Trafo Specifications Rating Three phase – Self –cooled – 60 Hertz ð Oil-immersed; ð R’Temp; ð Silicone ð 55/65C Rise ð 65C Rise Select one 300kVA ð 1000kVA ð 2500kVA ð 500kVA ð 1500kVA ð *3000kVA ð 750kVA ð 2000kVA ð *step only Select one Vault Type [above ground – dry vaults]……....ð Subway Type [below or above ground]……….…ð Select one [primary voltage – max 34.4kV - 200BIL] - specify voltage - Connected: Delta ð Wye ð Select one [tap changer for de-energized operation only] Primary taps: None…………………………….………….. ð Four 2 1/2 % below……………………….…ð Two 2 ½ % above & below………………….ð Specify ð Select one [secondary voltage – max step BIL is 95kV] 216GrdY/125 volts…………………….……ð 208GrdY/120 volts………………………..…ð 480GrdY/277 volts……………………….….ð Specify ð Select one [neutral connection] Standard solidly grounded low-voltage neutral blade ……. ð Insulated low-voltage neutral bushing……………………...ð Select one [primary disconnect and grounding switch-3 pole, 3 position, electrically interlocked-closed/open/grd. feeder] Dead Break………………………………………...ð Mag-Break [break magnetizing current only]….….ð No Primary Switch…………………………….…..ð Select one [primary cable entrance--specify cable size] Esna 200A wells, K1601, with hold down bracket..ð ….w/o.ð Esna 600A bush, K600T1…………………………………...ð Esna [specify] ð Wipe sleeve – 3 single-conductor…ð …(1) 3 conductor.…...ð Stuffing box – 3 single-conductor…ð …(1) 3 conductor.…...ð Pothead – 3 single-conductor……...ð … (1) 3 conductor……ð Options

Trafo Specifications

Embed Size (px)

DESCRIPTION

Tech Guide

Citation preview

Page 1: Trafo Specifications

Trafo SpecificationsRatingThree phase – Self –cooled – 60 Hertzð Oil-immersed; ð R’Temp; ð Siliconeð 55/65C Rise ð 65C RiseSelect one300kVA ð 1000kVA ð 2500kVA ð500kVA ð 1500kVA ð *3000kVA ð750kVA ð 2000kVA ð *step onlySelect oneVault Type [above ground – dry vaults]……....ðSubway Type [below or above ground]……….…ðSelect one [primary voltage – max 34.4kV - 200BIL]- specify voltage -Connected: Delta ðWye ðSelect one [tap changer for de-energized operation only]Primary taps: None…………………………….………….. ðFour 2 1/2 % below……………………….…ðTwo 2 ½ % above & below………………….ðSpecify ðSelect one [secondary voltage – max step BIL is 95kV]216GrdY/125 volts…………………….……ð208GrdY/120 volts………………………..…ð480GrdY/277 volts……………………….….ðSpecify ðSelect one [neutral connection]Standard solidly grounded low-voltage neutral blade ……. ðInsulated low-voltage neutral bushing……………………...ðSelect one [primary disconnect and grounding switch-3 pole,3 position, electrically interlocked-closed/open/grd. feeder]Dead Break………………………………………...ðMag-Break [break magnetizing current only]….….ðNo Primary Switch…………………………….…..ðSelect one [primary cable entrance--specify cable size]Esna 200A wells, K1601, with hold down bracket..ð ….w/o.ðEsna 600A bush, K600T1…………………………………...ðEsna [specify] ðWipe sleeve – 3 single-conductor…ð …(1) 3 conductor.…...ðStuffing box – 3 single-conductor…ð …(1) 3 conductor.…...ðPothead – 3 single-conductor……...ð … (1) 3 conductor……ð

OptionsLow voltage bushings bolted not welded……………………Primary entrance bolted not welded…………………………Primary entrance on tank cover not terminal chamber……....Primary entrance on front not top of chamber…………….....Hand Hole welded (ANSI) not bolted…..…………………...Ship can of terminal chamber compound with unit……….…

Page 2: Trafo Specifications

Provide phasing probe openings……………………………...Provide viewing window for primary switch………………...Provide special interlock scheme [specification required]…...Provide low voltage junction box [specify terminations]…….Provide thermometer with alarm contacts [specify]……….…Provide Qualitrol Relief [208-60, 10psi] on cover…….…….Network Transformers:Network Transformers are designed in accordance withANSI C57.12.40 and constructed with the corrosion resistanceequivalent of copper-bearing steel:Cover and Base 0.50in thickTank wall and housings 0.312in thickGE uses a special Network Transformer paint systemfor added corrosion resistance. Welded main cover, subbase,bushings, and liquid level gage are standard. Other valves, plugs,thermometer, etc are sealed threads. External hardware isaustenitic stainless steel, silicon bronze or the functionalequivalent. The finish is black and conforms to C57.12.32.All characteristics, definitions, terminology, and voltagedesignations and tests, except as otherwise specified herein, shallbe in accordance with the latest revisions of the followingAmerican National Standard Terminology, and Test Code forDistribution, Power, and Regulating Transformers:General Requirements C57.12.00 (IEEE Std 462)Terminology, C57.12.80Test Code, C57.12.90Loading, C57.92.19Separable Connectors, IEEE Std 386Terminal Markings and Connections, C57.12.70Finish, C57.12.32Subway Type Network Transformers are designed forfrequent/continuous submersion and use flat panel radiators withthe corrosion equivalence of 0.312 copper-bearing steel. Typicalapplication is grid-type secondary network systems to serve highdensity load areas of cities. The Subway Type NetworkTransformer may also be used in dry vault applications if desired.Vault Type Network Transformers are designed for dryvaults with occasional submersion using lighter weight panelradiators with the corrosion equivalence of 0.093 copper-bearingsteel. Typical applications are skyscrapers, high rise apartments,large office or manufacturing facilities where the reliability of aNetwork System is required.