TypeLoadsEtabs.doc

Embed Size (px)

Citation preview

  • 8/13/2019 TypeLoadsEtabs.doc

    1/3

    Dead loads are typically loads which the program can calculate by itself based ongeometry (length, width, thickness) and material properties specified (density). Steelframing member weights are automatically calculated by the program.

    Any dead load which cannot be calculated by the program need to be input as aSUPERDEAD

    . Examples of this could be slab finishes (marble, tile), masonry loads etc.Live load reduction is typically permitted for columns supporting multiple floors, asrecommended by ASCE . !he reduction of li"e load is based on probabilities. Assumethat you ha"e a #$ story building, with a column supporting a tributary area of %&'x%&' oneach floor. !he chances that each one of these floors has a li"e load at the same time isunlikely and the code allows you to reduce the load based on its nfluence Area .*reater the influence area, the more reduction you are allowed to take, but no more than a+& reduction on li"e loads. -inimum o / &.0 . Some restrictions apply, checkChapter 0 of ASCE (la noi se aplica pre"ederile 12&&3#&&+)

    Dead loads are weights of material, equipment or components that are relativelyconstant throughout the structure's life. Permanent loads are a wider category whichincludes dead loads but also includes forces set up by irreversible changes in a

    structure's constraints - for example, loads due to settlement, the secondary effects of prestress or due to shrinkage and creep in concrete.

    Also, 4ead oads are not limited to walls, floors, roofs, ceilings, stairways, built5in partitions, finishes, cladding and other similarly incorporated architectural and structuralitems, and fixed ser"ices e6uipment, including the weight of cranes. All dead loads areconsidered permanent loads.

    i"e loads, sometimes referred to as probablistic load include all the forces that are"ariable within the ob7ect's normal operation cycle. 8sing the staircase example the li"eload would be considered to be 5

    1ressure of feet on the stair treads ("ariable depending on usage and si9e):ind load (if the staircase happens to be outside)i"e loads do not include construction or en"ironmental loads such as;

    :ind loadSnow load#?i"e loads (

  • 8/13/2019 TypeLoadsEtabs.doc

    2/3

    !he reason for splitting loads into these categories is not always apparent, and in terms ofthe actual load on the ob7ect there is no difference between dead or li"e loading. =or themost part, the split occurs for use in safety calculations or ease of analysis on complexmodels.

    :hen considering the feasibility of a structure, safety always takes precedent and because of this, go"erning bodies around the world ha"e regulations to which structuresha"e to adhere. 8sing the example of the staircase, if it was intended for use in the 8 itwould ha"e to follow British and European Standards

    BS 0$ # 5 ndustrial type flooring and stair treadsBS $% $ 5 Code of practice for the design of straight stairsDther standards specific to the application (e.g. BS 202##5%;#&&2 5 1ermanent means ofaccess to machinery. Stairways, stepladders and guard5rails):ithin these standards a safety factor is usually determined where the structure should beable to withstand a certain force abo"e the maximum expected load. Dnce again using the

    staircase example, assuming it is an indoor medium5usage industrial staircase the currentsafety factor would be 2.0 times the maximum stress imposed by the dead load and 2.+times the maximum stress imposed by the li"e load. !he reason for the disparity between"alues, and thus the reason the loads are initially categorised as dead or li"e is becausewhile it is not unreasonable to expect a large number of people ascending the staircase atonce (or the wind speed increasing, snowfall or any other li"e load increase), it is lesslikely that the structure will experience much change in its permanent load. !he same can

    be said of many structures and so it is con"enient to assess loading based on itsapplication.

    Calculating combined loadst is worth noting that on first inspection it seems you should find the maximum stress foreach of dead and li"e, factor them and add them together. !his will gi"e you a massi"elyo"erestimated stress result. !he combination needs to be applied with great care andalmost exclusi"ely programmatically because you may only combine two stress results atthe same point. Since the maximum stress is "ery rarely at the same place in a structurefor dead and li"e it may well be the case that the o"erall increase is a fraction of theaddition of the two maximum stresses and in a completely different position two either ofthe two original maximums. !o clarify, take the staircase analysis. !he maximum stressunder dead load appears at the foot of a support beam and it is & Fmm5#, at this pointthe stress from the li"e load is $ Fmm5#. !he maximum stress under li"e load is +&

    Fmm5# and appears at the corner of the second stairtread where the dead load stress is %& Fmm5#. At a third point the stresses from both dead and li"e are $& Fmm5#. *i"en thesefigures you can see that the combined load cases for each point would be;

    2. & x 2.0 G $ x 2.+ / 2#. %& x 2.0 G +& x 2.+ / 2%%. $& x 2.0 G $& x 2.+ / 2$&As you can see the maximum combined stress appears away from both the original

  • 8/13/2019 TypeLoadsEtabs.doc

    3/3

    maxima but is still well under the # $ Fmm5# yield point of the structural steel thisstaircase is made of so in this case we could say that the structure is safe.