Click here to load reader
Upload
xing-xu
View
220
Download
5
Embed Size (px)
Citation preview
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 4 ( 2 0 1 1 ) 1 9 2 2e1 9 3 3
www. i ifi i r .org
ava i lab le at www.sc iencedi rec t .com
journa l homepage : www.e lsev ier . com/ loca te / i j re f r ig
Transient and steady-state experimental investigation offlash tank vapor injection heat pump cycle control strategy
Xing Xu, Yunho Hwang*, Reinhard Radermacher
Center for Environmental Energy Engineering, University of Maryland, College Park, 3163 Glenn L. Martin Hall Bldg., MD 20742, USA
a r t i c l e i n f o
Article history:
Received 28 February 2011
Received in revised form
18 July 2011
Accepted 11 August 2011
Available online 17 August 2011
Keywords:
Tank
Injection
Transient state
Steady state
Control
* Corresponding author. Tel.: þ1 301 405 524E-mail address: [email protected] (Y. H
0140-7007/$ e see front matter ª 2011 Elsevdoi:10.1016/j.ijrefrig.2011.08.003
a b s t r a c t
Recent research on vapor injection technique has been mostly focused on performance
improvement using different system configurations. The flash tank cycle typically shows
better performance than the internal heat exchanger cycle. However, the flash tank cycle
control strategy is not yet clearly defined. In this study, a novel cycle control strategy is
proposed for an R-410A vapor injection flash tank heat pump system and its feasibility was
experimentally investigated. The proposed novel cycle control strategy utilized an elec-
tronic expansion valve (EEV) for the upper-stage expansion and a thermostatic expansion
valve for the lower-stage expansion, and applied an electric heater in the vapor injection
line to introduce superheat to the injected vapor by providing a control signal to the upper-
stage EEV. Both transient and steady-state system behaviors were studied. The proposed
cycle control strategy was found to be able to provide reliable control to the system.
ª 2011 Elsevier Ltd and IIR. All rights reserved.
Etude experimentale en regime transitoire et permanent de lastrategie de regulation appliquee a un cycle a pompe a chaleuravec injection de vapeur du reservoir intermediaire
Mots cles : reservoir ; injection ; regime transitoire ; regime permanent ; regulation
1. Introduction
As the scroll compressor has been widely used in the air
conditioning/heat pumping industry, there have been
numerous research projects focused on applying vapor
injection technology in air conditioning/heat pumping
systems. It’s already known that there are two typical cycles
for vapor injection: the internal heat exchanger cycle and the
7.wang).ier Ltd and IIR. All rights
flash tank cycle, as shown in Figs. 1 and 2, respectively. The
wide injection ratio range of the internal heat exchanger cycle
is more favorable, because the injected vapor superheat could
be easily adjusted by the upper-stage expansion valve.
However, the performance of the internal heat exchange cycle
is lower than that of the flash tank cycle (Wang, 2008; Ma and
Zhao, 2008). This is due to the fact that the pressure drop
across the internal heat exchanger yields a reduced injection
reserved.
Nomenclature
COP coefficient of performance
EEV electronic expansion valve
h refrigerant enthalpy, kJ kg�1
_m mass flow rate, kg s�1
Ptotal total power consumption
PID proportional integral derivative
Q Cooling and heating capacity
RPM revolution per minute
TXV thermostatic expansion valve
Subscripts
air air side
in inlet condition
out outlet condition
ref refrigerant side
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 4 ( 2 0 1 1 ) 1 9 2 2e1 9 3 3 1923
pressure, which results in a reduced injection ratio. Moreover,
the cost of the flash tank is expected to be less than that of an
internal heat exchanger. Therefore, the flash tank cycle has
received more attention in recent years.
The research of flash tank cycle falls into two categories:
system level research and component level research (Xu et al.,
2011). The system level research is mostly focused on inves-
tigating the potential improvement under extreme weather
conditions by applying vapor injection technology. In low
temperature heating scenarios, Wang (2008) tested the flash
tank cycle at �18 �C and found the maximum capacity and
coefficient of performance (COP) improvements to be 33% and
23%, respectively. Bertsch and Groll (2008) tested a two-stage
heat pump system at very low ambient temperature of
�30 �C. The heating COP was found to be 2.1. For heat pump
water heating, Fan et al. (2008) tested a heat pump prototype
at the ambient temperature as low as �30 �C. The hot water
temperature was found to be between 55 �C and 60 �C. Choet al. (2009) studied a two-stage CO2 vapor injection cycle for
the cooling mode. The cooling COP of such cycle was
improved by 16.5% compared with that of the two-stage non-
injection cycle. In high ambient temperatures, Wang (2008)
also tested the flash tank cycle at 46 �C and found the COP
and capacity improvement to be 2% and 15%, respectively.
Research has also been conducted on components of the flash
tank cycle in order to optimize the overall system perfor-
mance. Examples include research on the different types of
compressors (Park et al., 2002; Liu et al., 2008), injection port
location (Wang et al., 2009a), injection pressure (Wang et al.,
2009a), and injection ratio (Winandy and Lebrun, 2002; Wang
et al., 2009b).
Despite the large amount of research efforts on the flash
tank cycle, few open publications exist regarding flash tank
control strategy. In the internal heat exchanger cycle, the
Condenser
Evaporator
Vapor-injected
CompressorInternal heat
exchanger
Upper-stage
expansion
valve
Lower-stage
expansion
valve
Fig. 1 e Internal heat exchanger vapor injection cycle.
upper-stage expansion valve can be controlled by the degree
of superheat in the internal heat exchanger outlet. However,
in the flash tank cycle, the injected vapor is in a saturated
state, therefore a conventional thermostatic expansion valve
(TXV) would not function properly. Moreover, the control of
the liquid level in the flash tank is critical to the reliability of
the system. The liquid level should be controlled in a manner
such that only vapor refrigerant is injected to the compressor.
