T1/R410A/60Hz(GC201603 - І )

U-MATCH SERIES SERVICE MANUAL

Page 2: U-MATCH SERIES SERVICE MANUAL

CONTENTS

PRODUCT INTRODUCTION ............................................................................................... 2

1 MODELS LIST .......................................................................................................................... 2

2 NOMENCLATURE .................................................................................................................... 2

3 FUNCTION ............................................................................................................................... 3

4 PRODUCT DATA ...................................................................................................................... 3

4.1 Product Data at Rated Condition ......................................................................................................... 3

4.2 Electrical Data ...................................................................................................................................... 4

INSTALLATION .................................................................................................................... 6

1 DIMENSION DATA ................................................................................................................... 6

2 UNIT INSTALLATION ............................................................................................................... 6

3 PIPING WORK ......................................................................................................................... 7

3.1 Connection Pipe ................................................................................................................................... 7

3.2 Installation Procedure .......................................................................................................................... 7

3.3 Matters of Attention .............................................................................................................................. 9

4 ELECTRIC WIRING................................................................................................................ 10

4.1 POWER CORD & AIR SWITCH ........................................................................................................ 10

4.2 WIRING DIAGRAM ............................................................................................................................ 10

4.3 Thermostat Wring ................................................................................................................................ 11

MAINTENANCE ................................................................................................................. 13

1 FLOW CHART OF TROUBLESHOOTING .............................................................................. 13

1.1 Air flow volume from air outlet of unit is abnormal ............................................................................. 13

1.2 The unit can not start up for cooling ................................................................................................... 14

1.3 Poor cooling effect ............................................................................................................................. 15

1.4 Noise or abnormal vibration of unit .................................................................................................... 16

2 DISASSEMBLY AND ASSEMBLY PROCEDURE OF MAIN PARTS ....................................... 17

2.1 Disassembly and Assembly of the Electric Box ................................................................................. 17

2.2 Disassembly and Assembly of the Fan Motor .................................................................................... 18

2.3 Disassembly and Assembly of the Evaporator and Drain Pan .......................................................... 19

2.4 Disassembly and Assembly of the Filter ............................................................................................ 21

3 EXPLOSIVE VIEWS AND PARTS LIST .................................................................................. 22

Page 3: U-MATCH SERIES SERVICE MANUAL

U-MATCH SERIES SERVICE MANUAL

1

PRODUCT

Page 4: U-MATCH SERIES SERVICE MANUAL

U-MATCH SERIES SERVICE MANUAL

2

PRODUCT INTRODUCTION

1 MODELS LIST

Model Nominal Capacity Power Supply

Appearance

Model name Product Code Refrigerant Btu/h Ph,V, Hz

HNF24/A-D EM116N0750 R410A 22000 1, 220/230, 60

HNF36/A-D EM116N0770 R410A 34000 1, 220/230, 60

HNF48/A-D EM116N0790 R410A 45000 1, 220/230, 60

HNF60/A-D EM116N0810 R410A 52000 1, 220/230, 60

2 NOMENCLATURE

HN F 24 / A - D

1 2 3 4 / 5

NO. Description Options

1 Series type

HN: Air Handler

HND: Duct Type

HNT: Floor Ceiling

HNW: Wall Mounted

2 Fan Default: Without Fan

F: With Fan

3 Normal capacity Nominal Cooling Capacity

=Number×1000Btu/h

4 Serial number A, B…….

5 Electrical source

D: 1Ph,220/230V,60Hz

K: 1Ph,220/240V,50Hz

M: 3Ph,380/415V,50Hz

F: 3Ph,208/230V,60Hz

R: 1Ph,208-230V,50/60Hz

Page 5: U-MATCH SERIES SERVICE MANUAL

U-MATCH SERIES SERVICE MANUAL

3

3 FUNCTION

Function Description

Remote control function The maximum control distance of remote controller is 10 m.

Easy installation It can be installed either horizontally or vertically.

