TWENTIES PROJECT Some preliminary results: summary August 2012

TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

TWENTIES PROJECT

Some preliminary

results: summary

August 2012

Page 2: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

2

www.twenties-project.eu

Demo 1

SYSERWIND DEMOSTRATION

Enhanced System Services From Wind

Roberto Veguillas, IBERDROLA Renovables

Page 3: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

3

DEMO 1 SYSERWIND (Leader: IBR)

www.twenties-project.eu

111 MW 122 MW

248 MW

Page 4: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

4

Active Power Control – Test Procedure

www.twenties-project.eu

Page 5: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

5

Active Power Control – Test Procedure

www.twenties-project.eu

Page 6: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

6 www.twenties-project.eu

Progress of works: voltage control test

Preliminary voltage tests in Huéneja cluster.

Page 7: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

7 www.twenties-project.eu

Implementation Architecture

Page 8: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

8 www.twenties-project.eu

Progress of works: voltage control test

Reactive power availability test in a single WF

Page 9: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

9 www.twenties-project.eu

Progress of works: voltage control test

Preliminary voltage tests in Huéneja cluster.

To be

smoothened

Saturation

Page 10: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

10

www.twenties-project.eu

Demo 2

Introducing Virtual Power Plants as ancillary services

providers

Anders Birke, DONG Energy

Page 11: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

11

DEMO 2 DERINT (Leader: DONG)

www.twenties-project.eu

Virtual Power Plants is a new source of

flexibility to the power system

Virtual Power Plants will create services out

of controlling distributed energy resources

Power Hub is almost just

another power plant

Power Hub delivers services to

several markets just like

traditional power plants and with

the same reliability

Each distributed energy resource

(DER) serves multiple purposes

in the VPP, and can produce

several service dependent of type

of DER

Power Hub controls the DERs

under full respect for the DERs

primary purpose

Page 12: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

12

The Virtual Power Plant is extended during the project

www.twenties-project.eu

Building the VPP

In the first year of the project

focus was on building the VPP:

• Building the conceptual

solution, including the IT

solution

• Attracting and installing control

of the DERs

• Running the daily operation,

selling and producing services

by optimizing the DERs

Year 2 Year 3 Year 1

Extended functionality and size

Just before the beginning of the

second year, the VPP started

selling its services to the market.

The second year’s objectives was

to continue the development of

the VPP, by adding more

functionality to the VPP and

increase the size of the VPP.

The VPP is now able to interface

to many different types of DERs,

by using a generic driver, and

the VPP is active in more

markets.

Innovative diversified offerings

The third year’s focus will be on

demonstrating the full potential of

the VPP technology,

demonstrating new and

innovative VPP services:

• Delivering virtual inertia at the

Faroe Islands in order to

reduce the number of black

outs.

• Delivering local reactive power

control.

In addition to this more DERs will

be added, both on the consump-

tion and production side, including

integration of wind power into the

portfolio.

Page 13: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

13

Power Hub is productive and it works

The VPP responds better to grid incidents

than Dong Energy Power's portfolio

www.twenties-project.eu

When the frequency in Europe dropped 2. Sept. 2011

Power Hub helped restoring the frequency

Page 14: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

14

www.twenties-project.eu

Demo 3

Drivers of Investment in offshore network capacity

4. June 2012

Twenties General Assembly 2012

Page 15: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

15

European transfer model: how much offshore grid?

Build a model of the whole of Europe

Centre national generation

portfolios and loads on single

nodes

Show international interconnections

Add putative offshore wind sites

Carry out hour-by-hour Europe-wide

dispatch based on

nodal loads

available generation

assumed ‘merit order’

heuristic model of hydro

Compare different network cases

Onshore nodes

Offshore nodes

DEMO 3 DC GRID (Leader: RTE)

Page 16: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

16

F0 / 1.2

1 / 9

3 (1)

1.2 / 1.2

1.1 /

1.1 2 / 4

2.2 / 4.5

3.4 / 6.7

0.5 / 1.4

0.8 /

1.2

0 / 1.0

1.2 /

2.5

0.5 / 1.1

1 / 5

1 / 1.5

Onshore Nodes

Offshore Nodes

2020 Onshore Links and Interconnectors

2020 Offshore Links

2030 Proposed Interconnectors

2030 Offshore Links to New Wind Farms

A

Q

D

L

H

CM N

I

K

E

B

G

U

TO

R

P

J

V

0.6 / 1.13 (1)

2.4 / 2.4

3 (1)

1.2 / 3

3.2 /

7.2

3 (1)

0 / 0.5

0.8 / 1.30.6 / 2.8

S

0 / 1.5

European transfer model with radial connections or an H-grid?