Xu et al. (2010) provided detailed analysis of the flash tank
cycle control strategy, yet more experimental data is needed
to validate the proposed approach of using a TXV for the
upper-stage expansion valve control. Jang et al. (2010) pre-
sented the method of using the flash tank inlet and outlet
mass balance in order to estimate the liquid level in the flash
tank. However, it’s not clear whether additional sensors, such
as mass flow meters, are needed to accurately measure the
refrigerant mass flow rate. Consequently, the development of
an effective flash tank cycle control strategy is essential to the
industrial application of the flash tank cycle.
The purpose of the current research is to experimentally
investigate the control strategy of the flash tank cycle for both
transient and steady-state operations. In addition, the liquid
level variations under different operation conditions have
been studied.
2. Experimental setup
2.1. Test facility and instrumentation
Fig. 3 shows the schematic of the test facility of a vapor
injection cycle, with a flash tank using R-410A as the refrig-
erant. It is comprised of a closed air loop and units located in
the environmental chamber. In the closed air loop, the air is
Condenser
Evaporator
Vapor-injected
CompressorFlash
tank
Upper-stage
expansion
valve
Lower-stage
expansion
valve
Fig. 2 e Flash tank vapor injection cycle.
P
P
T
T
P T
R.H.
R.H.
R.H.
Air Handing Unit
Air Flow
Nozzle
HumidifierIndoor Unit
Humidity sensor
9-thermocouple grid
Expansion valve
Check valve
Pressure transducer
Temperature transducer
Three way valve Mass f low rate meter
P T
P T
P T
P T
P TOutdoor coil
Outdoor unit
CLOSED AIR LOOP
ENVIRONMENTAL CHAMBER
Flash tank
Shut-of f valve
P T
1
2
3
4
Four way valve Sight glass
Compressor
Fig. 3 e Schematic of the test facility for a vapor injection flash tank cycle.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 4 ( 2 0 1 1 ) 1 9 2 2e1 9 3 31924
driven by the blower of the air handling unit. The air flows
through the nozzle, which measures the air volume flow rate,
and then enters the indoor unit. Within the inlet and outlet of
the indoor unit, two 9-thermocouple grids measure the
temperatures of the inlet and outlet air, respectively. Relative
humidity sensors were installed to measure the relative
humidity of the inlet and outlet air, respectively. An outdoor
unit is located in the environmental chamber. Thermocouples
and dew point sensors were installed to measure the air side
inlet and outlet temperatures and dew points, respectively. In
the cooling mode, the refrigerant leaves the compressor,
entering the outdoor unit for condensing. After the upper-
stage expansion valve (Bertsch and Groll, 2008), the refrig-
erant enters the flash tank; the vapor refrigerant is injected to
the compressor, while the liquid refrigerant enters the lower-
stage expansion valve (Fan et al., 2008), and circulates through
the indoor unit. After evaporating at the indoor unit, the
refrigerant then enters the suction port of the compressor to
complete the cycle. In the heating mode, the refrigerant
leaving the compressor circulates through the indoor unit for
condensing; then it is expanded through the upper-stage
expansion valve (Bertsch and Groll, 2008), and enters the
flash tank. The vapor refrigerant is injected to the compressor;
meanwhile the liquid refrigerant circulates through the lower-
stage expansion valve (Cho et al., 2009), evaporates in the
outdoor coil, and then enters the compressor to complete the
cycle. Pressure transducers and in-stream thermocouples
were installed in the system to measure the refrigerant-side
pressures and temperatures, respectively. Mass flow meters
were installed tomeasure the refrigerantmass flow rate of the
injected vapor and through the condenser. A watt meter was
installed to measure the compressor and outdoor power
consumption.
The compressor used in the experimental study is
a vapor-injected scroll compressor. It has a constant speed of
3500 RPMwith a displacement of 29.5 cm3. The specifications
of the outdoor and indoor heat exchangers are shown in
Table 1. It should be noted that the upper-stage expansion
valve (Bertsch and Groll, 2008) used in the system is an
electronic expansion valve (EEV) that has 500 steps. The
lower-stage expansion valves (Cho et al., 2009) and (Fan et al.,
2008), used in the system, are TXVs with a nominal capacity
of 14e21 kW. The vapor injection control valve (ANSI/
ASHRAE Standard 116-1995) is a manually operated meter-
ing valve. In the vapor injection test, this valve is fully
opened to allow vapor refrigerant to be injected to the
compressor.
Fig. 4 shows the flash tank used in the test. The two-phase
refrigerant enters the flash tank in themiddle part of the tank,
and is then separated into liquid and vapor phases. Liquid
refrigerant exits the flash tank from the port located at the
bottom, and vapor refrigerant leaves the flash tank from the
port at the top. A sight glass was installed in the flash tank to
monitor the liquid level, as well as to visualize the liquid-
evapor separation in the flash tank. A capacitance liquid level
sensor was installed through the top of the flash tank to
Table 2 e Specifications of the flash tank.
Parameter Unit Dimension
Flash tank height m 0.32
Diameter m 0.07
Flash tank volume m3 0.001
Sight glass height m 0.15
Table 1 e Specifications of the outdoor and indoor heatexchangers.