Wide range of static pressure Static pressure ranges from 0-0.64 inwg.

4 PRODUCT DATA

4.1 Product Data at Rated Condition

Mode

Item HNF24/A-D HNF36/A-D HNF48/A-D HNF60/A-D

Product Code EM116N0750 EM116N0770 EM116N0790 EM116N0810

Fan

Diameter (inch) 10 10 10 10

Width (inch) 8 8 10 10

Coil Drain Connection FPT

(inch) 3/4 3/4 3/4 3/4

Liquid (inch) 3/8 3/8 3/8 1/2

Suction (inch) 5/8 3/4 7/8 7/8

Electrical Data

Voltage (V) 220/230 220/230 220/230 220/230

Min Circuit Ampacity (A) 1.4 2.81 4.5 4.5

Max. Overload Device (A) 15 15 15 15

Min Volts (V) 198 198 198 198

Max Volts (V) 254 254 254 254

Fan Motor

FLA 0.62 1.25 2 2

Power Output (HP) 1/16 1/4 1/3 1/3

Dimension

Outline Dimension

(D/W/H)(mm) 540/460/1105 540/460/1105 540/540/1224 540/540/1224

Package Dimension

(D/W/H)(mm) 620/517/1170 620/517/1170 620/597/1289 620/597/1289

Net Weight (kg) 49 53 61 64

Gross Weight (kg) 53 57 66.5 68.5

Note: FLA stands for FULL LOAD AMPACIT

Page 6: U-MATCH SERIES SERVICE MANUAL

U-MATCH SERIES SERVICE MANUAL

4

4.2 Electrical Data

Model Power Supply

Ph V Hz

Fan Motor Air Switch

Qty. FLA Ampere

HNF24/A-D

1, 220/230, 60

1 0.62 15

HNF36/A-D 1 1.25 15

HNF48/A-D 1 2 15

HNF60/A-D 1 2 15

Notes:

RLA: Rated load amperes

LRA: Locked rotor amperes

FLA: Full load current

① Install the disconnect device with a contact gap of at least 3mm in all poles nearby the units

(Both indoor unit and outdoor unit).The appliance must be positioned so that the plug is

accessible.

② The specifications of the breaker and power cable listed in the table above are determined

based on the maximum power (maximum amps) of the unit.

③ The specifications of the power cable listed in the table above are applied to the

conduit-guarded multi-wire copper cable (like, YJV copper cable, consisting of PE insulated

wires and a PVC cable jacket) used at 40°С and resistible to 90°С (see IEC 60364-5-52). If the

working condition changes, they should be modified according to the related national standard.

④ The specifications of the breaker listed in the table above are applied to the breaker with the

working temperature at 40°С. If the working condition changes, they should be modified

according to the related national standard.

Page 7: U-MATCH SERIES SERVICE MANUAL

U-MATCH SERIES SERVICE MANUAL

5

INSTALLATION

Page 8: U-MATCH SERIES SERVICE MANUAL

U-MATCH SERIES SERVICE MANUAL

6

INSTALLATION

1 DIMENSION DATA

Table 1 Dimension of indoor unit

Unit: Inch

MODEL DIMENSION

A B C D E

HNF24/A-D 18-1/8"(460) 21-1/4"(540) 43-1/2"(1105) 11-5/8"(295) 16-3/4"(426)

HNF36/A-D 18-1/8"(460) 21-1/4"(540) 43-1/2"(1105) 11-5/8"(295) 16-3/4"(426)

HNF48/A-D 21-1/4"(540)

21-1/4"(540)

48-1/4"(1224) 11-5/8"(295) 1/2"(508)

HNF60/A-D 21-1/4"(540)

21-1/4"(540)

48-1/4"(1224) 11-5/8"(295) 1/2"(508)

2 UNIT INSTALLATION

Installation Site:

Such a place where cool air can be distributed throughout the room.

Such a place where condensate can be easily drained out.

Such a place that can withstand the weight of indoor unit.