Postulate a 2020 generation

‘background’

Assume new offshore wind (quite

far from shore) clustered around

hubs

Compare transfers between areas

and total power dispatches with

those in different structures

1. simple wind farm hub

connections to shore

2. simple WF connections plus

additional interconnectors

3. ‘H grid’

F

4.5 /

1.8

3.5 /

1.4

9 /

2.3

9 /

5.8

2 /

0.8

5.5 / 2.2

3 /

1. 5

2 / 1.6

6 /

1. 5

3.5 /

0.9

9 / 2.3

0.5 / 0.4

1 /

0.6

2 /

1

3.5 /

1.8

1.5 /

3

3.5 / 2.2

3.5 / 1.4

2 / 1.3

2 /

1.6

1 /

0.8

0.5 / 0.4

1 / 0.8

1 / 0.8

Onshore Nodes

Offshore Nodes

2020 Onshore Links and Interconnectors

2020 Offshore Links

2030 Offshore Links

8 / 3.2

A

Q

D

L

H

CM N

I

K

E

B

G

U

TO

R

P

0.6 / 0.5

S

J

V

Page 17: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

17

The need for DC breakers

Without DC breakers

fault any on the DC grid would need

to be cleared from the AC side of all

terminal

Lots of power lost

With DC fault location and DC

breakers, only the faulted branch

would be lost

Other branches can still transfer

power

What performance is required of a

DC breaker?

and what is the likely cost?

Page 18: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

18

Annual energy production in 2020

Page 19: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

19

Cost analysis

www.twenties-project.eu

€m Radial Radial + IC1 Radial + IC3 H-Grid 1 H-Grid 2

Capital Cost Differential excl.

Breakers 0 290 757 831 281

Capital Cost Differential Incl. Base

Case Breakers 0 290 757 1981 1073

Operational Cost Differential (excl.

unsupplied energy cost) 0 -700 -1235 -1128 -535

Operational Cost Differential (incl.

unsupplied energy cost) 0 -35700 -43735 -33628 -40535

Net Benefit (Cost) Breakers and Excl.

Unsupplied Energy Cost 0 -410 -478 -297 -254

Net Benefit (Cost) Breakers and Excl.

Unsupplied Energy Cost 0 -410 -478 837 522

Net Benefit (Cost) Breakers and Incl.

Unsupplied Energy Cost 0 -35410 -42978 -31663 -39478

DC breakers add

significantly to the cost

of the H-Grid

Incremental offshore capacity

in addition to the radial links

lowers operational costs

Including a

cost for

unsupplied

energy

has a

major

impact

A net benefit accrues to the H-Grid

when either DC breaker costs are

excluded or unsupplied energy

costs are included (or both)

Page 20: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

20

Preliminary findings

The benefits of increasing offshore network capacity to wind energy

production and use are clear but what form that network capacity

should take is uncertain

The cost of DC breakers will be a critical factor

Understanding the variability of flows across a meshed offshore

network is critical to optimisation

Creating the business case for offshore grids is challenging

Development of offshore wind generation and offshore network

capacity must be accompanied by measures to price carbon at an

appropriate level

DC Grid Control & Operation; Multi-terminal HVDC Grids; DC-breaker

prototype: challenges and advances

www.twenties-project.eu

Page 21: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

21

Twenties Demo 4 STORM MANAGEMENT

Nina Detlefsen, Energinet.dk (demo leader)

Page 22: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

22

Demo 4 - focus area

Storm events at Horns Rev 2

Balancing area: West Denmark

Imbalance will flow to

Germany

Regulating power can be

traded via Skagerak

DEMO 4 STORM MANAGEMENT

(LEADER: ENERGINET)

Page 23: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

23

Future offshore projects in Denmark

Total 4.6 GW

Page 24: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

24

Status for Demonstration 4

Scope

Demonstrating how

• .. a wind farm can be regulated according to the TSO or producer prior to the storm

• .. energy deficit will develop in time

• .. the energy deficit is balanced by balancing power as part of the system balance

• .. the system imbalance might be handled by hydro power from Norway

Status

New turbine controller has been developed

Controller is implemented in one turbine at HR2

Controller is expected to be installed in all turbines by August 1st, 2012

Collection of data is established

Animation/presentation of results are discussed

Page 25: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

25

Storm – no one are alike!

