Upload
others
View
4
Download
0
Embed Size (px)
Citation preview
( ' . .-?'
Westinghouse I.L. 41-201M
INSTALLATION • OPERAT10N • MAINTENANCE · : : :
.· . :1 · · · ·11: :· . . <s·:· .· · .,- · a .... : .. · > u:··:.: .. ·
G·
.:.> .. ..,.
. . .. · · ·l
·· · ·o·· ... · .·. ·.: .... .
N . . · s .. :···: ·:
< < :> .... ·•··.· .......... < : ( .:::.. . :· ::. :
: ·.·. · ··•••••· .
..:.· .. ....... . . < •.•• : •.. ·.·
. ... .. .... ::... . .··•· .· . •
TYPE CV VOLTAGE RELAY
CAUTION
Before putting relays into service, remove all blocking which may have been inserted for the purpose of securing the parts during shipment, make sure that all moving parts operate freely, inspect the contacts to see that they are clean and close properly, and operate the relay to check the settings and electrical connections.
APPLICATION
The Type CV Relays are single-phase inductiondisc type relays operating either on under or overvoltage or both. These relays are applied as a voltage fault detector operating in conjunction with other protective relays. The relays are also used as timing devices for various automatic operations.
CONTENTS
This instruction leaflet applies to the following types of relays:
CV- 1 Long Time Undervoltage Relay CV-2 Short Time Undervoltage Relay CV -4 Long Time Overvoltage Relay CV-5 Short Time Overvoltage Relay CV-6 Long Time Over or Undervoltage Relay CV-7 Short Time Over or Undervoltage Relay CV-8 Low Voltage Pickup Overvoltage Relay
CONSTRUCTION AND OPERATION
The Types CV- 1, CV-2, CV-4, CV-5, CV-6, and CV-7 Relays consist of a voltage unit and an indicating contactor switch (ICS). The principal component parts of the relay and their location are shown in Figs. l, 2, and 3.
The Type CV-8 Relay in addition to the above components also has a capacitor which is series tuned with the main coil of the electromagnet. This tuned circuit offers a low impedance to fundamental current and a high impedance to third harmonic currents. Hence, the relay has a low pickup value for fundamental voltage and a much higher value of pickup for third harmonic voltage. At rated voltage the electromagnet is saturated causing the circuit to be detuned. The impedance of the circuit is increased and limits the fundamental current to a safe value.
A. Voltage Unit (CV)
The overvoltage unit operates on the inductiondisc principle. A main tapped coil located on the . center leg of an "E" type laminated structure produces a flux which divides and returns through the outer legs. A shading coil causes the flux through the left leg (front view) to lag the main pole flux. The out-of-phase fluxes thus produced in the air gap causes a contact closing torque.
The undervoltage unit operates on the same principle as the overvoltage unit except the shading coil is on the right leg (front view). This causes the out-of-phase fluxes to produce a contact opening torque.
B. Indicating Contactor Switch (ICS)
The indicating contactor switch is a small d-e operated clapper type device. A magnetic armature, to which leaf-spring mounted contacts are attached, is attracted to the magnetic core upon energization of the switch. When the switch closes, the moving contacts bridge two stationary contacts, completing the trip circuit. Also, during
All possible contingencies which may arise during installation, operation, or maintenance, and all details and variations of this equipment do not purport to be co Fe red by these instructions. If further information is desired by purchaser regarding his particular installation, operation or maintenance of his equipment, the local Westinghouse Electric Corporation representatire should be contacted.
SUPERSEDES I.L. 41-201L DATED SEPTEMBER 1982 EFFECTIVE JANUARY 1984 www . El
ectric
alPar
tMan
uals
. com
www . El
ectric
alPar
tMan
uals
. com
I.L. 4 1-20 1 M
2
• • • " tl • c
l '
Fig. 1. Type CV-2 Relay Withou t Case. 1-Voltage Unit (CV). 2-lndicating Contactor Switch (ICS).
3-lndicating Contactor Switch Tap Block.
Fig. 2. Voltage Unit (CV). 1-Tap Block. 2-Tim e D ial. 3-Control Spring Assem bly. 4-D isc.
5-Stationary Contact Assem bly. 6-Permanent Magnet.
()
-·
www . El
ectric
alPar
tMan
uals
. com
www . El
ectric
alPar
tMan
uals
. com
I.L. 4 l-20 1 M
------
T
Fig. 3. Indicating Contactor Switch (ICS).
this operation two fingers on the armature deflect a spring located on the front of the switch, which allows the operation indicator target to drop. The target is reset from the outside of the case by a push rod located at the bottom of the case.
The front spring, in addition to holding the target, provides restraint for the armature and thus controls the pickup value of the switch.
CHARACTERISTICS
The low pickup CV-8 Overvoltage Relay is available with the following continuous voltages.
