  • 8/18/2019 TP48200A Quick Installation Guide (V100R001_01)

    1/27

    HUAWEI TECHNOLOGIES CO., LTD.

    TP48200A V100R001Quick Installation Guide

    Document Version: 01

    Part Number: 31505049Issued on: 2011-03-09

  • 8/18/2019 TP48200A Quick Installation Guide (V100R001_01)

    2/271

    Safety Information

    Copyright Huawei Technologies Co.,Ltd.2011.All rights reserved.

      Safety PrecautionsTo ensure your personal safety and to avoid damaging the equipment, pay attention to the safety symbols on

    the equipment and follow all instructions in this document. The "DANGER", "CAUTION" and "NOTE" marks do

    not represent all the safety instructions. They are only supp lements to the safety instructions.

    When operating Huawei products and equipment, you must comply with safety precautions and special safety

    instructions related to corresponding equipment provided by Huawei. The safety precautions in the document

    are related to only Huawei products. Huawei will not be liable for any consequences that result f rom the violationof universal regulations for safety operations and saf ety codes on design, production, and equipment use.

    Local Safety RegulationsWhen operating the device, comply with the local safety regulations.

    Personnel RequirementsOnly trained and qualified personnel are allowed to install, operate, and maintain Huawei equipment.

    Symbols

    CAUTION Indicates a potentially hazardous situation, which if not avoided, could result inequipment damage, data loss, performance deterioration, or unexpected results.

    Provides additional information.NOTE

    Human Safety

    Route cables in a proper sequence according to this document. For personal safety purposes, ensure that

    ground cables are installed before performing other operations.

    The construction personnel must be trained, understand basic safety p recautions, master related skills and

    have obtained related certificates.

    This document describes the precautions to be taken in specif ic installation scenarios.

    Conduct a power-on test within 72 hours af ter the power system is installed.

     

  • 8/18/2019 TP48200A Quick Installation Guide (V100R001_01)

    3/272

    Cabinet Appearance 3

    Tools 4

    System Components 5

    Installing the Cabinet 61.Fixing the Cabinet 6

    2. Installing Modules 7

    3. Installing Batteries 7

    Connecting Cables 81. Preparations 8

    2. Installing Ground Cable (g1) 9

    3. (Optional) Installing Dry Contact Signal Cables and

    Communication Cables 10

    4. Routing Power Cables for the DC-powered Loads (d1) 13

    5. Installing Power Cables for the Storage Batteries (d2) 14

    6. Installing AC Input Cables (a1) 15

    7. Routing Power Cables for the AC-powered Loads (a2) 16

    8. Verifying the Installation 17

    Commissioning the TP48200A 18

    1. Connecting Batteries to the Power System 182. Setting PMU 02B Parameters 19

    3. Power-On Check 21

    Power System Parameter List 25

    Contents

  • 8/18/2019 TP48200A Quick Installation Guide (V100R001_01)

    4/27

  • 8/18/2019 TP48200A Quick Installation Guide (V100R001_01)

    5/274

    Tools

     Adjustable

    wrench

    Nylon tie

    Electrical knife

    Torque wrench

    Wire stripper

    COAX crimping

    tool

    Multimeter 

    Claw hammer  Diagonal pliers

    Paint brush

    Hydraulic pliers Insulated handle

    Marker 

    Vacuum cleaner 

    Socket wrench

    Insulation tape

    Hammer drill(with Ф16 drill bit) Heat gun

    Flat-head

    screwdriver 

    (M3, M4)

    LevelHeat shrink tube

    Ladder (2 m)

    Insulating gloves

    & ESD gloves

    Phillips

    screwdriver 

    (M3, M4)

  • 8/18/2019 TP48200A Quick Installation Guide (V100R001_01)

    6/275

    System Components

    No. Specification Exterior  

    g1-Ground cable 35 mm2 - yellow and green The cable has ring terminals installed atboth ends.

    a1-AC input power cable 16 mm2 - black sleeve (core wire: red,yellow, green, and black) 4-pin equal-section cable

    The cable has cord endterminals installed at both ends.

    a2-Power cable to AC load As required by the custom er   Plug

    d1-Power cable to the DC load(BLVD)

     As required by the customer The cable has cord endterminals and ring terminals installed.

    d2-DC power cable to the battery 35 mm2 - Red cable and black cable The cable has cord end

    terminals and ring terminals installed.

    s1-Dry contact signalcable/Boolean value signalcable/Sensor signal cable/Surge

    protection signal cable

     As required by the customer The dry contact signal cable hascord end terminals installed, and the sensorsignal cable has multi-pin sockets installed.

    s2-FE signal cable As required by the customer The cable has RJ45 connectorsat both ends.