Parameter Unit Outdoor HeatExchanger
Indoor HeatExchanger
Tube length mm 2565 483
Tube outer
diameter
mm 7.9 9.5
Tube wall
thickness
mm 0.8 0.8
Tubes per bank e 32 26
Number of tube
banks
e 2 3
Coil in parallel e 1 2
Tube horizontal
spacing
mm 15.7 25.4
Tube vertical
spacing
mm 24.1 25.4
Fins per inch e 22 12
Fin thickness mm 0.1 0.1
Fin types e Wavy fin Wavy fin
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 4 ( 2 0 1 1 ) 1 9 2 2e1 9 3 3 1925
measure the liquid level inside of the flash tank. The capaci-
tance liquid level sensor has a length of 25.4 cm that is
equivalent to 80% of the flash tank height. Therefore the
sensor cannot measure the liquid level that is lower than 20%
of the flash tank height, since the sensor was installed
through the top of the flash tank. The main purpose is to
monitor the liquid level variations during different operating
conditions. Specifications of the flash tank are summarized in
Table 2. The uncertainties of all the sensors used in the
experimental study and performance parameters are shown
in Table 3.
Fig. 4 e Flash tank used in the experiment.
2.2. Control strategy analysis
In order to ensure no liquid refrigerant being provided to the
injection port, an additional device is needed in order to
control the upper-stage EEV. In this experimental study, an
electric heater was attached to the surface of the vapor
injection tube in order to provide superheat to the injected
vapor. The schematic of the flash tank cycle control strategy is
shown in Fig. 5. The heater power was varied to investigate
the performance variations at different degrees of superheat.
The superheatwasmeasured at the location of vapor injection
to the compressor. The EEV utilized the injected vapor
superheat to control its opening. This avoided the additional
cost of installing a liquid level sensor in potential industrial
application.
The EEV control was programmed in data acquisition
software, and the proportional-integral-derivative (PID)
control function built in data acquisition softwarewas utilized
to control the EEV. The user interface of the EEV-PID controller
is shown in Fig. 6. This interface provides the convenience to
control the system either by automatic or manual control. In
the automatic control mode, the PID controller automatically
controls the injected vapor superheat to reach the set point
value by regulating the upper-stage EEV opening. In the
manual mode, the EEV opening can be controlled by the
manual input value of the valve opening. In the experimental
study, the automatic control mode was used to reach the
automatic control of the system.
The injected vapor superheat can be used as the control
signal because it can effectively avoid the liquid refrigerant
injected to the compressor. The control algorithm works as
follows: A target degree of superheat is assigned to the PID
controller to control the EEV opening. If the liquid refrigerant
Table 3 e Uncertainties of sensors and calculatedparameters in the experimental study.
Sensor and Parameter Uncertainty
T type thermocouple (range: -200e350 �C) �0.5 �CPressure transducer (range: 0e3447 kPa) �3.79 kPa
Pressure transducer (range: 0e6895 kPa) �8.62 kPa
Relative humidity sensor (range: 0%e100%) �1.0%
Dew point sensor (range: -80e95 �C) �0.2 �CLiquid level sensor (range: 0e25.4 cm) �0.25 cm
Mass flow meter (range: 0e100 g s�1) �0.2% of flow rate
Watt meter (range: 0e5 kW) �0.5% of full scale
Cooling and heating capacity �3.6% of calculated
value
Cooling and heating COP �5.7% of calculated
value
Condenser
Evaporator
Compressor
Upper-stage
expansion
valve (EEV)
Lower-stage
expansion
valve (TXV)
Electric
heater
Sensing bulb
PID controller
Injected
vapor
superheat
Shutoff
valve
Fig. 5 e Schematic of the control strategy for the flash tank
cycle.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 4 ( 2 0 1 1 ) 1 9 2 2e1 9 3 31926
is to be injected with vapor refrigerant to the compressor by
the liquid flooding in the flash tank, the superheat of the
injected vapor would decrease rapidly. In this event, the
upper-stage EEV would reduce its opening to maintain the
target degree of superheat. This reduces the amount of liquid
flowing from the condenser to the flash tank, which reduces
the flash tank liquid level.
3. Test conditions
Both cooling and heating tests were conducted to evaluate the
system performance. The volume flow rate of the air circu-
lating in the closed air loop was set to be 0.58 m3 s�1. The test
conditions followed the ASHRAE Standard (1995), and are
illustrated in Table 4. Moreover, extended conditions of 46.1 �Cfor cooling and �17.8 �C for heating were added to investigate
Fig. 6 e The user interface of the EEV-PID controller.
the system behaviors at severe weather conditions. The
electric heater power input and the injected vapor superheat
were varied to investigate their effect on the system perfor-
mance as well as the liquid level variations in the flash tank.
4. Performance evaluation
In transient conditions, the system cooling and heating
capacities rely on the air side performance, since it’s difficult
to accurately obtain the refrigerant-side enthalpy in the first
few minutes after the system is started. In this scenario, the
capacity is calculated in Equation (1):
Qair ¼ _mair
�hair;out � hair;in
�(1)
Where _mair is the air mass flow rate; hair;out is the outlet air
enthalpy at the indoor heat exchanger, and hair;in is the inlet air
enthalpy at the indoor heat exchanger. The system cooling
and heating COP is defined in Equation (2):
COP ¼ Qair
Ptotal(2)
Where Ptotal is the total power consumption, which includes
the heat pump system power consumption and the electric
heater power consumption.
For steady-state operation, refrigerant-side performance
was used for the evaluation since the measurement in the
refrigerant side is more accurate than the air side. In this
scenario, the capacity is calculated in Equation (3):
Qref ¼ _mref
�href;out � href;in
�(3)
Where _mref is the refrigerant mass flow rate; href;out is the
refrigerant enthalpy at the indoor heat exchanger outlet, and
href;in is the refrigerant enthalpy at the indoor heat exchanger
inlet. The system cooling and heating COP is defined in
Equation (4):
COP ¼ Qref
Ptotal(4)
5. Experimental results
5.1. System startup
Ideally, the injected vapor superheat should always be main-
tained positive if the PID controller functions properly,
regardless of steady-state or transient system operations. The
first step is to examine the superheat variations during the
system startup to investigate the controllability of the PID
controller. Fig. 7 shows the injected vapor superheat varia-
tions during the system startup at different operating condi-
tions and heater power input. It can be seen that the injected
vapor superheat could always be controlled to reach the target
superheat within a relatively short period of time with
different superheat settings. The degree of superheat could
also be maintained to be non-negative to avoid liquid refrig-
erant being injected to the compressor. Moreover, the liquid
level variation is also closely related to the injected vapor
superheat. Fig. 8 shows the flash tank liquid level variations
Table 4 e Test conditions.