Such a place which has easy access for maintenance.

Such a place where permits easy connection with the outdoor unit.

Such a place where is 1m or more away from other electric appliances such as television, audio

device, etc.

Avoid a location where there is heat source, high humidity or inflammable gas.

Do not use the unit in the immediate surroundings of a laundry, a bath, a shower or a swimming

pool.

Be sure that the installation conforms to the installation dimension diagram.

Page 9: U-MATCH SERIES SERVICE MANUAL

U-MATCH SERIES SERVICE MANUAL

7

The space around the unit is adequate for ventilation.

When installing this air handler, please minimize the length of refrigerant tubing as much as possible.

Do not install the air handler in a location either above or below the condenser that violates the

instructions provided with the condenser. Service clearance is to take precedence. Allow a minimum of

24” in front of the unit for service clearance. When installing the unit directly over a finished ceiling (such

as an attic), an emergency drain pan is required under the unit. See local and state codes for

requirements. When installing this unit in an area that may become wet, elevate the unit with a sturdy,

non-porous material. Installation work might lead to physical damage (i.e. a garage), it is advised to

install a protective barrier to prevent such damage.

3 PIPING WORK

3.1 Connection Pipe

Model

External Diameter

(Inch)

Maximum

Length of

Connection Pipe

(m)

Maximum Drop

Height between

Outdoor and

Indoor Units(m)

Standard

Piping

(m)

Additional

Charge of

Refrigerant

(g/m) Gas Pipe (in) Liquid Pipe (in)

HNF24/A-D 5/8 3/8 15 15 7.6 54

HNF36/A-D 3/4 3/8 30 15 7.6 54

HNF48/A-D 7/8 3/8 30 15 7.6 54

HNF60/A-D 7/8 1/2 30 15 7.6 110

3.2 Installation Procedure

3.2.1 Evaporator Coil Metering Devices

(1) Remove 9/16 nut, then press the Schneider valve to release pressure, no gas indicates a possible

leak.

(2) After the gas has released, remove the 13/16 nut, Schneider valve and white teflon seal from the

liquid line distributor.

Page 10: U-MATCH SERIES SERVICE MANUAL

U-MATCH SERIES SERVICE MANUAL

8

(3) Take the tailpiece from the plastic accessory bag and slide the 13/16 nut into place.

(4) Confirm position of the white teflon seal and manually tighten the 13/16 nut.

(5) Torque the 13/16 nut to 20-30 ft-lbs.

Fig. 6

3.2.2 Connection of Pipeline

(1) Select connection pipe as per the capacity of outdoor unit.

(2) Braze suction line. Remove cap closure from suction line.

(3) Braze tailpiece to the line set liquid tube.

(4) Insert the suction line into the connection, slide the rubber grommet at least 18" away from the

braze joint.

Fig. 7

Note: The tightening torque of the 13/16 screw nut shall not be more than 30N·m.

3.2.3 Condensate Drain Pipe

Condensate removal is performed by attaching a 3/4” PVC pipe to the evaporator coil pan and

terminated in accordance with local or state Plumbing/HVAC codes. The installation must include a “P”

style trap and keep it close to the evaporator coil as much as possible. See the following figure for details

of a typical condensate line “P” trap. To prevent potential sweating and dripping on to finished space, it

may be necessary to insulate the condensate drain line located inside the building.

Page 11: U-MATCH SERIES SERVICE MANUAL

U-MATCH SERIES SERVICE MANUAL

9

3.3 Matters of Attention

When connecting the indoor unit with the connecting pipe, do not pull the big and small joints of

the indoor unit by force, so as to prevent the capillary of the indoor unit and other pipes from

breaking and leaking.

The connecting pipe shall be supported by proper bracket. The weight of the pipe shall not be

shared by the unit.

When brazing the outdoor unit with the connecting pipe, please make sure that the valve are

wrapped with wet cloth to cool down.

During the installation, we should carry out the thermal insulation for two pieces of drain pipe.