Type Relay
67 volts 199 volts
2 Minute Rating
140 volts 300 volts
The minimum voltage required to just close the CV-8 contacts is typically 8% of the continuous voltage. Typical operating times of the type CV-8 relay are shown on Fig. 10. An adjustable 5.4 to 20 volt relay with a 67 volt continuous and a 16 to 40 volt relay with a continuous of 199 volts is also available. However, the operate times for the adjustable CV-8 relay will differ from Fig. 10 and will depend on the pickup setting.
The CV-1 and CV-2 Undervoltage Relays, CV-4 and CV-5 Overvoltage Relays, and CV-6 and CV-7
Over or Undervoltage Relays are available in the following voltage ranges:
Range Taps 55-140 55 64 70 82 93 105 120 140
110-280 110 128 140 164 186 210 240 280
A. CV-1 and CV-2 Undervoltage RelaysCV-4 and CV-5 Overvoltage Relays
Tap value voltage is the minimum voltage required to just close the relay contacts. At this value of voltage, the moving contacts will leave the backstop of the time dial and move to close the front contacts. Normal operation of the two relays is such that the CV-1 and CV -2 undervoltage relays will open its contacts with application of voltages greater than tap value voltage, while the CV-4 and CV-5 overvoltage relay closes its contacts with voltages greater than tap value voltage. Thus, the operating curves of Figs. 1 1 and 12 of the undervoltage relays apply when the voltage is originally higher than tap value voltage and is suddenly reduced to a value shown on the curves. The operating curves of Figs. 13 and 14 of the overvoltage relays apply when the voltage is initially below tap value voltage and is suddenly raised to a value shown on the curves.
B. CV-6 and CV-7 Over or Undervoltage Relays
Tap value voltage is the value of voltage at which the stationary front contact closes. The
3 www . El
ectric
alPar
tMan
uals
. com
www . El
ectric
alPar
tMan
uals
. com
I.L. 4 1 -20 1 M
lloOIU.flklo C�lACTOI SllfC.
(OIIfACT M:llrl.,.dl(l.U Ot•UUIIlU O•U·•OLT-CiE • V'U IOU•fOLT"i[ - C40:W:O
fDT Vlh
IIOUCTIOI ..-rT
1£0 IIAIOl( TUf JI'ITCI
182A725
Fig. 4. Internal Sch ematic of th e Double Trip Type CV
Under or Overvoltage Relays in Type FT11 Case.
For th e Single Trip Relays the Circuits associated
with Terminal 2 are Omitted.
stationary back contact will close within 5% of this value.
When the relay is used as an overvoltage relay, the moving contact is made with the stationary back contact for values of applied voltage less than tap value voltage. With application of voltages greater than tap value voltage, the moving contact moves to close the front contact in a time as shown by the right-hand curves of either Figs. 15 or 16.
When the relay is used as an undervoltage relay, the moving contact is made with the stationary front contact for values of applied voltage greater than tap value voltage. With the application of voltages less than tap value voltage, the moving contact moves to close the back contact in a time as shown on the left-hand curves of either Figs. 15 or 16.
Trip Circuit
The main contacts will close 30 amperes at 250 volts d-e and the seal-in contacts of the indicating contactor switch will carry this current long enough to trip a circuit breaker.
The indicating contactor switch has two taps that provide a pickup setting of 0.2 or 2 amperes.
4
182Al27
Fig. 5. Internal Sch ematic of the Type CV Over or
Undervoltage Relay in Type FT11 Case.
To change taps requires connecting the lead located in front of the tap block to the desired setting by means of a screw connection.
Trip Circuit Constants
Indicating Con tactor Switch . ... 0.2 amp. tap 6. 5 ohms d-e resistance
2. 0 amp. tap 0. 15 ohms d-e resistance
SETTINGS
A. CV Unit
The setting of the CV unit can be defined either by tap setting and time dial position or by tap setting and a specific time of operation at some percentage of tap value voltage (e.g. on CV -4 120 tap setting, 2 time dial position or 120 tap setting, 12 seconds at 140 percent of tap value voltage).
To provide selective circuit breaker operation, a minimum coordinating time of 0.3 seconds plus circuit breaker time is recommended between the relay being set and the relays with which coordination is to be effected.
The connector screw on the terminal plate above the time dial connects various turns of the operating coil. By placing this screw in the
www . El
ectric
alPar
tMan
uals
. com
www . El
ectric
alPar
tMan
uals
. com
c:
various terminal plate holes, the relay will just close its contacts at the corresponding voltage of 55-64-70-82-93-105-120-140 volts or as marked on the terminal plate.