Test Indoor Outdoor Operation
DB WB RH DB WB RH DP
Extended condition 26.7 �C 19.4 �C 50.66% 46.1 �C NA NA NA Steady state cooling
A 35.0 �C Steady state cooling
B 27.8 �C steady state cooling
C �13.9 �C �21.41% Steady state cooling, dry coil
D Cyclic cooling, dry coil
High temp2 21.1 �C �15.6 �C �56.42% 8.3 �C 6.1 �C 72.9% 3.7 �C Steady state heating
High temp1 16.7 �C 14.7 �C 81.1% 13.4 �C Steady state heating
Low temp �8.3 �C �9.4 �C 69.8% �12.3 �C Steady state heating
High temp cyclic 8.3 �C 6.1 �C 72.9% 3.7 �C Cyclic heating
Frost acc. 1.7 �C 0.6 �C 82.0% �0.9 �C Steady state defrost
Extended condition �17.8 �C NA NA NA Steady state heating
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 4 ( 2 0 1 1 ) 1 9 2 2e1 9 3 3 1927
during the system startup at different operating conditions.
Some fluctuations could be seen in the first 3 min, and this
was due to the opening and closing of the EEV initiated by the
PID controller. It should be noted that the liquid level sensor
can only measure 80% of the flash tank height from the top of
the tank, and therefore as the liquid level is close to or lower
than 20% of the tank height, the liquid level appears to be
perfect steady. The liquid level never exceeds 50% of the entire
tank height, and this ensures reliable system operation. The
injected and total refrigerant mass flow rates in the system
startup are shown in Fig. 9 and Fig. 10, respectively. Large
variations can be observed in the first 5 min, and then the
mass flow rates tend to be steady.
5.2. Cooling cyclic test
In the real application, the air conditioning/heat pump
systems are turned on and off frequently. Therefore, it’s
worthwhile to investigate the system’s cyclic performance.
According to ASHRAE Standard (1995), cyclic cooling and
heating tests are comprised of 6 min compressor “on” time,
followed by 24 min compressor “off” time.
5.2.1. PID tuning of cooling cyclic testPID gains are critical factors that affect the transient behavior
of the PID controller, and therefore it’s necessary to find out
-2
0
2
4
6
8
10
12
14
0 1 2 3 4 5 6 7 8 9 10
Time [min]
Inje
cte
d v
ap
or s
up
erh
ea
t [
K]
Cooling: 46.1ºC
Cooling: 35.0ºC
Heating: 8.3ºC
Fig. 7 e Injected vapor superheat variations during the
system startup at different operating conditions.
the appropriate PID gains in order to reach optimum perfor-
mance for the system control. The output of the PID controller
in this study was normalized to be �100 to 100 to obtain more
general results for PID gains. The proportional gain makes
a change to the output that is proportional to the current error
value. The integral gain is the sum of the instantaneous error
over time and gives the accumulated offset that should have
been corrected previously. The derivative of the process error
is calculated by determining the slope of the error over time
and multiplying this rate of change by the derivative gain.
Different combinations of PID gains were tried, and from the
experiment it was found out that the EEV experienced large
variations when the derivative gain was used, and therefore
the derivative gain was set to be zero. Fig. 11 shows the
injected vapor superheat variations of PID tuning results of
cyclic cooling test. From the results it can be seen that small P
and I gains tend to yield a large variation, andwith larger P and
I gains the control curve looks better. P¼ 5.0, I¼ 0.5, D¼ 0, and
P ¼ 10, I ¼ 0.5, D ¼ 0, together with P ¼ 15, I ¼ 1.0, D ¼ 0 out-
performed other three different combinations of PID gains.
Fig. 12 shows the EEV opening variations during the PID tuning
of cooling cyclic test. The combination of P ¼ 2.0, I ¼ 0.2, D ¼ 0
and P ¼ 5.0, I ¼ 0.5, D ¼ 0 yield the least variations, and other
PID gains result in relative large variation of the EEV opening.
Fig. 13 shows the variations of indoor heat exchanger outlet
air temperature variations. It can be observed that with
0
5
10
15
20
25
30
35
40
45
50
0 1 2 3 4 5 6 7 8 9 10
Time [min]
Liq
uid
le
ve
l p
erc
en
ta
ge
[%
]
Cooling: 46.1ºC
Cooling: 35.0ºC
Heating: 8.3ºC
Fig. 8 e Flash tank liquid level variations during the system
startup at different operating conditions.
-2
0
2
4
6
8
10
12
0 1 2 3 4 5 6
Time [min]
Inje
cte
d v
ap
or s
up
erh
ea
t [
K]
P=1.0; I=0.02; D=0 P=2.0; I=0.2; D=0
P=5.0; I=0.1; D=0 P=5.0; I=0.5; D=0
P=10; I=0.5; D=0 P=15; I=1.0; D=0
Target superheat
Fig. 11 e PID tuning of cooling cyclic test: injected
superheat variations.
