TU BU trung the

Embed Size (px)

Citation preview

  • 7/28/2019 TU BU trung the

    1/6

    HCMC. PC SPECIFICATION

    MEDIUM VOLTAGE POWER CAPACITOR 200KVAR

    I. SCOPE :This specification should be applicable to outdoor medium voltage powercapacitor intended for power factor correction of medium alternatingvoltage power system.

    II. STANDARD OF MANUFACTURE AND TEST :IEC 871 : Shunt power capacitors for AC systems having a rated voltage

    above 660 V.

    III.DESCRIPTION :

    A. SERVICE CONDITIONS :

    The capacitor shall be designed and fabricated, suitable for outdoor

    service in Ho Chi Minh City, Vietnam under the following conditions:- Altitude : Up to 40m above sea level- Ambient air temperature :

    + Maximum : 55C+ Highest mean over any period of 24 hours : 45C+ Highest mean over any period of 01 year : 35C

    - Maximum relative humidity : 95%- Climate : Tropical, salty atmosphere, industrial contamination.- Solar radiation : 1000W/m2

    - Maximum wind velocity : 30m/s- Lightning stroke expectancy : 120 thunderstorm days per year.

    B. CONSTRUCTION :

    - The medium voltage power capacitor shall be single phase unit.- Type of service : outdoor.- Rated voltage (Un) : 8.66 KV.- Rated current (In) : 23A.- Rated frequency : 50 Hz.- Rated capacity : 200 KVAR- Maximum permissible voltage :

    + 12hours in every 24 hours : 110 % Un+ 30 min. in every 24 hours : 115 % Un+ 05 min. in every 24 hours : 120 % Un+ 01 min. in every 24 hours : 130 % Un

    - Maximum permissible current :+ Continuous operation : 130 % In+ Maximum current : 150 % In

    - Maximum permissible capacity : 135 % of rated capacity.- Tolerance of capacitance : - 5 % to + 10 % of rated value.- Dielectric :

    + Material : All film+ Impregnation : Non-PCB, Faradol 600 or Jarylic

    - Total power losses : 0.1 W/kvar./var/www/apps/conversion/tmp/scratch_2/138239072.doc 1/6

  • 7/28/2019 TU BU trung the

    2/6

    HCMC. PC SPECIFICATION

    MEDIUM VOLTAGE POWER CAPACITOR 200KVAR

    - Power frequency withstand voltage :+ Dry test for 1 minute : 60KV+ Wet test for 10 seconds : 50KV

    - Lightning impulse (1.2/50s) withstand voltage : 125 kV.- Build-in discharge resistor : Reduces terminal voltage to 50VAC or less

    from initial peak voltage of 2 times rated voltage within 5 minutesafter disconnection of unit.

    - Number of bushing : 02- Creepage distance : 25mm/KV

    - Insulation resistance between terminal and container : 1000 M.- Terminals : tin-plate parallel groove type for copper conductor range

    from 10-50mm2- Tank : Stainless steel

    Safety, not-rupture even fault situation is required

    -Life expectancy for 5% failure : 50 years.

    - Accessories :+ Studs, connectors and earth bars or conductors shall be provided to

    permit the connection of all metal works and electrical equipment toearth.

    + 02 bird caps.

    IV. TESTING REQUIREMENT :

    1. Testing items :

    a. Routine tests :- Capacitance measurement.

    - Capacitor loss tangent (tan) measurement.- Voltage test between terminals.- AC voltage test between terminals and container.- Test of terminal discharge device.- Sealing test.

    b. Type tests :- Thermal stability test.

    -Capacitor loss tangent (tan) measurement at elevated temperature.

    - AC voltage test between terminals and container.- Lightning impulse voltage test between terminals and container.- Short circuit discharge test

    2. Requirements :

    In order to ensure the quality of supplied goods , in case of bid winning ,the Tenderer shall supply routine test and copies of type test report metthe following requirements:

    a. Routine test shall be performed for each equipment.

    b. Type test report shall meet the followings :/var/www/apps/conversion/tmp/scratch_2/138239072.doc 2/6

  • 7/28/2019 TU BU trung the

    3/6

    HCMC. PC SPECIFICATION

    MEDIUM VOLTAGE POWER CAPACITOR 200KVAR

    - Testing sample : The same as the supplied item (manufacturer,original country, manufactures code as specified in tender document).

    - Testing items : Including testing items according to IEC 871.- Testing values shall be corresponding values as stated in Section III

    of this specification. If in section III, there are no corresponding values,testing values will be selected according to the standard specified insection II of this specification.