The nylon screw on the terminal plate holds the tap plate in position when taps are being changed. To use the position on the terminal plate in which the nylon screw is used, remove the nylon screw and place it in one of the unused holes. Then remove the tap screw and insert it in the terminal plate hole.
The CV-8 relay has no taps. Its minimum pickup of approximately 8% of continuous voltage is set by adjusting the restraint spring. For this setting, the adjustable resistor, where used, should be shorted out.
Where the resistor is used, the pickup setting can be adjusted from approximately 8% to 30% of the continuous voltage rating. This setting is made by adjusting the resistor. Note, however, that the CV-8 time curves shown in Fig. 10 apply only when the resistor is shorted out. Timing tests should be conducted after the resistor is used to change the pickup. This will insure proper coordination time for the desired pickup setting.
Instantaneous Reclosing
The factory adjustment of the voltage unit contacts provides a contact follow. Where circuit breaker reclosing will be initiated immediately after a trip by the overvoltage contact, the time of the opening of the contacts should be a minimum. This condition is obtained by loosening the stationary contact mounting screw, removing the contact plate and then replacing the plate with the bent end resting against the contact spring.
For double trip relays, the upper stationary contact is adjusted such that the contact rests solidly against the backstop. The lower stationary contact is then adjusted such that both stationary contacts make contact simultaneously with their respective moving contact.
B. Indicating Contactor Switch (ICS)
No setting is required on the ICS unit except the selection of the 0.2 to 2.0 ampere tap setting. This selection is made by connecting the lead located in front of the tap block to the desired setting by means of the connecting screw.
I.L. 4 1-20 1 M
ENERGY REOUI REMENTS
The 60 Hz burdens of the CV-1, CV-2, CV-4, CV-5, CV-6, CV-7 relays at rated voltage are as follows: (For 50 Hz, multiply voltamperes by 1.18, multiply watts by 1.38.)
Taps tJ. Rated 120 Volt 240 Volt Volt· Power Voltage Relay Relay Amps. Factor Watts
55 110 10.0 .38 3.8 64 128 7.0 .35 2.5 70 140 5.8 .34 2.0
120 or 82 164 4.0 .33 1.3 240 Volts 93 186 3.1 .31 1.0
105 210 2.4 .29 . 7 120 240 1.8 .28 .5 140 280 1.3 .26 .3
The 50 Hz and 60 Hz burdens of the CV-8 relays at continuous voltage do not exceed the following:
!::. Continuous
Voltage
199 67
Range
5.4 to 20V
16 to40V
Volt
Amps.
30 30
Power
Factor
.342 .342
CV -8 With Adjustable Pickup
Applied
Setting Voltage
5.4 67 20 67 16 199 40 199
Watts
10 10
VA
30 15 30 20
The short time ( 15 seconds) rating is 240V and 51 OV respectively for the 67 and 199V relay.
tJ. These relays will continuously stand either 110% of rated voltage or tap value voltage, whichever is higher.
INSTALLATION
The relays should be mounted on switchboard panels or their equivalent in a location free from dirt, moisture, excessive vibration, and heat. Mount the relay vertically by means of the four mounting holes on the flange for semi-flush mounting or by means of the rear mounting stud or studs for projection mounting. Either a mounting stud or the mounting screws may be utilized for grounding the relay. The electrical connections may be made directly to the terminals by means of screws for steel panel mounting or to
5 www . El
ectric
alPar
tMan
uals
. com
) www .
Elec
tricalP
artM
anua
ls . c
om
I.L. 4l-20 1 M
lltiCATIII CIIIITICIM ., Ttl
fiiOIIT Ylllf
182A726
Fig. 6. Internal Schematic of the Type CV-8 199 Volt
Relay in Type FT11 Case.
IIOICATIK
COIIUCTOI Sti'ITU
INT[RIOIAL SCM[MATIC
'" �----------.....,
IIDUCT I 01 Ull T
1£0 ftl.lOL£ - TUT S•l Tth
TUNIUL
188A307
Fig. 8. Internal Schematic of the Type CV-8 199 Volt
Relay in Type FT11 Case with Adjustable
Pickup.
6
IIOIUTIIt CIIIIT&CTOI •oTCI
.... , Ylllf
182A743
Fig. 7. Internal Schematic of the Type CV-8 67 Volt
Relay in Type FT21 Case.
llttCUtlt COITACTOI IWITCII ICS �----------
F"'MT vrrw
IIOUCTIOI UIIT
IUIITOI
llD I.IIDLE
TEIT IWITCII
TUIIIUL
185A038
Fig. 9. Internal Schematic of the Type CV-8 67 Volt
Relay in Type FT21 Case with Adjustable
Pickup. www . El
ectric
alPar
tMan
uals
. com
www . El
ectric
alPar
tMan
uals
. com
the terminal studs furnished with the relay for thick panel mounting. The terminal studs may be easily removed or inserted by locking two nuts on the stud and then turning the proper nut with a wrench.