    D.G. Sensor EMS

     ACDB

    DC load

    s2

    s1

    a1

    g1

    TP48200A

     AC power 

    DC power 

    Signal cable

    Ground cable

    Site ground bar  Battery

     AC load

    d1

    a2

    Main supply

    D.G. ATS

    d2

  • 8/18/2019 TP48200A Quick Installation Guide (V100R001_01)

    7/276

    Installing the Cabinet

    Fix the installation holes of expansion bolts and then install the expansion bolts.

    Install the cabinet.

    1 Fixing the Cabinet

    Line-drawing templateMarker 

    Installation hole of expansion bolts

    Ф 16

    Four M12x60expansion bolts

    Socket wrench

    Spring washer Flat washer Expansion sleeve

    Bolt

    Step1

    Step2

    Step3

    Cementbase

  • 8/18/2019 TP48200A Quick Installation Guide (V100R001_01)

    8/277

    (Optional) Install PSUs.By default, the cabinet is configured with two PSUs. Determine the number of PSUs to be installed based on customer requirements. Each PSU can output a maximum of 50 A current.

    Install batteries, and connect cables, then install the battery baffle plate.

    3 Installing Batteries

    2 Installing Modules

    Step1 Step2 Step3 Step4 Step5

    Remove the rack and battery baff le plate .

    Battery baffle plate

    RackRack

    +- +- +- +- +- +- +- +-

    Step6

    Battery baffle plate

  • 8/18/2019 TP48200A Quick Installation Guide (V100R001_01)

    9/278

    Connecting Cables

    1 Preparations

    Connect cables in the following sequence: g1 > s1 and s2 > d1 > d2 > a1 > a2

    Cables a1 and a2 are routed into the left cabling holes at the bottom of the cabinet, and cables g1 ,s1, s2, d1, and d2 arerouted into the right cabling holes at the bottom of the cabinet.

    Set all the circuit breakers to OFF.

    Prepare terminals based on the actual requirements.

    Ringterminal

    Cord endterminal

    Heat shrinktube

    Crimping tool Hydraulic pliers

    DCDB

    OFF

    OFF

    OFF

    OFF

    ACDB

  • 8/18/2019 TP48200A Quick Installation Guide (V100R001_01)

    10/279

    2 Installing Ground Cable (g1)

    Site ground bar 

    Ground cable

    Cable modules

    +- +- +- +-

  • 8/18/2019 TP48200A Quick Installation Guide (V100R001_01)

    11/2710

    3 (Optional) Installing Dry Contact Signal Cables and Communication Cables

    1.You need to determine the dry contact signal cables and communication cables to be connected based on customerrequirements.2. The following figure shows the ports on the monitoring module.

    FE

    COM-485/232

    Port Type Silkscreen Description

    Sensor port TEM_BAT Port for battery temperature detection

    Door Port for door status detection

    Smoke Port for smoke sensor detection

    WATER Port for water sensor detection

    TEM_HUM Port for humidity sensor detection

     Analog value detection AIN Port for battery in position detection

    Boolean value detectionport

    DIN1 Port for Boolean value input1

    DIN2 Port for Boolean value input2

    DIN3 Port for Boolean value input3

    DIN4 Port for Boolean value input4

    DIN5 Port for Boolean value input5

    DIN6 Port for Boolean value input6

    DIN7 Port for Boolean value input7

    Output dry contact ALM1 Port for smoke alarm

     ALM2 Port for door broken alarm

     ALM3 Port for PSU fault or PSU communicate fault alarm

     ALM4 Port for load fuse trip or battery fuse trip alarm

     ALM5 Port for battery temperature alarm or environmenttemperature alarm

     ALM6 Port for TCU alarm

     ALM7 Port for mains fault

     ALM8 Port for head lamp control

     ALM9 Port for SPD failure alarms

    Power electronicmanufacturing information

    PELU Power electronic manufacturing information port

  • 8/18/2019 TP48200A Quick Installation Guide (V100R001_01)

    12/2711

    Cable modules

     

    Signal cable

    D.G.

