Heat insulation
compressed to a thickness of 140 mm gives a value of 0,272 W/m 2K.
Determination of the required insulation thickness
in order to achieve a specific U-value
A cer tain k-value is specified. The final thickness of the compressed
thermal insulation depends on the number of clips used.
Example with 15 mm thick heat thermal barrier pads (red):
Required k-value: 0.32 W/m2K
Number of clips used: 2.0 per m 2
Minimum thickness of insulation to be installed 136 mm.
Supply thickness chosen: 150 mm.
Example based on Kalzip E140 compound clips (green):
Required U-value = 0,28 W/m2K.
Minimum thickness of heat insulation to be installed: (reading)
approx. 135 mm. Thickness chosen: 140 mm in compressed condition.
Thermal transmission coefficient is dependent on the insulation thickness and the number of clips (reading example)
5.1 Thermal insulation
The main applications of the Kalzip
system are non-ventilated, insulated
roof structures on trapezoidal decks,
timber lining or concrete. Where there
are low roof pitchs which lead to
insufficient ventilation velocity, it is not
advisable to construct a ventilated roof.
The thermal insulation is supplied with
approx. 20 mm excess thickness and
will be compressed by the inner surface
of the Kalzip sheets to the required
final thickness during installation. The
clips securing the Kalzip sheets to the
substructure penetrate the thermal
insulation and have the effect of heat
bridges. This effect increases the heat
transmission coefficient (k-value).
Influential parameters are among others
the thickness of the insulation and the
number of clips used. This phenomenon
has been experimentally investigated
with insulation materials of the thermal
conductivity group 040. The diagrams
below are derived from the results of
this study.They illustrate the dependen-
ce of the heat transmission coefficient
from the number of clips per area unit
in the specific range for normal con-
structional applications.
Design specifications
5a
8/10/2019 UK TechnBrosch
33/52
Design specifications
5b
5.2 Moisture proof
For insulated roofs and walls it is es-
sential to provide sufficient protection
against condensation in each and every
case. In this context vapour diffusion
(e.g. according to DIN 4108-3) as well
as air flows must be considered.
Superficial formation of condensate
on structural components
If the minimum values of heat transition
resistance according to DIN 4108-2
are observed, a verification of the
protection against condensation innon air-conditioned rooms such as
residential premises and offices is
generally not required providing that
these rooms are adequately heated
and ventilated according to the normal
standards.
In special cases for instance with
permanent high humidity levels it is
necessary to calculate the required
heat transition resistance in relation to
the actual internal climatic conditions.
Formation of condensate inside
multi-layer constructions
A vapour barrier must be installed
in order to prevent vapour from
penetrating from humid internal
rooms into the roof construction.
In wall structures vapour barriers
are generally not necessary.
To prevent humid internal air from
diffusing into the roofing system,
an airtight barrier must be installed,
which is fully sealed at all joints to
the adjacent structures, as requiredby the Energy Saving Directive. A
professionally fitted Kalzip vapour
barrier meets these requirements.
5.3 Sound absorption
Highly efficient sound absorption can
be easily achieved with Kalzip roofs
by constructive measures such as
incorporating additional layers, while
all benefits of the lightweight construc-
tions remain unaffected.
5.4 Fire/lightning protection
Fire protection
The demands concerning fire protection
of building materials and structural parts
etc. are specified in the local buildingregulations. According to DIN 4102-4
aluminium alloys are classified in cate-
gory A1 (not inflammable) without
special verification. Kalzip profiled
sheets even with organic coatings on
both sides and with class B insulation
layers underneath are classified as
resistant against flash-over and radiating
heat without any special verification
(hard roof covering).
Lightning protection
With a minimum thickness of 0.7 mm
the Kalzip aluminium roof and wall
cladding is classified by ENV 61024-1
as a natural part of the air termination
network when it is not necessary to
avoid the melting of sheets at the point
of impact or the ignition of inflammable
material under the covering surface.
Colour coating or 1 mm thick coats of
bitumen or 0.5 mm thick coats of PVC
are not considered as an isolation in
the sense of lightning protection.The
seaming at the flange is considered as
a electrical conductor, as the distanceof the sheets is less than 1mm. This
allows in many cases to avoid extensive
lightning protection measures.
