Upload
bioarquitectura
View
222
Download
0
Embed Size (px)
Citation preview
8/13/2019 Uea.filtrine.608 750g Wp Lp
1/2
FILTRINE Mfg. Co. 15 Kit St. Keene, NH 03431 USA800-930-3367 603-352-5500 FAX: 603-352-0330
w w w . f i l t r i n e . c o m c o o l @ f i l t r i n e . c o m LABOR & PARTS
608-7.5G-WP-LP[PCP-750G-WP-LP]
REV B 08.12.11
MODEL...................... PCP-750G-96-A-WP-LPHERMETIC SCROLL MODEL
SPECIFICATIONS
Cooling Capacity: Btu/hr [min / max] .........................................................................................96,000 Watts [min / max] ..........................................................................................28,128 Rating Conditions: Coolant Discharge Temperature .................................................... 68OF [20OC] Ambient Air Temperature .................................................................90OF [32OC]Condensing Unit: Compressor HP .....................................................................7 1/2 Description: Lifetime lubricated, hermetic scroll type supplied with
high/low pressure stat, freeze control, head and suction gauges,pump down solenoid valve, thermostatic expansion valve,refrigerant sight glass and dehydrator.
Cooling Tank & Evaporator: Capacity ...........................................95 Gals. [360 L] Construction: Welded stainless steel shell with stainless steel
immersion coil evaporator. Tank tested at 250# for 125# working
pressure, supplied with drain connection and insulated with closedcell thermo-elastomer with an R factor of 3.7.Pump: Motor HP ..................................................................................................... 1-1/2 Capacity .................................................30 GPM @ 40 PSI [114 lpm @ 4 bar] Description: Bronze fitted turbine pump mounted on a rubber
pad over a stainless steel condensation tray and supplied with unionsand service valves and a pressure relief bypass valve. All pipingand fittings brass, copper or bronze, and insulated with closed cellthermo-elastomer with an R factor of 3.7.
Adjustable Differential Thermostat:............................. 40Oto 90OF [4Oto 32OC] Temperature Stability .......................................................................2OF [1.4OC]CABINET: Anodized aluminum panels with stainless steel corner
legs and top on a welded angle iron frame. Panels removablewithout tools for access to all components.
Supply Power: .........................................208-230/60/3 or 460/60/3 or 380/50/3 Full Load Amps ............................................................................................42 or 21 NOTE: FLA may vary depending on options. See MCA and MOP ratings on as-built unit.Plumbing Connections In & Out ........................................... 1-1/4 [31mm] MPTDecibel Rating [nominal at 5 ft.] .....................................................................74dBAShipping Weight .............................................................................................. 2,200 lbs
FAIL SAFE OPTIONS [Designated by suffix]
-DPA DUAL PUMPS : Automatic switchover to backup pump on lossof coolant flow.
-LL LOW LEVEL INTERLOCK: Float switch in tank lights a warninglight if coolant level drops below safe low limit.
-LF LOW FLOW INTERLOCK: Flow switch lights a warning light if
flow rate drops below safe low limit.HT HIGH TEMPERATURE INTERLOCK: Thermostat lights a warning if coolant temperature rises above safe high limit.-AS AUTOMATIC SWITCHOVER TO CITY WATER : In case of
pump or compressor failure, city water switchover solenoids areactivated to allow for temporary cooling using city water.
-WP-GF WEATHER-RESISTANT, GLYCOL-FREE: For outdoorinstallation; chiller with in-line heater and circulating pumpconnected to UPS stand-by electrical system. Insures
recirculation of 50OF coolant even if power fails at below freezing temperatures.
FEATURES
Low Profile unit designed for rooftop mount-ing. Easily concealed by parapet... 44 overallheight for low visibilty
Outdoor chiller location removes heat andoperating noise from inside building
Standard anodized aluminum & stainlesssteel exterior for a lifetime of service
Ambient operating temps from -30OF to 120OF
Uses 404a Refrigerant
DESCRIPTION
A closed loop, packaged chiller designed specifically torecirculate a clean coolant at a constant temperature, pres-sure and flow. Ideal for all installations where a dependablesource of clean cooling water is not available.