To avoid generation of condensate on the connecting pipe and avoid leakage, the gas pipe and

the liquid pipe of the connecting pipe must be covered by thermal insulating materials, be

bundled by adhesive tape, and be isolated from air.

The joint connecting to the indoor unit must be wrapped by thermal insulating material. There

shall be no gap between the connecting pipe joint and the wall.

Due to there is protective pressure refrigerant in the indoor unit, when loosening the nuts on

the installing site, please pay more attention on the pressure so as to avoid the injury.

After the pipes are wrapped by protective materials, never bend the pipes to form very small angle,

otherwise the pipes may crack or break.

Use adhesive tape to wrap the pipes:

Use adhesive tape to bundle the connecting pipe and the cables together. To prevent condensate

from overflowing from the drain pipe, separate the drain pipe from the connecting pipe and the cables.

Use thermal insulation tape to wrap the pipes from the bottom of the outdoor unit until the upper end

of the pipe where the pipe enters the wall. When wrapping thermal insulation tape, the later circle of tape

must cover half of the front circle of tape.

Wrapped pipe must be fixed to wall by using pipe clamps.

Do not wrap the protective tape too tightly; otherwise the efficiency of thermal insulation may be

decreased. Ensure that the condensate drain tube is separate from the bundled pipes.

After the protective work is completed and the pipes are wrapped, use seal material to block the

hole in the wall, so as to prevent rain and wind from entering the room.

Page 12: U-MATCH SERIES SERVICE MANUAL

U-MATCH SERIES SERVICE MANUAL

10

4 ELECTRIC WIRING

4.1 POWER CORD & AIR SWITCH

Model Power Supply

(Ph, V, Hz) Capacity of Air Switch (A)

Minimum Sectional Area of Power

Cord (AWG)

HNF24/A-D

1, 220/230,60

15 16

HNF36/A-D 15 16

HNF48/A-D 15 16

HNF60/A-D 15 16

4.2 WIRING DIAGRAM

Model: HNF24/A-D, HNF36/A-D

Page 13: U-MATCH SERIES SERVICE MANUAL

U-MATCH SERIES SERVICE MANUAL

11

Model: HNF48/A-D,HNF60/A-D

4.3 Thermostat Wring

Page 14: U-MATCH SERIES SERVICE MANUAL

U-MATCH SERIES SERVICE MANUAL

12

MAINTENANCE

Page 15: U-MATCH SERIES SERVICE MANUAL

U-MATCH SERIES SERVICE MANUAL

13

MAINTENANCE

1 FLOW CHART OF TROUBLESHOOTING

1.1 Air flow volume from air outlet of unit is abnormal

Page 16: U-MATCH SERIES SERVICE MANUAL

U-MATCH SERIES SERVICE MANUAL

14

1.2 The unit can not start up for cooling

Page 17: U-MATCH SERIES SERVICE MANUAL

U-MATCH SERIES SERVICE MANUAL

15

1.3 Poor cooling effect

Page 18: U-MATCH SERIES SERVICE MANUAL

U-MATCH SERIES SERVICE MANUAL

16

1.4 Noise or abnormal vibration of unit

Page 19: U-MATCH SERIES SERVICE MANUAL

U-MATCH SERIES SERVICE MANUAL

17

2 DISASSEMBLY AND ASSEMBLY

PROCEDURE OF MAIN PARTS

2.1 Disassembly and Assembly of the Electric Box

Procedures Diagrams Operating Instructions

1. Remove the upper panel

● Loosen screws around the upper

panel with a screwdriver.

● Remove the upper panel away from

the unit.

2. Remove the electric box.

● Disconnect the power cord and

control line from the wiring terminals,

and then draw them out.

● Loosen screws around the electric

box with a screwdriver.

● Remove the electric box from the

unit.

3. Remove the electric

element.

● Disconnect the electric element from

the wiring terminal.

● Loosen screws around the electric

element with a screwdriver.