Building Official
mater ial class classif icat ion
A non- inflammable
materials
A 1
A 2
B inflammable
materials
B 1 flame resistant
materials
B 2 normal flammabiltymaterials
B 3 highly Inflammable
materials
Fire- Duration of
resistance- fire resistance
class in minutes
F 30 -> 30
F 60 -> 60
F 90 -> 90
F 120 -> 120
F 180 -> 180
Kalzip roof
Lightning protection with Kalzip
Kalzip wall
Break
Earthing
Connection
roof/wall
Connection to
the earthing
8/10/2019 UK TechnBrosch
34/52
Positioning scheme 1
Alumin ium clips/Compound clips
Positioning scheme 2
Alumin ium clips/Compound clips
d = clip distance d = clip distance
Distances not to scale
5.5 Roof systems
5.5.1 Rafter roof:
Kalzip sheets perpendicular
to the trapezoidal steel deck
A supporting trapezoidal deck forming
the substructure of the roof spans from
rafter to rafter running parallel to the
eaves. The clips are either fixed directly
to the top corrugations of the deck or
indirectly by means of spacers. The
fixing points are visible underneath the
supporting steel deck. The clips are
diagonally distributed on top of the steeldeck, so that all corrugations of the
deck are load bearing. The clips must
be located following a special pattern
to ensure even load distribution on the
trapezoidal steel deck both in the case
of positive loads (due to snow) or nega-
tive loads (due to wind or aerodynamic
suction).
A continous row of clips is to be
fitted along the ridge and the eaves.
In between the clips are arranged
diagonally. Distances depend
on the design loads, the Kalzip sheet
widths, the pitch of the ribs and the
support spacing of the trapezoidal
sheet underneath.
The number and positioning of the
clips as well as the joining elements
are indicated in the assembly plan.
Depending on the likely loads it
may be necessary to halve the
spacing of the clips at the corners
and along the edges of the roof.
(See dimension tables)
Kalzip perpendicular on timber lining
(see upper diagram on page 3d)
5.5.1 Applies accordingly.
The clips are fixed directly to the
timber lining. The clips must be
positioned on the timber lining in
accordance with positioning diagram
1 or 2. If the clips are to be positioned
next to each other, then the timber
board and its attachment to the
substructure must be statically verified.
A carpentry attachment is not sufficient.
Design specifications
5c
8/10/2019 UK TechnBrosch
35/52
Design specifications
5d
Distances not to scale
Positioning scheme 3
Alumin ium clips/Compound clips
d = clip distance = purlin spacing d = clip distance
Roof areas:For buildings up to a total width (a) of
30 m and closed walls the width of the
corner and edge areas can be reduced
to 2 m. Buildings with a total width
exceeding 30 m the width of the corner
and edge areas is one eight (a/8) of the
total width of the building. (reference:
DIN 1055 T-4 tables 11 and 12).
5.5.2 The purlin roof:
Kalzip parallel to inner skin
The clips are fixed to the purlins or the
inner skin spans parallel to the Kalzip
sheet. Depending on the design of the
bottom skin, an intermediate section
may be necessary with double skin
roofs. The clips are normally positioned
on top of each purlin.
In re-roofing projects with narrow spaced
purlins it may be sufficient to position
the clips on every second purlin only.
With regard to an even load distribution
the clips are alternately arranged on the
purlins.
A design calculation is required.
Please consult our local representative
for design calculations.
Positioning scheme 4
Aluminium clips/Compound clips
Clip positions with closer spaced purlins (re-roofing)
Central area
Edge area
Corner area
max. 2,0 m to a = 30 m
Roof areas
8/10/2019 UK TechnBrosch
36/52
Design specifications
5e
5.5.3 Kalzip DuoPlus
and Kalzip DuoPlus
The Kalzip DuoPlus system always
consists of a full layer of 10 cm thick,
rigid thermal insulation, the DuoPlus
rail, the DuoPlus clip and the special
screws for fixing the rail onto the sub-
structure.
In contrast to this, the Kalzip Duo
system does not contain a full layer of
rigid thermal insulation. Strips of rigid
insulation with a width of 24 cm and a
thickness of 10 cm are simply insertedunder the Kalzip DuoPlus rails.