For detailed FT Case information refer to I.L. 41-076.
ADJUSTMENTS AND MAINTENANCE
The proper adjustments to insure correct operation of this relay have been made at the factory. Upon receipt of the relay, no customer adjustments, other than those covered under "Settings", should be required.
Performance Check
The following check is recommended to verify that the relay is in proper working order:
A. CV Unit
1. Contact
a) By turning the time dial, move the moving contacts until they deflect the stationary contact to a position where the stationary contact is resting against its backstop. The index mark located on the movement frame should coincide with the "0" mark on the time dial. For double trip relays, the follow on the stationary contacts should be approximately 1/64".
b) For relays identified with a "T", located at lower left of stationary contact block, the index mark on the movement frame will coincide with the "0" mark on the time dial when the stationary contact has moved through approximately one half of its normal deflection. Therefore, with the stationary contact resting against the backstop, the index mark is offset to the right of the "0" mark by approximately .020". (For the type CV-6 and CV-7 relays the back contact has no follow when the front contact is through one-half of its follow). The placement of the various time dial positions in line with the index mark will give operating times as shown on the respective time-current curves. For double trip relays. the follow on the stationary contacts should be approximately 1/32".
I.L. 4 l -20 1 M
2. Minimum Trip Voltage
Set the time dial to position 6. Alternately apply tap value voltage plus 3% and tap value voltage minus 3%.
a. CV -4 and CV -5 Overvol tage Relays, CV -6 and CV-7 Over or Undervoltage Relays
The moving contact should leave the backstop at tap value voltage plus 3% and should return to the backstop at tap value voltage minus 3%.
b. CV-1 and CV-2 Undervoltage Relays
The moving contact should leave the backstop at tap value voltage minus 3% and should return to the backstop at tap value voltage plus 3%.
c. CV -8 Overvoltage Relays
The moving contact should leave the backstop between 8.3% and 7. 7% of continuous voltage. Note that the resistor, where used, should be shorted when making these measurements.
Where the resistor is used, the pickup setting can be adjusted from approximately 8% to 30% of the continuous voltage rating. This setting is made by adjusting the resistor. Note, however, that the CV-8 time curves shown in Fig. 10 apply only when the resistor is shorted out. Timing tests should be conducted after the resistor is used to change the pickup. This will verify proper coordination time for the desired pickup setting.
3. Time Curve
Table 1 shows the time curve calibration points for the various types of relays. With the time dial set to the indicated position, apply the voltages specified in Table 1 (e.g. for the CV -4, 140 percent of tap value voltage) and measure the operating time of the relay. The operating time should equal those of Table 1 plus or minus 5%. Note that the resistor, where used in CV-8, should be shorted when making this measurement.
B. Indicating Contactor Switch (ICS)
Close the main relay contacts and pass sufficient d-e current through the trip circuit to close
7 www . El
ectric
alPar
tMan
uals
. com
)
www . El
ectric
alPar
tMan
uals
. com
I.L. 4 l-20 1 M
1e contacts of the ICS. This value of current should not be greater than the particular res setting being used. The intlicator target should drop freely.
The contact gap should be approximately .047" between the bridging moving contact and the adjustable stationary contacts. The bridging moving contact should touch both stationary contacts simultaneously.
Routine Maintenance
All relays should be inspected periodically and the time of operation should be checked at least once every year or at such other time inte.r.rals as may be dictated by experience to be suitable to the particular application. Phantom loads should not be used in testing induction-type relays because of the resulting distorted current wave form which produces an error in timing.
All contacts should be periodically cleaned. A contact burnisher S# 182A836HO 1 is recommended for this purpose. The use of abrasive
'aterial for cleaning contacts s not recom. ended. because of the danger of embedding
small particles in the face of the soft silver con-tact and thus impairing the con tact.
Calibration
Use the following procedure for calibrating the relay if the relay has been taken apart for repairs, or the adjustments have been disturbed. This procedure should not be used until it is apparent that the relay is not in proper working order (See "Performance Check'').
A. CV Unit
1. Contact
a) By turning the time diaL move the moving contacts until they detlect the stationary contact to a position where the stationary contact is resting against its backstop. The index mark located on the movement frame should coincide with the "0" mark on the time dial. For double trip relays, the follow on the stationary contacts should be approximately 1/64".
b) For relays identified with a "T", located at lower left of stationary contact block. the in-
8
dex mark on the movement frame will coincide with the "0" mark on the time dial when the stationary contact has moved through approximately one half of its normal deflection. Therefore, with the stationary contact resting against the backstop, the index mark is offset to the right of the "0" mark by approximately .020". (For the type CV-6 and CV-7 relays the back contact has no follow when the front contact is through one-half of its follow). The placement of the various time dial positions in line with the index mark will give operating times as shown on the respective time-current cu.r.res. For double trip relays, the follow on the stationary contacts should be approximately 1/32".