● Remove the electric element from the

electric box.

Page 20: U-MATCH SERIES SERVICE MANUAL

U-MATCH SERIES SERVICE MANUAL

18

4. Mount the new electric

element.

● Place the electric element at the

proper position.

● Tighten the screws around the

electric element with a screwdriver.

● Wire the electric element to the

wiring terminal.

5. Reinstall the electric box.

● Place the electric box at the proper

position.

● Tighten screws around the electric

box with a screwdriver.

● Connect the power cord and control

line properly.

● Reassemble the unit as before.

2.2 Disassembly and Assembly of the Fan Motor

Procedures Diagrams Operating Instructions

1. Remove the upper panel.

● Loosen screws round the upper

panel with a screwdriver.

● Remove the upper panel from unit.

2. Remove the fan.

● Disconnect the wires of the fan from

the wiring terminal and draw them out.

● Loosen screws located at the front of

the fan with a screwdriver.

● Remove the fan from the unit.

Page 21: U-MATCH SERIES SERVICE MANUAL

U-MATCH SERIES SERVICE MANUAL

19

3. Remove the motor.

● Loosen screws fixing the motor and

fan blades.

● Loosen screw bolts fixing the

bracket.

● Remove the motor rightward from the

fan.

4. Reinstall the fan.

● Place the motor at the proper

position.

● Tighten screws fixing the motor and

fan blades.

● Tighten screw bolts fixing the motor

bracket.

● After the installation, reassemble the

unit as before.

2.3 Disassembly and Assembly of the Evaporator and Drain Pan

Procedures Diagrams Operating Instructions

1. Remove the upper panel.

● Loosen screws round the upper

panel with a screwdriver.

● Remove the upper panel from unit

2. Remove the lower panel

(1) and panel (2).

● Loosen screws round the lower panel

with a screwdriver.

● Remove the lower panel from unit.

Page 22: U-MATCH SERIES SERVICE MANUAL

U-MATCH SERIES SERVICE MANUAL

20

3. Remove the enhanced

frame if applicable.

● Remove the screws from enhanced

frame.

● Disassemble the enhanced frame

from the unit.

4. Remove the mounting

plate of the drain pan.

● Loosen screws at both side of the

mounting plate with a screwdriver.

● Remove the mounting plate from the

unit.

5. Remove the primary drain

pan.

● Remove the primary drain pan from

the unit.

6. Remove the secondary

drain pan.

● Remove the secondary drain pan

from the unit.

Page 23: U-MATCH SERIES SERVICE MANUAL

U-MATCH SERIES SERVICE MANUAL

21

7. Remove the evaporator.

● Remove the evaporator away from

the primary drain pan.

● Reassemble the unit as before.

2.4 Disassembly and Assembly of the Filter

Procedures Diagrams Operating Instructions

1. Remove the mounting plate.

● Loosen screws fixing the mounting

plate with a screwdriver.

● Remove the mounting plate away from

the unit.

2. Remove the filter screen.

● Remove the filter screen away from

the unit.

● After replacing the filter screen,

reassemble the unit as before.

Page 24: U-MATCH SERIES SERVICE MANUAL

U-MATCH SERIES SERVICE MANUAL

22

3 EXPLOSIVE VIEWS AND PARTS LIST

Model: HNF24/A-D, HNF36/A-D:

