1
TRAXTransformer & Substation Test System
Joacim Sköldin
2
Transformer – “The electric gear box”
� Fixed ratio, e.g. 100 kV / 10 kV� LTC (Load Tap Changer)
• 100±9x1.67% / 10 kV
� DETC (De-Energized Tap Changer)• Tuning voltage level• Change configuration, e.g. from Dzn10 to
Yzn11
3
Basic transformer model (impedance)
� Primary side:• Winding resistance, • Leakage Inductance
(X1+(N1/N2)2*X2)• Magnetization current
(excitation current)
� Secondary side• Winding resistance• Inductance
� Primary to secondary• Turn ratio (E1/E2)
4
Measuring the parameters
� Excitation/magnetization current (field) and no-load loss (factory) measurements
� Winding resistance measurements (factory and field)
� Load-loss measurements (factory)
� Short-circuit impedance (voltage) measurements (factory and field)
� Turn ratio (factory and field)
R+jX = R1+jX1 + (N1/N2)2 x (R2+jX2)
5
Summary - Impedance modeling� The ideal transformer combined with the
simple equivalent circuit describes the physics of the transformer well.
� The important measurement parameters are:� Magnetization/Excitation current
(voltage dependent)� Winding resistance (temperature
dependent)� Short-circuit impedance/Leakage
reactance� Turns ratio
6
Guides and standards for transformer testing
� Most standards (IEC and ANSI/IEEE) are focusing on new transformers and factory testing
� IEC 60076� IEC 60076-…� IEC 60076-18 SFRA
� IEEE
7
� Workgroups in Cigré have over the years produced a lot of Technical Brochures (TB) e.g. on sweep frequency response measurements (TB342), partial discharge (TB444), dielectric response measurements (TB414) etc
� IEEE 62-1995 is probably the most well-known guide for diagnostic field testing of oil filled power transformers. The guide today belong to the IEEE C57-series and last published revision is C57.152-2013
Guides and technical brochures for transformer FIELD testing
8
Cigré Technical Brochure 445, 2011
Guide for Transformer Maintenance
9
CIGRE TB 445
� Cigré TB 445, ”Guide for Transformer Maintenance”, was published 2011
� TB 445 is a comprehensive combination of education handbook, thesaurus and a guide for transformer maintenance including guidelines for how to perform measurements in the field
10
Section 5.1 ElectricalMeasurements Methods for On-Site Transformer Diagnosis
11
Diagnostic Technique
� Basic Electrical� Advanced Electrical� Dissolved Gas Analysis (DGA)
12
Basic Electrical� Winding Ratio - TRAX, TTR� Winding Resistance - TRAX, MTO� Magnetization current - TRAX, Delta, TTR� Capacitance and DF/PF - TRAX, Delta� Insulation Resistance - MIT� Core Ground Test - MIT
13
Advanced Electrical
� Frequency Response of Stray Losses (FRSL) - TRAX� Frequency Response Analysis - FRAX� Polarization/Depolarization - IDAX� Frequency Domain Spectroscopy - IDAX� Recovery Voltage Method� Electrical Detection of PD� Acoustical Detection of PD� UHF Detection of PD
14
Summary CIGRE TB 445
� TB 445 is a combination of a transformer handbook, thesaurus and application guide for transformer maintenance including guidelines for transformer field testing
� Lots of very good information. Details and guidelines can and will be discussed e.g. assessment data and advantages/disadvantages with different measurement methods (e.g. combined PDC-FDS combination versus true AC DFR/FDS measurements)
16
TRAX – Overview� Multi-function test system for transformer and substation testing � State-of-art winding resistance and tap-changer testing functionality
• 100A @ 50V compliance• Adaptive demagnetization• Tap-changer control• Dynamic resistance measurements
� High voltage ratio measurement (250 V and 2200 V output)� 3-phase circuit-breaker analyzer� Optional switchbox for 3-phase/6-winding measurements� Optional unit for insulation testing� CT and VT testing� And much more...
17
Target Markets
OEMs - High performance
Service companies - < 32 kg shipping
Utilities - Multi-function unit for substation testing
Power intensive industries - Toolbox for a lot of electrical tests
18
TRAX Strategy - Simplicity
19
Simplicity challenge…
20
TRAX - Target Applications
� Power transformer testing� CT and VT testing� Substation testing
• Circuit-breaker• Single-phase relay• Ground/earth• Multi-purpose…
� Generators and motors
21
Technical Overview- Generators and outputs
� Current generators• 100 A DC• 20 A AC• 800 (200) A AC
� Voltage generators• 2200 V AC• 250 V AC• 300 V DC
� Binary• 2 contacts for tap-changer and circuit-breaker operation with
internal voltage and current measurement
22
Technical Overview- Measurements
� Measurement channels• Internal current and voltage measurements on test signal
outputs• 4 x multi-purpose voltage/current measurements• 2 x DC voltage measurements• 1 x transducer input for motion transducer, Rogowski coils etc
� Binary inputs• 3 x dry/wet contacts for relay and circuit-breaker timing (main
and resistor)• 1 x trig input
23
Technical Overview- Accessories
� Optional switchbox for 3-phase/6-w winding resistance, turns ratio, magnetic balance, excitation current, short-circuit impedance etc
� Optional 12 kV tan delta/power factor testing� Optional 2000 A current output for primary testing� Optional 17 kV tan delta/power factor testing (generators and
motors)
24
Technical Overview- Instruments/Apps
� Standard transformer• Winding resistance• OLTC continuity• Demagnetization• Turns ratio• Excitation current• Short-circuit impedance
(leakage reactance)
25
Technical Overview- Instruments/Apps)
� Advanced transformer• OLTC DRM and dynamic
current (“ripple”)• Frequency Response of Stray
Losses (FRSL)• Magnetic balance
26
Technical Overview- Instruments/Apps
� Manual Control• Generators
– Manual control– Set values– Ramp
• External and internal measurement channels• Calculated parameters
– Resistance– Impedance– Reactance– Power– VA– Phase– Inductance– Capacitance– Arithmetics– Customer defined
27
Technical Overview –Instruments/Apps)
� CT/VT testing• CT excitation• Winding resistance• CT demagnetization• Current ratio• Voltage ratio• CT Rogowski• CT/VT low power/electronic• Burden• Voltage withstand
28
Technical Overview- Instruments/Apps)
� Substation• CB analyzer• LV CB• Relay• Timer• Phase-angle meter• Ground/earth/impedance
29
Intelligent simplicity Intuitive and easy to use Short-time learning processEasy to expand and upgrade
State-of-the-art WRM and OLTC capabilities
Fast and repeatable tests on all transformer configurations and sizes
Weight <32 kg in transport case Can be shipped as check-in luggage
Seven channel digital multimeter 4 + 3 analog external measurementchannels offers unmatched capabilities
3 phase circuit breaker analyzer Timing, motion, coil current, station voltage
Key Features & Benefits