Page 26: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

26

Twenties Demo 5 NETFLEX (Elia)

Demo Leader: Christophe Druet (Elia)

Contact: Christophe Druet (Elia), Jacques

Warichet (Elia),Jean-Jacques Lambin (Elia),

and Olivier Bronckart (Coreso)

Page 27: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

27

DEMO 5 NETFLEX (Leader: ELIA)

www.twenties-project.eu

Page 28: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

28 www.twenties-project.eu

Page 29: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

29

www.twenties-project.eu

Demo 6

FLEXGRID:

•Real time thermal rating project

•Increasing the wind penetration level in the EU Grid by

means of power flow control

Page 30: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

30

DEMO 6 FLEXGRID (Leader: REE)

www.twenties-project.eu

Fully integration of Renevawel energies / Better exploitation of the existing facilities

IDENTIFYING LATENT

EVACUATION

CAPACITY

MANAGING THE

FLOWS GAINED

FLEXIBILITY

INCREASED

HIGHER USE

Supplier(s) Inputs/Req'ts Process Output(s)/Req'ts Customer(s)

6.2. OLC

6.1. RTTR-DTS-

OPPC

Page 31: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

31

• Task 8.1.1: Definition of Monitoring system requirements. Completed

• Benchmarking of several commercial devices.

• Selection of technology provider: • Distributed temperature sensing (Raman Effect)

• Temperature accuracy:1-3ºC

• Typical resolution:10 m

• Weather stations

• Specification and design of RTTR system

• OPPC acceptance Tests and manufacturing.

Previous Steps

www.twenties-project.eu

6 singlemode OF

G.652D

DEMO 6.1 Real time thermal Rating Project

Page 32: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

32

• Task 8.1.1: Definition of Monitoring system requirements.

• Validation of accuracy of monitoring system

• Comparison: temperature measured vs. values obtained from current algorithms (IEEE 728 std) using measured ambient conditions.

• CTAR: Dynamic rating profile updated every 10 min.

Previous Steps

www.twenties-project.eu

DEMO 6.1 Real time thermal Rating Project

CTAR

•Temperature profile and hot spots

•Average temperature in every

section and standard deviation

•Weather conditions profile:

Data

Page 33: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

33

• Task 8.1.2: Selection of location of RTTR device. Completed

• Placed at north-east of Spain

• New line 220 kV “María-Fuendetodos”: 30 km length

• 11 straight joints

• Total installed wind power: 1730 MW.

• Task 14.1: Construction of 220 kV

“María-Fuendetodos” line:

• 13th of June: OPPC stringing

• Tower construction and civil works (foundations) on time.

• Commissioning in November of 2012

Previous Steps

www.twenties-project.eu

DEMO 6.1 Real time thermal Rating Project

Page 34: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

34 www.twenties-project.eu

•Task 8.1.3: Analysis on wind

power generation

disaggregation. Completed

•27% total installed wind

power in Aragón.

•≥ 50% of CTAC (current

static seasonal ratio).

Previous Steps

DEMO 6.1 Real time thermal Rating Project

Page 35: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

35

• Task 8.1.3: Selection of weather stations location. Completed

• Solar radiation[W/m2], wind velocity [m/s], wind direction [deg.], Tamb.

• Detailed topography of the line

• Meteorological forecast: 5 years (2007-2012). State Agency of Meteorology.

• Ruggedness of the land: European environmental agency.

Previous Steps

www.twenties-project.eu

DEMO 6.1 Real time thermal Rating Project

3dn

WS 1st

WS

2th

WS 4th

WS

5th

WS

6th

WS

Main wind

direction

Page 36: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

36

• Task 8.1.3: Computation of measurements on monitored lines.

• Development of Models to Calculate the Transmission Capacity:

• 1. CTAR: Dynamic Ratio based on DTS (IEEE-728).

• 2. CTAO: Operating Transmission Capacity

• 3. PCTAO: Prediction Operating Transmission Capacity Curve (1-4 hours)

• Task 8.1.4: Correlation analysis between the thermal behavior of the line and nearby wind production capacity

On going steps

www.twenties-project.eu

DEMO 6.1 Real time thermal Rating Project

Page 37: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

37

• To increase the level of renewable penetration in transmission grid by

•extending operational limits

•maintaining safety criteria (N/N-1 conditions)

Main objective

• To define an innovative solution, the Overload Line Controller (OLC) able to limit the renewable energy curtailment by redirecting power flows

• The OLC is based on mechanically switched series reactors, managed by a high-end control system (Mach2):

•Change the impedance of the line modifies the load flow

•Step-wise control increases grid flexibility and security

Approach

Magallón SET

220 kV

Large Wind Integration

Power control

N condition

Overloading

N-1 condition

Emergency control - max compensation

-200 -180 -160 -140 -120 -100 -80 -60 -40 -20 0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 5000

1

2

3

4

5

6

7

8

9

10

11

12

X: 60

Y: 11.93

Power Flow [MW]

Bin

Cou

nt/

To

tal

Cou

nt

[%]

Histogram of Power Flow, 220-kV Magallón-Entrerríos Line, 1 year data, 1-min intervals, 20 MW bins, Feb 2011 - Feb 2012