0
5
10
15
20
0 1 2 3 4 5 6 7 8 9 10
Time [min]
Inje
cte
d r
efrig
era
nt m
as
s f
low
ra
te
[g
/s]
Cooling: 46.1ºC
Cooling: 35.0ºC
Heating: 8.3ºC
Fig. 9 e Injected refrigerant mass flow rate variations
during the system startup at different operating
conditions.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 4 ( 2 0 1 1 ) 1 9 2 2e1 9 3 31928
P¼ 2.0, I¼ 0.2, D¼ 0 and P¼ 5.0, I¼ 0.5, D ¼ 0, the temperature
variation is more smooth, and this corresponds to the varia-
tions of EEV opening, as shown in Fig. 12. From the perfor-
mance point of view, P ¼ 5.0, I ¼ 0.5, D ¼ 0 outperformed
P ¼ 2.0, I ¼ 0.2, D ¼ 0. As a consequence, considering the time
for the injected vapor superheat to reach steady state, the
variation of the EEV opening, and the air side performance,
P ¼ 5.0, I ¼ 0.5, D ¼ 0 was found to be the most appropriate PID
gains for the cooling cyclic control.
5.2.2. Time delay to initiate the PID controllerAfter selecting the optimum PID gains, it’s also interesting to
study whether there is any difference if the PID controller is
initiated with different time delays after the system is started.
Since the cyclic test requires the system to be turned “on” for
6 min, and then turned “off”, therefore the delay time was
selected to be between 1 min and 5 min Fig. 14 shows the
indoor heat exchanger air outlet temperature variations with
different delay time to initiate the PID controller. It can be seen
that only with 1 min delay time, the transition of air side
temperature is not smooth, and there is no difference between
other delay time and the case without delay initiating the PID
0
20
40
60
80
100
0 1 2 3 4 5 6 7 8 9 10
Time [min]
To
ta
l re
frig
era
nt m
as
s f
low
ra
te
[g
/s]
Cooling: 46.1ºC
Cooling: 35.0ºC
Heating: 8.3ºC
Fig. 10 e Total refrigerant mass flow rate variations during
the system startup at different operating conditions.
controller. Therefore it’s recommended to turn on the PID
controller when the system is started, and no delay for the PID
controller is needed.
5.2.3. Cooling cyclic test resultsFig. 15 shows the cooling cyclic test results with vapor injec-
tion “on” and “off”. It can be seen that the indoor heat
exchanger outlet air temperature with vapor injection “on” is
lower than with vapor injection “off”, which means that the
cooling capacity delivered by vapor injection “on” is higher
than with vapor injection “off”. Calculation shows the
improvement is 10.1%. However, the power consumption also
becomes higher as vapor injection is initiated, which also can
be seen from Fig. 15. This results in a degradation of cooling
COP of 2.4%, which is within measurement uncertainty.
Therefore it seems that vapor injection can still be beneficial
when larger cooling capacity is needed in mild temperature
conditions.
5.3. Heating cyclic test
5.3.1. PID tuning of heating cyclic testPID tuning was also conducted for heating cyclic test in
a similar manner as the cooling cyclic test. Fig. 16 shows the
0
10
20
30
40
50
60
70
80
0 1 2 3 4 5 6
Time [min]
EE
V o
pe
nin
g [
%]
P=1.0; I=0.02; D=0 P=2.0; I=0.2; D=0
P=5.0; I=0.1; D=0 P=5.0; I=0.5; D=0
P=10; I=0.5; D=0 P=15; I=1.0; D=0
Fig. 12 e PID tuning of cooling cyclic test: EEV opening
variations.
0
5
10
15
20
25
30
0 1 2 3 4 5 6
Time [min]
Ou
tle
t a
ir t
em
pe
ra
tu
re
[ºC
]
0
0.5
1
1.5
2
2.5
3
Po
we
r c
on
su
mp
tio
n [
kW
]
VI off - inlet air VI on - inlet air
VI off - outlet air VI on - outlet air
VI off - power consumption VI on - power consumption
Fig. 15 e Cooling cyclic test: comparison between VI “on”
and VI “off”.
10
12
14
16
18
20
22
24
26
28
0 1 2 3 4 5 6
Time [min]
Ou
tle
t a
ir t
em
pe
ra
tu
re
[ºC
]
P=1.0; I=0.02; D=0 P=2.0; I=0.2; D=0
P=5.0; I=0.1; D=0 P=5.0; I=0.5; D=0
P=10; I=0.5; D=0 P=15; I=1.0; D=0
Fig. 13 e PID tuning of cooling cyclic test: indoor heat
exchanger outlet air temperature.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 4 ( 2 0 1 1 ) 1 9 2 2e1 9 3 3 1929
injected vapor superheat variations using different combina-
tions of PID gains. Similar trend could be seen as the cooling
cyclic test. Small P and I gains tend to yield a large variation of
the control variable, and P¼ 10, I¼ 0.5,D¼ 0 and P¼ 15, I¼ 1.0,
D ¼ 0 result in the least variations of the injected vapor
superheat. Fig. 17 shows the EEV opening variations with
different PID gains. P ¼ 1.0, I ¼ 0.02, D ¼ 0 and P ¼ 5.0, I ¼ 0.1,
D ¼ 1 result in large variations of the EEV opening, and other
PID gains lead to less variations of the EEV opening. Fig. 18
illustrates the indoor heat exchanger outlet temperature
variations with different PID gains. The optimum perfor-
mance was reached when P ¼ 10, I ¼ 0.5, D ¼ 0. Therefore,
P ¼ 10, I ¼ 0.5 and D ¼ 0 was selected for the PID gains for
heating cyclic test.
5.3.2. Time delay to initiate the PID controllerDifferent time delays for the heating cyclic test were also
performed. Fig. 19 shows the air outlet temperature variations
with different time delays to initiate the PID controller. It was
also found thatmaximumperformance can be achievedwhen
there is no delay in turning on the PID controller, whichmeans
that the PID controller was turned on as soon as the system is
turned on. Therefore, there is no need for time delay in initi-
ating the PID controller.