In the case of both systems, only the
named components will be permitted.
The arrangement of the rails and the
number of connecting elements are
outlined in the installation plan. The
DuoPlus clips are secured against
shifting by means of a plastic strip
that is attached in the factory.
First of all the rigid thermal insulation is
placed on the substructure. A full layer
of rigid insulation is used in the case
of Kalzip DuoPlus. Strips of rigid
insulation are used in the Kalzip Duo
system and any spaces between these
strips are filled with soft thermal insula-
tion or rigid insulation. The DuoPlus
rails are then arranged on the thermal
insulation in accordance with the
installation plan and are connected to
the substructure through the thermal
insulation.
The special DuoPlus clips are inserted
into the rail and rotated so that they arepositioned parallel to the seam direction
(minimum rotation angle = 45o).
8/10/2019 UK TechnBrosch
37/52
Design specifications
5f
The first row of clips, at the start ofthe installation surface (gable end), is
aligned precisely and fixed into the rail
by means of a screw through the base
of the clip. The remaining clips are
inserted into the rail and positioned
parallel to the Kalzip seam direction.
Every tenth row of clips is fixed with a
screw to prevent shifting.
The final row of clips, at the end of the
installation surface (gable end), is also
secured into the rail by means of a screw
through the clip base. The compressible
thermal insulation is then placed on topand pressed over the clips. The Kalzip
roof structure can then be installed as
normal.
The DuoPlus rail must be long enough
to cover at least two ribs of the trape-
zoidal deck and can be secured in it.
If this is not possible, then a section of
adequate length can be installed next
to the first row (see positioning diagram
for rafter roof and purlin roof).
Positioning scheme Kalzip
Rafter roofThe system requires that the DuoPlus rails are positioned at an angle of 45 .
Positioning scheme Kalzip purlin roof
The system requires that the DuoPlus rails are positioned parallel to the purlins.
Ridge
Railspacing
Eav
es
Rafter spacing Rafter spacing
DuoPlusrail
DuoPlusclip
45
Eaves
Rafter spacing Rafter spacing
Stainlesssteelscrew
Gableend
Clip
spacing
Panelspacing=
Clip
spacingR
idge
DuoPlusrail
Stainlesssteelscrew
Gableend
Distances not to scale
DuoPlusclip
8/10/2019 UK TechnBrosch
38/52
Design specifications
5g
The following fixing elements are recommended for the Kalzip system:
5.6 Connections
The Kalzip profiled sheets are fixed to
the substructure by means of extruded
aluminium clips. The bottom flange of
each clip is fitted with several bore holes.
Depending on the substructure special
fixing elements are used. Note: The
number of the fixing elements required
depends on the static requirements and
must be determined in each and every
case. Both in the edge and corner areas
of roofs as well as in the edge areas of
walls the fixing elements must be
dimensioned for increased wind suction.
The anchoring depth for screws in timber
substructures is to be calculated according
to DIN 1055 T2. The minimum anchoring
depth (sg) for screws in timber is four times
their diameter (4xds). The maximum
anchoring depth is 12xds. (ds = nominal
diameter of the screw). The fixing ele-
ments must be made either of aluminium
or stainless steel. The use of galvanized
carbon steel is excluded. Regarding the
correct application of the fixing elements,
the manufacturers recommendations
must be strictly observed.