2. Minimum Trip-Voltage
The adjustment of the spring tension in setting the minimum trip voltage value of the relay is most conveniently made with the damping magnet removed.
With the time dial set on "0", wind up the spiral spring by means of the spring adjuster until approximately 6-3/4 convolutions show .
Set the relay on the minimum tap setting and the time dial to position 6.
a. CV-4 and CV-5 Overvoltage, CV-6 and CV-7 Over or Undervoltage
Adjust the control spring tension so that the moving contact will leave the backstop of the time dial at tap value voltage + 1. 0% and will return to the backstop at tap value voltage - 1.0%.
b. CV-1 and CV-2 Undervoltage Relays
Adjust the control spring tension so that the moving contact will leave the backstop of the time dial at tap value voltage -1.0% and will return to the backstop at tap value voltage + 1.0%.
c. CV-8 Low Pickup Overvoltage Relay
Adjust the control spring so that the moving contact will close at 8.2% or more of continuous voltage and return to the backstop at 7.8% or less of continuous voltage. The fixed, or adjustable resistor. where used, should be shorted during these measurements and the short removed when completed.
www . El
ectric
alPar
tMan
uals
. com
www . El
ectric
alPar
tMan
uals
. com
Where the resistor is used, the pickup setting can be adjusted from approximately 8% to 30% of the continuous voltage rating. This setting is made by adjusting the resistor. Note, however, that the CV-8 time curves shown in Fig. 10 apply only when the resistor is shorted out. Timing tests should be conducted after the resistor is used to change the pickup. This will verify proper coordination time for the desired pickup setting.
3. Time Curve Calibration
Install the permanent magnet.
a. CV-1 and CV-2 Undervoltage Relay
Use test circuit of Fig. 18. With switch "S" opened, adjust resistor "A" until voltmeter reads tap value voltage or higher. Close switch "S" and adjust resistor " B " until the voltmeter reads 50 percent of tap value voltage. Open switch "S" and allow the moving contact to move to the backstop of the time dial. Close switch "S" and measure operating time.
Adjust the permanent magnet gap until the operating time corresponds to the value given in Table 1.
b. CV -4 and CV -5 Overvoltage Relay, CV-8 Low Pickup Overvoltage Relay
Apply the indicated voltage of Table I and measure the operating time. Adjust the permanent magnet keeper until the operating time corresponds to the value given in Table 1.
l.L. 4 l-20 1 M
c. CV-6 and CV-7 Ov�r or Undervoltage Relay
Apply the indicated voltage of Table 1 and measure the operating time. Adjust the permanent magnet keeper until the operating time corresponds to the value given in Table 1.
Measure the reset time of the disc from the stationary front contact to the stationary back con tact. This time should be as shown in Table 1.
Table 1
Percent Tap Time Type Value Voltage or Dial Relay Pickup Voltage Setting
CV1 50 6 CV2 50 6 CV4 140 6 CV5 140 6 CV6 140 6 CV7 140 6 CV8 800 6
Operating Time
in Sec.
68 8.6
37.5 6.8
33 5.9 3.0
Reset Time
in Sec.
32.5 5.7
B. Indicating Contactor Switch -Unit (ICS)
Close the main relay contacts and pass sufficient d-e current through the trip circuit to close the contacts of the ICS. This value of current should not be greater than the particular ICS setting being used. The indicator target should drop freely.
RENEWAL PARTS Repair work can be done most satisfactorily at
the factory. However, interchangeable parts can be furnished to the customers who are equipped for doing repair work. When ordering parts, always give the complete nameplate data.
9 www . El
ectric
alPar
tMan
uals
. com
)
www . El
ectric
alPar
tMan
uals
. com
I.L. 4 1 -20 1 M
10
16
14
12
10
6
4
2
0 0
w_.
'
'
'
'
+-+--+ -Lj t
I
'
1-+..j-
'
I
'
'
'
I
I
I
'
'
'
' I
· t -r---+
I
+-
-t f-L+ --rlt- I •
H-1 -r-+ +- +- l t-_; � �- --'
\�-4 ' '' i '
I __ L l \l '.
I
' ' '
�'-
..._ .L �
+�� - . t t-
!--... � • I
-
... .. . h-1---t .. � T •-
� +>-+-�
-+
t \ -r-
+ +
j_ - -
; t I-I I l I � LL rf ;
··�
+ H-
+ ++-1 r t-ft i r.
-t_tt +-t -;+-
f-+.l-' . •
t �H - H·-�---+- -
I
.,__t..;....