X: 100

Y: 10.95

X: 80

Y: 11.69

X: 40

Y: 9.423

X: 20

Y: 6.672

X: 0

Y: 4.397

X: 120

Y: 9.672

X: 140

Y: 8.367

X: 160

Y: 6.46

X: 180

Y: 5.069

X: 200

Y: 4.161

X: 220

Y: 3.001

X: 240

Y: 1.945

X: 260

Y: 1.372

X: 280

Y: 0.9765

X: 300

Y: 0.5139

X: -20

Y: 1.464

X: -40

Y: 0.5427X: -80

Y: 0.181

X: -60

Y: 0.3238X: -100

Y: 0.1452X: -180

Y: 0.03519

X: -160

Y: 0.03519

X: -140

Y: 0.03035

X: -120

Y: 0.07447

X: 340

Y: 0.1152

X: 360

Y: 0.1009

X: 380

Y: 0.05958X: 420

Y: 0.02234

X: 440

Y: 0.02122

X: 460

Y: 0.004841

X: 400

Y: 0.03537X: 480

Y: 0.004841

X: 500

Y: 0.0005585

X: 320

Y: 0.2124

Page 38: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

38

Mechanical Design Mach2 Control System

Pref

Sensors &

Sotfware

Impedance

SelectionPower System

Pmeas

Xref Xset

Closed Loop Control

Impedance Controller

ON/OFFImpedance

Estimation

V

I

Hysteresis block

• Different control modes available locally and remotely

• Fast and reliable calculation of the compensation level needed given the operating conditions

• Avoid a large number of switching actions, thus increasing the OLC lifetime

Main Features

Page 39: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

39

Power Flow Control Modes

Grid Operator ModeSelection

P regulation

Closed Loop

Operator sets Preg

Pline ≈ Preg

Plimit

Closed Loop

Operator sets Plimit

Pline < Plimit

Zmode

Open Loop

Operator selects Zvalue

Zline1 =Zvalue+ Zline

Zmax

Open Loop

Operator selects maximum compensation

Emergency Mode

(Back-up)

Operator sets S emergency: seasonal ratio / defined value

If Sline> Semergency Zmax

Time response < 3sec

0 5 10 15272

274

276

278

280

282

284

286

288

290

Time [s]

S1

:Sb

ran

ch

Ma

ga

llón

-En

tre

rrio

s n

o O

LC

[M

VA

]

Plimit

OLC inserts X1

0 2 4 6 8 10 12 14 16 18 20220

230

240

250

260

270

280

Time [s]

Sb

ran

ch

Ma

ga

llón

-En

tre

rrio

s [

MV

A]

File: vargen_plots.out

X1

X4

X3

0 1 2 3 4 5 6 7 8 9 10240

260

280

300

320

340

360

380

Time [s]

S1

:Sb

ran

ch

Ma

ga

llón

-En

tre

rrio

s n

o O

LC

[M

VA

] S

2:S

bra

nch

Ma

ga

llón

-En

tre

rrio

s O

LC

[M

VA

]

Contingency without OLC

Contingency with OLC

Emergency Operation

S emergency

Page 40: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

40

www.twenties-project.eu

WP 15

Javier García González, IIT-Comillas

Page 41: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

41

Economic assessment of the provision of active power control by

wind generation (demo # 1 in Spain)

Economic assessment of the provision of voltage control by wind

generation (demo # 1 in Spain)

www.twenties-project.eu

Page 42: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

42

Perfect information case

ROM model

2020 Results:

OPEXA − OPEXB = 52.88 M€ ( ↓ 0.76% ).

• Thermal output is reduced by 0.27%

WIND OUTPUT increases, WIND SPILLAGE decreases

www.twenties-project.eu

Wind Output Comparison No Reserves Reserves Difference

Wind Output / WF 95.94 % 96.44% -0.5%

Wind Spillage / WF 4.06% 2.44% 1.62%

Wind Up Reserve / WF 0 1.11%

WFWindGeneration Spillage WindUpReserve

Page 43: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

43

Wind up reserve was slightly more penalized than hydro and thermal ones.