    Routing Dry Contact/Sensor Signal Cables (s1)

    Press the white contact plate using a flat-head screwdriver. Insert the two wires at one end of the signal cable into thecorresponding ports, and then pull out the screwdriver to fasten the dry contact signal cable.

    Connect the sensor cable and SPD signal cable to the corresponding ports on the UIM 02A.

    +- +- +- +-

  • 8/18/2019 TP48200A Quick Installation Guide (V100R001_01)

    13/2712

    Cable modules

     

    Signal cable

    Routing FE Signal Cable (s2)

    COM

    +- +- +- +-

  • 8/18/2019 TP48200A Quick Installation Guide (V100R001_01)

    14/2713

    Cable modules

    4 Routing Power Cables for the DC-powered Loads (d1)

    Ensure that cables are connectedto circuit breakers securely.

    DCDB

    Load

    Load

    RTN+

    +

    -

    +-

    +- +- +- +-

    Install the DC power output cables for the DC-powered loads.

    Remove the protection plate from the DCDB, and then connect the cables by referring to the following f igure.

    For the negative terminalof DC power cables

    For the positive terminalof DC power cables

  • 8/18/2019 TP48200A Quick Installation Guide (V100R001_01)

    15/2714

    Cable modules

    Connect the negative terminal and positive terminal of the storage battery to the power system: Loosen the upper bolts of thebattery input port, insert the –48 V power input cable and positive terminal into the cabling holes, and then tighten the boltssecurely using a screwdriver.

    5 Installing Power Cables for the Storage Batteries (d2)

    Remove any of the three copper busbars through which the batteriesare connected in series.

    + -

    For the negative terminalof DC power cablesofthe storage battery

    outside the cabinet

    For the positive terminalof DC power cablesof thestorage battery outside

    the cabinet

  • 8/18/2019 TP48200A Quick Installation Guide (V100R001_01)

    16/2715

    Cable modules

    6 Installing AC Input Cables (a1)

    Route the AC input cables through the cabling holes on the left of the cabinet, and connect the neutral wire to the

    corresponding terminal.

    Connect the L1-phase, L2-phase, and L3-phase lines to the AC input circuit breaker.

     AC input cables support three-phase power input.

    Before connecting AC input cables, disconnect the ACDB f rom the TP48200A.

    AC power distribution unit

    ACDB

    +- +- +- +-

    For AC power cables

  • 8/18/2019 TP48200A Quick Installation Guide (V100R001_01)

    17/2716

    7 Routing Power Cables for the AC-powered Loads (a2)

    ACDB

    Socket connectto AC load

    Cable modules

    Connect the power cables of the AC-powered loads to the socket.

    +- +- +- +-

    For AC power cables

  • 8/18/2019 TP48200A Quick Installation Guide (V100R001_01)

    18/2717

    8 Verifying the Installation

    NO. Item

    1 Verify that the cabinet is properly installed and that cables are securely connected.

    2 Verify that cables are routed in an untangled and orderly fashion.

    3 Verify that idle cabling holes have rubber plugs installed.

    4 Verify that cabling holes are sealed with fireproof mud and that idle cabling holes have rubber plugs installed.

    The fireproof mud is placed in the packing box of the cabinet base.

    5 Verify that short circuits do not exist between live wires (L1, L2 and L3), between live wires and ground cables,

    between live wires and neutral wires (busbar), and between 0 V copper busbars and–48 V copper busbars

    (between–48 V busbar measurement points 1 and 2 and the RTN+ busbar).

    6 Verify that the paint on the surface of the cabinet does not peel off.

    DCDB

    ACDB

    Ground bar 

    RTN+

    Battery BLVD

    -48V

    measurementpoint 1

    -48V

    measurementpoint 2

    L1L2L3

    N

  • 8/18/2019 TP48200A Quick Installation Guide (V100R001_01)

    19/2718

    Set the circuit breaker for the battery string in the DCDB to ON.

    Install the removed copper busbar through which the batteries are connected in series. Then connect the battery string to thepower system.

    ON

    Battery

    BAT ON

    Normal

    Commissioning the TP48200A

    1 Connecting Batteries to the Power System

    Set the power switch to BAT ON if no information is displayed on the PMU 02B after the circuit breaker for thebattery string in the DCDB is set to ON. Then set the power switch to Normal after two minutes to protect the battery

    string from being overdischarged. If the voltage of the battery string is lower than 40 V, set the power switch toNormal two minutes after the mains is connected. Otherwise, a power failure occurs on the PMU 02B.