Exploded Views

Page 25: U-MATCH SERIES SERVICE MANUAL

U-MATCH SERIES SERVICE MANUAL

23

Spare Parts List

No Description

HNF24/A-D HNF36/A-D

Part Code EM116N0750 Part Code EM116N0770

Product Code Qty Product Code Qty

1 Lower Cover Plate Sub-Assy '01262200008 1 '01262200008 1

2 Lower Cover Plate Sub-Assy '01262200009 1 '01262200009 1

3 Top Cover Board Sub-Assy '01262200007 1 '01262200007 1

4 Insulating Board '75142201 1 '75142201 1

5 Left Side Plate Sub-Assy '01312200005 1 '01312200005 1

6 Assistant Drain Pan '26902200002 1 '26902205 1

7 Motor for Centrifugal Fan '1570220101 1 '1570220101 1

8 Fan Mounting Plate '01322200008 1 '01322200008 1

9 Terminal Board '42010255 1 '42010255 1

10 Terminal Board '42011147 1 '42011147 1

11 Main Board '30221901 1 '30221901 1

12 Electric Box Assy '01392200050 1 '01392200010 1

13 Top Cover Plate Sub-Assy '01262200010 1 '01262200010 1

14 Vent Panel '02222200002 1 '02222200002 1

15 Transformer '43110286 1 '43110286 1

16 Capacitor '33000071 1 '33000074 1

17 Terminal Board '4201019601 1 '4201019601 1

18 Mid Clapboard '01242200002 1 '01242200002 1

19 Baffle of Electric Heater '01352200002 1 '01352200002 1

20 Fan Motor '15702214 1 '1570221403 1

21 Rear Side Plate Sub-Assy '01312200009 1 '01312200009 1

22 Evaporator Assy '01022200020 1 '01022200016 1

23 Valve Core '0738000123 1 '0738000112 1

24 Water Tray Support '01842214 1 '01842214 1

25 Main Drain Pan '26902200001 1 '26902200001 1

26 Filter Sub-Assy '1172220202 1 '1172220202 1

27 Right Side Plate Sub-Assy '01312200007 1 '01312200007 1

28 Choke Plug '76718209 8 '76718209 8

29 Serum Cap '26902209 2 '26902209 4

Page 26: U-MATCH SERIES SERVICE MANUAL

U-MATCH SERIES SERVICE MANUAL

24

HNF48/A-D, HNF60/A-D:

Page 27: U-MATCH SERIES SERVICE MANUAL

U-MATCH SERIES SERVICE MANUAL

25

Spare Parts List

No Description

HNF48/A-D HNF60/A-D

Part Code EM116N0790 Part Code EM116N0810

Product Code Qty Product Code Qty

1 Insulating Board '75142201 1 '75142201 1

2 Lower Cover Plate Sub-Assy '01262200015 1 '01262200015 1

3 Lower Cover Plate Sub-Assy '01262200017 1 '01262200017 1

4 Top Cover Board Sub-Assy '01262200019 1 '01262200019 1

5 Filter Sub-Assy '1172220201 1 '1172220201 1

6 Evaporator Assy '01022200023 1 '01022200029 1

7 Right Side Plate Sub-Assy '01312200017 1 '01312200017 1

8 Rear Side Plate Sub-Assy '01312200019 1 '01312200019 1

9 Capacitor '33000074 1 '33000074 1

10 Transformer '43110286 1 '43110286 1

11 Choke Plug '76718209 8 '76718209 8

12 Fan Motor '15702245 1 '15702245 1

13 Motor for Centrifugal Fan '1570220201 1 '1570220201 1

14 Board(opening of tuyere) '02222200005 1 '02222200005 1

15 Terminal Board '4201019601 1 '4201019601 1

16 Electrical Heater Baffle Plate '01352200002 1 '01352200002 1

17 Terminal Board '42010255 1 '42010255 1

18 Main Board '30221901 1 '30221901 1

19 Mid Clapboard '01242200003 1 '01242200003 1

20 Top Cover Plate Sub-Assy '01262200013 1 '01262200013 1

21 Terminal Board '42011147 1 '42011147 1

22 Mounting Plate '01322200007 1 '01322200007 1

23 Electric Cabinet Assy '01392200025 1 '01392200025 1

24 Water Tray '26902204 1 '26902204 1

25 Secondary Water Tray '26902205 1 '26902207 1

26 Left Side Plate Sub-Assy '01312200015 1 '01312200015 1

27 Valve Core 0738000126 1 '0738000127 1

Page 28: U-MATCH SERIES SERVICE MANUAL