-i-
I
'
-
TYPICAL TIME CURVES TYPE CV-8
OVERVOLTAGE RELAY 50/60 HERTZ
I
' I
t . - +--- � I t
�tr H+ -H-
�+ .;._.__ --* -IT- rFt: +.-L '
i � 7-J-#= - ·-
+ r-
' tt :±± -+---t-- + �_._;. tl 1---\-- - +--� '- H- +t· � H ! t- +-t-++-1·11 �1
+- t-t t -
ft t f � l ' CL�l � .L -+r-+: -t-\-\- I + Hl -t-- -t-t· 1-t- t--r-· t-'- tt I \ '' , . I' A �'\H- _,_ _ _ t +·I +-
·1 7·t·:- I�T -r�t \+N t - � � -- ..,.. [ I j_ .... ++-+ '\ "-! · ' \!'\ -� · N �"'s- + ...L '" " ' ,, " ' I ' ' . ..... I'X
' .... _j_"'o. � " .. I' f-h-l'o. T " .X TIME DIAL '.� .. -� -4-� �f-
'I 1\.L I"
'
- li;;;t' "' ;o..,. � 11 ... "" � .,. ' 10 ... ....... � ' I . �
' "" --1� � gJ:�+ . ..... I � 8 ..... ..... ... ..... I ' 7 -" :..... I -- !"'oo.
.,..6 -..... -" '1'"'05 �
..... -4 ---I 3 !""
� 2 �
' 1
112 -:-�- '
�00 800 1200 PER CEHT PICK-UP VOLTAGE
-.. I
..,.. I� ----
- I
J,.J._._
loOO
l ·-
'
·t I l F rt¢= I - +++
I + �q '
SETTING I '
'
' I
I ' ' I
! ' '
' ' I
I
I ' I I
I
Curve 418252
Fig. 10. Typical Time Curves of the Type CV-8 Low Pickup Overvoltage Relay.
6
www . El
ectric
alPar
tMan
uals
. com
www . El
ectric
alPar
tMan
uals
. com
()
0
I I I I I I I I I I -- TYPICAL TIME CURVES - TYPE CV-1 � f- UNDERVOLTAGE RELAY f- 50/60 HERTZ f-
I I
I
+ -I ' I
' I !/ I I I I I ;.,..- !/ SETTING / : i/1 TIME DIAL L..; .....,. L/
_I I _/ ., Ll I-� I .., : _, A I I u� i I �· Vl ' _,_. I
10 -r I ,_... / 1,; I I I I ' g I I """"' I ' ..., Lt .--r 8� lL ""' v I J.o-r I / ,_ I I 7
I I X � I I .¥ I i ......... Ll 6
_;,. I ' I i �� : :....;,... ' 5 I looo!"" ' �
I ./ I I I ....,... I
I I I ..A' - L ,.... I I I ...... � I
I .......... I I I I I I .,.. I i I ! I I ---:
i ' ..........- I I I
I I I I I I I I : ........
--' I ' I I , I i I I : ! I I : I 1 ,_l
i I i I I I I I I '
I I I ! I ' I
II
1
_1 'L j 1_
1/_ lL 1_
1/ 1/ ,
!J
If II
I�
v lL I !/ I I
1/ IJ I
'L
1/ iL If � W". l I
/ I ' IJ
_l IJI
�14 I
f I ....., , I '
' l 3 j_ ' i
I ....,. Jll'i' f I I [, 2 I I I I I i �:
A I ..... I
,- l i I ' I '
: I .., ! I � :
I I .... .--
-± ..... � I l . I I I j_ I . I I I
j II
I
j
II 11 IL
II
II
i/
1/ u
1/ I
I
/ I
I I
It'_ 1
.,
/2
I I I I
I
I I
I
I I '
I
:
l
i
I
_l I I I
l l . I
I.L. 4 1-20 1 M
160
1
1 140
130
120
110
100
go
II) 0
80 �
70
60
50
30
20
10
0
u U-1 II)
10 20 30 40 50 60 70 80 100 PEfl CENT TAP VALUE VOLTAGE
Fig. 11. Typical Time Curves of the Type CV-1 Long Time Undervoltage Relay.
Curve 418251
11 www . El
ectric
alPar
tMan
uals
. com
)
www . El
ectric
alPar
tMan
uals
. com
I .L. 4 1 -20 IM
-
0
12
TYPICAL TIME CURVES TYPE CV-2
UNDERVOL TAGE RELAY 50/60 HERTZ
I J l !Ill J 11
rT II l
11 II 1/ 11
II , 1/ IT
11 II I� II If 11 i/ J " II ;J iJ 1/ I� II
I� � 1 If
""' I� TP4 DIAl SETTING ,... ,... � J , "'" l..ol I� J II
.. 11 � "'" I� ioo"" """ " i/ J
.... 10 L,.; II"" I� T ........ 9 "'" i/ II
- ""' ' ""'"'" 8 .. ""'
� , ""' 7 ,... 11 1-" v If" 11 .... 6 ],jill I.- ii'
!5 v 11 .... ""' 1.;1
""' 14 IJj IJ ... L..o l.i'
loooo ... 3 ""'
I-' ,;.- ., '-"" ..... 2 .... .... .._,_ 1 II
�...o.- . ! �l't
� I
10 20 30 140 50 60 70 80 90 PER CENT TAP YALUE VOLTAGE
Fig. 12. Typical Tim e Curves of the Type CV-2 Sh ort Tim e Undervoltage Relay.