Fixing position Appropriate fixing element**
Eaves angle to Kalzip Blind rivet 5 x 12
Ridge closure to seam Blind rivet 5 x 8
Spacer to seam Blind rivet 5 x 8
Ridge flashing to ridge closure Sealing blind rivet 4,8 x 9,6
Gable end channel to seam Blind rivet 5 x 8
Gable end hook to clip Self-tapping screw A 6,5 x 19
Fixed point: Clip to Kalzip seam Blind rivet 5 x 12 K9
Sealing joints Kalzip or soaker connection Sealing blind rivet 4,8 x 9,6
Top-hat section to trapezoidal sheet Bulb tite rivet 5 W*
Kalzip DuoPlus rotatable clip/Kalzip DuoPlus rail SD2 - S16 - 6,0 x 127
Clip on steel substructure
Clip with and without TK5 Bulb tite rivet 5 W*
to steel purlin t = 0,75 - 3,0 mm
Clip with and without TK5 or TK 15, Screw SFS SDK2*
or E clip respectively, to steel purlin t = 0,75 - 1 ,2 mm
Clip with and without TK5 or TK 15, Screw SFS SDK3*
or E clip respectively, to steel purlin t = 1,20 - 3 ,2 mm
Clip with and without TK5 or TK 15 Self-drilling screw 5,5 x L*
to steel purlin t = 1,5 - 2,0 mm Self-tapping screw 6,5 x L*
Clip with and without TK5 or TK 15 Self-drilling screw 5,5 x L*
to steel purlin t = 2,0 - 6,0 mm Self-tapping screw 6,25 x L*Clip with and without TK5 or TK 15 Self-tapping screw 6,25 x L*
to steel purlin t > 6 mm
Clip on timber substructure
Clip to timber purlin 2 Drilling screws 6,5 x L*
2 Screws A 6,5 x L (vorbohren)
Clip to timber lining Timber materials from 24 mm onwards: 2 Drilling screws SFS
SDK2 timber lining, 30 mm: 2 Screws A 6,5 x L (pre-drilled)
E- Clip to timber lining Timber materials from 24 mm onwards: 2 Drilling screws SFS
SDK2 timber lining, 30 mm: 2 Screws A 6,5 x L (pre-drilled)
All dimensions in mm
** In the case of blind rivets and sealed blind rivets, aluminium is used for the sleeve and stainless steel for the mandrel.
Stainless Steel is used for the screws. Please observe the information and specifications of the rivet and screw manufacturers.
The application and the structural conditions should be taken into consideration when selecting attachments and material.
* The length of the rivet or screw must be adapted to the required gripping length.
8/10/2019 UK TechnBrosch
39/52
8/10/2019 UK TechnBrosch
40/52
Design specifications
5i
5.10 Skylights/Smoke/heat extractors
Corus Bausysteme supply complete
units in a variety of dimensions for
the installation of skylights, smoke
extractors, etc. These units consist
of a steel soaker with skylight and
a multipart, welded aluminium
connecting frame.
For arched roofs, special curved soakers
are required. The soakers can either
be welded or sealed (in the case of a
minimum roof pitch of 2.9) into the
roofing. Welding is the recommendedoption.
The right drawing shows a welded
connecting frame. For more detailed
information on installation please refer
to the assembly instructions which are
supplied with the skylights.
Skylights and smoke extractors must
not be walked on. As these must be
regularly accessed for servicing and
maintenance work, it is recommended
that the area around the opening is
reinforced with rigid thermal insulation.
Welded connecting frame
Thermal separation
Connecting frame
Soaker
frame
Covering frame
Rigid thermal insulation
Static exchange Trapezoidal profile
Kalzip
Vapour barr ier
8/10/2019 UK TechnBrosch
41/52
5j
Design specifications
5.12 Substructures
Kalzip roofs can be installed on all
kinds of substructures. With metal or
timber substructures the clips are directly
fixed to the substructure. With metal
substructures contact corrosion must
be taken into consideration. As, with
the exception of Kalzip AF, there is
no direct contact between Kalzip and
the substructure, the thermal barrier
pads under the clips provide sufficient
separation.
On concrete substructures a suitablyanchored steel section or timber batten
(minimum thickness 40 mm) must be in-
serted.
5.13 Cantilevers/clip bars
If the roof is to protrude at the eaves,
additional substructures are dispensable
providing that the clips are installed as
clip bars. They are fixed to the roof with
appropriate length and serve as support
for the Kalzip sheets as well as a fixing
for the gutter (see table of roof projec-
tions and 5.14).
5.14 Installation rules
Individual verification is required in
each and every case. Roof projections
are not accessible. The ends of the
Kalzip sheets must be joined with an
eaves angle. The length of the clip bars
is outlined in the diagram opposite.
5.11 Transverse joints
It is not always possible to produce
the required Kalzip sheet length in one
element. In most cases the length of
the sheets is determined by transport
limitations, so that the sheets must be
joined by overlapping. Especially with
arched roofs the maximum loading
height of the trucks must be observed.