  • 8/18/2019 TP48200A Quick Installation Guide (V100R001_01)

    20/2719

    1. Set the preceding parameters based on the actual situation.

    2. The number of battery strings can be 0, 1, or 2. If one battery string is required, set the battery capacity

    according to the fuse position. For example, if the storage string is connected to BF1-, set the battery

    capacity to battery capacity 1; if the storage batteries are connected to the BF2-, set the battery capacity to

    battery capacity 2.

    3. Button description:

    2 Setting PMU 02B Parameters

    4. The parameter settings on the LCD of the PMU 02B are only for reference. For details on how to set PMU

    02B parameters, see the TP48200A & ETP48200 Monitoring Module User Manual.

    Parameter Value Description

    System Type Type of the power system.

    Batt String Number of battery strings.

    Capacity Battery capacity.

    Install Date Date when the power system is installed.

    IP Address IP address of the PMU 02B.

    Subnet Mask Subnet mask of the PMU 02B.

    Gateway Gateway IP address.

    Date System date.

    Time System time.

    Button Description

    ▲or▼ You can press▲ or▼ scroll the m enu or set a selected parameter.

    Cancel Press Cancel to return to the previous menu without saving the settings.

    Enter  On the standby screen, press Enter to display the main menu.

    On the main menu screen, press Enter to display the sub-menu.

    On the sub-menu screen, pressEnter to save the settings.

    Notes:

    •The system information screen will be displayed if you do not perform any operations using the buttons within five

    minutes.

    •The background light of the LCD will turn off if you do not perform any operations within eight minutes.

    •On the standby screen, you can press▲ and Enter at the same time to reduce the LCD contrast, or press▼ and

    Enter to increase the LCD contrast.

  • 8/18/2019 TP48200A Quick Installation Guide (V100R001_01)

    21/2720

    Jan.01.00

    53.6VDC 227VAC

    Load:0.0A

    Batt:0.0A

    MAIN MENU

    Alarm & Status

    Settings

    Maintenance

    Settings

    Engineer Settings

    Enter 

    Modify PWD

    User 

    Init ParaNo

    System Type

    TP48200A

    Version Info

    Enter Password:

    >#

    Enter 

    Enter 

    10020# Enter 

    MAIN MENU

    Alarm & Status

    Settings

    Maintenance

    Enter 

    Enter Password:

    >#

    00200# Enter 

    Settings

    Comm Settings

    Batt Settings

    DC Settings

    Jan.01.00

    53.6VDC 227VAC

    Load:0.0A

    Batt:0.0A

    MAIN MENU

    Alarm & Status

    Settings

    Maintenance

    Enter 

    Batt String:

    1

    Capacity 1:400Ah

    Batt Settings

    Batt Selection

    Batt off Para

    Charge Para

    Enter 

    Enter 

    MAIN MENU

    Alarm & Status

    Settings

    Maintenance

    Enter 

    Enter Password:

    >#

    00102# Enter 

    Settings

    Comm Settings

    Batt Settings

    DC Settings

    Settings

    Comm Settings

    Batt Settings

    DC Settings

    Enter 

    Capacity 2:

    0Ah

    Install Date:

    Jan.01’00

    Jan.01.00

    53.6VDC 227VAC

    Load:0.0A

    Batt:0.0A

    MAIN MENU

    Alarm & Status

    Settings

    Maintenance

    Enter 

    PMU Address:0

    COM Port

    RS485/RS232 Port

    Enter 

    Enter 

    MAIN MENU

    Alarm & Status

    Settings

    Maintenance

    Enter 

    Enter Password:

    >#

    00102# Enter 

    Settings

    Comm Settings

    Batt Settings

    DC Settings

    Settings

    Comm Settings

    Batt Settings

    DC Settings

    Modem Select:

    NoBaud: 9600

    Enter 

    PMU Address:0

    COM PortRS485/RS232 Port

    Enter 

    IP Address:192.168.0.10

    Subnet Mask:

    255.255.0.0

    Gateway:

    192.168.0.1

    Jan.01.00

    53.6VDC 227VAC

    Load:0.0A

    Batt:0.0A

    MAIN MENU

    Alarm & Status

    Settings

    Maintenance

    Enter 

    Text: English

    Disp Contrast:3

    Date:Jan.01’00

    Enter 

    Enter 

    MAIN MENU

    Alarm & Status

    Settings

    Maintenance

    Enter 

    Enter Password:

    >#

    00102# Enter 

    Settings

    Comm Settings

    Batt Settings

    DC Settings

    Settings

    Tel No Settings

    Night Charge Set

    System Settings

    Text: English

    Disp Contrast:3

    Date:Jan.01’00

    Text: English

    Disp Contrast:3

    Date:Jan.01’00

    Time:

    Jan.01’00

    Capacity 2:

    0Ah

    Install Date:Jan.01’00

    Batt String:

    1Capacity 1:

    400Ah

    IP Address:

    192.168.0.10

    Subnet Mask:

    255.255.0.0

    English

    Osmanli

    English

    Osmanli

    English

    Osmanli

    English

    Osmanli

  • 8/18/2019 TP48200A Quick Installation Guide (V100R001_01)

    22/2721

    Connect the mains to the power system only if related battery string parameters for the PMU02B are

    correctly set. Otherwise, the battery string may be damaged.

    Check whether the voltages of the RTN+ busbar and -48 V measurement points 1and 2 are the same as the battery

    voltage displayed on the monitoring module using a multimeter. If not, contact related personnel or handle theproblems by referring to the TP48200A Maintenance Guide.

    DCDB

    RTN+

    Battery BLVD

    -48Vmeasurement

    point 1

    -48Vmeasurement

    point 2

    3 Power-On Check

  • 8/18/2019 TP48200A Quick Installation Guide (V100R001_01)

    23/2722

    Set the AC circuit breaker to ON and repeat step 1. Check whether the voltages of the RTN+ busbar and -48 V

    measurement points 1 and 2 range from 43.2 V to 57.6 V.

    ACDB

    L1L2L3N

    DCDBRTN+

    Battery BLVD

    -48Vmeasurement

    point 1

    -48Vmeasurement

    point 2

    SOCKET

    HEATER

  • 8/18/2019 TP48200A Quick Installation Guide (V100R001_01)

    24/2723

    Ensure that the power switch is set to Normal.

    Set the circuit breaker for the Load based on site requirements. The circuit breaker for the fan must be set to ON. Checkwhether the loads work normally. If a load works abnormally, handle the fault by referring to the user manual of the loaddevice.

    BAT ON

    Normal

    HEATER

    Fan

  • 8/18/2019 TP48200A Quick Installation Guide (V100R001_01)

    25/2724

    Verify that the fans run properly in the cabinet.

    Verify that the lamp is on in the cabinet.

    Re-install the protection plates on the ACDB and DCDB.

    Check whether the EMS can receive the information from the power system. If not, check whether the IP address is setcorrectly and the PMU is connected properly.

    Observe the operation of the power system for 15 minutes. If no alarms are generated, and current/voltage parameters of the

    storage battery and loads are set properly, lock the door to the cabinet, give the key to the cabinet door to the customer, andclean the site before leaving the site.

  • 8/18/2019 TP48200A Quick Installation Guide (V100R001_01)

    26/2725

    Power System Parameters

    Parameter Value Range Default Value 1st Rev Date Sign 2st Rev Date Sign

    Batt String 0 –2 1

    Capacity 1 30 –1000 400 Ah

    Capacity 2 30 –1000 0 Ah

    IP Address 0.0.0.0 –255.255.255.255

    192.168.0.10

    Subnet Mask 0.0.0.0 –255.255.255.255

    255.255.0.0

    Gateway 0.0.0.0 –255.255.255.255

    192.168.0.1

    Date   Dec.31’99 Jan.01’00

    Time 23:59 01:01

    LLVD BLVD –DCUnder Volt

    44.0V

    BLVD 35V –LLVD 43.0V

    Battery Float 43.20V –57.6V 53.5V

    Battery Boost 43.20V –57.6V 56.5V

    Rect Sleep Yes/No No

    LLVD Enable Yes/No No

    BLVD Enable Yes/No Yes

    Current LimitCoefficient

    0.05 –0.25 0.10C10

    Battery TempHigh

     –500C to +1000C 500C

    Amb Temp High   –500C to +1000C 500C

    Power System Parameter List

  • 8/18/2019 TP48200A Quick Installation Guide (V100R001_01)

    27/27

    HUAWEI TECHNOLOGIES CO., LTD.Huawei Industrial Base Bantian Longgang

    Shenzhen 518129