0
5
10
15
20
25
30
0 1 2 3 4 5 6
Time [min]
Ou
tle
t a
ir t
em
pe
ra
tu
re
[ºC
]
1 min delay
2 min delay
3 min delay
4 min delay
5 min delay
No delay
Fig. 14 e Cooling cyclic test: performance variations with
different time delays for PID controller.
5.3.3. Heating cyclic test resultsFig. 20 shows the heating cyclic test results with vapor injec-
tion “on” and “off”. It can be seen that there is no visible
difference in the air outlet temperature for vapor injection
“on” and “off” modes, which indicates that the heating
capacity with vapor injection “on” and “off” is almost the
same. Calculation shows that the improvement is only 0.6%,
which is within the measurement uncertainty. However, the
power consumption with vapor injection “on” is significantly
higher than that with vapor injection “off”, and this yields
a degradation of heating COP of 13.4%. Therefore it’s recom-
mended to turn off vapor injection during mild temperature
conditions since no benefit could be achieved.
5.4. Cyclic test results and discussions
From the cooling and heating cyclic tests it can be seen that
PID gains are important parameters that significantly affect
the system performance. P ¼ 5.0, I ¼ 0.5, D ¼ 0 was found to
be the most appropriate PID gains for the cooling cyclic
control, and P ¼ 10, I ¼ 0.5 and D ¼ 0 were most suitable PID
gains for heating cyclic test. The difference in P gain value in
cooling and heating tests may be due to different perfor-
mance behavior of lower-stage expansion valve. Although
-4
-2
0
2
4
6
8
10
12
0 1 2 3 4 5 6
Time [min]
Inje
cte
d v
ap
or s
up
erh
ea
t [
K]
P=1.0; I=0.02; D=0 P=2.0; I=0.2; D=0
P=5.0; I=0.1; D=0 P=5.0; I=0.5; D=0
P=10; I=0.5; D=0 P=15; I=1.0; D=0
Target superheat
Fig. 16 e PID tuning of heating cyclic test: injected
superheat variations.
15
20
25
30
35
40
0 1 2 3 4 5 6
Time [min]
Ou
tle
t a
ir t
em
pe
ra
tu
re
[ºC
]
1 min delay
2 min delay
3 min delay
4 min delay
5 min delay
No delay
Fig. 19 e Heating cyclic test: performance variations with
different time delays for PID controller.
0
10
20
30
40
50
60
0 1 2 3 4 5 6
Time [min]
EE
V o
pe
nin
g [
%]
P=1.0; I=0.02; D=0 P=2.0; I=0.2; D=0
P=5.0; I=0.1; D=0 P=5.0; I=0.5; D=0
P=10; I=0.5; D=0 P=15; I=1.0; D=0
Fig. 17 e PID tuning of heating cyclic test: EEV opening
variations.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 4 ( 2 0 1 1 ) 1 9 2 2e1 9 3 31930
lower-stage expansion valve for cooling and heating test has
the same nominal capacity, the manufacture imperfection
may introduce difference in its response, which further
affects the PID gains for the upper-stage expansion valve.
Different time delays were tried for cooling and heat cyclic
tests, and it was found that the initiating the PID controller
following the start of system yields the best performance.
For cooling cyclic mode, a capacity improvement of 10.1%
was observed, and a COP degradation of 2.4% was noticed.
For heating mode, a capacity improvement of 0.6% was
observed, yet a COP degradation of 13.4% was seen.
However, it should be noted that the cooling and heating
COP at the cyclic conditions with vapor injection “on” are not
as good as the scenarios with vapor injection “off” are not
simply due to the PID controller, but also due to the fact that
the current system only gives COP improvement at low
ambient temperatures. The current system was evaluated
regarding vapor injection “off” and “on” modes at different
cooling and heating temperatures without any PID
controller, as shown in Fig. 21. It can be seen that the COP
improvement was only found at �8.3 �C and �17.8 �Cconditions, and therefore the PID controller itself should not
account for all the COP degradations.
15
20
25
30
35
40
0 1 2 3 4 5 6
Time [min]
Ou
tle
t a
ir t
em
pe
ra
tu
re
[ºC
]
P=1.0; I=0.02; D=0 P=2.0; I=0.2; D=0
P=5.0; I=0.1; D=0 P=5.0; I=0.5; D=0
P=10; I=0.5; D=0 P=15; I=1.0; D=0
Fig. 18 e PID tuning of heating cyclic test: indoor heat
exchanger outlet air temperature.
5.5. Steady-state behavior of different injectionsuperheats and heater power input
The injected vapor superheat is affected by two factors: the
heater supply power and EEV opening. The EEV opening
affects the injected vapor superheat because it controls the
injection pressure in the flash tank. The system performance
varies depending on the heater power input as well as the
selected superheat setting. Both cooling and heating tests
were conducted.
5.5.1. Steady state cooling testFig. 22 illustrates the steady-state test results of cooling COP
variations with different ambient conditions, heater power
input and degrees of superheat. For 27.8 �C condition, the COP
variationswith 60W and 90Wheater power input is small, yet
the COP tends to decrease with 30 W heater power input. This
is because with the same target superheat setting, decreasing
the heat power input lowers the injection pressure in the flash
tank in order to match up the superheat. Moreover, if the
heater power input is kept constant, increasing the target
superheat value also results in decreased injection pressure in
order tomatch the increasing superheat. This can also be seen
from the liquid level variations, as shown in Fig. 23. The
0
5
10
15
20
25
30
35
40
0 1 2 3 4 5 6
Time [min]
Ou
tle
t a
ir t
em
pe
ra
tu
re
[ºC
]
0
0.5
1
1.5
2
2.5
3
Po
we
r c
on
su
mp
tio
n [
kW
]
VI off - inlet air VI on - inlet air
VI off - outlet air VI on - outlet air
VI off - power consumption VI on - power consumption
Fig. 20 e Heating cyclic test: comparison between VI “on”
and VI “off”.