Obviously, the requirements for abso-
lute tightness of the overlapping joints
are very high. Therefore it is necessary
to take great care when making over-
lapping joints. Overlaps are positionedon top of the support, if the joint is
located at the fixed point. Otherwise
the profiled sheets have to be joined
directly next to the support. Joints can
be either welded or sealed.
Welded joints
The Kalzip sheets to be joined must have
an overlap of approx. 10-20 mm. The
welding seams should be supported (for
instance by a Z-section or a rigid thermal
insulation with an intermediate layer of
aluminium foil).
Sealed joints
(only possible with minimum roof pitch of 2.9)
The profiled sheets are installed in a
precise sequence according to the
assembly instructions. The critical
tightness of seal is achieved by three
rows of silicone in the joint zone of the
individual profiled sheets plus two rows
of sealing rivets. The overlap is 200 mm.
1
3
42
Direction of assembly
1
2
Clip bar spacings
Roof projection (a) Kalzip 65/... 50/...
over last
support 305 333 400 422 429
1 m every every every every every
(0,5 m)* 2nd sheet 2nd sheet 2nd sheet sheet sheet
1,5 m every every every impossible impossible
(0,9 m)* sheet sheet sheet
Depending on the construction width of the Kalzip sheets and the desired roof projection the clip bars
must be fitted to each or every second seam. The table is applicable for a snow load of 0.75 kN/m2.
*Values apply to clip type L10.
8/10/2019 UK TechnBrosch
42/52
8/10/2019 UK TechnBrosch
43/52
Kalzip Dimensioning tables
5j
6. Kalzip Dimensioning tables
6.1 Thermal conductivity coefficients
with 15 mm thick thermal barrier pads (black) and E-Clip (green)
For example reading please refer to page 5a.
8/10/2019 UK TechnBrosch
44/52
Kalzip Dimensioning tables
6a
6.1.1 Thermal conductivity coefficientsKalzip DuoPlus roof (WLG 040)
0,3
0,25
0,150 0,5 1 1,5 2 2,5 3 3,5 4
160
Thickness WD
[mm]
180
200
220
240
0,2
Clips per m2
U-value[W/(m2K)]
8/10/2019 UK TechnBrosch
45/52
Kalzip Dimensioning tables
6b
Line Kalzip Sheet Snow load Wind suction
type thickness kN/m2
t/mm building heights
0 - 8 m 8 - 20 m 20 - 100 m
0,75 1,00 1,25 RB* EB* RB* EB* RB* EB*
1 65/305 0,80 2,50 2,40 2,00 2,20 1,65 2,00 1,10 1,45 0,80
2 65/333 0,90 3,15 2,50 2,00 2,80 1,80 2,00 1,10 1,45 0,80
3 1,00 3,30 2,50 2,10 3,15 1,80 2,00 1,10 1,45 0,804 1,20 3,30 2,50 2,20 3,30 1,80 2,00 1,10 1,45 0,80
5
6 65/400 0,80 2,50 2,30 2,00 2,00 1,50 1,70 0,95 1,20 0,70
7 0,90 2,95 2,50 2,00 2,60 1,50 1,70 0,95 1,20 0,70
8 1,00 3,30 2,50 2,00 2,75 1,50 1,70 0,95 1,20 0,70
9 1,20 3,30 2,50 2,00 2,75 1,50 1,70 0,95 1,20 0,70
10
11 50/333 0,80 2,10 1,90 1,80 2,20 1,65 2,00 1,15 1,45 0,80
12 0,90 2,60 2,00 2,00 2,80 1,80 2,00 1,15 1,45 0,80
13 1,00 2,80 2,20 2,00 3,15 1,80 2,05 1,15 1,45 0,80
14 1,20 3,00 2,30 2,00 3,30 1,80 2,05 1,15 1,45 0,80
15
16 50/429 0,80 2,00 1,80 1,70 1,85 1,40 1,55 0,85 1,02 0,65
17 0,90 2,45 1,90 2,00 2,40 1,40 1,55 0,85 1,02 0,65
18 1,00 2,70 2,10 2,00 2,55 1,40 1,55 0,85 1,02 0,65
19 1,20 2,90 2,20 2,00 2,55 1,40 1,55 0,85 1,02 0,65
20
21 NatureRoof 0,80 1,80 1,55 1,40 2,20 1,65 2,00 1,15 1,45 0,80
22 65/333 0,90 1,80 1,55 1,40 2,80 1,80 2,00 1,15 1,45 0,80
23 1,00 1,80 1,55 1,40 3,15 1,80 2,05 1,15 1,45 0,80
24 1,20 1,80 1,55 1,40 3,30 1,80 2,05 1,15 1,45 0,80
Supporting width in [m]
Separate design calculation for substructure is required. In the values under snow loads the wind suction forces under normal
conditions are already taken into consideration.