www.twenties-project.eu

Wind Output Comparison No Reserves Reserves Difference

HydroUpRes/ UP_REQ 60.16 % 60.16% 0 %

ThermalUpRes/ UP_REQ 39.74% 37.78% 1.96%

WindUpRes/ UP_REQ 0% 1.96% -1.96%

DeficitUp/UP_REQ

0.09% 0.09% 0%

UP_REQUIREMENTHydroUpRes ThermalUpRes WindUpReserve DeficitUp

www.twenties-project.eu

Wind Output Comparison No Reserves Reserves Difference

HydroDwRes/ DW_REQ 76.80 % 69.61% 7.19%

ThermalDwRes/ DW_REQ 23.14% 20.84% 2.30%

WindDwRes/ DW_REQ 0 9.53% -9.53%

DeficitDw/DW_REQ

0.05% 0.005% 0.045%

DW_REQUIREMENTHydroDwRes ThermalDwRes WindDwReserve DeficitDw

Page 44: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

44

Perfect information case

www.twenties-project.eu

OUTPUT No Reserves

[GWh] Reserves

[GWh] Diference

[GWh] percentage

%

THERMAL 142036 141656 380 0,27

NUCLEAR 58587 58587 0 0,00

CARBON 27862 27796 66 0,24

CCGT 55550 55254 297 0,53

GAS 36 19 17 46,58

HYDRO 27676 27676 0 0,00

WINDOUTPUT 71949 72329 -380 -0,53

ENS 0 0 0 0,00

Other RES 89339 89339 0 0,00

(DEMAND) 331000 331000 0 0,00

Page 45: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

45

Economic assessment of the provision of active power control by

wind generation (demo # 1 in Spain)

Economic assessment of the provision of voltage control by wind

generation (demo # 1 in Spain)

www.twenties-project.eu

Page 46: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

46

www.twenties-project.eu

Quantify the reduction or increase of the power losses within the

distribution network

The increase of the losses profile in HNet and in MNet depends on the

characteristics of the network evaluated

In a distribution network with a significant common infrastructure

(HNet) the optimal operation corresponds to wind farms generating

reactive power

In distribution networks with a small common infrastructure the

optimal operation of the wind farms is that they consume the

reactive power generated in their own infrastructure

For common distribution networks that allocate wind farms, the loss

reduction is not very significant.

Voltage control-Losses: Conclusions

Transmissionnetwork bus

Wind farms of other promoters

Wind farms of one promoter

Common infraestructure

132 kV400 kV

132 kV400 kV

Transmissionnetwork bus

Wind farms of other promoters

Wind farms of one promoter

Transmissionnetworkbus

Windfarmsof otherpromoters

Windfarmsof onepromoter

Transmissionnetworkbus

Windfarmsof otherpromoters

Windfarmsof onepromoter

PnetWF2 = Pgross2WF2 ( 1-fWF2 )

20 kV20 kV

20 kV20 kV

HNet

MNet

MNet

Pgross1WF2

Pgross2WF2

WF1 WF2

WF3WF4

Page 47: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

47

Voltage collapse curves

www.twenties-project.eu

Active Power

Vo

lta

ge

Vmax

VTNet

Penetration limit dueto overvoltages

Active Power

Vo

lta

ge

Vmax

VTNet

Penetration limit dueto voltage collapse

Off-peak scenario Peak scenario

(a) (b)

Wind power penetration limits

Page 48: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

48

Fuentes del Alcarria VTN = 1.00

Comparison of the voltage collapse curve

1 2 3 4 5 6 7 8 90.88

0.9

0.92

0.94

0.96

0.98

1

1.02

1.04

1.06

Scenario

Vo

lta

ge

(p

.u.)

0 2 4 6 8 10 120.9

0.92

0.94

0.96

0.98

1

1.02

1.04

1.06

Scenario

Vo

ltag

e (

p.u

.)

Without voltage control With voltage control

Wind Penetration increment

Improves up to 33%

Limit at 0.95 pu

www.twenties-project.eu

Page 49: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

49

Economic impact assessment of network flexibility tested in CWE by

Elia (demo # 5)

Economic impact assessment of network flexibility in Spain by REE

(demo # 6)

www.twenties-project.eu

Page 50: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

50

EDF participation in WP15

• Find Economic impact of demo 5

• Transit capability of existing transmission network will be enhanced:

• The result may be an increase in the NTC between neighboring countries

• The aim of the study is the assessment of the economical balance of this changes (impact on market prices) at a cross-border scale including Benelux, France and Germany

Main objective

• Cost-benefits assessment (CBA) • Benefits in terms of « Total Welfare » provided by the DLR vs costs to implement it

• Only cross-border effects assessed (no internal reinforcements benefits evaluated, only trade effects)

Approach

Page 51: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

51

• Done in a wide European perimeter

• Commercial links connect the different zones,

with monthly NTC as the maximal power that can

be transmitted

• The demo will provide a function linking

NTC and wind

• EDF will perform a comparison between 2

cases:

• Business-as-usual case without DLR

implementation by 2020

• DLR case: DLR devices are supposed to be

widely deployed on French and Belgian networks

by 2020

Cost-benefits assessment (CBA) by EDF

Page 52: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

52

81 scenarios corresponding to real experienced weather conditions: various

demands, intermittent renewable generation, generation availabilities

(contingencies), water inflows > compute monthly value of water

EDF’s market model & Elia inputs

Page 53: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

53 www.twenties-project.eu

Open question: level of granularity of the NTC profiles

Page 54: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

54

Economic impact assessment of network flexibility tested in CWE by

Elia (demo # 5)