0
20
40
60
80
100
120
0 2 4 6 8 10
Degree of superheat [K]
Liq
uid
le
ve
l h
eig
ht p
erc
en
ta
ge
[%
]
27.8ºC - 30W heater power 27.8ºC - 60W heater power
27.8ºC - 90W heater power 35.0ºC - 60W heater power
35.0ºC - 90W heater power 46.1ºC - 60W heater power
Fig. 23 e Flash tank liquid level variations at different
steady-state cooling ambient conditions, heater power
input and degrees of superheat.
-5%
0%
5%
10%
15%
20%
25%
30%
28.2%
[46.1ºC]
15.6%
[35.0ºC]
10.8%
[27.8ºC]
21.0%
[8.3ºC]
25.8%
[-8.3ºC]
28.4%
[-17.8ºC]
Maximum injection ratio
Imp
ro
ve
me
nt
Capacity improvement
COP improvement
Cooling Heating
Fig. 21 e Capacity and COP improvements at different
ambient conditions with the maximum injection ratio
compared to vapor injection “off”, steady-state
performance without any PID controller.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 4 ( 2 0 1 1 ) 1 9 2 2e1 9 3 3 1931
average liquid level for 60 W heater power and 90 W heater
power is higher than that with 30 W heater power at the
temperature of 27.8 �C. Higher liquid level indicates higher
injection pressure, because the upper-stage expansion valve’s
opening is increased in order to increase the injection pres-
sure, and also results in more liquid flowing into the flash
tank. The COP variations for 35.0 �C and 46.1 �C are relatively
small, and this indicates that the performance is not quite
sensitive when the heater power varies from 60 W to 90 W.
The cooling capacity variations show similar trend as the
cooling COP variations, which is shown in Fig. 24.
5.5.2. Steady state heating testThe heating performance variations are different from that of
the cooling results. Fig. 25 shows the steady-state heating COP
variations at different ambient conditions, heater power input
and degrees of superheat. At 8.3 �C condition, the general
trend is that higher heater power input yields higher heating
COP, and lowering the target superheat also results in higher
COP. An explanation for this is that when the target superheat
is set to be a constant value, increasing the heater power input
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
0 2 4 6 8 10
Degree of superheat [K]
Co
olin
g C
OP
27.8ºC - 30W heater power 27.8ºC - 60W heater power
27.8ºC - 90W heater power 35.0ºC - 60W heater power
35.0ºC - 90W heater power 46.1ºC - 60W heater power
Fig. 22 e Steady-state test of cooling COP variations at
different ambient conditions, heater power input and
degrees of superheat.
induces the EEV to enlarge its opening in order to increase the
injection pressure in the flash tank, thus maintaining the
same degree of superheat. This results in higher injection
ratio and improves heating COP. Moreover, the liquid level in
the flash tank is also increased. Likewise, if the heater power
input is kept constant, decreasing the target superheat value
also results in increased injection pressure in order to match
the decreasing superheat. For �17.8 �C condition with 60 W
heater power input, the trend is similar to that of 8.3 �Ccondition. However, as the heater power input increases to
90 W, the heating COP remains almost constant. This is
because in this condition, the system injection pressure
already reaches its maximum, and therefore lowering the
superheat cannot increase the injection ratio anymore. This
can also be seen in the liquid level variations, as shown in
Fig. 26. At �17.8 �C with 60 W heater power input, decreasing
the superheat shows a trend of increasing liquid level height.
However, for 90 W heater power input, the liquid level in the
flash tank is above 80% of the flash tank height. The upper-
stage expansion valve’s opening cannot be increased
anymore as the superheat decreases because it would result
in liquid flooding the compressor. In this scenario the system
8
9
10
11
12
13
14
0 2 4 6 8 10
Degree of superheat [K]
Co
olin
g c
ap
ac
ity
[k
W]
27.8ºC - 30W heater power 27.8ºC - 60W heater power
27.8ºC - 90W heater power 35.0ºC - 60W heater power
35.0ºC - 90W heater power 46.1ºC - 60W heater power
Fig. 24 e Steady-state test of cooling capacity variations at
different ambient conditions, heater power input and
degrees of superheat.
4
6
8
10
12
14
0 2 4 6 8 10
Degree of superheat [K]
He
atin
g c
ap
ac
ity
[k
W]
-17.8ºC - 60W heater power -17.8ºC - 90W heater power
8.3ºC - 60W heater power 8.3ºC - 90W heater power
Fig. 27 e Steady-state test of heating capacity variations at
different ambient conditions, heater power input and
degrees of superheat.
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
0 2 4 6 8 10
Degree of superheat [K]
He
atin
g C
OP
-17.8ºC - 60W heater power -17.8ºC - 90W heater power
8.3ºC - 60W heater power 8.3ºC - 90W heater power
Fig. 25 e Steady-state test of heating COP variations at
different ambient conditions, heater power input and
degrees of superheat.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 4 ( 2 0 1 1 ) 1 9 2 2e1 9 3 31932
stability is also compromised since the liquid level is very
high, which is represented in the error bar in the heating COP.
The heating capacity variation shows the same trend as the
heating COP, as shown in Fig. 27.
5.5.3. Steady-state results and discussionsSystem performance is an important factor in selecting the
appropriate heater power input and superheat settings. For
the cooling mode, there is no big difference with 60W or 90W
heater power input, yet 30 W heater power input seems to be
insufficient in reaching optimum performance. The optimum
performancewas observedwith 4 Ke6 K degrees of superheat.