32
30
28
26
214
22
20
18 V)
16 �
1�
12
10
8
0
'
' 2
0 100
0 u � V)
Curve 418250
0
www . El
ectric
alPar
tMan
uals
. com
www . El
ectric
alPar
tMan
uals
. com
•
1 60
1 50
1 110
130
1 20
1 1 0 '
100
QO "' 0 z 80 3
a .... "'
7 0
6 0
50
ljQ
30
20 '
1 0
0 0 1 10
lj 3
2
1
l f�,
1 20 1 30
�
8
7
6
5
1 140
l .L. 4 l -20 1 M
TY P I C A L TI M E C U R V E S
T Y P E CV·4
0 V E R V O L TAG E R E L A Y
50/60 H E R T Z
1 1 T l �f 0 I A L S f T T I I V
10
1 50 1 60 1 70 1 80 1 90 200 2 1 0 220 �30 240 2 50
P E R C E N T OF TAP VAL U E VOl TAGE
406C887
Fig. 7 3. Typical Time Curves of the Type CV4 Long Time Overvoltage Relay.
13 www . El
ectric
alPar
tMan
uals
. com
)
www . El
ectric
alPar
tMan
uals
. com
l .L. 4 1 -20 1 M
(/) >-w <! > ..J a: w � Ill a: � u ' w w > o a: ::2' u <! w w r- I t- � ..J O ..J >- o � <! t- > o ' u a: lll � w >- > t- 0
'
'
'
' '
'
I '
' '
'
'
-- �
�
'
'
•
Fig. 7 4.
14
'
'
'
'
I
"""" �
..
'
'
... ...
'
i
'
l-' '
'
I
...,.. �
'
'
0 -
�· -1-1-... "'
� • -a
� ... % 1-
/ .L'f
_,..
....... ...-_...
' ' '
�
· - 1-- -t-i-
L
- 1.;" -
2 Ot
y
..,.. '
'
CD ,._ SO N003S
'
---t + t '
- it:: +-t
�
'
.p I · ' ' · t1 I J I
1 I 1/ , '
L ' '
·� � L
:A. 1 ' .ll ' l '
if: I A I '
L .A L CD
.... � _.It' <0 on L
�
,;'[ "'
"'
'
'
..,
Typical Time Curves of the Type CV-5 Short Time Overvoltage R elay.
� 0 g "'
0 fJ 0 ,_ "'
,
0 ' 0 "'
� "'
.
' � j.. "'
� 0 "' "' ... '-' 0 4 - ... "' �
0 :» ...
0 � 0 ..J ... ..
'
""
(J Q, o • Cll 1--
1-.. ...
0 u CD _ .,. ...
Q,
0 ....
0 0 -
0 on
� '
0 "'
-
� 0 "' -
0 -
8 0
406C884
www . El
ectric
alPar
tMan
uals
. com
www . El
ectric
alPar
tMan
uals
. com
a: w > 0
Fig. 15.
0 0 0 "'
SONOjlS
:::
0 .....
"' '
,_ ,_
... ,. ,_
Cll
0 "'
..,
"'
"'
0
"'
i: "' 0 � 0 ... "'
0 "' "' 0 ;;;
8 .. 0 � 0 !2
�
�
�
j ... _ ..., : _. 0 0 <'> > ...
"' :: � 0 >
!:! .. - ... : 0 >-= �
u a:
� o 2 � 0 Q
� 0 CD
0 .....
0 C>
0 ..
0 2
li
0 "'
2
0
Typical Tim e Curves of the Type CV-6 Long Tim e Over and Undervoltage Relay.
I .L. 4 1 -20 1 M
4 06C882
1 5 www . El
ectric
alPar
tMan
uals
. com
www . El
ectric
alPar
tMan
uals
. com
I .L. 4 1 -20 1 M
16
a: UJ > 0
� � ,.._-! .._.... M � � H-'-i � � �;:r;:r O)t= SONOJlS
::
::
'
N
8 "'
0 �
� 0 � N
� S! N
'j N
� 0 N .
0 .
� � ,
.,
�
r 0 "
r
1- S! - �
> �
_4ij 0 "' 0.