Economic impact assessment of network flexibility in Spain by REE

(demo # 6)

www.twenties-project.eu

Page 55: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

55 www.twenties-project.eu

Analysis with PSS/E

Wind curtailment computation

Loading analysis for 2011, 2013 and 2020

Simulate possible system states (boundary

conditions) under which wind may be curtailed

For each case, compute the amount of wind

curtailment (local wind power that cannot be

evacuated due to line overloading)

How wind curtailment is reduced when line

capacity limits are increased due to:

FACTS (line reactance sensitivities)

RTTR (line capacity sensitivities)

* Wind curtailment profiles changed by FACTS and RTTR

REE expertise

Wind curtailment characterization

Critical lines’ loading 2011 Overloads

When?

N, N-1 and N-2 (maintenance)

Demand: peak/valley; summer/winter

Conventional generation

Hydro generation (dry/wet)

Power flows from other areas affecting

line loading

How often? Number of hours

How much? Energy, power

Wind curtailment profile in 2011

Wind curtailment profiles for 2013 and 2020 When? Boundary conditions identified by REE

New conditions depending on the evolution of wind capacity and network extensions within the period 2011-2020 (PSS/E)

How often? Based on the number of hours of wind curtailment in 2011

More/less hours depending on the evolution of wind capacity and network extensions within the period 2011-2020 (PSS/E)

How much? Computed with PSS/E for each situation leading to wind curtailment

After the characterization of wind spillages: system economic assessment with ROM

Page 56: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

56

Preliminary analyses for 2011 FACTS: “Installed” in the 220kV Magallón-Entrerríos line

Data:

220kV Magallón-Entrerríos line flows in 2011

Maneuvers in the 220kV Magallón substation to avoid line

overloading in 2010

PSS/E files of 2011

OLC steps

0

200

400

600

800

1000

1200

1400

60%

70%

80%

90%

100%

110%

120%

Lin

e lo

adin

g

Line loading Additional wind capacity

MW

50%

60%

70%

80%

90%

100%

110%

120%

220

kV M

agal

lón

-En

trer

río

s lo

adin

g

OLC steps and network reconfiguration

N-1 (contingency 400kV Magallón-Peñaflor) N

overload (n-1)

0

100

200

300

400

500

600

700

Max

imu

m a

dd

tio

nal

win

d c

apac

ity

(MW

)

OLC steps

N-1 (contingency 400kV Magallón-Peñaflor)

Additional wind

Page 57: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

57

www.twenties-project.eu

WP 16

Poul Sørensen, DTU Wind Energy

Page 58: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

58

WP16: EU wide assessment of demonstration replication potential

Presentation of selected results

Task force 1:

• Frequency control from wind turbines in France (EDF)

• Ancillary services from wind turbines in Germany (IWES Fh)

• Economic impact of VPPs in Germany / Spain (IWES, DTU, DONG

Energy - Comillas)

Task force 2:

• Offshore wind power scenarios (DTU)

• Hydro potential and grid constraints North (SINTEF )

• Economic impact assessment (DTU, Energinet.dk)

Task force 3:

• Questionaire to ENTSO-E (REE, Elia - Comillas)

www.twenties-project.eu

Page 59: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

59

Upscaling of demo 1 to France

1

•Demand•Intermittent power sources:- Wind- Photovoltaic- Run-of-river hydro

UncertaintiesPlants availabilityAnd maintenance schedule

Balancing of supply and demand:- power generation- frequency control reserves

Costs CO2 emissions

Power generation plan covering 1 year

Unit commitment model : OPUS

OPUSObjective : Minimization of production costs taking into account plants’ dynamic constraints

INPUTS

OUTPUTS

Power Generation CapacityPower plants :• Nuclear• Coal• CCGT• Hydro

Storage Units :- Hydro

Economic framework(Fuel Costs, CO2)

490 scenarii

Page 60: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

60

First results : Power of frequency control provided by wind power

0

50

100

150

200

250

0

100

200

300

400

500

600

700

800

900

1000

1

22

4

3

64

8

5

10

6

12

7

14

8

16

9

19

0

211

2

32

2

53

2

74

2

95

3

16

3

37

3

58

3

79

4

00

4

21

4

42

4

63

4

84

Ho

urs

of

fre

qu

en

cy c

on

tro

l p

rovid

ed

by

win

d p

ow

er

Ave

rag

e f

req

ue

nc

y c

on

tro

l p

ow

er

pro

vid

ed

b

y w

ind

po

we

r (M

W)

Scenarii

Average frequency control power provided by wind power (MW)