Filtrine PCP chillers use a storage-type cooling tank, withimmersion coil evaporator, to provide close temperaturecontrol of recirculating coolants. The tank is sealed toprevent coolant evaporation or fouling, and suppliedwith a liquid level gauge, fill port and clean out. Thepump recirculates the coolant at a constant temperature,pressure and flow.
TYPICAL LOW PROFILE CHILLER
RECIRCULATING LOOP CHILLERLOW PROFLE / WEATHER-RESISTANT
LIFETIME WARRANTY- Consult factory for details.
ONE YEAR WARRANTY- All parts covered FOB jobsite for [12]months from start-up date or [15] months from date of shipment
- whichever comes first. Consult factory for details.
START-UP and FIRST YEAR SERVICE- Filtrine can arrange
start-up and first year service on all parts and labor. To help prevent
costly down-time, regular maintenance is available on a contractual
basis. Consult factory for details.
FILTRINE IS ISO 9001-2008 REGISTERED
PRODUCT LINE APPROVED MARK AVAILABLE
http://www.filtrine.com/mailto:[email protected]:[email protected]://www.filtrine.com/8/13/2019 Uea.filtrine.608 750g Wp Lp
2/2
FILTRINE Mfg. Co. 15 Kit St. Keene, NH 03431 USA800-930-3367 603-352-5500 FAX: 603-352-0330
w w w . f i l t r i n e . c o m c o o l @ f i l t r i n e . c o m LABOR & PARTS
608-7.5G-WP-LP[PCP-750G-WP-LP]
REV B 08.12.11
STANDARD OPERATING CONDITIONS
OUTDOOR AMBIENT:
-20OF to 90OF (10Oto 32OC)
OPTIONAL OPERATING CONDITIONS:
OUTDOOR AMBIENT:
Down to -30OF (-34OC)
Up to 100OF (38OC)
Up to 110OF (43OC)
Up to 120OF (49OC)
NOTE: Higher ambient options may affect unit dimensions.
All inform ati on giv en on this bullet in is for gen eral use onl y. Con fir m specif ications wit h fac tor y for your spe cif ic requ iremen t.
VENTILATION PANELS
TYPICAL VENTILATION: Air intake at Rear, air discharge at Right
End and Left End.
Manufacturer recommends 24 inch minimum clear space op-
posite all ventilation panels.
REMOVABLE SERVICE PANELS
Located on Front & Left End.
Manufacturer recommends 36 inch clearance at Front for service
and 36 inch clearance at Left End for access to controls.
CHANNEL SKIDS
Allow an additional 4 (10cm) to depth and 2 (5cm) to height
for channel skids. Center of 5/8 (16mm) mounting holes
located 6 (15cm) from chiller end and 1 (2.5cm) from chiller
edge front and rear.
TYPICAL WEATHER-RESISTANT, LOW PROFILE CHILLER SCHEMATIC
W
H
FRONT
D
1 2
6 34
7
8 9
LEGEND
1.........Fill Port2.........Sight Glass3.........Return4.........Discharge6.........Elect. Conn.7.........Indicator Lamps8.........Head Press.9.........Suction Press.
VENTILATION
LEFT END
VENTILATION
RIGHT END
VENTILATION
REAR
CHILLER DIMENSIONS and WEIGHTS
FILTRINEMODEL NUMBER
W D H SHIP WT
in cm in cm in cm lb kg
PCP-750G-96-A-WP-LP 82 239 87 221 44 112 2200 950
Dimensions & weights may vary depending on options installed-consult factory.
http://www.filtrine.com/mailto:[email protected]:[email protected]://www.filtrine.com/