0 N
0
..... o o
0 "'
0 .,
0 "'
Fig. 16. Typical Time Curves of the Type CV. J Short Time O ver and Undervoltage Relay.
0
406C883
www . El
ectric
alPar
tMan
uals
. com
www . El
ectric
alPar
tMan
uals
. com
()
z Q 1-C2 co
<1 u L1.. 0
� n.. � :::, �
() <t -, (/) <X: w (.!) � _J 0 > n.. � 1-
60 -5 0 4 0
30
20
-t O
8
6 5 4
3
2
-
.8
.6 .5
� .3 . 2
I
H+ �t1 � -
-
r=
- +-+--1 -
-
. -
::::50� HER
� t=
r-tW-
TZ p...:-
vO HE R1TZf-= r-1--
'-f.- �-
- --
f-+ i- . f+t c-r-. 3 4 . 5 .6 .8
l\ II \ If
- -
'(
l.L. 4 1 -20 1 M
L
TY P I CA L F R E Q U E N C Y
R E S P O N S E C U R V E S
T Y P E C V -8
O V E R V O LTA G E R E LA Y
50/60 H E R TZ
2 3 4
APPLIED FREQUENCY AS A MULTIPLE OF RATED FREQUENCY
Curve 619585
Fig. 1 7. Typical Sensitivity Curves of the Type CV-8 L ow Voltage Pickup Overvoltage Relay.
17 www . El
ectric
alPar
tMan
uals
. com
www . El
ectric
alPar
tMan
uals
. com
I .L . 4 1 -20 1 M
Fig. 18.
18
( T J •U STOPS 1 TO � T I • E • �EM AUI. IHAT ) STOP co• ucT oPEJIS)
1 TO ( T I • ER STARTS
J T I N£ 11: _,EM S • l TCH sun " S " ClOSES)
.t..C. SUPPl f
183A023
Diagram of Test Connections of the Type CV
Undervoltage Relay.
ro ( TI•U STOPS f ! NU .. (If AUI. Ul.IT S TO, COO TACT OP E.M S )
ro ( T I • E R SlUTS T I M U wt!OI S•l TCJI& START "S" Cl OS E S )
TEST SWI TCM
L-------��--------------._-o i::�· s_· __ A_. c_._� __ •�--'
Fig. 19.
183A024
Diagram of Test Connections of the Type CV
Overvoltage Relay.
(� e.
www . El
ectric
alPar
tMan
uals
. com
www . El
ectric
alPar
tMan
uals
. com
a r 2 - zr r · s rr'&C'T a - n-wdt;;st ---
)
( 16 1 .93) P R O J E C T I O N M TG.
. 563 ( 14 .30 )
I.L. 4 1 -20 1 M
(l�� �DIA. 4 HOLE S FOR '
, 1 90 - 32 MTG. SCREWS
PAN E L CUT O U T S DRI L L I N G
FOR SEM I - F LUSH MTG
2 .'328 ( 59. 1 3 )
(l��bl OIA. 2 HOLES
570 7900
Fig. 20. Outline and D rilling for FT 1 1 Case used for Projection and/or Semi-Flush Case.
19 www . El
ectric
alPar
tMan
uals
. com
www . El
ectric
alPar
tMan
uals
. com
I .L. 4 1 -20 I M
I t_ I
10 .438 ( 2 65. 1 3 )
t
5 .2 19 ( 1 32 . 56 )
WTERNAL-E XTERNAL TOOTHED WASHERS 1.8 1 3
. 190 -32 SCREW (4 6.05) FOR THICK PANELS I
. 563 ( 14 . 30) ·250 OIA. 4 HOLES FOR
16 • 35) . 1 90 -32 MTG. SCREWS
PANEL C U TO U T 8 DR I LLING FOR SE M I - F L U S H MTG .
. 250 + .g l6 ( .39� ) 1 (6. 35 ) - 375 1 .031 --t:-1.031 -;--- 1.031 � 1.031 ""1 (9. 5 3 ) R. 26. 1 9 ) ·(26. 1 9 ) (26 . 1 9 ) (26. 1 9 ) .
USE . 190-32 STUOS'"-L---4--��--�-- '-�-J-----L���----r---�Hr LTERMINAL
NUMBER
57D 790 1
Fig. 2 1. Ou tline and Drilling for FT2 1 Case used for Projection and/or S�mi-Fiush Case
{For 67 Volt CV-8 Relay Only)
W E S T I N G H O U S E R E LAY - I N ST R U M E N T D I V I S I O N
E L E C T R I C C O R P O R A T I O N C O R A L S P R I N G S , FL 33065
Printed in U.S.A
0
www . El
ectric
alPar
tMan
uals
. com
www . El
ectric
alPar
tMan
uals
. com