Hours of frequency control

Page 61: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

61

Task force 1 in Germany

www.twenties-project.eu

Ancillary Services from Wind Turbines

1

Economic Impact of Control Reserve Provision

Results for negative secondary reserve bids

95 % 99 % 99.9 % 99.99 %

x 107

Security Level

Co

stR

ed

uctio

n[€

]

0

2

4

6

8

10

12

1 HOUR

4 HOURS

24 HOURS

Cost reductions at 99.99 % confidence interval of the offer• Maximum on secondary reserve markets: 24 % (≈45 Mio. €)• Maximum on minute reserve markets: 21 %

Probabilistic forecast

Offer control reserve

Bid on german control reservemarkets (day-ahead)

Economic Impact

Page 62: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

62

Results for negative secondary reserve bids

www.twenties-project.eu

95 % 99 % 99.9 % 99.99 %

x 107

Security Level

0

2

4

6

8

10

12

1 HOUR

4 HOURS

24 HOURS

Cost R

ed

uctio

n [€

]

Bit length:

Page 63: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

63

Economic impact of VPPs in Germany / Spain

Comillas model of

VPP

Impact assessment in

Germany using

Wilmar

Impact assessment in

Spain using ROM

www.twenties-project.eu

Unit u Unit u Dayahead

market

Reserve

market

e uh

iuh

ouh

guh cu

h

S ingle Bus

Page 64: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

64

10 W 0 10 E

20 E 30 E

45 N

50 N

60 N

65 N

70 N

Task force 2+: Offshore wind power scenarios

www.twenties-project.eu

Country MW installed end 2020

MW installed end 2030

Baseline High Baseline High

Belgium 2,156 2,156 3,956 3,956

Denmark 2,811 3,211 4,611 5,811

Estonia 0 0 1,695 1,695

Finland 846 1,446 3,833 4,933

France 3,275 3,935 5,650 7,035

Germany 8,805 12,999 24,063 31,702

Ireland 1,155 2,119 3,480 4,219

Latvia 0 0 1,100 1,100

Lithuania 0 0 1,000 1,000

Netherlands 5,298 6,298 13,294 16,794

Norway 415 1,020 3,215 5,540

Poland 500 500 500 500

Russia 0 0 500 500

Sweden 1,699 3,129 6,865 8,215

UK 13,711 19,381 39,901 48,071

TOTAL 40,671 56,194 113,663 141,071

Page 65: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

65 www.twenties-project.eu

Aggregated wind farm model – original storm controller

wind turbine model aggregated wind farm model

Page 66: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

66

Task force 2+: Hydro Power Potential

Plant Most likely (MW) Optimistic (MW)

Pump Storage Plant Tonstad 1400 1400

Pump Storage Plant Holen 700 1000

Pump Storage Plant Kvilldal 1400 2400

Power Plant Jøsenfjord 1400 2400

Pump Storage Plant Tinnsjø 1000 2000

Pump Storage Plant Tinnsjø 1400 2400

Power Plant Lysebotn 400 1800

Power Plant Mauranger - 400

Power Plant Oksla 700 700

Pump Storage Plant Tysso 700 1000

Power Plant Sy-Sima 700 1000

Power Plant Aurland 700 700

Power Plant Tyin 700 1000

Amount of new power

capacity 11200 18200

www.twenties-project.eu EWEA 2012 Annual Event

Page 67: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

67 www.twenties-project.eu EWEA 2012 Annual Event

Tyin

Holen

Tonstad

Hol

Jøsenf jorden

Tinnsjø

Nore

Mauranger/Oksla/Tysso

Kvilldal

Lysebotn

Sima

Aurland

Grid Implications of Hydro Power Flexibility in Norway (WP16.2.3: Grid Implications)

Page 68: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

68 www.twenties-project.eu EWEA 2012 Annual Event

Offshore grid topologies

radial meshed

Page 69: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

69

Task force 2+: Economic impact assessment

Tasks

Compare socio-economics of North European offshore wind power with

• original and new wind turbine storm controls

• 2020 and 2030 – baseline and high wind cases

• 2020 and 2030 hydro potential

Tools

WILMAR for Europe – to simulate the power system commitment and

dispatch with 1 h time steps

CorWind – to simulate wind power variability

+ Simba for Denmark – Energinet.dk tool simulating the operation within the

hour with 5 min time steps

Outputs (expected)

Energy cost / emission savings due to new storm control

Reserve requirements in Denmark with old and new controls www.twenties-project.eu

Page 70: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

70

Upscaling of task force 3

Upscaling in Spain in WP15 (Comillas)

Questionaire to ENTSO-E (REE, Elia - Comillas)