The clip spacing must not exceed half the supporting width of the supporting trapezoidal steel deck.
Area of app lication: enclosed buildings, roofs w ithout roof l ights and additiona l loads that need to be accepted by the roof skin.
* EB = corner area / * RB = edge area
The table does not apply to Kalzip DuoPlus .
6.2 Clip spacings
The values given are not standard values. They do not serve as a replacement for project specific consultations.
6.2.1 Rafter roof (multi-span sheets) with aluminium clips
Clip fixing: directly to trapezoidal steel deck tmin = 0.75 mm. Two fixing elements per clip
Self-tapping screw SFS SDK or bulb tite rivet
8/10/2019 UK TechnBrosch
46/52
Kalzip Dimensioning tables
6c
6.2.2 Rafter roof (multi-span sheets) with compound clips
Clip fixing: directly to trapezoidal steel deck tmin = 0.75 mm. Two fixing elements per clip
(Self-tapping screw SFS SDK).
Line Kalzip Sheet Snow load1) Wind suction
type thickness kN/m2
t/mm building heights
0 - 8 m 8 - 20 m 20 - 100 m
0,75 1,00 1,25 RB* EB* RB* EB* RB* EB*
1 65/333 0,80 2,50 2,40 2,00 2,20 1,65 2,00 1,10 1,45 0,80
2 65/305 0,90 3,15 2,50 2,00 2,80 1,80 2,00 1,10 1,45 0,80
3 1,00 3,30 2,50 2,10 3,15 1,80 2,00 1,10 1,45 0,804 1,20 3,30 2,50 2,20 3,30 1,80 2,00 1,10 1,45 0,80
5
6 65/400 0,80 2,50 2,30 1,85 2,00 1,50 1,70 0,95 1,20 0,70
7 0,90 2,95 2,30 1,85 2,60 1,50 1,70 0,95 1,20 0,70
8 1,00 3,00 2,30 1,85 2,75 1,50 1,70 0,95 1,20 0,70
9 1,20 3,00 2,30 1,85 2,75 1,50 1,70 0,95 1,20 0,70
10
11 50/333 0,80 2,10 1,90 1,80 2,20 1,55 1,75 0,95 1,25 0,70
12 0,90 2,60 2,00 2,00 2,80 1,80 2,00 1,10 1,45 0,80
13 1,00 2,80 2,20 2,00 3,15 1,80 2,00 1,10 1,45 0,80
14 1,20 3,00 2,30 2,00 3,30 1,80 2,05 1,15 1,45 0,80
15
16 50/429 0,80 2,00 1,80 1,70 1,85 1,20 1,35 0,75 0,95 0,55
17 0,90 2,45 1,90 1,70 2,40 1,40 1,55 0,85 1,00 0,65
18 1,00 2,70 2,10 1,70 2,55 1,40 1,55 0,85 1,00 0,65
19 1,20 2,80 2,15 1,70 2,55 1,40 1,55 0,85 1,00 0,65
20
21 NatureRoof 0,80 1,80 1,55 1,35 2,20 1,65 2,00 1,10 1,45 0,80
22 65/333 0,90 1,80 1,55 1,35 2,80 1,80 2,00 1,10 1,45 0,80
23 1,00 1,80 1,55 1,35 3,15 1,80 2,00 1,10 1,45 0,80
24 1,20 1,80 1,55 1,35 3,30 1,80 2,05 1,15 1,45 0,80
Supporting width in [m]
* EB = corner area / * RB = edge area
1) The supporting widths for snow load also apply to the wind suction load in the normal range for building heights 100 m.
8/10/2019 UK TechnBrosch
47/52
Kalzip Dimensioning tab