For the heating mode, 90 W heater power input shows better
performance than 60W heater power input. However, it’s also
very important to consider the flash tank liquid level varia-
tions under different operating conditions. For the cooling
mode, the liquid level with 60 W and 90 W power input
exceeds 60% of the flash tank height, and therefore it’s better
to select power input lower than 60 W. For the heating mode,
90 W heater power input yields a liquid level higher than 80%
at the ambient temperature of �17.8 �C. Therefore, 60 W
heater power input is preferred.
0
20
40
60
80
100
120
0 2 4 6 8 10
Degree of superheat [K]
Liq
uid
le
ve
l h
eig
ht p
erc
en
ta
ge
[%
]
-17.8ºC - 60W heater power -17.8ºC - 90W heater power
8.3ºC - 60W heater power 8.3ºC - 90W heater power
Fig. 26 e Flash tank liquid level variations at different
steady-state heating ambient conditions, heater power
input and degrees of superheat.
In overall, when the systemperformance and reliability are
both considered, 4 Ke6 K degrees of superheat is preferred. For
heating mode, 60 W heater power input is preferred to 90 W;
for coolingmode, 30Wheater power input is preferred to 60W
and 90 W.
6. Conclusions
This paper investigates the experimental control strategy of
a flash tank vapor injection heat pump cycle. Both transient
and steady-state performances have been studied. In the
experiments, an electric heater was applied to introduce
positive superheat to the injected vapor. An EEV coupled with
a PID controller in data acquisition software was employed to
provide accurate control of the injected vapor superheat. In
the transient study, different PID gains were investigated
regarding their effects on the system performance, and most
suitable PID gains were obtained for cooling and heating cyclic
tests. Different time delays were tried for initiating the PID
controller, and it was found that initiating the PID controller
following the startup of the system yields the best perfor-
mance, and no time delay is needed. Through experiment it
was found out that the PID controller was able to provide
accurate control of the EEV to reach the target superheat. In
addition, the injected vapor superheat was varied to investi-
gate its effect on the system performance and the flash tank
liquid level variations. This also provides useful information
to analyze the feasibility of using the injected vapor superheat
as the control signal. Through steady-state and transient
cooling and heating tests, it was found that the injected vapor
superheat can be effectively used as the control signal of the
upper-stage expansion valve. The effect of different settings
of superheat and heater power input on the system perfor-
mance was also investigated. Considering the system perfor-
mance and reliability of controlling the flash tank liquid level,
4 Ke6 K degrees of superheat is a recommended value. For
heating mode, 60 W heater power input is preferred to 90 W;
for coolingmode, 30Wheater power input is preferred to 60W
and 90 W.
i n t e r n a t i o n a l j o u r n a l o f r e f r i g e r a t i o n 3 4 ( 2 0 1 1 ) 1 9 2 2e1 9 3 3 1933
Acknowledgment
We gratefully acknowledge the support of this effort from the
sponsors of the Alternative Cooling Technologies and Appli-
cations Consortium and the Center for Environmental Energy
Engineering (CEEE) at the University of Maryland, and Emer-
son Climate Technologies.
r e f e r e n c e s
ANSI/ASHRAE Standard 116-1995, 1995. Methods of Testing forRating Seasonal Efficiency of Unitary Air Conditioners andHeat pumps. ASHRAE, Atlanta, GA, USA.
Bertsch, S.S., Groll, E.A., 2008. Two-stage air-source heat pump forresidential heating and cooling applications in northern USclimate. Int. J. Refrig. vol. 31, 1282e1292.
Cho, H., Baek, C., Park, C., Kim, Y., 2009. Performance evaluationof a two-stage CO2 cycle with gas injection in the coolingmode operation. Int. J. Refrig. vol. 32, 40e46.
Fan, S., Liu, Q., He, S., Scroll compressor development for air-source heat pump water heater applications, Proceedings ofInternational Refrigeration and Air Conditioning Conferenceat Purdue, 2008.
Jang, Y., Lee, E., Chin, S., Ha, S., 2010. Effects of flash and vaporinjection on the air-to-air heat pump system. InternationalRefrigeration and Air Conditioning Conference at Purdue.
Liu, F., Huang, H., Ma, Y., Zhuang, R., 2008. An experimental studyon the heat pump water heater system with refrigerantinjection. Proceedings of International Refrigeration and AirConditioning Conference at Purdue.
Ma, G.Y., Zhao, H.X., 2008. Experimental study of a heat pumpsystem with flash tank coupled with scroll compressor. Energ.Build. vol. 40, 697e701.
Park, Y.C., Kim, Y., Cho, H., 2002. Thermodynamic analysison the performance of a variable speed scroll compressorwith refrigerant injection. Int. J. Refrig. vol. 25,1072e1082.
Wang, B., Shi, W., Li, X., 2009a. Numerical analysis on the effectsof refrigerant injection on the scroll compressor. Appl. Therm.Eng. vol. 29, 37e46.
Wang, X., Hwang, Y., Radermacher, R., 2009b. Two-stage heatpump system with vapor-injected scroll compressor usingR410A as a refrigerant. Int. J. Refrig. vol. 32, 1442e1451.
Wang, X. Performance investigation of two-stage heat pumpsystem with vapor injected scroll compressor. Ph.D.Dissertation, University of Maryland College Park, 2008.
Winandy, E.L., Lebrun, J., 2002. Scroll compressors using gas andliquid injection: experimental analysis and modeling. Int. J.Refrig. vol. 25, 1143e1156.
Xu, X., Hwang, Y., Radermacher, R., Pham, H.M., 2010. Controlstrategy of vapor injection cycle. International Refrigerationand Air Conditioning Conference at Purdue.
Xu, X., Hwang, Y., Radermacher, R., 2011. Refrigerant injectionfor heat pumping/air conditioning systems: Literaturereview and challenges discussions. Int. J. Refrig. vol. 34,402e415.