Contact to EDF re. WP15.7 (Economic impact of demo 5 in CORESO)

www.twenties-project.eu

Page 71: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

71

www.twenties-project.eu

WP 17

Optimising planning and permitting

for Offshore Interconnectors

Jos Spits.TenneT TSO

Page 72: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

72

Optimising planning and permitting for Offshore Interconnectors

Recent offshore interconnector projects

Barriers for offshore interconnectors

Objectives WP17

Method WP17

Preliminary findings and conclusions WP17

Results WP17

www.twenties-project.eu

Page 73: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

73

Recent offshore interconnectors projects

North Sea and Baltic Sea

1. Shore to shore interconnectors

2. Farm to shore connectors

3. Combined solutions (e.g. COBRAcable)

WP17 -Virtual projectcase TRIFFID

Three-leg interconnector NL-DE-DK

Wind tee-in

www.twenties-project.eu

Page 74: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

74

Barriers for offshore interconnectors Risk factors for planning and permitting of interconnectors seem:

Timeline overruns…

No timely consent from all authorities

Transnational coordination is lacking

Research scope is unsettled

Budget overruns…

Route length increases when detouring restricted areas

Additional surveys

Internal projectmanagement…

Dedicated project teams (highly complex projects)

Involvement of management

Page 75: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

75

Objectives WP17

Optimising the planning and permitting for offshore interconnectors

Goal = Strengthening predictability of consenting and making processes leaner

Improving efficiency of projects: 20% reduction in cost and time

Interconnectors projects applying best practices will have a 20% reduction of costs and

time for planning and permitting

Improving effectiveness of projects: 30% of permits improved

Best practices are targeting 30% of the number of permits and consents for new

licensing of interconnectors.

Page 76: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

76

Method WP17

Three result areas:

1. Analysis of recent European practices for spatial planning and permitting for

offshore interconnectors (D.1)

2. Case study on three-legged offshore interconnector TRIFFID with possible wind tee-

in (D.2)

3. Best practice recommendations for spatial planning and permitting (D.2)

Research components:

A. Public acceptance / stakeholder management

B. Test case interconnector with multiple landing points and linking up wind farms

C. Regulatory issues / market models

D. Review on European consenting studies

www.twenties-project.eu

Page 77: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

77

WP17 - Virtual projectcase TRIFFID

www.twenties-project.eu

Virtual Triffid case based on COBRAcable interconnector between the Netherlands and

Denmark, and Sylwin 1 connector to offshore wind farm in German waters

Simulating: Planning and permitting

Regulation and business

case

Market models and

operations

Page 78: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

78

Preliminary findings and conclusions WP17 (1)

1. Coordinating overall cable route evaluation

Transnational cable routes are subject to partial evaluation of route sections at fairly

local level.

WP17 recommends that cooperation agreements with and between national planning

authorities are entered to facilitate overall and holistic evaluation of cable route

design.

Mediation with competing sea users,

primarily nature conservation, shipping

interest and other infrastructures

Page 79: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

79

Preliminary findings and conclusions WP17 (2)

2. The EIA is a transnational reference

The Environmental Impact Assessment is applied by all planning authorities and may

serve as a common skeleton.

WP17 recommends that a common road map for EIA studies is applied with shared

practices for scoping of studies and documentation.

Note that impacts from cable installation and operation seem fairly limited. Up to date

cable installation disturbs less than a meter band in the seabed.

Page 80: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

80

Preliminary findings and conclusions WP17 (3)

3. Best available technology as reference

The cable technologies and impacts are very similar from the one project to the other.

In practice there is a lot of repetitive work when preparing documentation for

planning consents.

WP17 recommends that best available technologies are nominated by a transnational

body.

Flow chart of interconnector planning and

implementation

Page 81: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

81

Preliminary findings and conclusions WP17 (4)

4. Benefits of interconnectors are to be recognised against competing

interests

The socio-economic justification of interconnectors is weak when balancing with

Natura2000 sites, shipping and other sea uses.

WP17 recommends that interconnectors need to be recognized as vital infrastructure

for renewable electricity.

Matrix of statutory and other

stakeholders

Page 82: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

82

Preliminary findings and conclusions WP17 (5)

5. Early screening of route design is preferable

Maritime spatial plans with corridors and gates for preferential use may partly serve

as tool for cable routing.

WP17 recommends that, next to master plan for offshore grids, also tools for

mediating and possibly acceptance of routes in restricted zones are necessary

(co-existence with other sea uses).

Page 83: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

83

Results WP17

Towards a new (regional) planning and permitting concept

Public affairs

Planning and permitting

Regulatory issues

Deliverables

Thematic guidelines / good practice cases on subsea cable development and

consenting

Test case interconnector project TRIFFID with multiple landing points and wind farm

link-up as prelude for an offshore grid.

www.twenties-project.eu

Page 84: TWENTIES PROJECT Some preliminary results: summary …...•New line 220 kV “María-Fuendetodos”: 30 km length •11 straight joints •Total installed wind power: 1730 MW. •Task

www.twenties-project.eu