CO2/T../S Series Space Sensors Installation Instructions TG201171 Issue 2, 10/10/2011 1 Installation Instructions CO2/T/../S Space CO2, Humidity and Temperature Sensors Important: Retain these instructions 1 Dimensions 2 Requirements 1 UNPACKING 3 INSTALLATION CO2/T/../S Installation Instructions TG201171 HO 2 -20 °C -4 °F +60 °C +140 °F 0 %RH 95 %RH 2 STORING It is recommended that the installation should comply with the HSE Memorandum of Guidance on Electricity at Work Regulations 1989. For USA, install equipment in accordance with National Electric Code. 86 mm (3.39”) 86 mm (3.39”) 26 mm (1.02”) a b c > 50 cm (20”) 1.5 m (5 ft) e d f g Display option

Trend CO2/T/../S Space CO2, Humidity and Temperature ... · 4 CO2/T../S Series Space Sensors Installation Instructions TG201171 Issue 2, 10/10/2011 CO2/T/../S Installation Instructions

  • Upload
    others

  • View
    12

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Trend CO2/T/../S Space CO2, Humidity and Temperature ... · 4 CO2/T../S Series Space Sensors Installation Instructions TG201171 Issue 2, 10/10/2011 CO2/T/../S Installation Instructions

CO2/T../S Series Space Sensors Installation Instructions TG201171 Issue 2, 10/10/2011 1

Installation InstructionsCO2/T/../S

Space CO2, Humidity and Temperature Sensors

Important: Retain these instructions

1 Dimensions

2 Requirements

1 UnpaCkIng

3 InSTallaTIOn

CO2/T/../S Installation Instructions TG201171

H O2

-20 °C-4 °F

+60 °C+140 °F

0 %RH 95 %RH2 STORIng

It is recommended that the installation should comply with the HSE Memorandum of Guidance on Electricity at Work Regulations 1989.For USA, install equipment in accordance with National Electric Code.

86 m

m (3

.39”

)

86 mm (3.39”) 26 mm (1.02”)a

b c> 50 cm (20”)

1.5 m(5 ft)

ed

fg

Display option

Page 2: Trend CO2/T/../S Space CO2, Humidity and Temperature ... · 4 CO2/T../S Series Space Sensors Installation Instructions TG201171 Issue 2, 10/10/2011 CO2/T/../S Installation Instructions

2 CO2/T../S Series Space Sensors Installation Instructions TG201171 Issue 2, 10/10/2011

CO2/T/../S Installation Instructions

2 Requirements (continued)

3 Remove backplate 4 Mount backplate

5 Remove cutout(s) 6 Route cable(s) 7 Remove foil

3 InSTallaTIOn (continued)

i

H O2

-20 °C(-4 °F)

+60 °C(+140 °F)

0 %RH 100 %RH non -condensing

h

0 °C(32 °F)

+40 °C measurement (104 °F)

lk

a b back box (BESA)

wallwall box 60 mm (2.36”)

35 mm (1.38”)

35 mm (1.38”)

FR

ABS

35 mm (1.38”)

35 mm (1.38”)

as required

Do not use this hole

Page 3: Trend CO2/T/../S Space CO2, Humidity and Temperature ... · 4 CO2/T../S Series Space Sensors Installation Instructions TG201171 Issue 2, 10/10/2011 CO2/T/../S Installation Instructions

CO2/T../S Series Space Sensors Installation Instructions TG201171 Issue 2, 10/10/2011 3

Installation Instructions CO2/T/../S

9 assemble unit 10 Configure IQ

8 Wire to Controller

24 V Supply

24 V Supply

3 InSTallaTIOn (continued)

IQ1xx/2xx

IQ3

3 analogue input channels linked for Voltage (V), ensure correct polarity

3 analogue input channels linked for Voltage (V), ensure correct polarity

GNDCO2

INGND

TH

IN

IN

+24 Vac/dc0 VCO2/T/./H/S

CO2/T/./H/S

0 (0V)

+ (+24V)N+2 (in)

TH

0 (0V)N (in)+ (+24V)

0 (0V)

+ (+24V)N+1 (in)

GNDCO2GND

+24 Vac/dc0 V

}}}

CO2

CO2

Temp.

Temp.

*Hum.

*Hum.

The 24 Vac/dc supply should be dedicated, isolated, and greater than 650 mA.

*The humidity output is only available on CO2/T/H/DISP/S and CO2/T/H/S.

backplate

‘click’

IQ Configuration Manual 90-1533IQ3 Configuration Manual TE200768

IQ

IQ

or

Page 4: Trend CO2/T/../S Space CO2, Humidity and Temperature ... · 4 CO2/T../S Series Space Sensors Installation Instructions TG201171 Issue 2, 10/10/2011 CO2/T/../S Installation Instructions

4 CO2/T../S Series Space Sensors Installation Instructions TG201171 Issue 2, 10/10/2011

CO2/T/../S Installation Instructions

Please send any comments about this or any other Trend technical publication to [email protected]

© 2011 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative..

Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.

Trend Control Systems limitedAlbery House, Springfield Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.comTrend Control System USa6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel:(425) 869-3900 Fax:(425) 869-8445 www.trend-americas.com

11 Set up IQ Sensor Types

10 Test System

5 DISpOSal4 MaInTenanCe

Temperature0 to 10 V for 0 to +40 °C (32 to 104 °F)

CO2 concentration0 to 10 V for 0 to 2000 ppm

Humidity (/H/ option only)0 to 10 V for 0 to 100 %RHMeasurement range 0 to 95 %RH

It is recommended to use SET (software tool) for the setting of sensor type modules. For all IQ2 series controllers with firmware version 2.1 or greater, or IQ3 series controllers, the following SET Unique Sensor References should be used: CO2 V (ppm) Humidity V (%RH) - /H/ option only Temp V 0+40 (°C) Temp V +32+104 F (°F)Alternatively set scaling mode to 5 (characterise), and enter scaling manually as defined in the appropriate tables below. Note that for IQ3, scaling mode and exponent do not need to be set up.For all other IQ controllers see Sensor Scaling Reference Card TB100521A.

3 InSTallaTIOn (continued)

Units °C °FY Input type 0 (volts)E Exponent 3U Upper 40 104L Lower 0 32P Points 2x Ix Ox1 0 0 322 10 40 104

Units ppmY Input type 0 (volts)E Exponent 4U Upper 2000L Lower 0P Points 2x Ix Ox1 0 02 10 2000

Units %RHY Input type 0 (volts)E Exponent 3U Upper 100L Lower 0P Points 2x Ix Ox1 0 02 10 100

IQ� � ∆ T

Temperature CO2 Concentration, Humidity (/H/ option only)

∆ CO2∆ H

Check display if DISP option fitted

Weee Directive :At the end of their useful life the packaging and product should be disposed of by a suitable recycling centre.Do not dispose of with normal household waste. Do not burn.

Over time, the sensing element may become covered in dust. The dust can be removed using compressed air. Under no circumstances should water or cleansing agents be used on the sensing elements.