    V. REQUIREMENT OF TECHNICAL TENDER DOCUMENT :

    - Technical description, data sheets, catalogues and other materialsubmitted with the quotation must enable the buyer's engineers tothoroughly evaluate the proposals as to its compliance with the inquiryspecifications.

    - Minimum requirements :+ Detailed summary of deviations to inquiry specification.+ Completed inquiry data sheet expressed at clause VI.+ Type test report met the requirements as specified section IV.+ Brochures and catalogues containing outline dimensions, main

    electrical dataand installation details.+ Certificate of quality management.

    VI. DATA SHEET :

    No SPECIFICATION UNIT REQUIREMENT TENDER

    1. Item No.2. Manufacturer3. Country4. Manufacturers code5. Standards of factory and

    testIEC 871

    6. Standards of quality

    management7. Member approve ofcertificate ofmanagement

    8. In case of bid winning ,the Tenderer shallsupply routine test andcopies of type testreport met therequirements of sectionIV .

    Yes

    A. SERVICECONDITIONS

    9. The capacitor shall be/var/www/apps/conversion/tmp/scratch_2/138239072.doc 3/6

  • 7/28/2019 TU BU trung the

    4/6

    HCMC. PC SPECIFICATION

    MEDIUM VOLTAGE POWER CAPACITOR 200KVAR

    designed and fabricated,suitable for outdoorservice in Ho Chi MinhCity, Vietnam under thefollowing conditions:

    10. Altitude Up to 40m above sealevel

    11. Ambient air temperature:+ Maximum+ Highest mean overany period of 24 hours+ Highest mean overany period of 01 year

    CC

    C

    5545

    35

    12. Maximum relativehumidity

    % 95

    13. Climate

    14. Solar radiation W/m2 100015. Maximum wind velocity : m/s 3016. Lightning stroke

    expectancy :120 thunderstorm

    days per year.

    B. CONSTRUCTION :

    17. The medium voltagepower capacitor shall besingle phase unit.

    Yes

    18. Type of service Outdoor19. Rated voltage (Un) KV 8.6620. Rated current (In) A 2321. Rated frequency Hz 5022. Rated capacity KVAR 20023. Maximum permissible

    voltage ::

    + 12hours in every 24hours: 110 % Un

    + 30 min. in every 24hours: 115 % Un

    + 05 min. in every 24hours: 120 % Un

    + 01 min. in every 24hours: 130 % Un

    110% Un

    115% Un120% Un130% Un

    /var/www/apps/conversion/tmp/scratch_2/138239072.doc 4/6

  • 7/28/2019 TU BU trung the

    5/6

    HCMC. PC SPECIFICATION

    MEDIUM VOLTAGE POWER CAPACITOR 200KVAR

    24. Maximum permissiblecurrent :+ Continuous operation+ Maximum current

    130 % In150 % In

    25. Maximum permissiblecapacity

    135 % of ratedcapacity

    26. Tolerance of capacitance

    - 5 % to + 10 % ofrated value.

    27. Dielectric :+ Material+ Impregnation

    All filmNon-PCB, Faradol

    600 or Jarylic28. Total power losses W/kvar

    . 0.1

    29. Power frequencywithstand voltage :+ Dry test for 1 minute+ Wet test for 10seconds

    KVKV

    6050

    30. Lightning impulse

    (1.2/50s) withstandvoltage

    KV 125

    31. Build-in dischargeresistor

    Reduces terminalvoltage to 50VAC

    or less from initialpeak voltage of2times rated

    voltage within5 minutes afterdisconnection of

    unit32. Number of bushing 0233. Creepage distance mm/K

    V25

    34. Insulation resistance

    between terminal andcontainer

    M. 1000

    35. Terminals Tin-plate parallelgroove type for

    copper conductorrange from 10-

    50mm236. Tank Stainless steel37. Safety, not-rupture even

    fault situation is requiredYes

    38. Life expectancy for 5%failure 50 years

    39. Accessories :

    /var/www/apps/conversion/tmp/scratch_2/138239072.doc 5/6

  • 7/28/2019 TU BU trung the

    6/6

    HCMC. PC SPECIFICATION

    MEDIUM VOLTAGE POWER CAPACITOR 200KVAR

    + Studs, connectors andearth bars or conductorsshall be provided topermit the connection ofall metal works andelectrical equipment toearth.+ 02 bird caps.

    Yes

    Yes